Copyright © 2018 Exor International S.p.A. – Verona, Italy Subject to change without notice The information contained in this document is provided for informational purposes only. While efforts were made to verify the accuracy of the information contained in this documentation, it is provided “as is” without warranty of any kind. Third-party brands and names are the property of their respective owners. www.exorint.com
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
Table of Contents
Introduction 4
Safety guide 5
1 Product overview 6
2 Standards and approvals 7
3 Technical specications 8
4 Technical data 10
4.1 Dimensions 14
4.2 Installation environment 16
4.3 Installation procedure 17
5 Connections 18
5.1 Serial port 20
5.2 Ethernet port 21
5.3 Option plugin module 22
6 Power supply, grounding and shielding 24
7 Battery 25
8 Cleaning faceplates 26
9 Getting started 26
10 System settings 27
11 LED indicator on front panel 30
12 Unpacking and packing Instructions 31
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
Introduction
The operational guidelines described below is information which relates to the device, installation, tran­sportation, storage, assembly, use and maintenance.
This Operating Instruction describes the main features of the operator panels. The Guide refers to the following models:
eTOP504 Operator interface with TFT color 4,3” display touchscreen eTOP506 Operator interface with TFT color 5.7” display touchscreen eTOP507 Operator interface with TFT color 7” widescreen display touchscreen eTOP507M Operator interface with TFT color 7” widescreen display touchscreen, 1GHz CPU eTOP510 Operator interface with TFT color 10.4” display touchscreen eTOP512 Operator interface with TFT color 12.1” display touchscreen eTOP513 Operator interface with TFT color 13.3” widescreen display touchscreen eTOP515 Operator interface with TFT color 15” display touchscreen
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
Safety Guide
The manual contains safety standards that must be respected for the personal safety and to avoid damage. Indications of attention are divided into three levels of severity:
DANGER: indicates a failure to observe safety rules and such failure may cause death or serious injuries.
ATTENTION: indicates a failure to observe safety rules and that deciency may cause damage.
CAUTION: indicates a failure to observe safety rules and that deciency may cause defects to the equipment
or inconsistencies.
CAUTION
ATTENTION
DANGER
!
!
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
1 Production Overview
The Exor eTOP Series 500 HMI products combine state-of-the-art features and top performance with an oustanding design. They are the ideal choice for all demanding HMI applications including factory and building automation.
The eTOP Series 500 HMI panels have been designed to run the JMobile software.
• Designed for use with JMobile HMI software.
Full vector graphic support. Native support of SVG graphic objects. Trasparency and alpha
blending.
Full object dynamics: control visibility and transparency, move, resize, rotate any object on screen.
Change properties of basic and complex objects.
TrueType fonts.
Multilanguage applications. Easily create and manage your applications in multiple languages to meet global requirements. Far East languages are supported. Tools available in JMobile Studio
support easy third-party translations and help reducing development and maintenance costs of the application.
Data display in numerical, text, bargraph, analog gauges and graphic image formats.
Rich set of state-of-the-art HMI features: data acquisition, alarm handling, scheduler and timed
actions (daily and weekly schedulers, exception dates), recipes, users and passwords, RSS feeds, rotating menus.
Includes support for a wide range of communication drivers for Factory systems.
Multiple drivers communication capability.
Remote monitoring and control. Client-Server functionality.
On-line and Off-line simulation with JMobile Studio.
Powerful scripting language for automating HMI applications. Script debugging improves efciency
in application development.
Rich gallery of vector symbols and objects.
Optional plug-in modules for eldbus systems, I/O and controllers.
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
2 Standards and Approvals
The products have been designed for use in an industrial environment in compliance with the 2014/30/
EU EMC Directive. The products have been designed in compliance with: EN 61000-6-4 EN 55011 Class A
EN 61000-6-2 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
The installation of these devices into the residential, commercial and light-industrial environments is al­lowed only in the case that special in measures are taken in order to ensure conformity to EN 61000-6-3.
The products are in compliance with the Restrictions on Certain Hazardous Substances (RoHS) Directive
2011/65/EU
In compliance with the above regulations the products are CE marked.
Product Identication
The product may be identied through a plate attached to the rear cover. You will have to know the type
of unit you are using for correct usage of the information contained in the guide.
An example of this plate is shown in the gure below:
eTOP504 product model name ETOP504U1P1 product part number
1846 year/week of production
AA00001HP123456789AA serial number 040100A15011000 version id of the product
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
3 Technical Specications
Touch screen technology Resistive
Back-up battery
3V 50mAh Lithium, rechargeable, not user-replaceable,
model VL2330. Fuse Automatic
Serial Port
RS-232, RS-485, RS-422 software congurable
User memory Flash 128MB for eTOP504, 506, 507 Flash 256MB for eTOP507M, eTOP510, 512, 513, 515
Recipe memory Flash Hardware clock Clock/Calendar with back-up battery Accuracy RTC (at 25°C operating) <100ppm
Environmental conditions
Operating temperature (vertical 0 ÷ +50°C EN 60068-2-14 installation) Storage temperature -20 ÷ +70°C EN 60068-2-14 Operating and storage humidity 5 ÷ 85 % RH not-condensing EN 60068-2-30 Vibrations 5 ÷ 9 Hz, 7 mm
p-p
EN 60068-2-6
9 ÷ 150 Hz, 1 g
Shock ± 50 g, 11 ms, 3 pulses per axis EN 60068-2-27 Protection class IP66 front panel * EN 60529
* The front face of the unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the “Environmental conditions”. Even though the level of resistance unit is equivalent to these standards, oils
that should have no effect on the panel can possibly harm the unit. This can occur in areas where either vaporized oils are present, or where low viscosity cutting oil are allowed to adhere to the unit for long periods of time. If the front face protection sheet on the panel becomes peeled off, these conditions can lead to the ingress of oil into the panel and separate protection measures are suggested. If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the original level of the protection cannot be guaranteed.
Electromagnetic Compatibility (EMC)
Radiated disturbance test Class A EN 55011 Electrostatic discharge immunity test 8 kV (air electrostatic discharge) EN 61000-4-2
4 kV (contact electrostatic discharge)
Radiated, radio-frequency, 80 MHz ÷ 1 GHz, 10V/m EN 61000-4-3 electromagnetic eld immunity test 1,4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
Burst immunity test ± 2 KV DC power port EN 61000-4-4 ± 1 KV signal line Surge immunity test ± 0,5 KV DC power port (line to earth) EN 61000-4-5 ± 0,5 KV DC power port (line to line) ± 1 KV signal line (line to earth)
Immunity to conducted disturbances inducted by radiofrequency eld 0.15 ÷ 80 MHz, 10V EN 61000-4-6
Voltage dips, short interruptions and voltage variations immunity test Port: AC mains; Level:
100% duration: 1 cycle and 250 cycles (50Hz); 40% duration: 10 cycles (50Hz); 70% duration: 25 cycles (50Hz); Phase: 0°-180° Test executed on the 230Vac side of the Exor International Power Supply EN 61000-4-11
Durability information
Backlight service life 40000 Hrs. or more (LED type) (Time of continuos operation until the brightness of the
backlight reaches 50% of the rated value when the sorrounding air temperature is 25°C) - see Note 1
Front foil 10 years if the surrounding air temperature is 25°C (without directly exposure to sunlight or UV ray)
UV Resistance Indoor applications: After 300 hours cycled humidity in
QUV accelerated weathering, some yellowing and brittleness may be present. - see Note 2.
Touch screen reliability > 1 milion operations
Note 1: Extended use in environments where the surrounding air temperature is 40°C or higher may degrade
backlight quality/reliability/durability.
Note 2: Solvent resistance:
Contact for 1/2 hour at 21°C, No visible effect: Acetone, Butyl Cellosolve, Cyclohexanone, Ethyl Acetate,
Hexane, Isopropyl Alcohol, MEK, Methylene Chloride, Toluene, Xylene Contact for 24 hours at 49°C, No visible effect: Coffee, Ketchup, Lemon Juice, Mustard (slight yellow stain), Tea, Tomato juice.
3 Technical Specications
10
MANUGENETOP5xx - Version 2.00 © 2018 EXOR International S.p.A. - Subject to change without notice
4 Technical Data
Model eTOP504 eTOP506
Display / Backlight
TFT Color / LED TFT Color / LED
Colors
64K 64K
Resolution
480x272 320x240
Diagonal (inches)
4.3” 5.7”
Dimming
yes yes
User memory Flash
128 MB 128 MB
SD card slot
yes yes
Recipe memory
Yes. Flash memory storage limited only by
available memory
Yes. Flash memory storage limited only by
available memory
Serial Port
RS-232, RS-485, RS-422
DB9 female software congurable
RS-232, RS-485, RS-422
DB9 female software congurable
Ethernet port
2 10/100 Mbit with integrated switch 2 10/100 Mbit with integrated switch
USB port
1 Host interface version 2.0 and version
1.1
2 Host interface, 1 version 2.0,
1 version 2.0 and 1.1
Expansion slot
1 Optional Plugin 2 Optional Plugin
Battery
rechargeable rechargeable
Real Time Clock
yes yes
Voltage
18-32VDC (*) 18-32VDC (*)
Current rating (at 24VDC)
0.4A 0.65A
Weight
1 Kg 1 Kg
(*) For applications requiring compliance with EN 61131-2 and specically in reference to 10 ms voltage dips, the
minimum power supply voltage is 18Vdc,