
SceneSelect II
Scene-setting and Dimming System
SLD1205
LEADING EDGE DIMMER
Instruction Manual
Contents
Warning ............................................................. 2
Features ............................................................ 2
Important Safeguards ........................................ 2
Internal View ................................................... ...3
Mounting ............................................................ 4
Supply & Load Cable Connections .................... 5
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: 01942 719229 Fax: 01942 272767 Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
Connecting Serial Control Cables...................... 6
Hardware Controls ............................................ 7
Dimmable Lamps Chart .................................... 7
Changing Scenes Using The Program Key ........8
Troubleshooting................................................. 9
Specification ..................................................... 9
Ex-Or
W4103H

WARNING
ISOLATE FROM
MAINS SUPPLY BEFORE
REMOVING THIS COVER
NO USER SERVICEABLE PARTS INSIDE
SERVICE BY QUALIFIED PERSONNEL ONLY
Warning
TO REDUCE THE RISK OF FIRE OR
ELECTRIC SHOCK, DO NOT EXPOSE
THIS DEVICE TO RAIN OR
MOISTURE.
DO NOT ENERGISE UNLESS THE
FRONT COVER IS IN PLACE.
THIS DEVICE MUST BE EARTHED.
INSTALLATION, PROGRAMMING AND
MAINTENANCE MUST BE CARRIED
OUT BY QUALIFIED PERSONNEL.
Features
Simple Supply Requirements
Single phase and neutral at 60A or
Three phase and neutral at 20A per phase
12 Dimmed Outputs
Each 5A output is independently
regulated, protecting loads from voltage
surges and spikes.
MCB Protection
Each output is protected by a 6A single
pole thermal magnetic circuit breaker.
Convection Cooled
This device is convection cooled,
requiring no forced cooling system when
installed in accordance with these
instructions.
Many Control Options
Control of this device can be from any of
the SceneSelect II range of control panels
and ancillary products.
Simple Installation
Wall mount enclosure with mounting lugs
facilitates installation. A cable gland plate
is provided at the top of the enclosure for
supply cables and at the right-hand side
for load cables with a knockout for the
low voltage (LV) control at the bottom.
Important Safeguards
Read Instructions We recommend that you
read this Instruction Manual prior to
commencement of installation. Retain these
instructions and give the end user the
'Changing Scenes Using the Program Key'
guide on page 8, if applicable.
Tro ub le sh oo ti ng - I f p r ob le ms a re
e n c o u n t e r e d , p l e a s e c h e c k t h e
troubleshooting section on page 9 before
calling Ex-Or technical support.
Special Programming This device will only
operate in ‘basic’ mode unless programmed
via a computer. Should programming be
required, contact Ex-Or for details. Once the
data cable is connected to the device(s), the
factory default settings will allow any control
panel to control all channels in all dimmers.
Power Sources This device should only be
operated from the type of supply specified on
the front panel. This device must be earthed.
Output Circuits The load on a single circuit
should not exceed 5A. Loads should be
calculated to ensure that the total device load
of 60A is not exceeded. Some types of load
have special requirements. Check the
Dimmable Lamps Chart on page 7 for more
information.
Megger Testing Do not megger test any
circuitry connected to the dimming system, as
damage to the electronics may result.
Mounting Location This device must be
mounted the right way up, on a vertical surface
(refer to page 4 for mounting instructions). The
specified minimum clearance of 200mm for all
sides must be adhered to. Install in a dry, wellventilated location. This device may emit
some mechanical noise. Take this into
account when deciding the mounting location.
Data Cable The recommended cable for
connections to the programming socket is
4 pair patch (multi-stranded) CAT5 screened
cable. This cable should be segregated from
mains cables by a minimum distance of
300mm unless the FTP cable itself is mainsrated. If expected cable runs are over 600
metres for bus cables or 12 metres for
analogue cables, consult Ex-Or for advice. Do
not cut or terminate live data cables.
Load Type The factory default settings are for
all channels to be dimmable. Do not terminate
any non-dimmable loads until the relevant
channel has been programmed as switching
only. See the Dimmable Lamps Chart on
page 7.
2
SLD1205 Instruction Manual - W4103H

SLD1205 Instruction Manual - W4103H
3