Ex-Or DLE1205 Installation Instructions

SceneSelect II
Scene-setting and Dimming System
SLD1205
LEADING EDGE DIMMER
Instruction Manual
Contents
Warning ............................................................. 2
Features ............................................................ 2
Important Safeguards ........................................ 2
Internal View ................................................... ...3
Mounting ............................................................ 4
Supply & Load Cable Connections .................... 5
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: 01942 719229 Fax: 01942 272767 Email: technicalsales.ex-or@honeywell.com
Connecting Serial Control Cables...................... 6
Hardware Controls ............................................ 7
Dimmable Lamps Chart .................................... 7
Changing Scenes Using The Program Key ........8
Troubleshooting................................................. 9
Specification ..................................................... 9
Ex-Or
W4103H
WARNING
ISOLATE FROM MAINS SUPPLY BEFORE REMOVING THIS COVER
NO USER SERVICEABLE PARTS INSIDE
SERVICE BY QUALIFIED PERSONNEL ONLY
Warning
TO REDUCE THE RISK OF FIRE OR ELECTRIC SHOCK, DO NOT EXPOSE THIS DEVICE TO RAIN OR MOISTURE.
DO NOT ENERGISE UNLESS THE FRONT COVER IS IN PLACE.
THIS DEVICE MUST BE EARTHED. INSTALLATION, PROGRAMMING AND
MAINTENANCE MUST BE CARRIED OUT BY QUALIFIED PERSONNEL.
Features
Simple Supply Requirements
Single phase and neutral at 60A or Three phase and neutral at 20A per phase
12 Dimmed Outputs
Each 5A output is independently regulated, protecting loads from voltage surges and spikes.
MCB Protection
Each output is protected by a 6A single pole thermal magnetic circuit breaker.
Convection Cooled
This device is convection cooled, requiring no forced cooling system when installed in accordance with these instructions.
Many Control Options
Control of this device can be from any of the SceneSelect II range of control panels and ancillary products.
Simple Installation
Wall mount enclosure with mounting lugs facilitates installation. A cable gland plate is provided at the top of the enclosure for supply cables and at the right-hand side for load cables with a knockout for the low voltage (LV) control at the bottom.
Important Safeguards
Read Instructions We recommend that you read this Instruction Manual prior to commencement of installation. Retain these instructions and give the end user the 'Changing Scenes Using the Program Key' guide on page 8, if applicable. Tro ub le sh oo ti ng - I f p r ob le ms a re e n c o u n t e r e d , p l e a s e c h e c k t h e troubleshooting section on page 9 before calling Ex-Or technical support. Special Programming This device will only operate in ‘basic’ mode unless programmed via a computer. Should programming be required, contact Ex-Or for details. Once the data cable is connected to the device(s), the factory default settings will allow any control panel to control all channels in all dimmers. Power Sources This device should only be operated from the type of supply specified on the front panel. This device must be earthed. Output Circuits The load on a single circuit should not exceed 5A. Loads should be calculated to ensure that the total device load of 60A is not exceeded. Some types of load have special requirements. Check the Dimmable Lamps Chart on page 7 for more information. Megger Testing Do not megger test any circuitry connected to the dimming system, as damage to the electronics may result. Mounting Location This device must be mounted the right way up, on a vertical surface (refer to page 4 for mounting instructions). The specified minimum clearance of 200mm for all sides must be adhered to. Install in a dry, well­ventilated location. This device may emit some mechanical noise. Take this into account when deciding the mounting location.
Data Cable The recommended cable for connections to the programming socket is 4 pair patch (multi-stranded) CAT5 screened cable. This cable should be segregated from mains cables by a minimum distance of 300mm unless the FTP cable itself is mains­rated. If expected cable runs are over 600 metres for bus cables or 12 metres for analogue cables, consult Ex-Or for advice. Do not cut or terminate live data cables.
Load Type The factory default settings are for all channels to be dimmable. Do not terminate any non-dimmable loads until the relevant channel has been programmed as switching only. See the Dimmable Lamps Chart on page 7.
2
SLD1205 Instruction Manual - W4103H
Internal View
SLD1205 Instruction Manual - W4103H
3
Loading...
+ 7 hidden pages