Ex-Or CPW665MF, CPW665 Installation Instructions

CDW1U1
Factory Configuration
When the unit is shipped, terminals L and CL are linked. A spare link is supplied (in the spare terminals). When this is fitted between SWL and CL, a connected detector will control both luminaire outputs, switching any connected luminaires OFF once the time delay has elapsed.
A neon in the connection chamber indicates when power is present.
Connections are made as illustrated below. Two spare terminals are provided for termination purposes. Live (L) is routed to the 6-way detector connector. Maintained Live (ML) is routed to the two luminaire connectors.
Connect Digital Box
Installation Instructions
WARNING 230V a.c.
SWL is the switched live output from the detector.
CL is the ’connected’ live routed to the 6-way luminaire output socket. This is used when controlling regulating luminaires. In this configuration, the mains supply to the regulating luminaires is not switched.
Made in UK
Ambient -5 to 50 C
No user-serviceable
parts inside
OneSwitch
Dimming Control
MLS BUS
OUT
IN
-
-
+
+
NOT MAINS
Refer to installation instructions for LK1 and LK2
Refer to detector data for allowed
Dimming Control load
Use only specified cable types
TM
MAINS INPUT
230V 50Hz
6 A max load
LK2
LK1
-
+
L
in
Linked Internally
CL
SWL
L
N MLL
THIS UNIT
MUST BE
EARTHED
Spare Terminals
nc nc
Dimming Control Terminals
The Dimming Control signals from each detector to its group of luminaires are accessible at terminals under the screw-fixed cover.
W
The connections to this equipment should be made by a suitably qualified person in accordance with the current wiring regulations.
The unit must be earthed.
The CDW1U1 Connect Digital Box provides an efficient way to inter­connect a presence detector and luminaires using industry standard
H2
H1
connectors or a prefabricated wiring system (modular wiring). A detector can control both regulating and fixed-output luminaires. The total CD Box load must not exceed 6A. Please check the detector specification for all control parameters.
Dimensions
Electrical Connections
Screw terminals are provided under the cover for power supply connections and extension of the dimming control to other CD Boxes. Override switches may also be connected here providing a means to manually control the switched live connections to the luminaires. Where detectors are connected that utilise the MLS Bus, terminals for connection to the Bus system are also provided. Terminals are also provided for use with Ex-Or’s OneSwitch Dimming, providing simple on/off, raise/lower control - please refer to detector literature for additional information.
The installation should provide means of supply disconnection and over-current protection. Please refer to diagrams overleaf for further information.
Fixing
The box should be sited on a suitable smooth, flat surface using the two
CASE HEIGHT (H1) = 41mm WIDTH (W) = 190mm (248mm inc. fixing flanges) DEPTH (D) = 137mm OVERALL HEIGHT (H2) = 185mm (INCLUDING PLUG AND LEAD) WEIGHT =1kg FIXING CENTRES = 220mm
Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
MAXIMUM LOAD PER CDW1U1: 6 Amps
RECOMMENDED CIRCUIT PROTECTION: Max 16 Amp Circuit Breaker. This may serve several CDW1U1s, depending upon the actual loads installed.
SUPPLY TERMINAL CAPACITY: 4.0mm
MLS BUS & ONESWITCH TERMINAL CAPACITY: 4.0mm
CASE MATERIAL: BRIGHT GALVANISED STEEL 1.0mm THICK
end fixing flanges. Consideration should be given to the box’s location as access will be required to install the plugs. The box must not be distorted when fixing.
Alternatively, the box may be rod-fixed. In this case, the fixing should be substantial enough to withstand the action of plugging and un-plugging connectors.
Ex-Or
Haydock Lane, Haydock, Merseyside WA11 9UJ Tel: +44 (0)1942 719229 Fax: +44 (0)1942 272767 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
D
2
2
W4223B
Detector and Luminaire Connection
Luminaires and detectors are connected as outlined below using industry-standard leads and plugs. Some detectors require only one lead for connection.
Regulating Luminaire
Distribution Unit with Mains-Based Dimming (Switch Dim) (for use with Digital Ballasts)
MLS Bus + MLS Bus
OneSwitch
Detector
­Neutral
Dimming Control
SWL
Live
­+
SWL
Neutral
Maintained Live
To controlled luminaires
Luminaires
Neutral
Maintained Live
Dimming Control
CL
­+
OneSwitch
Dimming Control
MLS BUS
OUT
IN
-
-
+
-
+
+
L
in
CL
SWL
L
Spare Terminals
N MLL
nc nc
Fixed-Output Luminaire
Pluggable PIR
Connection Examples
Single Detector (dual-output) with two groups of luminaires and OneSwitch Input
Flying leads from e.g. MLS2421D
MLS Digital Gold Presence Detector
with OneSwitch Dimming
Detector
MLS Bus +
-
MLS Bus OneSwitch
Dimming Control
MLS BUS
OUT
IN
-
-
+
+
+
Neutral
Dimming Control
-
in
SWL
Live
­+
Maintained Live
L
To controlled (emergency) luminaires
SWL
Neutral
CL
SWL
L
LK1
Luminaires
N MLL
Neutral
Maintained Live
Dimming Control
Spare Terminals
nc nc
Switch Dim
Input
Mains-based dimming must not be used in conjunction with Ex-Or’s range of presence detectors.
From
Supply
Isolator
Single Detector with one group of luminaires
Flying lead from a
Presence Detector
CL
MLS Bus + MLS Bus
­+
OneSwitch
-
Detector
Neutral
Dimming Control
SWL
Live
­+
Maintained Live
To controlled analogue or digital luminaires
SWL
Neutral
Luminaires
Neutral
Maintained Live
Dimming Control
CL
­+
Dimming Control
MLS BUS
OUT
IN
-
-
+
-
+
+
L
in
CL
SWL
L
LK2
Spare Terminals
N MLL
nc nc
OneSwitch
MLS bus
(to next
MLS device or
CD Box)
Input
Normally-closed
keyswitch for
manual emergency
test of emergency
luminaires
Please note that in the example above, the Mains supply to the regulating luminaire (6-pole) is not switched. Once no occupancy has been detected for the duration of the time delay, the ballast(s) connected here will go to zero output.
Auxiliary Items
CPW6 CPW4 CPW633 CPW635 CPW643 CPW645 CPW653 CPW655 CONNECT 5m Luminaire Lead - 6-pole, 5-core GST 18/6 plug CPW663 CPW665 CONNECT 5m Emergency Luminaire Connector - 6-pole/6-core CPW433 CONNECT 3m Luminaire Lead - 4-pole, 3-core GST 18/4 plug CPW435 CONNECT 5m Luminaire Lead - 4-pole, 3-core GST 18/4 plug CPW443 CONNECT 3m Luminaire Lead - 4-pole, 4-core GST 18/4 plug CPW445 CONNECT 5m Luminaire Lead - 4-pole, 4-core GST 18/4 plug CPW443MF CONNECT 3m Luminaire/Detector Extension Cable - 4-pole, 4-core male/female CPW445MF CONNECT 5m Luminaire/Detector Extension Cable - 4-pole, 4-core male/female CPW663MF CONNECT 3m Luminaire/Detector Extension Cable - 6-pole, 6-core male/female CPW665MF CONNECT 5m Luminaire/Detector Extension Cable - 6-pole, 6-core male/female
Luminaire Connection Plug - 6-pole Wieland GST Luminaire Connection Plug - 4-pole Wieland GST CONNECT 3m Luminaire Lead - 6-pole, 3-core GST 18/6 plug CONNECT 5m Luminaire Lead - 6-pole, 3-core GST 18/6 plug CONNECT 3m Emergency Luminaire Connector - 6-pole/4-core CONNECT 5m Emergency Luminaire Connector - 6-pole/4-core CONNECT 3m Luminaire Lead - 6-pole, 5-core GST 18/6 plug
CONNECT 3m Emergency Luminaire Connector - 6-pole/6-core
From
Supply
Isolator
Notes:
(i) The dimming control connections are mains rated
(ii) Unit must not be used with multi-phase connections
From Supply Isolator
Loading...