Ex-Or CDW4U1UL Installation Instructions

by Honeywell
Connect UltraLite
Connection Centre
CDW4U1UL
Installation Instructions
WARNING 230V a.c.
The connections to this equipment should be made by a suitably qualified person in
It is strongly recommended to use Ex-Or latching type connectors.
The unit must be earthed.
Connect UltraLite provides an efficient way to interconnect presence detectors and luminaires using industry standard connectors. One detector can be connected to up to four luminaires depending upon the configuration required.
Dedicated UltraLite detectors are available as well as a range of Plugs and Leads to convert LightSpot HD sensors for use with the UltraLite CD Box (see back page for part numbers).
Electrical Connections
Screw terminals are provided under the cover for power supply connections. Override switch may also be connected here providing a means to control the switched live connections to the luminaires.
The installation should provide means of supply disconnection and over-current protection.
The cover of the cable chamber is removed by inserting the tip of a flat bladed screwdriver into the catch recess and exerting light pressure on the handle in an inboard direction while lifting the long outboard edge of the cover.
The cable entries, for 20mm conduit, bushes or glands are semi-pierced in the walls of the cable chamber and can easily be removed from the outside with a 20mm hole saw.
If the cables are not routed right into the box through conduit or trunking, a cable restraining gland must be fitted at the cable entry for strain relief.
Fixing
The box should be sited on a suitable, smooth, flat surface using the two end fixing flanges. Consideration should be given to the box’s location as access will be required to install the plugs. The box must not be distorted when fixing.
Alternatively, the box may be rod-fixed. In this case, the fixing should be substantial enough to withstand the action of plugging and un-plugging connectors.
Factory Configuration A red indicator in the connection chamber indicates that power is present.
ML
Lin
Lin
N
E
E
SWA
PB-A
MAINTAINED LIVE
Internally connected to A1-4
LIVE INPUT
Internally connected to detector live Lin internally linked
MAINS INPUT: 230V 50Hz Max load on any single outlet: 6A Max total load: 16A tc: 5 - 50 C No user-serviceable parts inside
EARTH INPUT
Protected Earth E terminals internally linked
(Connect wall switches here if not using plug-in detectors)
Spare (no internal connection)
Manual input OneSwitch
(Only when used with compatible detectors)
Connections are made as illustrated to the left.
Live (Lin) is routed to the detector connector.
Maintained Live (ML) is routed to the 4 luminaire
connectors, A1-A4.
SWA is the switched live output from a detector connected to detector socket.
Detector Connection
There is one detector connection position on each box. The detector is connected by a flying lead and GST18/7 plug.
Switched Live
Live - Supply to detector
Push Button input to detector
Dimming control -
Detector output
Neutral
Ensure max detector load is not exceeded
-
+
Luminaire Connection
There are four luminaire outlets on each box. Each luminaire is connected by a flying lead and GST18/6 plug.
for allowed ballast load
Simple schematic showing connection information:
A+
A-
Switched Live
Neutral
Maintained Live
Dimming control
See Detector Data
Detector
-
+
Maintained Live Live In Live In Neutral Earth Earth
SWA Spare Push Button A
Max load 6A per output
If the detector socket is not occupied by a presence detector, that socket may be used for a luminaire. The plug, however, will need to be 7-pole and wired appropriately.
Connection Examples
Single Detector with 4 Luminaires
(For load information, see Note under Technical Data)
A4 A3 A2 A1
Detector
Up to 4 luminaires
Link wire is required for dimming type of detectors
ML
L
L
N
E
E
SWA
PB-A
K
Emergency Test
Key-Switch*
Manual control
Distribution Unit with External Low-Voltage Dimming Control
230V Supply
* Emergency Test Key-Switch wired
to remove mains supply from all of the Connection Centre
A4 A3 A2 A1
Up to 5 luminaires
ML
L
L
N
E
E
SWA
PB-A
A-
A+
no
connection
no
connection
no
connection
Spare
no
connection
no
connection
no
connection
ML
L
N
E
From
External
Dimming
Control
From
Supply
Isolator
Distribution Unit with Mains-Based ‘OneTouch’ Dimming (for use with compatible Digital Ballasts)
A4 A3 A2 A1
Up to 5 luminaires
ML
L
L
N
E
E
SWA
PB-A
PB-B
A-
no
connection
no
connection
Spare
no
connection
no
connection
no
connection
no
connection
ML
L
N
E
Manual control
From
Supply
Isolator
A+
Notes:
(i) The dimming control connections are mains rated. (ii) Unit must not be used with multi-phase connections. (iii) Mains-based dimming must not be used in conjunction with Ex-Or’s range of presence
detectors.
Dimensions
W
D 2
H
F
Height (H) = 50mm (108mm including plug and lead) Width (W) = 315mm (361mm including mounting feet) Depth (D) = 205mm Fixing Centres (F) = 340mm Weight = 1.85 kg
Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe) PRODUCT RATING/RECOMMENDED CIRCUIT PROTECTION: 16 Amps MAXIMUM LOAD PER OUTLET: 6 Amps* MAXIMUM TOTAL LOAD: 16 Amps* SUPPLY TERMINAL CAPACITY: 6.0mm (2 x 2.5mm ) DIMMING TERMINAL CAPACITY: 4.0mm CASE MATERIAL: Polycarbonate CASE FINISH: Lightly textured light grey WEIGHT: 1.27kg
* Note: These specifications relate to the product when used as a simple wiring device. When mains-switching presence detector is used in conjunction with this equipment, it is the presence detector which will normally dictate the maximum load. It is important to check, and not exceed, the specification of the current-switching presence detector, which will typically be around 6 Amps.
2 2
2
Auxiliary Items
Luminaire Leads: CPWL633 Connect 3m Luminaire Connector - 6-pin/3-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL635 Connect 5m Luminaire Connector - 6-pin/3-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL653 Connect 3m Luminaire Connector - 6-pin/5-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL655 Connect 5m Luminaire Connector - 6-pin/5-core, Wieland GST 18/6 c/w Ex-Or locking mechanism
Emergency Luminaire Leads: CPWL643 Connect 3m Luminaire Connector - 6-pin/4-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL645 Connect 5m Luminaire Connector - 6-pin/4-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL663 Connect 3m Luminaire Connector - 6-pin/6-core, Wieland GST 18/6 c/w Ex-Or locking mechanism CPWL665 Connect 5m Luminaire Connector - 6-pin/6-core, Wieland GST 18/6 c/w Ex-Or locking mechanism
Plugs with Latching Shell CPWL6 For luminaire: GST18/6 6-pole male plug with Ex-Or locking mechanism (complete) CPWL7 For detector: GST 18/7 7-pole Wieland GST male plug with Ex-Or locking mechanism (complete)
Latching Shell only CPWL6S For luminaire: GST-6 Ex-Or plug-locking mechanism (shell only) CPWL7S For detector: GST-7 Ex-Or locking mechanism (shell only)
Leads for the connection of LightSpot HD sensors: LSHDDLW753 LightSpot HD Dimming lead, Wieland 7-pin/5-core - 3 metre LSHDDLW755 LightSpot HD Dimming lead, Wieland 7-pin/5-core - 5 metre LSHDSLW753 LightSpot HD Switching lead, Wieland 7-pin/5-core - 3 metre LSHDSLW755 LightSpot HD Switching lead, Wieland 7-pin/5-core - 5 metre LSHDDSLW763 LightSpot HD Dimming and Switching lead, Wieland 7-pin/6-core - 3 metre LSHDDSLW765 LightSpot HD Dimming and Switching lead, Wieland 7-pin/6-core - 5 metre LSHDQBL226 LightSpot HD QuickLink Bus lead, 2-pin/2-core - 6 metre LSHDQBL2210 LightSpot HD QuickLink Bus lead, 2-pin/2-core - 10 metre
Connect UltraLite Detectors: MLS2421DFCWL7 Connect Gold Series LightSpot Microwave dual-output for DSI ballasts - flush MLS2421DALIFCWL7 Connect Series LightSpot Microwave dual-output for DALI ballasts - flush MLS2021DFDFCWL7 Connect Gold Series LightSpot PIR dual-output for DSI ballasts - flush MLS2021DALIFCWL7 Connect Gold Series LightSpot PIR dual-output for DALI ballasts - flush
Connect UltraLite detectors incorporate the facility for OneSwitch operation and are supplied with 3m cable and 7-way latching plug.
These products do not have MLS functionality and cannot be connected using MLS cable.