The connections to this equipment should be made by a suitably qualified person in
accordance with the current wiring regulations.
It is strongly recommended to use Ex-Or latching type connectors.
The unit must be earthed.
Connect UltraLite provides an efficient way to interconnect presence detectors and luminaires
using industry standard connectors. One detector can be connected to up to four luminaires
depending upon the configuration required.
Dedicated UltraLite detectors are available as well as a range of Plugs and Leads to convert
LightSpot HD sensors for use with the UltraLite CD Box (see back page for part numbers).
Electrical Connections
Screw terminals are provided under the cover for power supply connections. Override switch
may also be connected here providing a means to control the switched live connections to the
luminaires.
The installation should provide means of supply disconnection and over-current protection.
The cover of the cable chamber is removed by inserting the tip of a flat bladed screwdriver into
the catch recess and exerting light pressure on the handle in an inboard direction while lifting the
long outboard edge of the cover.
The cable entries, for 20mm conduit, bushes or glands are semi-pierced in the walls of the cable
chamber and can easily be removed from the outside with a 20mm hole saw.
If the cables are not routed right into the box through conduit or trunking, a cable restraining
gland must be fitted at the cable entry for strain relief.
Fixing
The box should be sited on a suitable, smooth, flat surface using the two end fixing flanges.
Consideration should be given to the box’s location as access will be required to install the plugs.
The box must not be distorted when fixing.
Alternatively, the box may be rod-fixed. In this case, the fixing should be substantial enough to
withstand the action of plugging and un-plugging connectors.
Factory Configuration
A red indicator in the connection chamber indicates that power is present.
ML
Lin
Lin
N
E
E
SWA
PB-A
MAINTAINED LIVE
Internally connected to A1-4
LIVE INPUT
Internally connected to detector live
Lin internally linked
MAINS INPUT: 230V 50Hz
Max load on any single outlet: 6A
Max total load: 16A
tc: 5 - 50 C
No user-serviceable parts inside
EARTH INPUT
Protected Earth
E terminals internally linked
(Connect wall switches
here if not using
plug-in detectors)
Spare (no internal connection)
Manual input OneSwitch
(Only when used with compatible detectors)
Connections are made as illustrated to the left.
Live (Lin) is routed to the detector connector.
Maintained Live (ML) is routed to the 4 luminaire
connectors, A1-A4.
SWA is the switched live output from a detector
connected to detector socket.
Detector Connection
There is one detector connection position on
each box. The detector is connected by a flying
lead and GST18/7 plug.
Switched Live
Live - Supply to detector
Push Button input to detector
Dimming control -
Detector output
Neutral
Ensure max
detector load is
not exceeded
-
+
Luminaire Connection
There are four luminaire outlets on each box.
Each luminaire is connected by a flying lead and
GST18/6 plug.
for allowed ballast load
Simple schematic showing connection information:
A+
A-
Switched Live
Neutral
Maintained Live
Dimming control
See Detector Data
Detector
-
+
Maintained Live
Live In
Live In
Neutral
Earth
Earth
SWA
Spare
Push Button A
Max load 6A
per output
If the detector socket is not occupied by a presence detector, that socket may be used for a
luminaire. The plug, however, will need to be 7-pole and wired appropriately.
Connection Examples
Single Detector with 4 Luminaires
(For load information, see Note under Technical Data)
A4 A3 A2 A1
Detector
Up to 4 luminaires
Link wire is required for dimming type of detectors
ML
L
L
N
E
E
SWA
PB-A
K
Emergency Test
Key-Switch*
Manual
control
Distribution Unit with External Low-Voltage Dimming Control
230V Supply
* Emergency Test Key-Switch wired
to remove mains supply from all
of the Connection Centre
A4 A3 A2 A1
Up to 5 luminaires
ML
L
L
N
E
E
SWA
PB-A
A-
A+
no
connection
no
connection
no
connection
Spare
no
connection
no
connection
no
connection
ML
L
N
E
From
External
Dimming
Control
From
Supply
Isolator
Distribution Unit with Mains-Based ‘OneTouch’ Dimming
(for use with compatible Digital Ballasts)
A4 A3 A2 A1
Up to 5 luminaires
ML
L
L
N
E
E
SWA
PB-A
PB-B
A-
no
connection
no
connection
Spare
no
connection
no
connection
no
connection
no
connection
ML
L
N
E
Manual
control
From
Supply
Isolator
A+
Notes:
(i) The dimming control connections are mains rated.
(ii) Unit must not be used with multi-phase connections.
(iii) Mains-based dimming must not be used in conjunction with Ex-Or’s range of presence
detectors.
Dimensions
W
D
2
H
F
Height (H) = 50mm (108mm including plug and lead)
Width (W) = 315mm (361mm including mounting feet)
Depth (D) = 205mm
Fixing Centres (F) = 340mm
Weight = 1.85 kg
Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
PRODUCT RATING/RECOMMENDED CIRCUIT PROTECTION: 16 Amps
MAXIMUM LOAD PER OUTLET: 6 Amps*
MAXIMUM TOTAL LOAD: 16 Amps*
SUPPLY TERMINAL CAPACITY: 6.0mm (2 x 2.5mm )
DIMMING TERMINAL CAPACITY: 4.0mm
CASE MATERIAL: Polycarbonate
CASE FINISH: Lightly textured light grey
WEIGHT: 1.27kg
* Note: These specifications relate to the product when used as a simple wiring device. When
mains-switching presence detector is used in conjunction with this equipment, it is the
presence detector which will normally dictate the maximum load. It is important to check, and
not exceed, the specification of the current-switching presence detector, which will typically
be around 6 Amps.
Plugs with Latching Shell
CPWL6 For luminaire: GST18/6 6-pole male plug with Ex-Or locking mechanism (complete)
CPWL7 For detector: GST 18/7 7-pole Wieland GST male plug with Ex-Or locking mechanism (complete)
Latching Shell only
CPWL6S For luminaire: GST-6 Ex-Or plug-locking mechanism (shell only)
CPWL7S For detector: GST-7 Ex-Or locking mechanism (shell only)
Leads for the connection of LightSpot HD sensors:
LSHDDLW753 LightSpot HD Dimming lead, Wieland 7-pin/5-core - 3 metre
LSHDDLW755 LightSpot HD Dimming lead, Wieland 7-pin/5-core - 5 metre
LSHDSLW753 LightSpot HD Switching lead, Wieland 7-pin/5-core - 3 metre
LSHDSLW755 LightSpot HD Switching lead, Wieland 7-pin/5-core - 5 metre
LSHDDSLW763 LightSpot HD Dimming and Switching lead, Wieland 7-pin/6-core - 3 metre
LSHDDSLW765 LightSpot HD Dimming and Switching lead, Wieland 7-pin/6-core - 5 metre
LSHDQBL226 LightSpot HD QuickLink Bus lead, 2-pin/2-core - 6 metre
LSHDQBL2210 LightSpot HD QuickLink Bus lead, 2-pin/2-core - 10 metre
Connect UltraLite Detectors:
MLS2421DFCWL7 Connect Gold Series LightSpot Microwave dual-output for DSI ballasts - flush
MLS2421DALIFCWL7 Connect Series LightSpot Microwave dual-output for DALI ballasts - flush
MLS2021DFDFCWL7 Connect Gold Series LightSpot PIR dual-output for DSI ballasts - flush
MLS2021DALIFCWL7 Connect Gold Series LightSpot PIR dual-output for DALI ballasts - flush
Connect UltraLite detectors incorporate the facility for OneSwitch operation and are supplied with 3m cable and 7-way latching plug.
These products do not have MLS functionality and cannot be connected using MLS cable.
Honeywell Ex-Or
Albery House, Springfield Road,
Horsham, West Sussex RH12 2PQ
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
32317481-001 RevB
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.