Ex-Or CDW10U5 Installation Instructions

Installation Instructions
CDW10U5
CDW10U52L
Installation Instructions
CDW10U5 for 3-wire mains systems CDW10U52L for 4-wire mains systems (with externally switched Maintained Live)
The CD BOX is an intelligent connection box providing connections for up to ten luminaires, five MLS2000CDR dedicated detectors and five switch inputs. The unit is designed to simplify installation whilst providing an intelligent managed lighting system. All the connections are pluggable. (Hardwired options are also available.)
Parts list
1 CD BOX 1 4-pole Mains Power Connector (black c/w hood) 1 4-way Switch Input Connector c/w link 4 Open 20mm dia Grommets 1 Paper label for contractor to note box/circuit references 1 MLS Bus Plug Set (MLSPG)
A list of optional extras can be found on the back page.
NOTE When installing patch leads between CD Boxes or between CD Boxes and Detectors, care must be taken to protect the plug connection from damage or contamination by dirt or grease etc.
Electrical Connection
The connections to this equipment should be made by a suitably qualified person and in accordance with the current wiring regulations. For the following connections it will be necessary to remove the screw-fixed access panel. (The access panel must be replaced upon completion of any installation work.)
10 industry standard 6-pin luminaire output sockets
Rear view - cover removed
Output sockets for FailSafe Bus and additional box interface leads
MLS Bus and FailSafe Bus Mains supply Plug/socket connection to reduce installation time
5 detector and 5 switch input sockets along the front of the unit
Fixing
The box should be sited on a suitable, smooth, flat surface using the two end fixing flanges. Consideration should be given to the box’s location as access will be required to install the plugs.
The box must not be distorted when fixing. (If the box is to be mounted on an uneven surface, it may be necessary to use packing pieces or self- adhesive stand-off feet.)
When the CD Box is to be rod-fixed, the fixing should be substantial enough to withstand the action of plugging and un­plugging connectors.
CDW10U5
Internal link
This unit requires unswitched L i v e, E a r t h a n d N e u t ra l connections to the four-pin plug supplied.
CDW10U52L
This unit requires Live, Earth, Neutral and Maintained Live connections to the four-pin plug supplied.
1
E V
LI
No internal link
1
E V
I L
N
2
L
H T R A E
N
T
EA HR
N O
I TC
O N
EC
EU RA
N
N T
KE A
ON
M
2
D
L A
INE
E
TR
A
V
U
LI
E
INT
N
A M
Pluggable Wiring
Ensure that suitably rated cable is used to fit and fix the hood to the base of the plug.
Hardwired
Insert the four-pin mains plug into the socket on the CD Box. To connect the cable into the terminal block it will be necessary to fit a cable restraint. This can be attached to the 20mm dia cable entry holes. Most forms of cable restraint/containment are suitable when used with a 20mm dia adaptor.
A red LED indicates when power is present.
MLS Bus Connection Note: The MLS Bus is polarity-conscious.
The cable used should be two-core 1.5mm unscreened
2
twisted pair, mains-rated LSF insulated.
The MLS Bus connection can be made in one of two ways:
1) Using ready-assembled extension leads (as listed on the back page).
2) Using the MLSPG plug set. Fit cable as the above specification, then assemble on site to the required lengths.
Emergency Testing
The CD Box is able to operate three types of emergency test:
1.Conventional - Where the test is conducted by switching
the maintained live supply externally (CDW10U52L only).
2.Test switching through the MLS bus - The power supply
(RB2000) is supplied fitted with an emergency test key-switch which communicates through the bus by opening a normally closed relay in the CD Box, thus breaking the maintained live supply to simulate a mains failure.
Both these options require manual recording of the test results.
3.With an automatic test system such as the Ex-Or
FailSafe - The CD Box has provision for linking an
addressable emergency test bus. Although designed for use with the Ex-Or FailSafe system, the CD Box may be used with any emergency testing bus.
Emergency Testing continued
The FailSafe bus is polarity conscious. To assist with installation, the input and outlet terminals have polarity indicated with a + or -.
Connection to the CD Box may be via the plug set FSPG using cable to the required specification (see Emergency Testing literature) or via ready-made leads FS5M and FS10M (see separate data sheet for full specification).
When making up bus connection leads or purchasing ready­made leads it is the installing contractor’s responsibility to ensure compatibility with the system used.
Should it be necessary to remove the CD Box from either the MLS or the FailSafe bus system, by un-plugging the male and female connections from the box and linking them together, the continuity of the bus is maintained.
At this point, the access panel should be re-fitted as further access is not necessary.
Luminaire Connection Note: only one luminaire should be connected to each outlet.
There are 10 luminaire outlets (5 pairs) on each box. Each luminaire is connected by a flying lead and GST18/6 plug, Ex-Or part code CPW6. (A full list can be found on the back page.)
Live output
Override Switch Input Connection, Normal Operation
Note: Each switch input overrides the two luminaire outlet sockets with the corresponding numbers.
The switches should be two-way with a centre off position. When operating with detectors set to semi-automatic, retractive switches are recommended. For override or non-detector operation, latching switches should be used.
The connection to the box is via the four-way smaller re­wireable plug.
The connections must be as detailed.
Link supplied fitted
Auto (COM on switch)
On
Off
Switch 1
Override Switch Input Connection, OneSwitch Operation
Note: OneSwitch input controls the two luminaire outlet sockets with the corresponding numbers.
The switches should be double-pole push-to-make retractive switches.
Neutral
Maintained Live - Maximum load 2 Amps total per box
-
Digital dimming control - Maximum 4 ballasts per output
+
(wired in parallel)
On emergency luminaires with FailSafe testing, care should be taken to ensure the correct polarity of connections. Use plug EPW2 or lead and plug EPW223. Connect the FailSafe lead to the red two-pin sockets on the back of the box (not under the connection cover).
Detector Connection Note: each detector controls the two luminaire outlet sockets with corresponding numbers.
The connection of the MLS2000CDR detectors is simplified by the use of plug-in patch leads which are available in 2m, 3m, 5m and 10m lengths. When plugging into the box, care should be taken to select the correct socket. (Use only Ex-Or patch leads. Do not exceed 10m length on any patch lead.) The box operates a system of hierarchy whereby a detector will control all the luminaire outlets to the left up to the point where another detector is connected.
5
Switch
5
Switch
Detector
5
Detector
5
4
Switch
4
Switch
Detector
4
Detector
4
3
Switch
3
Switch
Detector
3
Detector
3
2
Switch
2
Switch
Detector
2
Detector
2
1
Switch
1
Switch
Detector
1
Detector
1
The connection to the box is via the four-way smaller re­wireable plug.
The connections must be as detailed.
Link supplied fitted
On
Auto (COM on switch)
Off
Switch 1
As with the detectors, the override inputs operate a system of hierarchy, overriding all outlets to the left up to the point where another switch-plug is present. In order to stop the influence of a switch at any point, insert a plug with the link fitted and no other connection to it.
Note that the hierarchy of override switches operates in parallel with, and independent from, the hierarchy of the detectors and will take priority over any detectors connected in its path.
5
Switch
Detector
5
4
Switch
Detector
4
3
Switch
Detector
3
2
Switch
Detector
2
1
Switch
Detector
1
5
Switch
Detector
5
4
Switch
Detector
4
3
Switch
Detector
3
2
Switch
Detector
2
1
Switch
Detector
1
5
Switch
Detector
5
4
Switch
Detector
4
3
Switch
Detector
3
2
Switch
Detector
2
1
Switch
Detector
1
In the event of additional luminaire outlets being required, it is possible to create a notional 20, 30, 40 or 50-way CD Box by connecting boxes together. The hierarchy system for both detectors and override switches will then extend to all linked boxes.
CD Boxes may be linked together by using the 2m, 3m, 5m and 10m patch leads plugged into the expansion sockets on the back of the box (use only Ex-Or patch leads). A maximum of five CD Boxes may be linked this way.
Expansion sockets
(Downstream) (Upstream)
IN
OUT
IN
5
Switch
Detector
5
4
Switch
Detector
4
3
Switch
Detector
3
2
Switch
Detector
2
Switch
CD Box 2 CD Box 1
W
H
Dimensions
HEIGHT (H) = 44mm
WIDTH (W) = 340mm
DEPTH (D) = 235mm
FIXING CENTRES = 370mm
OVERALL HEIGHT (INCLUDING PLUG, LEAD AND PLUG REMOVAL CLEARANCE) = 185mm
WEIGHT = 2.2Kg
OUT
1
Detector
1
D
Max lead length 10m
IN
4
Switch
Detector
4
Detector
5
5
Switch
Technical Data
Operational supply: 230v 50Hz Maximum load: 16A Maximum load per luminaire outlet: 2A (do not exceed 16A per box) A maximum of four digital dimming ballasts may be connected to each
luminaire outlet A maximum of 20 ballasts may be connected to each CD Box. Maintained live maximum output: 2A total per box
Supply terminal capacity: 1 x 2.5mm or 1 x 4.0mm
Override switch input connector: 1.5mm
MLS bus connector: 2.5mm
Emergency test bus connector: 2.5mm A maximum of five CD Boxes may be linked through the expansion
sockets. Only one detector may be connected to each detector input. Case material: Bright galvanized steel 1.0mm thick Finish: Natural
2
Detector
3
Switch
2 2
2
Switch
Detector
2
3
2
2
1
Switch
OUT
Detector
1
Auxiliary Items
MLS2000CDR MLS CONNECT Digital Remote Detector RB2000 MLS Digital Bus Power Supply RB2000LT MLS Digital Bus Power Supply ‘Lite’ CPW633 Luminaire Connection Lead: 6-pin/3-core/3m CPW643 Luminaire Connection Lead: 6-pin/4-core/3m CPW653 Luminaire Connection Lead: 6-pin/5-core/3m CPW663 Luminaire Connection Lead: 6-pin/6-core/3m BT5E020GY Patch Lead: 2m BT5E030GY Patch Lead: 3m Do not join to make BT5E050GY Patch Lead: 5m longer leads BT5E100GY Patch Lead: 10m CTB92084231902 Override Switch Input Connector
Ex-Or
Novar ED&S Limited Haydock Lane, Haydock, Merseyside WA11 9UJ Tel: +44 (0)1942 719229 Fax: +44 (0)1942 508753 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
MLSPG Plug Set for MLS Bus FSPG Plug Set for FailSafe Bus MLS05H6CT15MGFG MLS Bus Extension Lead: 5m (with glands) MLS10H6CT15MGFG MLS Bus Extension Lead: 10m (with glands) FS05H6CT15MF FailSafe Bus Extension Lead: 5m FS10H6CT15MF FailSafe Bus Extension Lead: 10m FS05H6CT15MGFG FailSafe Bus Extension Lead: 5m (with glands) FS10H6CT15MGFG FailSafe Bus Extension Lead: 10m (with glands) CPW6 Luminaire Connection Plug: 6-pin EPW223 FailSafe Bus Luminaire Connection Lead: 3m EPW2 FailSafe Luminaire Plug: 2-pin
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
W4077E
Loading...