Ex-Or CDW10U2UL Installation Instructions

by Honeywell
Connect UltraLite
Connection Centre
CDW10U2UL
Factory Configuration
When the unit is shipped, the dimming control and switched lives are linked in the terminal space. LK2 and LK3 MUST BE REMOVED if two detectors with dimming outputs are connected to the box. (LK1 must also be removed when using analogue detectors.)
A red indicator in the connection chamber indicates that power is present.
MAINTAINED LIVE
Internally connected to A2-6 and B2-6
ML
Co nnectio ns are ma de as
LIVE INPUT
Lin
Internally connected to A1 and B1 Lin internally linked
Lin
MAINS INPUT: 230V 50Hz Max load on any single outlet: 6A Max total load: 16A
N
tc: 5 - 50 C No user-serviceable parts inside
E
EARTH INPUT
Protected Earth E terminals internally linked
E
illustrated to the left. Two spare te rminals ar e pr ovided for termination purposes. Live (Lin) is routed to the two detector connectors (A1 and B1). Maintained Live (ML) is routed to the ten luminaire connectors, A2-A6 and B2-B6. SWA is the switched live output from a detector connected to A1.
SWB is the switched live output
GROUP A
SWA
(Connect wall switches here if not using plug-in detectors)
SWB
GROUP B
Manual input OneSwitch
PB-A
Group A
(Only when used with compatible detectors)
Manual input OneSwitch
Group B
PB-B
LK1 External Link
from a detector connected to B1. LK1 is a common connection between the switched live from each detector position. It must be rem ov e d t o s ep a ra te the luminaires into two groups.
Installation Instructions
WARNING 230V a.c.
The connections to this equipment should be made by a suitably qualified person in accordance with the current wiring regulations.
It is strongly recommended to use Ex-Or latching type connectors.
The unit must be earthed.
Connect UltraLite provides an efficient way to inter-connect presence detectors and luminaires using industry standard connectors. One or two detectors can be connected to up to ten luminaires depending upon the configuration required.
Electrical Connections
Screw terminals are provided under the cover for power supply connections and extension of the dimming control to other Connect Boxes. Override switches may also be connected here providing a means to control the switched live connections to the luminaires.
The installation should provide means of supply disconnection and over­current protection. Please refer to diagrams overleaf for further information.
The cover of the cable chamber is removed by inserting the tip of a flat bladed screwdriver into the catch recess and exerting light pressure on the handle in an inboard direction while lifting the long outboard edge of the cover.
The cable entries, for 20mm conduit, bushes or glands are semi-pierced in the walls of the cable chamber and can easily be removed from the outside with a 20mm hole saw.
If the cables are not routed right into the box through conduit or trunking, a cable restraining gland must be fitted at the cable entry for strain relief.
Fixing
The box should be sited on a suitable, smooth, flat surface using the two end fixing flanges. Consideration should be given to the box’s location as access will be required to install the plugs. The box must not be distorted when fixing.
Alternatively, the box may be rod-fixed. In this case, the fixing should be substantial enough to withstand the action of plugging and un-plugging connectors.
Spare
Spare
Spare terminals have no internal connection
External Links
B A B+ A+
_ _
Dimming Control
LK2
NOTE: Links 2 and 3 MUST BE REMOVED when
LK3
using two dimming detectors
Dimensions
Height (H) = 50mm (108mm including plug and lead) Width (W) = 315mm (361mm including mounting feet) Depth (D) = 205mm
Dimming Control Terminals
The Dimming Control signals from each detector to its group of luminaires are accessible at terminals under the connection chamber cover. Links are factory fitted to join the two groups on to one detector.
W
D 2
D
H
F
Fixing Centres (F) = 340mm Weight = 1.85 kg
Technical Data
OPERATING VOLTAGE: 230V 50Hz (UK & Europe) PRODUCT RATING/RECOMMENDED CIRCUIT PROTECTION: 16 Amps MAXIMUM LOAD PER OUTLET: 6 Amps* MAXIMUM TOTAL LOAD: 16 Amps* SUPPLY TERMINAL CAPACITY: 6.0mm (2 x 2.5mm ) DIMMING TERMINAL CAPACITY: 4.0mm CASE MATERIAL: Polycarbonate CASE FINISH: Lightly textured light grey
* Note: These specifications relate to the product when used as a simple wiring device. When mains-switching presence detectors are used in conjunction with this equipment, it is the presence detectors which will normally dictate the maximum load. It is important to check, and not exceed, the specification of the current-switching presence detectors, which will typically be around 6 Amps.
Ex-Or
Novar ED&S Limited Haydock Lane, Haydock, Merseyside WA11 9UJ Tel: +44 (0)1942 719229 Fax: +44 (0)1942 272767 Email: technicalsales.ex-or@honeywell.com www.ex-or.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
2 2
2
W5007C
Detector Connection
There are two detector connection positions on each box. The detector is connected by a flying lead and GST18/7 plug.
Switched Live
Neutral
Ensure max detector load is not exceeded
Live - Supply to detector
Push Button input to detector
Dimming control -
Detector output
-
+
Luminaire Connection
There are ten luminaire outlets on each box. Each luminaire is connected by a flying lead and GST18/6 plug.
Max load 6A per output
-Switched Live
Neutral
Maintained Live
Dimming control
See Detector Data
for allowed ballast load
-
+
A simple schematic showing connection information (including two spare terminals) follows:
Detector A
Group A
Maintained Live Live In Live In Neutral Earth Earth
Top Half
SWA SWB PushButton-A
PushButton-B Bottom Half
Spare
Spare
B-
A-
Group B
Detector B
If sockets A1 and B1 are not occupied by presence detector, those sockets may be used for luminaires, however the plug will need to be 7-pole and wired appropriately.
B+
A+
Connection Examples
Single Detector with 10 Luminaires (For load information, see Note under Technical Data)
A6 A5 A4 A3 A2 A1
B6 B5 B4 B3 B2 Not
Up to 10 luminaires
Auxiliary Items
LK1 is not required for analogue or switching type of detectors
used
ML
L
L
N
E
Detector
E
SWA
LK1
SWB
PB-A
no
PB-B
connection
B-
LK2
A-
B+
LK3
A+
Luminaire Leads:
CPWL633 3m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL635 5m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL643 3m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL645 5m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL653 3m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL655 5m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
Plug & Latching Shell (for luminaire): CPWL6 GST 18/6 Plug & Ex-Or Latching Shell Emergency Luminaire Leads:
CPWL663 3m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell CPWL665 5m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
Plug & Latching Shell (for detector):
CPWL7 GST 18/7 Plug & Ex-Or Latching Shell
UltraLite Detectors:
MS1100PFSWCWL7 Bronze Series PIR with photocell - slimline flush MS1200PFSWCWL7 Silver Series PIR with photocell - slimline flush
Manual control
ML
L
From Supply Isolator
N
E
Two Detectors (For load information, see Note under Technical Data)
A6 A5 A4 A3 A2 A1
GROUP A
GROUP B
B6 B5 B4 B3 B2 B1
LK1 is not required for analogue or switching type of detectors
Detector
Detector
ML
L
L
N
E
E
SWA
SWB
PB-A
PB-B
B-
A-
B+
A+
LK1
Remove
Links
LK2 and LK3
ML
L
N
E
Manual control
From
Supply
Isolator
Distribution Unit with External Low-Voltage Dimming Control
Up to 6 luminaires
A6 A5 A4 A3 A2 A1
B6 B5 B4 B3 B2 B1
Up to 6 luminaires
ML
SWA
SWB
PB-A
PB-B
B-
A-
B+
A+
L
L
N
E
E
no
connection
no
connection
no
connection
LK1
no
connection
no
connection
ML
L
N
E
External
Dimming
Control
From
From Supply Isolator
Distribution Unit with Mains-Based ‘OneTouch’ Dimming (for use with compatible Digital Ballasts)
A6 A5 A4 A3 A2 A1
B6 B5 B4 B3 B2 B1
Up to 12 luminaires
Notes:
(i) The dimming control connections are mains rated
ML
SWA
SWB
PB-A
PB-B
B-
A-
B+
A+
L
L
N
E
E
no
connection
no
connection
LK1
no
connection
no
connection
ML
L
From Supply Isolator
N
E
Manual control
Remove
Links
LK2 and LK3
(ii) Unit must not be used with multi-phase connections (iii) Mains-based dimming must not be used in conjunction with
Ex-Or’s range of presence detectors.
UltraLite Detectors cont:
MS2000DFCWL7 Silver Series PIR for DSI ballasts - flush MS2000DALIFCWL7 Silver Series PIR for DALI ballasts - flush MLS2421DFCWL7* Gold Series Microwave dual-output for DSI ballasts - flush MLS2421DALIFCWL7* Gold Series Microwave dual-output for DALI ballasts - flush MLS2021DFDFCWL7* Gold Series PIR dual-output for DSI ballasts - flush MLS2021DALIFCWL7* Gold Series PIR dual-output for DALI ballasts - flush UltraLite detectors incorporate the facility for OneSwitch operation and are supplied with 3m cable
and 7-way latching plug.
* These products do not have MLS functionality and cannot be connected using an MLS cable.