Exodraft EBC10v2 Fitting, Installation And Operating Instructions

Page 1
EBC10v2
EBC10v2
Fitting, installation and operating instructions
Read and save these instructions!
UK
Page 2
3120074 EBC10v2 UK 20190506
1. Specications .............................................................................................4
1.1 Dimensions and capacity ...................................................................................4
2. Product information .......................................................................................5
2.1 Accessories ................................................................................................6
2.2 Fitting .....................................................................................................6
2.2.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Layout of the user interface .................................................................................8
2.3.1 Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3.2 Terminal board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Mechanical installation ................................................................................... 10
2.5 Display .................................................................................................. 11
2.5.1 Using the interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.5.2 Setting the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5.3 Locked home screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.6 Introduction to the user interface ......................................................................... 14
2.7 Setup .................................................................................................... 15
2.7.1 Chimney draft setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.8 Pre/post-purge ........................................................................................... 16
2.9 Temperature Sensor ...................................................................................... 17
2.10 Quick menu for setpoint ..................................................................................17
3. Settings and troubleshooting .............................................................................18
3.1 Error codes ............................................................................................... 18
3.2 Overview of the service menu ............................................................................18
3.2.1 Light-emitting diodes and terminal board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.2.2 Switch between the basic functions of pressure control and supply air . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4. Pressure regulation of exodraft chimney fans ..............................................................22
4.1 Application .............................................................................................. 22
4.2 Functioning .............................................................................................. 22
4.3 Electrical connection ..................................................................................... 22
4.4 Wiring examples ......................................................................................... 22
4.4.1 One boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.2 Continuous operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4.3 One boiler with potential free contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
4.4.4 One boiler and extra monitoring with PDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.4.5 One boiler with potential free contact and temperature sensor input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5. Pressure regulation of supply air fan .......................................................................28
5.1 Application ..............................................................................................28
5.2 Mode of operation ....................................................................................... 28
5.3 Electrical connection ..................................................................................... 28
6. EU Declaration of Conformity .............................................................................29
Page 3
3120074 EBC10v2 UK 20190506
Symbols:
The following symbols are used throughout this manual to bring attention to potential danger or to important information about the product.
Prohibition symbol:
Failure to observe instructions marked with a prohibition symbol is associated with serious injury or death.
Danger symbol:
Failure to observe instructions marked with a danger symbol is associated with personal injury or material damage.
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY, OBSERVE THE FOLLOWING:
• Use this unit in the manner indicated by the manufacturer. If you have questions, contact the supplier.
• Before servicing the unit: Switch of the power and ensure that no one can turn it back on accidentally.
• Installation work should be done by qualied individuals according to applicable statutory regulations.
• Follow directions of the manufacturer along with general safety guidelines.
• This unit must be grounded during installation.
Disposal:
No special disposal requirements. Disposal of this product should be carried out in accordance with statutory regulations regarding electronic waste.
Installation: ________________________________
Installer: _________________________________
Installation Date: ____________________________
Page 4
4 • Technical specications
1. Specications
1.1 Dimensions and capacity
exodraft EBC10v2 Styring
Power supply V 1x 230 V / 50 Hz Max. motor load kW/hp 0.35/0.5 Operating temperature °C -20 to 50 Selection of operations Pa 0-150 Tolerance Pa +/-5% +24V supply mA 100 Max. Control and alarm relay Max 230 VAC/4A AC1 - 24 VDC/2A DC1 Boiler inputs 10-48 VDC / 10-230 VAC Output TRIAC VAC 10-230 Temperature Input Pt1000 Dimensions AxBxC 175 x 175 x 100 mm Weight kg 1.5 IP-rating IP 54 Fuse A 4.0T
XTP-150 sensor
Power supply VDC 24 VDC(+/- 15%) IP-Rating IP 54 Output VDC 0-10 VDC, max 10 mA Operating temperature °C -25 to 50 Tolerance Pa +/-5% Dimensions mm 80 x 82 x 55,5
Chimney Probe
Dimensions H mm 108
I mm 89
3120074 EBC10v2 UK 20190506
A
B
Page 5
3120074 EBC10v2 UK 20190506
Product information • 5Product information • 5
2. Product information
Description
EBC10v2 (exodraft Boiler Control) is a specially developed control component for constant pressure regulation of chimney draft. Available in variant:
• EBC10v2EU01 is suitable for indoor installation
By changing the setup, EBC10v2 can also:
• Regulate the supply of fresh air to the boiler room (see section 4).
Guide structure
EBC10v2 can be used either to control exodraft chimney fans or to control supply air fans.
The guide is divided into six sections::
• Section 1. Specications
• Section 2. ”Product Information”.
• Section 3: Settings and Troubleshooting
Section 4: Pressure control of exodraft chimney fans (default setting).
• EBC10v2 ensures and monitors consistent pressure in the chimney.
• EBC10v2 can also be used for boiler systems with modulating burners.
• The automation monitors the draft in the chimney, disabling the burner in case of malfunction.
• The automation is designed for both solid fuel boilers, atmospheric gas boilers, and boilers with oil and gas blow torches.
• EBC10v2 can control a chimney fan directly.
Section 5: Pressure control of supply air fan.
• EBC10v2 is used for control of a supply air fan.
• EBC10v2 ensures and monitors consistent pressure in the boiler room.
• The automation monitors the pressure in the boiler room, disabling the burner in case of malfunction.
• EBC10v2 can control a supply air fan directly.
Section 6: EU Declaration of Conformity
Page 6
6 • Product information6 • Product information
EBC10v2 includes the following:
EBC10v2
3120074 EBC10v2 UK 20190506
B
D
E
C
A
Pos. Part Item no. Function
A EBC10v2 EBC10v2EU01 Control of exodraft chimney fans and blow fans. For indoor
installation.
B Pressure
transducer (XTP)
D Measuring probe
for EBC10v2EU01
E 2 m. Silicone hose 2000335 Supplies the pressure transducer (XTP) with reference pressure
Instructions 3120070
XTP150 Measures the air pressure in boiler room, chimney, or outdoor
atmospheric pressure.
3200813 Measures pressure in the chimney.
from the measuring probe or from outdoors.
2.1 Accessories
Part Item no. Function
Relay ES12 For connection of more than two boilers External PDS PDSBOX Measures pressure in the chimney Rep. switch REP-AFB Isolation switch Measuring probe 90° 3200814 Measures pressure in the chimney (Pos. C)
2.2 Fitting
Cable length Max. cable length between EBC10v2 and XTP: 100 m. Max. cable length between EBC10v2 and chimney fan / fan: 100 m. Max. cable length between XTP and measuring probe 2 m.
Page 7
B1
3120074 EBC10v2 UK 20190506
2.2.1 Connection diagram
EBC10v2 is to be tted and connected as shown in the diagram below.
Product information • 7Product information • 7
B2
EBC10v2
A
Control of. Fitting procedure
Chimney fan
Note!
• Install EBC10v2EU01 and the pressure transducer (XTP) in the boiler room.
• Fit the measuring probe (A) in the boiler ue or in the manifold. However, for atmospher­ic boilers, the probe must always be positioned after the draft hood.
• Connect the hose from the measuring probe to the negative terminal on the pressure transducer “B1”.
• When the measuring probe is placed outside, it must be installed in a manner that pre­vents the formation of condensation or ice. EBC10v2EU01 comes with a straight measur­ing probe.
• EBC10v2 must always be installed where it is protected from wind and weather (rain, snow, etc.)
A
Ø 6.5
A
Ø 6.5
A
Supply air fan • Install the control and the pressure transducer (XTP) in the boiler room.
• Connect the hose for measuring reference pressure (outdoor atmospheric pressure) to the negative terminal “B1” on the pressure transducer. Run the hose outside the building to a place not exposed to the weather. The open end of the hose may be installed inside a box as described at the top of the next page.
Note! • Particularly when wanting positive pressure* in the chimney / boiler room:
• Connect the hose to the positive terminal on the pressure transducer “B2”.
• EBC10v2 comes with only 2 m of hose.
Note!
*The default setting of the EBC10v2 is for negative pressure regulation, but local statutory regulations may require constant positive pressure.
**Do not install the pressure transducer in an airtight enclosure, as it uses the atmospheric pressure for reference..
Page 8
8 • Product information8 • Product information
3120074 EBC10v2 UK 20190506
Make sure to position the pressure transducer (XTP) correctly.
Note Do not blow into the valves of the XTP.
For outdoor installation, place the pressure transducer where it is not exposed to the weather. For outdoor installation, the pressure transducer should be placed in a box tted with a hole (Ø2mm) in the bottom. The hole serves to ensure correct reference pressure and prevent water entry
If the pressure transducer is positioned where insects have access to the free end, installing a sinter lter is recommended
2.3 Layout of the user interface
2.3.1 Panel
EBC10v2
G
Pos. Del Funktion
A USB • USB Interface B Display • Shows operation and changes in the user interface (menu system)
• Indicates alarms
• shows normal operation status
C • Go forward/up in the menu system
A B
C D E F
D • Approves your action
• Forward
E • Go down in the menu system
F • Interrupt action
• Back
G Fuse • Fuse type
Page 9
3120074 EBC10v2 UK 20190506
Product information • 9Product information • 9
2.3.2 Terminal board
The following explains connection options for the terminal board
Terminal Betegnelse Terminal Use
1 PE Ground 18 Inactiv
2 Supply - L1 19 Inactiv 3
4 Chimney fan – N 21 Inactiv 5 Chimney fan - L1 (Regulating) 22 XTP-0V DC power supply
6 Chimney fan - PE Ground 23 XTP-24V DC power supply
7 Frequency converter relay NO 24 Inactiv 8 Inactiv 25 Inactiv 9 Inactiv 26 Inactiv 10 Alarm Out - NO 27 0V DC Power supply
Supply – N
20 Inactiv
(transducer)
(transducer)
11 Alarm Out - C 28 24 VDC power supply (Max.
100 mA)
12 Voltage input from appliance /
boiler 1 thermostat optocoupler (+) (10-230V AC/DC
13 Voltage input from appliance /
boiler 1 thermostat optocoupler (-) (10-230V AC/DC
14 Burner 1 relay switch-Normally
open (max. 230 VAC, 2 amps.)
15 Burner 1 relay switch-Common
(max. 230 VAC, 2 amps.) 16 Inactiv 33 Pt1000 17 Inactiv 34 Not used
* However, terminals 30, 31, and 32 may be used for connecting other auxiliary monitoring equipment as well.
29 24 VDC power supply (Max.
100 mA)
30 PDS-NC (normally closed)
Proven draft switch
31 PDS-NO (normally open) Prov-
en draft switch
32 PDS-C (shared) Tested draft
switch
35 Pt1000
Page 10
100 m
2 m
EBC10v2 Control
EBC10v2
10 • Product information10 • Product information
3120074 EBC10v2 UK 20190506
2.4 Mechanical installation
The control and the transducer must be installed inside, preferably in the boiler room. The control does not need to be installed in a cabinet.
Do not install the transducer in an airtight enclosure. It uses the boiler room pressure / atmospheric pressure as reference pressure.
The control can be installed directly on the wall or somewhere similar.
Take o the lid. The installation holes are placed under the plastic screws keeping the cover in place. The distance between the control and the transducer should not exceed 100 m.
EBC10v2
Page 11
3120074 EBC10v2 UK 20190506
Product information • 11Product information • 11
2.5 Display
The diagram below shows the layout of the display on the EBC10v2. All possible display values are indicated:
INTAKE : 36 Pa
OUT : 15 %
SETPOINT : 55 Pa
The purpose of the display is to indicate:
• Operating information (pressure, etc.)
• Alarms
• Parameters
• Set points
• USB
2.5.1 Using the interface
The user interface is operated via four buttons with the following functions:
Tast Funktion
• Activate the service menu
• Edit and save settings
• Go to menu item and adjust value
• Return to operation screen from any point in the menu system
• Reset alarm when “Manual Reset” is selected in menu 2.3.
Page 12
12 • Product information12 • Product information
2.5.2 Setting the language
It is possible to change the language on the display. The default setting is in English. To set the language on the screen, follow these steps:
Step Action Display
• Go to the Main Menu
• Select 4. User Interface
MAIN MENU
1 REGULATION 2 ALARM 3 SERVICE
4 USER INTERFACE
3120074 EBC10v2 UK 20190506
• Select 1. Display
• Select 1. Language
• Use the arrow keys to switch between languages
• Finish the approval/storage via the check box
• The display should now have switched to the desired language
USER INTERFACE
1 DISPLAY
DISPLAY
1 LANGAUGE
2 UNITS 3 LCD BACKLIGHT 4 LCD CONTRAST
DISPLAY
LANGUAGE
ENG
ENG
4
4 1
4 1 1
Page 13
3120074 EBC10v2 UK 20190506
2.5.3 Locked home screen
Access to the service menu is open as a default. It is possible to lock the home screen with a code.
To turn the code on/o, follow these steps:
Step Action Display
• Go to the Main Menu
• Select 3. Service
MAIN MENU
1 REGULATION 2 ALARM
3 SERVICE
4 USER INTERFACE
Product information • 13Product information • 13
• Select 7. Enable Pin
• Use the arrow keys to toggle between o and on
SERVICE
2 I/O-VIEW 3 OPTION 4 FACTORY DEFAULTS 5 MANUAL MODE 6 USB CONFIG
7 ENABLE PIN
SERVICE
ENABLE PIN
ON
• Approve/Save with chech mark
If you have selected the code to be enabled:
• Activate the service menu (keep the check button pressed for 5 seconds)
• Enter code 3142
• Set the value with the arrows and conrm on the way / nally with the check button
ENTER PIN CODE
3142
3
3 7
Page 14
14 • Product information14 • Product information
2.6 Introduction to the user interface
Menu structure
Only qualied personnel should use the service menu
3120074 EBC10v2 UK 20190506
The service menu consists of four main menus, each divided into submenus.
• 1. Regulation
• 2. Alarms
• 3. Service
• 4. User interface
Function description Display indicates
Menu: 11.1 Pressure regulation: 0-95%: 0-150 Pa
1.2 Operating mode: Continuous or Intermittent
1.3 Pre-purge: Time and speed mode
1.4 Post-purge: Time and speed mode
1.5 Sensor: Range min. and max.
1.6 Properties: See page 18 (2.9 Service menu overview)
Menu: 22.1 Error: Alarm type
2.2 Error log: Alarm log covering 19 readings
2. 3 Reset: Automatic or manual
MAIN MENU
1 REGULATION
2 ALARM 3 SERVICE 4 USER INTERFACE
REGULATION
1 SET PRESSURE
2 OPERATION MODE 3 PRE-PURGE 4 POST-PURGE 5 SENSOR 6 PROPERTIES
ALARM
1 ERROR
2 ERROR LOG 3 RESET
1
2
Menu:33.1. Version no.
3.2 I/0-view: Input/output monitor/activator
3.3 Option: Bearing cycle, prime, draft input delay.
3.4 Factory presets: Default settings 5 Manual mode: TRIAC/frequency converter output 0-100% 6 USB cong: Updating of rmware, conguration les
Menu: 44.1: Display: Language, units, and LCD settings
See page 18 (2.9 Service menu overview) for detailed overview
SERVICE
1 VERSION
2 I/O-VIEW 3 OPTION 4 FACTORY DEFAULTS 5 MANUAL MODE 6 USB CONFIG
USER INTERFACE
1 DISPLAY
3
4
Page 15
3120074 EBC10v2 UK 20190506
2.7 Setup
2.7.1 Chimney draft setting
To set the pressure in the chimney, follow the procedure detailed below:
Step Action Display
• Start the system
• EBC10v2 displays the actual negative pressure (in this example, 55 Pa)
EXHAUST : 149 Pa
OUT : 48 %
SETPOINT : 55 Pa
Product information • 15Product information • 15
2*
• Press and hold for 5 seconds to get into the service menu
• Enter code: 3142
• Select menu 1
• Select menu 1.1
• Set required pressure
Note: This procedure only covers setting the pressure in the chimney. * Only if the controller is locked with a pin code
MAIN MENU
1 REGULATION
2 ALARM 3 SERVICE 4 USER INTERFACE
REGULATION
1 SET PRESSURE
2 OPERATION MODE 3 PRE-PURGE 4 POST-PURGE 5 SENSOR 6 PROPERTIES
REGULATION
SET PRESSURE 37 % : 55 Pa
7
RANGE 2-95 %
1
1 1
Page 16
16 • Product information16 • Product information
2.8 Pre/post-purge
To set up pre-/post-purge period, follow procedure below:
Step Action Display
• Start the system
• EBC10v2 displays the actual negative pressure (in this example, 55 Pa)
3120074 EBC10v2 UK 20190506
INTAKE : 149 Pa
OUT : 100 %
SETPOINT : 55 Pa
2*
• Press and hold for 5 seconds to get into the service menu
• Enter code: 3142
• Select menu 1
• w
• Regulation 1
• Select menu 1.2 Pre-purge
• Select menu 1.3 Post-purge
• Select either 1.3.1 Time or 1.3.2 speed mode
5 • Set the desired time in seconds
• 0-1800 seconds
MAIN MENU
1 REGULATION
2 ALARM 3 SERVICE 4 USER INTERFACE
REGULATION
1 SET PRESSURE 2 OPERATION MODE
3 PRE-PURGE
4 POST-PURGE 5 SENSOR 6 PROPERTIES
PRE-PURGE
1 TIME
2 SPEED MODE
PRE-PURGE
TIME
0
RANGE 0-1800 Sec
1
1 3
1 3 1
6 • Fix 20-100
• or variable
• Finish and return to operation screen with
* Only if the controller is locked with a pin code
PRE-PURGE
SPEED MODE
Fix 100
1 3 2
Page 17
3120074 EBC10v2 UK 20190506
2.9 Temperature Sensor
To activate the temperature sensor, follow the procedure below:
Step Action Display
• Go to the Main Menu
• Select 1. Regulation
MAIN MENU
1 REGULATION
2 ALARM 3 SERVICE 4 USER INTERFACE
Product information • 17Product information • 17
• Select 7. Temperature sensor
• Select 1. Enable Sensor
• Use the arrow keys to toggle between o and on
• Approve/Save with chech mark
REGULATION
2 OPERATION MODE 3 PRE-PURGE 4 POST-PURGE 5 SENSOR 6 PROPERTIES
7 TEMP. SENSOR
TEMP. SENSOR
1 ENABLE SENSOR
2 ENABLE AUTOSTART 3 START TEMPERATURE 4 STOP TEMPERATURE 5 FORCED OP. 6 TEMP. ALARM
TEMP. SENSOR
ENABLE SENSOR
ON
2.10 Quick menu for setpoint
To access the set point menu quickly, follow the procedure below:
Step Action Display
• Start the system
• EBC24 displays the actual negative pressure (in this exam­ple, 55 Pa)
INTAKE : 149 Pa
OUT : 100 %
SETPOINT : 55 Pa
1
1 7
1 7 1
• Press
• Use the arrow keys to switch between the set pressure
• Approve/Save with chech mark
REGULATION
SET PRESSURE
19
RANGE 0-150 Pa
Page 18
18 • Product information18 • Product information
3120074 EBC10v2 UK 20190506
3. Settings and troubleshooting
3.1 Error codes
Most terminal connections are monitored for correct operation. An LED light indicates operating status. If a light comes on, it is an indication that everything is functioning correctly, while a light going out indicates a problem in the circuit it monitors. In addition, error codes are shown on the display.
The error codes are:
Display Explanation
A1 Draft Exhaust Insucient pressure may be due to:
1. Chimney fan has insucient capacity
2. Mechanical or electrical fan failure
3. Blocked chimney
4. Introduction of excessive dilution air
5. XTP sensor not responding correctly A2 Power Fault Indicates that there has been a power fault A3 XTP-Exhaust Indicates a disconnected signal from the XTP sensor on the exhaust side to the control. May
A4 Error Start Indicates that the control has been unable to release the burner within 15 minutes. A5 Alarm Override Indicates alarm has been disregarded A6 Draft Input Missing signal from PDS function. Indicates a defective function. A7 RS485 error No communication between EBC10v2 and modbus network A8 Priority The draft has been insucient and therefore the control has been in priority
be caused by:
1. Lose connections
2. Faulty XTP-sensor
3. Defective controller
3.2 Overview of the service menu
The service menu is built in 4 levels and associated submenus.
Menu Sub-menu Function Display Description Classication Standard
1 Exhaust EXHAUST
11 Draft set point SET EXHAUST Adjustment of exhaust setpoint. 2%-95% af sensor 17% 12 Operation mode EXHAUST MODE Continuous or intermittent operation. In inter-
mittent mode the exhaust fan runs only if one or more boiler inputs are active.
13 Pre-purge PRE-PURGE Pre-purge settings
131 Time TIME Pre-purge time in seconds 0-1800 0 132 Operation mode SPEED MODE Select variable if the pre-purge should be con-
trolled by the XTP-sensor or have a xed speed.
14 Post-purge POST-PURGE Post-purge settings
141 Time TIME Post-purge time in seconds 0-1800 0 142 Operation mode SPEED MODE Select variable if the post-purge should be con-
trolled by the XTP-sensor or have a xed speed.
15 Sensor SENSOR
151 Min. pressure RANGE MIN XTP minimum pressure in Pa. -500 – 500 Pa 0 152 Max. pressure RANGE MAX XTP Maximum pressure in Pa. 0 – 1000 Pa 150 Pa
16 Parameters PROPERTIES
161 Alarm limit draft ALARM LIMIT Select the alarm limit of the draft. The value is in
% of the set point.
162 Alarmdelay ALARM DELAY Select a alarm delay from 0-120 seconds. 0 – 120 s 15 163 Min. voltage SPEED MIN Mimimum speed of the fan 0 – MENU 164 15 % 164 Max. voltage SPEED MAX Maksimum speed of the fan. MENU 163-100% 100 165 Xp EXHAUST Xp Proportional gain. 0-30 15 166 Ti EXHAUST Ti Integral gain. 0-30 8
167 Sampling rate SAMPLING RATE Set the sampling rate for the PID Loop 1-10 10
168 Pressure type PRESSURE MODE Positive or negative pressure in the stack. Positive or Negative Negative
Continuous/ Intermittent
Variable / FIX 20-100% FIX 100%
Variable / FIX 20-100% Variable
If 167 = "Negative" ->50
- 80 %. If 167 = "Positive" -> 150
- 300 %"
Intermittent
64 % (167 = "Negative") 144 % (167 = "Positive")
Page 19
3120074 EBC10v2 UK 20190506
Menu Sub-menu Function Display Description Classication Standard
17 Temperature Sensor TEMP. SENSOR
171 Enable Sensor ENABLE SENSOR Enables the temperature sensor and displays
172 Enable Autostart ENABLE AUTOSTART Enables the temperature as a start signal for the
173 Start Temperature START TEMPERA-
TURE
174 Stop Temperature STOP TEMPERATURE Sets the stop temperature 0-Start Temperature - 5 35° C
the current temperature on the main screen
controller Sets the start temperature 40-100° C 40° C
On/O O
On/O O
Product information • 19Product information • 19
175 Forced operation FORCED OP.
1751 Set Forced opera. SET FORCED OP. Enables the full speed operation of the
On/O O chimney fan, if the forced operation temperature setpoint is reached
1752 Temperature Limit Temperature Limit
Sets the limit temperature
5-450° C 250° C
176 Temperature Alarm TEMP. ALARM
1761 Enable Temp. Alarm ENABLE. TEMP.
ALARM
Enables the alarm relay if the setppoint is reached
On/O O
1762 Alarm Limit ALARM LIMIT Sets the alarm limit 25-450° C 450° C 1763 Alarm Delay ALARM DELAY Sets the delay before the alarm 0-60 Seconds 5
169 Application APPLICATION Sets if the control has to work as Exhaust
Exhaust / Intake Exhaust or Intake
2 ALARM
3 Service
21 22
23
31 32
321 BURNER I/O AUX OUT XXX
322 EXHAUST I/O EXH XTP x.xV OFF
323 Draft input DRAFT INPUT ON/
Alarm Status Alarm log
Reset
Version no. I/O
ERROR ERROR LOG The last 10 alarms will be saved in the menu.
RESET Selecting "AUTO" will automatic reset the
SERVICE
VERSION Software version is showed. I/O-VIEW
AUX IN XX
EXH VFD x.xV OFF
OFF
The error is shown here
MAN / AUTO AUTO alarm after 15 seconds. If "MAN" is selected, the "X" has to be pressed.
In this menu the status of the boiler I/O is shown. By pressing athe AUX OUT relays can be activated by pressing up and down. Multiple activations of the a button will move from relay 1 to 6 XTP, VFD and VFD relay status for Exhaust.
Draft Input I/O status.
324 Alarm relay ALARM OUTPUT
ON/OFF
33 Options OPTION
331 Bearing cycle BEARING CYCLE Selecting "YES" will enable a bearing cycle on
332 Allow prime Selecting a number from 0-250 will enable the
333 Draft Input Delay DRAFT INPUT DELAY The delay before the control goes into Fraft
34 Factory reset FAC TORY If "YES" is selected, a factory reset will be
35 Manual Mode MANUAL MODE Set a specic value for a continuous
36 USB conguration USB CONFIG
361 format USB FORMAT USB Selecting "YES" will format the USB ash drive.
362 Data Log DATA LOG USB /
INTERNAL
363 Save cong. le SAVE CONFIG FILE Slecting "YES" provides the possibility to select
364 Load cong. le LOAD CONFIG FILE Selecting "YES" will download the current
365 Upgrade rmware UPGRADE FIRM-
WARE
4 User Interface USER INTERFACE
41 Display DISPLAY
411 Language LANGUAGE Language. ENG/DEU/DNK/SWE/
412 Pressure units UNITS Pa or inWC units. Pa / inWC inWC 413 LCD backlight LCD BACKLIGHT LCD backlight turned on or not. The USE param-
414 LCD contrast LCD CONTRAST 10 – 100 % 50
Alarm relay output status.
present fans, if the boilers has not been active for 24 hours.
prime function. This allows the boilers to be activated even though no sucient draft is present.
Alarm
performed.
chimney fan speed.
Notice! All data will erased! Selecting "USB" will store the alarm log on the USB ash drive, "INT" will store the log in the internal memory.
congurationles stored on the USB ash drive.
conguration to the USB ash drive. This function provides the possibility to upgrade the rmware by means of a USB Stick
eter will cause the backligt to be turned on if a button is pressed.
ON/OFF ON
0-250 s / o O
0-20 s 0 s
YES/NO NO
0-100% 0%
i.e. disabled
YES / NO NO
USB / INT INT
YES / NO NO
YES / NO NO
ENG
NOR/FRA/ESP
ON / OFF / USE ON
Page 20
PT1000
PT1000
20 • Product information20 • Product information
3120074 EBC10v2 UK 20190506
3.2.1 Light-emitting diodes and terminal board
The chart below lists the terminal board connection options and light-emitting diode displays.
No. Designation Max. load Meaning when the light-emitting diode is:
1, 2 og 3 SUPPLY IN 230-240 V AC +/- 10 % green: EBC20 is connected to power supply
4, 5 og 6 FAN OUT 3A green: the Triac output is active 7 og 8
VFD OUT 9, 10 og 11 ALARM OUT 250 V AC, 8A, AC3 green: the relay is active 12 og 13 BOILER 1 IN 18 til 230 V DC/V AC green: the input is active 14 og 15 BURNER 1 OUT 250 V AC, 4A, AC3 green: the relay is closed 16 og 17 Idle 18 og 19 Idle 28 og 29 24 V DC OUT 100 mA green: voltage is OK
20 og 21 Idle 20 mA green: output is active 22, 23 og 24 XTP IN green: XTP connected
30, 31 og 32 PDS IN * green: C & NO are closed
250 V AC, 8A, AC3 green: the relay is closed
red: overload
red: return voltage > 12 V DC
* However, terminals 30, 31, and 32 may be used for connecting other auxiliary monitoring equipment as well.
Page 21
3120074 EBC10v2 UK 20190506
Pressure control • 21
3.2.2 Switch between the basic functions of pressure control and supply air
Default settings EBC10v2 defaults to constant pressure regulation of exodraft chimney fans (basic function 1 Exhaust/Intake)
Change of basic function
Step Action Display
• Press and hold for 5 seconds
2*
• Enter code: 3142
• Use arrows to select followed by
EXHAUST : 149 Pa
OUT : 15 %
SETPOINT : 55 Pa
ENTER PIN CODE
3142
• Select menu 1 Regulation
• Select menu 1.6 Properties
• Select menu 1.6.9 application
• Select menu 1.6.9 application
1 Pressure regulation of exodraft chimney fans (Exhaust)
2 Pressure control of Supply air fan (Indtake)
• Finish and return to operation screen
MAIN MENU
1 REGULATION
2 ALARM 3 SERVICE 4 USER INTERFACE
REGULATION
1 SET PRESSURE 2 OPERATION MODE 3 PRE-PURGE 4 POST-PURGE 5 SENSOR
6 PROPERTIES
PROPERTIES
4 SPEED MAX 5 PRESSURE XP 6 PRESSURE TI 7 SAMPLING RATE 8 PRESSURE MODE
9 APPLICATION
PROPERTIES
APPLICATION
INTAKE : 149 Pa
OUT : 100 %
SETPOINT : 55 Pa
1
1 6
1 6 9
* Only if the controller is locked with a pin code
Page 22
22 • Pressure control
4. Pressure regulation of exodraft chimney fans
4.1 Application
Field of application
• EBC10v2 can also be used for boiler systems with modulating burners.
• The automation is designed for both solid fuel boilers, atmospheric gas boilers, and boilers with oil and gas blow torches.
• EBC10v2 can control a chimney fan directly.
4.2 Functioning
General function
• The automation monitors the draft in the chimney, disabling the burner in case of malfunction (the alarm diode on the EBC10v2 turns on).
• When the boiler thermostat demands heat, the chimney fan will start at max. voltage.
• When the EBC10v2 registers sucient chimney draft, the burner is released.
• The EBC10v2 maintains the set pressure by regulating the voltage. The pressure is shown in the display.
• In the event of insucient venting, the burner will initially be disconnected after 15 seconds. Insucient venting is less than 64% of the set value, corresponding to less than 80% of ow.
• When the boiler turns o, the chimney fan stops as well. It is, however, possible to set a post-purge period for the chimney fan (see page 23). Alternatively, the control system can be connected in a way that keeps the chimney fan running continuously (see page 21).
3120074 EBC10v2 UK 20190506
Light-emitting diodes and output signals
All inputs and outputs are connected to a light-emitting diode for monitoring and servicing of the system (see section
2.9.1 Light-emitting diodes and terminal board, page 17)
4.3 Electrical connection
This work must be performed by a qualied electrician in accordance with locally applicable rules and
legislation.
Installation of the supply cable must comply with applicable legislation and regulations. The grounding terminal ( ) must always be connected.
When connecting a pressure transducer (XTP) shielded cable must be used.
Isolation switch
exodraft a/s stresses that according to EU’s Machinery Directive, an isolation switch must be incorporated into the xed installation. The isolation switch is not supplied by exodraft, but is available as an accessory.
4.4 Wiring examples
As a constant pressure regulator for exodraft chimney fans, the EBC10v2 can be connected to a range of dierent signals. The following pages are wiring examples and illustrate the following:
4.4.1 One boiler
4.4.2 Continuous operation
4.4.3 One boiler with potential free contact
4.4.4 One boiler and extra monitoring with PDS
4.4.5 One boiler with potential free contact and temperature sensor input
exodraft recommends contacting the boiler manufacturer for correct connection to the boiler automation.
Page 23
3120074 EBC10v2 UK 20190506
SUPPLY IN
VFD Out
L1 N N
FAN MOTOR OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUT BOILER
1 - IN
BURNER 1 - OUT
BOILER 2 - IN
BURNER 2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDS Pt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTP RS485
4.4.1 One boiler
Pressure control • 23
This example shows how to connect a voltage signal (18-230 V AC/DC) to EBC24 to start/stop the chimney fan.
• Connect the supply to terminals 1-3.
• Connecting the boiler:
• Connect the burner start signal (L) to terminal 12.
• Connect the neutral wire to terminal 13.
• The start signal for the burner is sent from terminal 15.
• Loop terminals 12 and 14.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the dis­play to terminal 6.
Page 24
SUPPLY IN
VFD Out
L1 N N
FAN MOTOR OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUT BOILER
1 - IN
BURNER 1 - OUT
BOILER 2 - IN
BURNER 2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDS Pt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTP RS485
24 • Pressure control
4.4.2 Continuous operation
3120074 EBC10v2 UK 20190506
This example shows how to connect a voltage signal (23 V DC) to EBC10v2 to start the chimney fan.
• Connect the supply to terminals 1-3.
• Loop terminals 12 and 29.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to terminal 6.
Page 25
SUPPLY IN
VFD Out
L1 N N
FAN MOTOR OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUT BOILER
1 - IN
BURNER 1 - OUT
BOILER 2 - IN
BURNER 2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDS Pt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTP RS485
3120074 EBC10v2 UK 20190506
4.4.3 One boiler with potential free contact
Pressure control • 25
The example shows how a voltage signal (24 V DC) is connected to EBC24 for the chimney fan to run continuously.
• Connect the supply to terminals 1-3.
• Loop terminals 12 and 29.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to terminal 6.
Page 26
26 • Pressure control
4.4.4 One boiler and extra monitoring with PDS
3120074 EBC10v2 UK 20190506
SUPPLY IN
L1 N N
FAN MOTOR OUT
REG
VFD Out
NO
ALARM OUT BOILER
C
NC
NO
BURNER
BOILER
1 - IN
1 - OUT
C
+/~
-/~
NO
C
2 - IN
+/~
-/~
BURNER 2 - OUT
24 VDC
C
NO
0V
VFD
0V
24V
NC
0-10V
PDS Pt1000
NO
C
Pt1000
XTP RS485
0V
24V
0-10V
Pt1000
0V
A
B
This example shows how to connect a potential free contact to the EBC24 to start/stop the fan:
• Connect the supply voltage to terminals 1-3.
• Connection to the boiler:
• Connect the potential free contact to terminals 12 & 29.
• Loop terminals 13 & 28.
• Connect the burner start signal to terminals 14 & 15.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the dis­play to terminal 6.
Page 27
1 2 3 4 5 6 7 8
SUPPLY IN
VFD Out
L1 N N
FAN MOTOR OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUT BOILER
1 - IN
BURNER 1 - OUT
BOILER 2 - IN
BURNER 2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDS Pt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTP RS485
3120074 EBC10v2 UK 20190506
4.4.5 One boiler with potential free contact and temperature sensor input
Pressure control • 27
This example shows how to connect a PDS to EBC24. The PDS supplies extra monitoring
• Connecting PDS:
• Remove the factory installed wiring between terminals 30 and 32.
• Connect PDS to terminals 30, 31 and 32.
• Connect the supply to terminals 1-3.
• Connecting the boiler:
• Connect the potential free contact to terminals 12 & 29.
• Connect the burner start signal to terminals 14 & 15.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to terminal 6.
Page 28
28 • Pressure control
3120074 EBC10v2 UK 20190506
5. Pressure regulation of supply air fan
5.1 Application
General
• The EBC10v2 is used to control a supply air fan.
• EBC an control a supply air fan directly.
Positioning
24 cInstall the EBC10v2 and the pressure transducer (XTP) in the boiler room as described in section 2.2 Fitting, pages 6+7
5.2 Mode of operation
General function
• The EBC10v2 monitors the pressure in the boiler room and disconnects the burner in the event of errors (the alarm diode on the EBC10v2 will turn on).
• When the pressure in the boiler room changes, the EBC10v2 will change the fan speed in order to meet the set point pressure for the boiler room.
• The EBC10v2 is connected to the boiler system in such a way that when a heating requirement arises, the EBC10v2 will start the fan, delaying the start of the boilers until the pressure in the boiler room is ade­quate.
• A safety function ensures that if the pressure in the boiler room is insucient, the EBC22 will shut down the boilers the EBC10v2 will shut down the boilers, should the pressure in the boiler room become insu­cient.
5.3 Electrical connection
This work must be performed by a qualied electrician in accordance with locally applicable rules and legislation.
Installation of the supply cable must comply with applicable legislation and regulations. The grounding terminal ( ) must always be connected.
When connecting a pressure transducer (XTP) shielded cable must be used.
Isolation switch
exodraft a/s stresses that according to EU’s Machinery Directive, an isolation switch must be incorporated into the xed installation.
The isolation switch is not supplied by exodraft, but is available as an accessory.
exodraft recommends contacting the boiler manufacturer for correct connection to the boiler automation.
Page 29
3120074 EBC10v2 UK 20190506
6. EU Declaration of Conformity
Declaration of Conformity
Pressure control • 29
DK: EU-Overensstemmelseserklæring GB: Declaration of Conformity DE: EU-Konformitätserklärung FR: Déclaration de conformité de l’Union Européenne NO: EU-Samsvarserklæring
exodraft a/s
C.F. Tietgens Boulevard 41
DK-5220 Odense SØ
-erklærer på eget ansvar, at følgende produkter:
-hereby declares that the following products:
-erklärt hierdurch auf eigene Verantwortung, daß folgende Produkte:
-déclare, sous sa propre responsabilité, que les produits suivants:
-erklærer på eget ansvar at følgende produkter:
-som er omfattet af denne erklæring, er i overensstemmelse med følgende standarder:
-were manufactured in conformity with the provisions of the following standards:
-die von dieser Erklärung umfaßt sind, den folgenden Normen:
-auxquels s’applique cette déclaration sont en conformité avec les normes ci-contre:
-som er omfattet av denne erklæring, er i samsvar med følgende stan­darder:
EN 60335-1, EN60335-2-102, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 14459:2008
-i.h.t bestemmelser i direktiv:
-in accordance with
-entsprechen gemäß den Bestimmungen der folgenden Richtlinien:
-suivant les dispositions prévues aux directives:
-i.h.t bestemmelser i direktiv:
-Lavspændingsdirektiv:
-the Low Voltage Directive:
-Niederspannungsrichtlinie:
-Directive Basse Tension:
-Lavspenningsdirektivet:
2014/35/EC
-EMC-direktivet:
-and the EMC Directive:
-EMV-Richtlinie:
-Directive Compatibilité Electromagnétique:
-EMC-direktivet:
2014/30/EC
Odense, 03.04.2017
-Adm. direktør
-Managing Director
Jørgen Andersen
NL: EU-Conformiteits verklaring SE: EU-Överensstämmelsedeklaration FI: EU-Vaatimustenmukaisuusvakuutus IS: ESS-Samræmisstaðfesting IT: Dichiarazione di Conformità Unione Europea
-veklaart dat onderstaande producten:
-deklarerar på eget ansvar, att följande produkter:
-vastaa siltä, että seuraava tuote:
-Staðfesti à eigin àbyrgð, að eftirfarandi vörur:
-dichiara con la presente che i seguenti prodotti:
EBC24
-zijn vervaardigd in overeenstemming met de voorschriften uit de hieronder genoemde normen en standaards:
-som omfattas av denna deklaration, överensstämmer med följande standarder:
-jota tämä selvitys koskee, on seuraavien standardien mukainen:
-sem eru meðtalin i staðfestingu Pessari, eru i fullu samræmi við eftirtalda staðla:
-sono stati fabbricati in conformità con le norme degli standard seguenti:
-en voldoen aan de volgende richtlijnen:
-enligt bestämmelserna i följande direktiv:
-seuraavien direktiivien määräysten mukaan:
-med tilvisun til àkvarðana eftirlits:
-in conformità con le direttive:
-de laagspanningsrichtlijn:
-Lågspänningsdirektivet:
-Pienjännitedirektiivi:
-Smáspennueftirlitið:
-Direttiva Basso Voltaggio:
-en de EMC richtlijn:
-EMC-direktivet:
-EMC-direktiivi:
-EMC-eftirlitið:
-Direttiva Compatibilità Elettromagnetica:
-Algemeen directeur
-Geschäftsführender Direktor
-Président Directeur Général
-Verkställande direktör
-Toimitusjohtaja
-Framkvemdastjori
-Direttore Generale
Page 30
Page 31
Page 32
DK: exodraft a/s
C. F. Tietgens Boulevard 41 DK-5220 Odense SØ Tel: +45 7010 2234 Fax: +45 7010 2235 [email protected] www.exodraft.dk
SE: exodraft a/s
Kasten Rönnowsgatan 3B 4tr SE-302 94 Halmstad Tlf: +46 (0)8-5000 1520 [email protected] www.exodraft.se
NO: exodraft a/s
Storgaten 88 NO-3060 Svelvik Tel: +47 3329 7062 [email protected] www.exodraft.no
UK: exodraft Ltd.
10 Crestway, Tarleton GB-Preston PR4 6BE Tel: +44 (0)1494 465 166 Fax: +44 (0)1494 465 163 [email protected] www.exodraft.co.uk
DE: exodraft GmbH
Soonwaldstraße 6 DE-55569 Monzingen Tel: +49 (0)6751 855 599-0 Fax: +49 (0)6751 855 599-9 [email protected] www.exodraft.de
3120074 EBC10v2 UK 20190506
Loading...