6. EU Declaration of Conformity .............................................................................29
Page 3
3120074 EBC10v2 UK 20190506
Symbols:
The following symbols are used throughout this manual to bring attention to potential danger or to important
information about the product.
Prohibition symbol:
Failure to observe instructions marked with a prohibition symbol is associated with serious injury or death.
Danger symbol:
Failure to observe instructions marked with a danger symbol is associated with personal injury or material
damage.
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY, OBSERVE THE FOLLOWING:
• Use this unit in the manner indicated by the manufacturer. If you have questions, contact the supplier.
• Before servicing the unit: Switch of the power and ensure that no one can turn it back on accidentally.
• Installation work should be done by qualied individuals according to applicable statutory regulations.
• Follow directions of the manufacturer along with general safety guidelines.
• This unit must be grounded during installation.
3
Disposal:
No special disposal requirements. Disposal of this product should be carried out in accordance with statutory
regulations regarding electronic waste.
Installation: ________________________________
Installer: _________________________________
Installation Date: ____________________________
Page 4
4 • Technical specications
1. Specications
1.1 Dimensions and capacity
exodraft EBC10v2 Styring
Power supplyV1x230 V / 50 Hz
Max. motor loadkW/hp0.35/0.5
Operating temperature°C-20 to 50
Selection of operationsPa0-150
TolerancePa+/-5%
+24V supplymA100 Max.
Control and alarm relayMax 230 VAC/4A AC1 - 24 VDC/2A DC1
Boiler inputs10-48 VDC / 10-230 VAC
Output TRIACVAC10-230
Temperature InputPt1000
DimensionsAxBxC175 x 175 x 100 mm
Weightkg1.5
IP-ratingIP 54
FuseA4.0T
XTP-150 sensor
Power supply VDC24 VDC(+/- 15%)
IP-RatingIP 54
Output VDC0-10 VDC, max 10 mA
Operating temperature°C-25 to 50
TolerancePa+/-5%
Dimensionsmm80 x 82 x 55,5
Chimney Probe
DimensionsH mm108
I mm89
3120074 EBC10v2 UK 20190506
A
B
Page 5
3120074 EBC10v2 UK 20190506
Product information • 5Product information • 5
2. Product information
Description
EBC10v2 (exodraft Boiler Control) is a specially developed control component for constant pressure regulation of
chimney draft. Available in variant:
• EBC10v2EU01 is suitable for indoor installation
By changing the setup, EBC10v2 can also:
• Regulate the supply of fresh air to the boiler room (see section 4).
Guide structure
EBC10v2 can be used either to control exodraft chimney fans or to control supply air fans.
The guide is divided into six sections::
• Section 1. Specications
• Section 2. ”Product Information”.
• Section 3: Settings and Troubleshooting
Section 4: Pressure control of exodraft chimney fans (default setting).
• EBC10v2 ensures and monitors consistent pressure in the chimney.
• EBC10v2 can also be used for boiler systems with modulating burners.
• The automation monitors the draft in the chimney, disabling the burner in case of malfunction.
• The automation is designed for both solid fuel boilers, atmospheric gas boilers, and boilers with oil and
gas blow torches.
• EBC10v2 can control a chimney fan directly.
Section 5: Pressure control of supply air fan.
• EBC10v2 is used for control of a supply air fan.
• EBC10v2 ensures and monitors consistent pressure in the boiler room.
• The automation monitors the pressure in the boiler room, disabling the burner in case of malfunction.
• EBC10v2 can control a supply air fan directly.
Section 6: EU Declaration of Conformity
Page 6
6 • Product information6 • Product information
EBC10v2 includes the following:
EBC10v2
3120074 EBC10v2 UK 20190506
B
D
E
C
A
Pos.PartItem no.Function
AEBC10v2EBC10v2EU01Control of exodraft chimney fans and blow fans. For indoor
installation.
BPressure
transducer (XTP)
DMeasuring probe
for EBC10v2EU01
E2 m. Silicone hose2000335Supplies the pressure transducer (XTP) with reference pressure
Instructions3120070
XTP150Measures the air pressure in boiler room, chimney, or outdoor
atmospheric pressure.
3200813Measures pressure in the chimney.
from the measuring probe or from outdoors.
2.1 Accessories
PartItem no.Function
RelayES12For connection of more than two boilers
External PDSPDSBOXMeasures pressure in the chimney
Rep. switchREP-AFBIsolation switch
Measuring probe 90°3200814Measures pressure in the chimney (Pos. C)
2.2 Fitting
Cable length
Max. cable length between EBC10v2 and XTP: 100 m.
Max. cable length between EBC10v2 and chimney fan / fan: 100 m.
Max. cable length between XTP and measuring probe 2 m.
Page 7
B1
3120074 EBC10v2 UK 20190506
2.2.1 Connection diagram
EBC10v2 is to be tted and connected as shown in the diagram below.
Product information • 7Product information • 7
B2
EBC10v2
A
Control of.Fitting procedure
Chimney fan
Note!
• Install EBC10v2EU01 and the pressure transducer (XTP) in the boiler room.
• Fit the measuring probe (A) in the boiler ue or in the manifold. However, for atmospheric boilers, the probe must always be positioned after the draft hood.
• Connect the hose from the measuring probe to the negative terminal on the pressure
transducer “B1”.
• When the measuring probe is placed outside, it must be installed in a manner that prevents the formation of condensation or ice. EBC10v2EU01 comes with a straight measuring probe.
• EBC10v2 must always be installed where it is protected from wind and weather (rain,
snow, etc.)
A
Ø 6.5
A
Ø 6.5
A
Supply air fan• Install the control and the pressure transducer (XTP) in the boiler room.
• Connect the hose for measuring reference pressure (outdoor atmospheric pressure) to
the negative terminal “B1” on the pressure transducer. Run the hose outside the building
to a place not exposed to the weather. The open end of the hose may be installed inside
a box as described at the top of the next page.
Note!• Particularly when wanting positive pressure* in the chimney / boiler room:
• Connect the hose to the positive terminal on the pressure transducer “B2”.
• EBC10v2 comes with only 2 m of hose.
Note!
*The default setting of the EBC10v2 is for negative pressure regulation, but local statutory
regulations may require constant positive pressure.
**Do not install the pressure transducer in an airtight enclosure, as it uses the atmospheric
pressure for reference..
Page 8
8 • Product information8 • Product information
3120074 EBC10v2 UK 20190506
Make sure to position the pressure transducer (XTP) correctly.
Note
Do not blow into the valves of the XTP.
For outdoor installation, place the pressure transducer where it is not exposed to the weather. For outdoor
installation, the pressure transducer should be placed in a box tted with a hole (Ø2mm) in the bottom. The
hole serves to ensure correct reference pressure and prevent water entry
If the pressure transducer is positioned where insects have access to the free end, installing a sinter lter is
recommended
2.3 Layout of the user interface
2.3.1 Panel
EBC10v2
G
Pos.DelFunktion
AUSB• USB Interface
BDisplay• Shows operation and changes in the user interface (menu system)
• Indicates alarms
• shows normal operation status
C• Go forward/up in the menu system
A
B
C
D
E
F
D• Approves your action
• Forward
E• Go down in the menu system
F• Interrupt action
• Back
GFuse • Fuse type
Page 9
3120074 EBC10v2 UK 20190506
Product information • 9Product information • 9
2.3.2 Terminal board
The following explains connection options for the terminal board
TerminalBetegnelseTerminalUse
1PE Ground18Inactiv
2Supply - L119 Inactiv
3
4Chimney fan – N21Inactiv
5Chimney fan - L1 (Regulating)22 XTP-0V DC power supply
6Chimney fan - PE Ground23 XTP-24V DC power supply
7 Frequency converter relay NO24 Inactiv
8 Inactiv25Inactiv
9Inactiv26Inactiv
10 Alarm Out - NO270V DC Power supply
(max. 230 VAC, 2 amps.)
16Inactiv33 Pt1000
17Inactiv34Not used
* However, terminals 30, 31, and 32 may be used for connecting other auxiliary monitoring equipment as well.
2924 VDC power supply (Max.
100 mA)
30 PDS-NC (normally closed)
Proven draft switch
31PDS-NO (normally open) Prov-
en draft switch
32PDS-C (shared) Tested draft
switch
35 Pt1000
Page 10
100 m
2 m
EBC10v2 Control
EBC10v2
10 • Product information10 • Product information
3120074 EBC10v2 UK 20190506
2.4 Mechanical installation
The control and the transducer must be installed inside, preferably in the boiler room. The control does not need to be
installed in a cabinet.
Do not install the transducer in an airtight enclosure. It uses the boiler room pressure / atmospheric pressure
as reference pressure.
The control can be installed directly on the wall or somewhere similar.
Take o the lid.
The installation holes are placed under the plastic screws keeping the cover in place.
The distance between the control and the transducer should not exceed 100 m.
EBC10v2
Page 11
3120074 EBC10v2 UK 20190506
Product information • 11Product information • 11
2.5 Display
The diagram below shows the layout of the display on the EBC10v2. All possible display values are indicated:
INTAKE : 36 Pa
OUT : 15 %
SETPOINT : 55 Pa
The purpose of the display is to indicate:
• Operating information (pressure, etc.)
• Alarms
• Parameters
• Set points
• USB
2.5.1 Using the interface
The user interface is operated via four buttons with the following functions:
TastFunktion
• Activate the service menu
• Edit and save settings
• Go to menu item and adjust value
• Return to operation screen from any point in the menu system
• Reset alarm when “Manual Reset” is selected in menu 2.3.
Page 12
12 • Product information12 • Product information
2.5.2 Setting the language
It is possible to change the language on the display. The default setting is in English.
To set the language on the screen, follow these steps:
StepActionDisplay
1
• Go to the Main Menu
• Select 4. User Interface
MAIN MENU
1 REGULATION
2 ALARM
3 SERVICE
4 USER INTERFACE
3120074 EBC10v2 UK 20190506
2
• Select 1. Display
3
• Select 1. Language
4
• Use the arrow keys to switch between languages
• Finish the approval/storage via the check box
• The display should now have switched to the desired
language
USER INTERFACE
1 DISPLAY
DISPLAY
1 LANGAUGE
2 UNITS
3 LCD BACKLIGHT
4 LCD CONTRAST
DISPLAY
LANGUAGE
ENG
ENG
4
4 1
4 1 1
Page 13
3120074 EBC10v2 UK 20190506
2.5.3 Locked home screen
Access to the service menu is open as a default.
It is possible to lock the home screen with a code.
2 ENABLE AUTOSTART
3 START TEMPERATURE
4 STOP TEMPERATURE
5 FORCED OP.
6 TEMP. ALARM
TEMP. SENSOR
ENABLE SENSOR
ON
2.10 Quick menu for setpoint
To access the set point menu quickly, follow the procedure below:
StepActionDisplay
1
• Start the system
• EBC24 displays the actual negative pressure (in this example, 55 Pa)
INTAKE : 149 Pa
OUT : 100 %
SETPOINT : 55 Pa
1
1 7
1 7 1
2
• Press
• Use the arrow keys to switch between the set pressure
• Approve/Save with chech mark
REGULATION
SET PRESSURE
19
RANGE 0-150 Pa
Page 18
18 • Product information18 • Product information
3120074 EBC10v2 UK 20190506
3. Settings and troubleshooting
3.1 Error codes
Most terminal connections are monitored for correct operation. An LED light indicates operating status. If a light comes
on, it is an indication that everything is functioning correctly, while a light going out indicates a problem in the circuit it
monitors. In addition, error codes are shown on the display.
The error codes are:
DisplayExplanation
A1 Draft ExhaustInsucient pressure may be due to:
1. Chimney fan has insucient capacity
2. Mechanical or electrical fan failure
3. Blocked chimney
4. Introduction of excessive dilution air
5. XTP sensor not responding correctly
A2 Power FaultIndicates that there has been a power fault
A3 XTP-ExhaustIndicates a disconnected signal from the XTP sensor on the exhaust side to the control. May
A4 Error StartIndicates that the control has been unable to release the burner within 15 minutes.
A5 Alarm OverrideIndicates alarm has been disregarded
A6 Draft InputMissing signal from PDS function. Indicates a defective function.
A7 RS485 errorNo communication between EBC10v2 and modbus network
A8 PriorityThe draft has been insucient and therefore the control has been in priority
be caused by:
1. Lose connections
2. Faulty XTP-sensor
3. Defective controller
3.2 Overview of the service menu
The service menu is built in 4 levels and associated submenus.
Menu Sub-menuFunctionDisplayDescriptionClassicationStandard
1ExhaustEXHAUST
11Draft set pointSET EXHAUSTAdjustment of exhaust setpoint.2%-95% af sensor17%
12Operation modeEXHAUST MODEContinuous or intermittent operation. In inter-
mittent mode the exhaust fan runs only if one
or more boiler inputs are active.
13Pre-purgePRE-PURGEPre-purge settings
131TimeTIMEPre-purge time in seconds0-18000
132Operation modeSPEED MODESelect variable if the pre-purge should be con-
trolled by the XTP-sensor or have a xed speed.
14Post-purgePOST-PURGEPost-purge settings
141TimeTIMEPost-purge time in seconds0-18000
142Operation modeSPEED MODESelect variable if the post-purge should be con-
trolled by the XTP-sensor or have a xed speed.
15SensorSENSOR
151Min. pressureRANGE MINXTP minimum pressure in Pa.-500 – 500 Pa0
152Max. pressureRANGE MAXXTP Maximum pressure in Pa.0 – 1000 Pa150 Pa
16ParametersPROPERTIES
161Alarm limit draftALARM LIMITSelect the alarm limit of the draft. The value is in
% of the set point.
162AlarmdelayALARM DELAYSelect a alarm delay from 0-120 seconds.0 – 120 s15
163Min. voltageSPEED MINMimimum speed of the fan0 – MENU 16415 %
164Max. voltageSPEED MAXMaksimum speed of the fan.MENU 163-100%100
165XpEXHAUST XpProportional gain.0-3015
166TiEXHAUST TiIntegral gain.0-308
167Sampling rateSAMPLING RATESet the sampling rate for the PID Loop1-1010
168Pressure typePRESSURE MODEPositive or negative pressure in the stack.Positive or NegativeNegative
Continuous/
Intermittent
Variable / FIX 20-100% FIX 100%
Variable / FIX 20-100% Variable
If 167 = "Negative" ->50
- 80 %.
If 167 = "Positive" -> 150
- 300 %"
Intermittent
64 % (167 = "Negative")
144 % (167 = "Positive")
Page 19
3120074 EBC10v2 UK 20190506
Menu Sub-menuFunctionDisplayDescriptionClassicationStandard
17Temperature SensorTEMP. SENSOR
171Enable SensorENABLE SENSOREnables the temperature sensor and displays
172Enable AutostartENABLE AUTOSTART Enables the temperature as a start signal for the
173Start TemperatureSTART TEMPERA-
TURE
174Stop TemperatureSTOP TEMPERATURE Sets the stop temperature0-Start Temperature - 5 35° C
the current temperature on the main screen
controller
Sets the start temperature 40-100° C40° C
On/OO
On/OO
Product information • 19Product information • 19
175Forced operationFORCED OP.
1751 Set Forced opera.SET FORCED OP.Enables the full speed operation of the
On/OO
chimney fan, if the forced operation
temperature setpoint is reached
1752 Temperature Limit Temperature Limit
Sets the limit temperature
5-450° C250° C
176Temperature Alarm TEMP. ALARM
1761 Enable Temp. Alarm ENABLE. TEMP.
ALARM
Enables the alarm relay if the setppoint is
reached
On/OO
1762 Alarm LimitALARM LIMITSets the alarm limit25-450° C450° C
1763 Alarm DelayALARM DELAYSets the delay before the alarm0-60 Seconds5
169ApplicationAPPLICATIONSets if the control has to work as Exhaust
Exhaust / IntakeExhaust
or Intake
2ALARM
3Service
21
22
23
31
32
321BURNER I/OAUX OUT XXX
322EXHAUST I/OEXH XTP x.xV OFF
323Draft inputDRAFT INPUT ON/
Alarm Status
Alarm log
Reset
Version no.
I/O
ERROR
ERROR LOGThe last 10 alarms will be saved in the menu.
RESETSelecting "AUTO" will automatic reset the
SERVICE
VERSIONSoftware version is showed.
I/O-VIEW
AUX IN XX
EXH VFD x.xV OFF
OFF
The error is shown here
MAN / AUTOAUTO
alarm after 15 seconds. If "MAN" is selected,
the "X" has to be pressed.
In this menu the status of the boiler I/O is
shown. By pressing athe AUX OUT relays
can be activated by pressing up and down.
Multiple activations of the a button will move
from relay 1 to 6
XTP, VFD and VFD relay status for Exhaust.
Draft Input I/O status.
324Alarm relayALARM OUTPUT
ON/OFF
33OptionsOPTION
331Bearing cycleBEARING CYCLESelecting "YES" will enable a bearing cycle on
332Allow primeSelecting a number from 0-250 will enable the
333Draft Input DelayDRAFT INPUT DELAY The delay before the control goes into Fraft
34Factory resetFAC TORYIf "YES" is selected, a factory reset will be
35Manual ModeMANUAL MODESet a specic value for a continuous
36USB congurationUSB CONFIG
361format USBFORMAT USB Selecting "YES" will format the USB ash drive.
362Data LogDATA LOG USB /
INTERNAL
363Save cong. leSAVE CONFIG FILESlecting "YES" provides the possibility to select
364Load cong. leLOAD CONFIG FILE Selecting "YES" will download the current
365Upgrade rmwareUPGRADE FIRM-
WARE
4User InterfaceUSER INTERFACE
41DisplayDISPLAY
411LanguageLANGUAGELanguage.ENG/DEU/DNK/SWE/
412Pressure unitsUNITSPa or inWC units.Pa / inWCinWC
413LCD backlight LCD BACKLIGHTLCD backlight turned on or not. The USE param-
414LCD contrastLCD CONTRAST10 – 100 %50
Alarm relay output status.
present fans, if the boilers has not been active
for 24 hours.
prime function. This allows the boilers to be
activated even though no sucient draft is
present.
Alarm
performed.
chimney fan speed.
Notice! All data will erased!
Selecting "USB" will store the alarm log on the
USB ash drive, "INT" will store the log in the
internal memory.
congurationles stored on the USB ash drive.
conguration to the USB ash drive.
This function provides the possibility to
upgrade the rmware by means of a USB Stick
eter will cause the backligt to be turned on if a
button is pressed.
ON/OFFON
0-250 s / oO
0-20 s0 s
YES/NONO
0-100%0%
i.e. disabled
YES / NONO
USB / INTINT
YES / NONO
YES / NONO
ENG
NOR/FRA/ESP
ON / OFF / USEON
Page 20
PT1000
PT1000
20 • Product information20 • Product information
3120074 EBC10v2 UK 20190506
3.2.1 Light-emitting diodes and terminal board
The chart below lists the terminal board connection options and light-emitting diode displays.
No.DesignationMax. loadMeaning when the light-emitting diode is:
1, 2 og 3SUPPLY IN230-240 V AC +/- 10 %green: EBC20 is connected to power supply
4, 5 og 6FAN OUT3Agreen: the Triac output is active
7 og 8
VFD OUT
9, 10 og 11ALARM OUT250 V AC, 8A, AC3green: the relay is active
12 og 13BOILER 1 IN18 til 230 V DC/V ACgreen: the input is active
14 og 15BURNER 1 OUT250 V AC, 4A, AC3green: the relay is closed
16 og 17Idle
18 og 19Idle
28 og 2924 V DC OUT100 mAgreen: voltage is OK
20 og 21Idle20 mAgreen: output is active
22, 23 og 24 XTP INgreen: XTP connected
30, 31 og 32 PDS IN *green: C & NO are closed
250 V AC, 8A, AC3green: the relay is closed
red: overload
red: return voltage > 12 V DC
* However, terminals 30, 31, and 32 may be used for connecting other auxiliary monitoring equipment as well.
Page 21
3120074 EBC10v2 UK 20190506
Pressure control • 21
3.2.2 Switch between the basic functions of pressure control and supply air
Default settings
EBC10v2 defaults to constant pressure regulation of exodraft chimney fans (basic function 1 Exhaust/Intake)
Change of basic function
StepActionDisplay
1
• Press and hold for 5 seconds
2*
• Enter code: 3142
• Use arrows to select followed by
EXHAUST : 149 Pa
OUT : 15 %
SETPOINT : 55 Pa
ENTER PIN CODE
3142
3
• Select menu 1 Regulation
• Select menu 1.6 Properties
4
• Select menu 1.6.9 application
5
• Select menu 1.6.9 application
6
1Pressure regulation of exodraft chimney fans (Exhaust)
4 SPEED MAX
5 PRESSURE XP
6 PRESSURE TI
7 SAMPLING RATE
8 PRESSURE MODE
9 APPLICATION
PROPERTIES
APPLICATION
INTAKE : 149 Pa
OUT : 100 %
SETPOINT : 55 Pa
1
1 6
1 6 9
* Only if the controller is locked with a pin code
Page 22
22 • Pressure control
4. Pressure regulation of exodraft chimney fans
4.1 Application
Field of application
• EBC10v2 can also be used for boiler systems with modulating burners.
• The automation is designed for both solid fuel boilers, atmospheric gas boilers, and boilers with oil and
gas blow torches.
• EBC10v2 can control a chimney fan directly.
4.2 Functioning
General function
• The automation monitors the draft in the chimney, disabling the burner in case of malfunction (the alarm
diode on the EBC10v2 turns on).
• When the boiler thermostat demands heat, the chimney fan will start at max. voltage.
• When the EBC10v2 registers sucient chimney draft, the burner is released.
• The EBC10v2 maintains the set pressure by regulating the voltage. The pressure is shown in the display.
• In the event of insucient venting, the burner will initially be disconnected after 15 seconds. Insucient
venting is less than 64% of the set value, corresponding to less than 80% of ow.
• When the boiler turns o, the chimney fan stops as well. It is, however, possible to set a post-purge period
for the chimney fan (see page 23). Alternatively, the control system can be connected in a way that keeps
the chimney fan running continuously (see page 21).
3120074 EBC10v2 UK 20190506
Light-emitting diodes and output signals
All inputs and outputs are connected to a light-emitting diode for monitoring and servicing of the system (see section
2.9.1 Light-emitting diodes and terminal board, page 17)
4.3 Electrical connection
This work must be performed by a qualied electrician in accordance with locally applicable rules and
legislation.
Installation of the supply cable must comply with applicable legislation and regulations.
The grounding terminal ( ) must always be connected.
When connecting a pressure transducer (XTP) shielded cable must be used.
Isolation switch
exodraft a/s stresses that according to EU’s Machinery Directive, an isolation switch must be
incorporated into the xed installation. The isolation switch is not supplied by exodraft, but is available
as an accessory.
4.4 Wiring examples
As a constant pressure regulator for exodraft chimney fans, the EBC10v2 can be connected to a range of dierent
signals. The following pages are wiring examples and illustrate the following:
4.4.1 One boiler
4.4.2 Continuous operation
4.4.3 One boiler with potential free contact
4.4.4 One boiler and extra monitoring with PDS
4.4.5 One boiler with potential free contact and temperature sensor input
exodraft recommends contacting the boiler manufacturer for correct connection to the boiler
automation.
Page 23
3120074 EBC10v2 UK 20190506
SUPPLY IN
VFD Out
L1 NN
FAN MOTOR
OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUTBOILER
1 - IN
BURNER
1 - OUT
BOILER
2 - IN
BURNER
2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDSPt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTPRS485
4.4.1 One boiler
Pressure control • 23
This example shows how to connect a voltage signal (18-230 V AC/DC) to EBC24 to start/stop the chimney fan.
• Connect the supply to terminals 1-3.
• Connecting the boiler:
• Connect the burner start signal (L) to terminal 12.
• Connect the neutral wire to terminal 13.
• The start signal for the burner is sent from terminal 15.
• Loop terminals 12 and 14.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to terminal 6.
Page 24
SUPPLY IN
VFD Out
L1 NN
FAN MOTOR
OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUTBOILER
1 - IN
BURNER
1 - OUT
BOILER
2 - IN
BURNER
2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDSPt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTPRS485
24 • Pressure control
4.4.2 Continuous operation
3120074 EBC10v2 UK 20190506
This example shows how to connect a voltage signal (23 V DC) to EBC10v2 to start the chimney fan.
• Connect the supply to terminals 1-3.
• Loop terminals 12 and 29.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display
to terminal 6.
Page 25
SUPPLY IN
VFD Out
L1 NN
FAN MOTOR
OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUTBOILER
1 - IN
BURNER
1 - OUT
BOILER
2 - IN
BURNER
2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDSPt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTPRS485
3120074 EBC10v2 UK 20190506
4.4.3 One boiler with potential free contact
Pressure control • 25
The example shows how a voltage signal (24 V DC) is connected to EBC24 for the chimney fan to run continuously.
• Connect the supply to terminals 1-3.
• Loop terminals 12 and 29.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the
display to terminal 6.
Page 26
26 • Pressure control
4.4.4 One boiler and extra monitoring with PDS
3120074 EBC10v2 UK 20190506
SUPPLY IN
L1 NN
FAN MOTOR
OUT
REG
VFD Out
NO
ALARM OUTBOILER
C
NC
NO
BURNER
BOILER
1 - IN
1 - OUT
C
+/~
-/~
NO
C
2 - IN
+/~
-/~
BURNER
2 - OUT
24 VDC
C
NO
0V
VFD
0V
24V
NC
0-10V
PDSPt1000
NO
C
Pt1000
XTPRS485
0V
24V
0-10V
Pt1000
0V
A
B
This example shows how to connect a potential free contact to the EBC24 to start/stop the fan:
• Connect the supply voltage to terminals 1-3.
• Connection to the boiler:
• Connect the potential free contact to terminals 12 & 29.
• Loop terminals 13 & 28.
• Connect the burner start signal to terminals 14 & 15.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to terminal 6.
Page 27
12345678
SUPPLY IN
VFD Out
L1 NN
FAN MOTOR
OUT
REG
NO
C
NC
NO
C
+/~
-/~
+/~
-/~
NO
C
ALARM OUTBOILER
1 - IN
BURNER
1 - OUT
BOILER
2 - IN
BURNER
2 - OUT
C
NO
24 VDC
0V
24V
NC
NO
C
Pt1000
Pt1000
PDSPt1000
VFD
0V
0-10V
0V
24V
0-10V
0V
A
B
XTPRS485
3120074 EBC10v2 UK 20190506
4.4.5 One boiler with potential free contact and temperature sensor input
Pressure control • 27
This example shows how to connect a PDS to EBC24. The PDS supplies extra monitoring
• Connecting PDS:
• Remove the factory installed wiring between terminals 30 and 32.
• Connect PDS to terminals 30, 31 and 32.
• Connect the supply to terminals 1-3.
• Connecting the boiler:
• Connect the potential free contact to terminals 12 & 29.
• Connect the burner start signal to terminals 14 & 15.
• Loop terminals 13 and 28.
• Connect the chimney fan to terminals 4-6.
• Connect the pressure transducer (XTP) to terminals 22-24 with a shielded cable, and connect the display to
terminal 6.
Page 28
28 • Pressure control
3120074 EBC10v2 UK 20190506
5. Pressure regulation of supply air fan
5.1 Application
General
• The EBC10v2 is used to control a supply air fan.
• EBC an control a supply air fan directly.
Positioning
24 cInstall the EBC10v2 and the pressure transducer (XTP) in the boiler room as described in section 2.2 Fitting, pages
6+7
5.2 Mode of operation
General function
• The EBC10v2 monitors the pressure in the boiler room and disconnects the burner in the event of errors
(the alarm diode on the EBC10v2 will turn on).
• When the pressure in the boiler room changes, the EBC10v2 will change the fan speed in order to meet
the set point pressure for the boiler room.
• The EBC10v2 is connected to the boiler system in such a way that when a heating requirement arises, the
EBC10v2 will start the fan, delaying the start of the boilers until the pressure in the boiler room is adequate.
• A safety function ensures that if the pressure in the boiler room is insucient, the EBC22 will shut down
the boilers the EBC10v2 will shut down the boilers, should the pressure in the boiler room become insucient.
5.3 Electrical connection
This work must be performed by a qualied electrician in accordance with locally applicable rules and
legislation.
Installation of the supply cable must comply with applicable legislation and regulations.
The grounding terminal ( ) must always be connected.
When connecting a pressure transducer (XTP) shielded cable must be used.
Isolation switch
exodraft a/s stresses that according to EU’s Machinery Directive, an isolation switch must be
incorporated into the xed installation.
The isolation switch is not supplied by exodraft, but is available as an accessory.
exodraft recommends contacting the boiler manufacturer for correct connection to the boiler
automation.
Page 29
3120074 EBC10v2 UK 20190506
6. EU Declaration of Conformity
Declaration of Conformity
Pressure control • 29
DK: EU-Overensstemmelseserklæring
GB: Declaration of Conformity
DE: EU-Konformitätserklärung
FR: Déclaration de conformité de l’Union Européenne
NO: EU-Samsvarserklæring
exodraft a/s
C.F. Tietgens Boulevard 41
DK-5220 Odense SØ
-erklærer på eget ansvar, at følgende produkter:
-hereby declares that the following products:
-erklärt hierdurch auf eigene Verantwortung, daß folgende Produkte:
-déclare, sous sa propre responsabilité, que les produits suivants:
-erklærer på eget ansvar at følgende produkter:
-som er omfattet af denne erklæring, er i overensstemmelse med
følgende standarder:
-were manufactured in conformity with the provisions of the following
standards:
-die von dieser Erklärung umfaßt sind, den folgenden Normen:
-auxquels s’applique cette déclaration sont en conformité avec les
normes ci-contre:
-som er omfattet av denne erklæring, er i samsvar med følgende standarder:
EN 60335-1, EN60335-2-102, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 14459:2008
-i.h.t bestemmelser i direktiv:
-in accordance with
-entsprechen gemäß den Bestimmungen der folgenden Richtlinien:
-suivant les dispositions prévues aux directives:
-i.h.t bestemmelser i direktiv:
-Lavspændingsdirektiv:
-the Low Voltage Directive:
-Niederspannungsrichtlinie:
-Directive Basse Tension:
-Lavspenningsdirektivet:
2014/35/EC
-EMC-direktivet:
-and the EMC Directive:
-EMV-Richtlinie:
-Directive Compatibilité Electromagnétique:
-EMC-direktivet:
2014/30/EC
Odense, 03.04.2017
-Adm. direktør
-Managing Director
Jørgen Andersen
NL: EU-Conformiteits verklaring
SE: EU-Överensstämmelsedeklaration
FI: EU-Vaatimustenmukaisuusvakuutus
IS: ESS-Samræmisstaðfesting
IT: Dichiarazione di Conformità Unione Europea
-veklaart dat onderstaande producten:
-deklarerar på eget ansvar, att följande produkter:
-vastaa siltä, että seuraava tuote:
-Staðfesti à eigin àbyrgð, að eftirfarandi vörur:
-dichiara con la presente che i seguenti prodotti:
EBC24
-zijn vervaardigd in overeenstemming met de voorschriften uit de
hieronder genoemde normen en standaards:
-som omfattas av denna deklaration, överensstämmer med följande
standarder:
-jota tämä selvitys koskee, on seuraavien standardien mukainen:
-sem eru meðtalin i staðfestingu Pessari, eru i fullu samræmi við
eftirtalda staðla:
-sono stati fabbricati in conformità con le norme degli standard
seguenti:
-en voldoen aan de volgende richtlijnen:
-enligt bestämmelserna i följande direktiv:
-seuraavien direktiivien määräysten mukaan:
-med tilvisun til àkvarðana eftirlits:
-in conformità con le direttive:
-de laagspanningsrichtlijn:
-Lågspänningsdirektivet:
-Pienjännitedirektiivi:
-Smáspennueftirlitið:
-Direttiva Basso Voltaggio:
-en de EMC richtlijn:
-EMC-direktivet:
-EMC-direktiivi:
-EMC-eftirlitið:
-Direttiva Compatibilità Elettromagnetica:
-Algemeen directeur
-Geschäftsführender Direktor
-Président Directeur Général
-Verkställande direktör
-Toimitusjohtaja
-Framkvemdastjori
-Direttore Generale
Page 30
Page 31
Page 32
DK: exodraft a/s
C. F. Tietgens Boulevard 41
DK-5220 Odense SØ
Tel: +45 7010 2234
Fax: +45 7010 2235
[email protected]
www.exodraft.dk