Exide Technologies 95.10 User Manual

INSTALLATION
&
OPERATING
INSTRUCTIONS
INDEX
Section 1 - GENERAL INFORMATION
1.0 Relay Gel Batteries 1
Section 2 - SAFETY PRECAUTIONS
2.0 Safety Alert 1
2.1 Sulfuric Acid Burns 1
2.2 Explosive Gases 1
2.3 Electrical Shock and Burns 1
2.4 Important Message 2
Section 3 - RECEIPT OF SHIPMENT
3.0 Delivery Inspection 2
3.1 Concealed Damage 3
Page
Section 4 - STORAGE PRIOR TO INSTALLATION
4.0 Storage Location 3
4.1 Storage Interval 3
Section 5 - GENERAL INSTALLATION CONSIDERATIONS
5.0 Battery Location 3
5.1 Battery Orientation 4
5.2 Ventilation 4
5.3 Temperature Variations 4
5.4 Floor Loading 4
5.5 Floor Anchoring 4
5.6 Open Circuit Voltage Check 5
Section 6 - RACK SYSTEM - INSTALLATION
6.0 Placement of Units 5
(continued on next page)
i
INDEX (continued)
Section 7 - ELECTRICAL INSTALLATION CONSIDERATIONS
7.0 Connecting Cables 5
7.1 Paralleling 5
7.2 Connection Preparation 5
7.3 Torqueing 6
7.4 Connections 6
7.5 Connection Check 6
7.6 Battery To Charger Connection 6
7.7 Connection Resistance 7
Section 8 - INITIAL CHARGE
8.0 Constant Voltage Initial Charge 7
Section 9 - OPERATION
Page
9.0 Float Charge 8
9.1 Float Voltages 8
9.2 Voltmeter Calibration 9
9.3 Recharge 9
9.4 Determining State of Charge 10
9.5 Effects of Temperature 10
9.6 Effects of Float Voltage 11
Section 10 - EQUALIZATION
10.0 Equalizing Charge 11
10.1 Equalizing Frequency 11
Section 11 - MAINTENANCE SCHEDULE 12
Section 12 - TAP CONNECTIONS 13
Section 13 - TEMPORARY NON-USE 13
Section 14 - UNIT CLEANING 13
Battery Maintenance Report Template 14
ii
SECTION 1 - GENERAL INFORMATION
1.0 RELAY GEL VRLA BATTERIES
In normal use, the battery will not release hydrogen gas or acid mist, and will not leak acid. However, there is the possibility that under abnormal operating conditions hydrogen gassing, acid mist, and leaking electrolyte could occur. Thus
®
GNB
Industrial Power recommends that Section 2 of these instructions entitled “SAFETY PRECAUTIONS” be reviewed thoroughly and strictly followed when working with batteries.
SECTION 2 - SAFETY PRECAUTIONS
2.0 SAFETY ALERT
The safety alert symbol at left appears
throughout this manual. Where the symbol
appears, obey the safety message to avoid
personal injury.
CAUTION
Before proceeding with the unpacking, handling, installation and operation of this sealed lead-acid storage battery, the following general information should be reviewed together with the recommended safety precautions.
DANGER
2.1 SULFURIC ACID BURNS
SULFURIC ACID BURNS
Batteries contain sulfuric acid which can cause burns and other serious injury. In the event of contact with sulfuric acid, flush immediately and thoroughly with water. Secure medical attention immediately.
When working with batteries, wear rubber apron and rubber gloves. Wear safety goggles or other eye protection. These will help to prevent injury if contact is made with the acid.
DANGER
2.2 EXPLOSIVE GASES
EXPLOSIVE GASES
Batteries could generate explosive gases, which when released, can explode and cause blindness and other serious injury. If the safety vent opens while the explosive gases are being generated (e.g., in the event of a charger malfunction), these explosive gases will be released.
Keep sparks, flame and smoking materials away from the battery area and explosive gases.
DANGER
ELECTRICAL SHOCK
2.3 ELECTRICAL SHOCK AND BURNS
AND BURNS
All installation tools should be adequately insulated to minimize the possibility of short­ing across connections.
1
Never lay tools or other metallic objects on the batteries as shorting, explosions and personal injury may result.
Multi-cell systems attain high voltages; therefore, extreme caution must be exercised during installation of a battery system to prevent serious electrical burns or shock.
Loose or dirty connectors/connections can cause battery fires. Keep all connectors/ connections clean and torques at proper values. Keep outside of batteries clean and dry. Neutralize any acid corrosion with a cloth moistened with a solution of baking soda and water, then wipe off all traces of soda.
Do not move or shift racks/cabinets once installed without first disconnecting load to rack/cabinet and all inter-rack/cabinet connections. Consult wiring diagrams for location of these connections.
Do not lift cells by terminal posts. Do not tamper with post seals, protective covers, pressure relief vents or other battery components.
Disconnect the AC and DC circuits before working on batteries or charging equipment.
Assure that personnel understand the risk of working with batteries, and are prepared and equipped to take the necessary safety precautions. These installation and operating instructions should be understood and followed. Assure that you have the necessary equipment for the work, including insulated tools, rubber gloves, rubber aprons, safety goggles and face protection.
CAUTION !
If the foregoing precautions are not fully understood, clarification should
be obtained from your nearest GNB representative. Local conditions may
introduce situations not covered by GNB Safety precautions. If so, contact
the nearest GNB representative for guidance with your particular safety
problem before proceeding to install or service these batteries. Refer to
applicable federal, state and local regulations as well as industry
standards.
2.4 IMPORTANT MESSAGE
The symbol at left indicates an important
message. If not followed, damage to and/or
impaired performance of the battery may
result.
SECTION 3 - RECEIPT OF SHIPMENT
3.0 DELIVERY INSPECTION
Immediately upon delivery, examine for possible damage caused in transit. Damaged packing material could indicate rough handling. Make a descriptive notation on the delivery receipt before signing. If cell or unit damage is found, request an inspection by the carrier and file a damage claim immediately. Any battery with post or seal damage should be replaced.
2
3.1 CONCEALED DAMAGE
Within 15 days of receipt, examine all batteries for concealed damage. If damage is noted, immediately request an inspection by the carrier and file a concealed damage claim. Any delay in notifying carrier may result in loss of right to reimbursement for damages.
SECTION 4 - STORAGE PRIOR TO INSTALLATION
4.0 STORAGE LOCATION
If the battery is not to be installed at the time of receipt, it is recommended that it be stored indoors in a cool [25°C (77°F)], clean, dry location. Do not stack pallets or possible battery damage may occur.
4.1 STORAGE INTERVAL
The storage intervals between the date of shipment and the date of initial charge should not exceed six (6) months. The battery should be given its initial charge (refer to Section 8) before the end of the above stated storage interval. Storage at elevated temperatures will result in accelerated rates of self discharge. A general rule of thumb is that for every 10°C (18°F) increase above 25°C (77°F) the time interval for initial charge should be halved. For example, if a battery was stored at 35°C (95°F) the initial charge time interval would be 3 months. If the battery was stored at 30°C (86°F) the initial charge time interval would be 4.5 months. Storage beyond these periods without proper charge can result in excessive sulfation of the plates which is detrimental to battery performance and life.
SECTION 5 - GENERAL INSTALLATION CONSIDERATIONS
Prior to starting the installation of the RELAY GEL battery system, a review of this sec­tion is strongly recommended.
5.0 BATTERY LOCATION
It is recommended that the battery be installed in a clean, cool, dry location. Floors should be reasonably level and able to support the battery weight. A location having an ambient temperature of 25°C (77°F) will result in optimum battery life and performance. Temperatures below 18°C (65°F) reduce battery efficiency. Temperatures above 27°C (80°F) will result in a reduction of battery life. Continuous operation above 50°C (122°F) is not recommended.
A designated aisle space should be provided to permit initial installation and future service or surveillance of the batteries.
3
5.1 BATTERY ORIENTATION
YES
N
ONO
The RELAY GEL battery can only be installed in a vertical orientation with the posts pointing up (per Figure 1). This battery may not be placed on its sides. Contact your local GNB Industrial Power representative if you require the battery to be placed in a different orientation.
Figure 1
5.2 VENTILATION
The RELAY GEL battery is a valve regulated battery which under normal recommended charging in a stationary application does not vent any gases.
However, should the battery be subjected to excessive overcharge, hydrogen and oxygen can be vented to the atmosphere. Therefore, the battery should NEVER BE INSTALLED IN AN AIRTIGHT ENCLOSURE. Sufficient precautions must be taken to prevent excessive overcharge. Normal ventilation sufficient for human occupation will be adequate to avoid hazardous conditions.
Tests have confirmed that more than 99% of gases generated are recombined within the battery. Under normal operating conditions, no special ventilation and/or battery room is required.
RELAY GEL batteries can be installed in close proximity to electronic equipment only when the heat generated by this equipment is removed by ventilation.
5.3 TEMPERATURE VARIATIONS
Sources of heat or cooling directed on portions of the battery can cause temperature variations within the strings resulting in cell voltage differences and eventual compromise of battery performance. Heat sources, such as heaters, sunlight or associated equipment, can cause such temperature variations. Similarly, air conditioning or outside air vents should not directly influence portions of battery string temperatures. Every effort should be made to keep temperature variations within 3°C (5°F).
5.4 FLOOR LOADING
The area where the battery system is to be installed should have the capability to support the weight of the battery as well as any auxiliary equipment. The total battery weight will depend on the battery size, number of batteries, as well as the configuration involved. Prior to installation, a determination should be made that the floor integrity is adequate to accommodate the battery system.
5.5 FLOOR ANCHORING
Where seismic conditions are anticipated, floor anchoring should be provided. Such anchoring is the responsibility of the user.
4
5.6 OPEN CIRCUIT VOLTAGE CHECK
The voltage of each unit should be checked to insure the voltage is at least 12.6 volts. If any unit has a voltage lower than 12.6 volts, follow the initial charge procedures shown in Section 8.
SECTION 6 - RACK SYSTEM - INSTALLATION
6.0 PLACEMENT OF UNITS ON RACK
When installing units on a rack, start on the lower tier for stability and safety reasons. Place units on the rack so that the positive (+) of one unit is connected to the negative (-) of the next unit. Standard spacing is 12mm (1/2 inch) minimum between units.
Determine the number of units to be placed on each row. If a row of units does not fill the entire rack length, fill the remaining space with foam cell spacers in seismic installations.
SECTION 7 - ELECTRICAL INSTALLATION CONSIDERATIONS
7.0 CONNECTING CABLES: BATTERY SYSTEM TO OPERATING EQUIPMENT
Battery performance is based on the output at the battery terminals. Therefore, the shortest electrical connections between the battery system and the operating equipment should be used for maximum total system performance. A terminal plate kit should be utilized when connecting multiple cables to a battery terminal post.
DO NOT SELECT CABLE SIZE BASED ON CURRENT CARRYING CAPACITY ONLY. Cable size selection should provide the lowest voltage drop possible between the battery system and operating equipment. Excessive voltage drop will reduce the desired support time of the battery system.
7.1 PARALLELING
Where it is necessary to connect battery systems in parallel to obtain sufficient capacity, cable connections from the bus/load to each of the parallel strings is preferred rather than inter-string paralleling. The maximum number of parallel strings recommended by GNB in high rate applications is 4.
Cables should be sized to minimize voltage drop, and for proper current carrying capability. They should be as short as possible. However, the lengths of cables for all of the systems being paralleled to the load should be equal in length and size to provide proper load sharing on discharge plus satisfactory recharge with the same float voltage per string. Care should be taken to ensure the overall resistance of the connection between batteries and equipment bus are consistent between strings.
7.2 CONNECTION PREPARATION
Gently clean contact surfaces only by using a brass suede brush, 3M Scotch Brite
®
Green scouring pad, or #00 grade steel wool being careful not to remove lead plating from inter-unit connectors. Immediately after contact areas are cleaned, apply a thin coat-
®
ing of NO-OX-ID
“A” grease to these surfaces only.
5
7.3 CONNECTION TORQUEING
After cleaning contact surfaces, install all connectors hand tight to allow for final alignment of units. Once final alignment is made, all connections should be torqued to the value shown on the battery label (typically this value is 11.3 N-M or 100 inch-lb.)
Complete connection of units by installing the inter-tier cables and terminal plates (when required).
Caution
, do not make connections to the load at this time.
7.4 CONNECTIONS
Battery terminal and intercell connections should be corrosion free and tight for trouble-free operation. Periodically, these connections should be inspected to ensure cleanliness and integrity.
CAUTION
DO NOT WORK ON CONNECTIONS WITH BATTERY
CONNECTED TO CHARGER OR LOAD
If corrosion is present, disconnect the connector from the terminal. Gently clean the affected area using a brass suede brush, 3M Scotch Brite
®
Green scouring pad, or #00 steel wool being careful not to remove lead plating from interunit connectors. Apply a thin coat of NO-OX-ID®“A” grease to the cleaned contact surfaces. Re-install connec­tors and retorque connections.
All terminals and intercell connections should be retorqued at least once every year.
Maintaining electrical integrity of connectors is important, since poor connections will result in reduced battery output and, in extreme cases, may add to heating and could result in melted battery posts, circuit interruptions, or battery fires.
7.5 BATTERY TO CHARGER CONNECTION
The positive (+) terminal of the battery should be connected to the positive (+) terminal of the charger and the negative (-) terminal of the battery to the negative (-) terminal of the charger. A terminal plate kit should be utilized when connecting multiple cables to a battery terminal post.
6
7.6 CONNECTION RESISTANCE
Electrical integrity of connections can be objectively established by measuring the resistance of each connection. These resistances are typically in the microhm range. Meters are available which determine connection resistance in microhms. Be sure that the probes are touching only the posts to insure that the contact resistance of connector to post is included in the reading.
Resistance measurements or microhm measurements should be taken at the time of installation and annually thereafter. Initial measurements at installation become the bench mark values and should be recorded for future monitoring of electrical integrity.
It is important that the bench mark value for all similar connections be no greater than 10% or 5 microhms, whichever value is greater over the average. If any connection resis­tance exceeds the average by more than 10% or 5 microhms, whichever is greater, the connection should be remade so that an acceptable bench mark value is established.
Bench mark values for connection resistances should also be established for terminal plates, where used, as well as cable connections. Bench mark values should preferably be established upon installation.
All bench mark values should be recorded. Annually, all connection resistances should be remeasured. Any connection which has a resistance value 20% above its bench mark value should be corrected.
SECTION 8 - INITIAL CHARGE
8.0 CONSTANT VOLTAGE METHOD
Batteries lose some charge during shipment as well as during the period prior to installation. A battery should be given its initial charge as soon as possible after receipt.
Constant voltage is the only charging method allowed. Most modern chargers are of the constant voltage type.
Determine the maximum voltage that may be applied to the system equipment. This voltage, divided by the number of cells connected in series, will establish the maximum volts per cell (VPC) that may be used.
Table A lists recommended voltages and charge time for the initial charge. Select the highest voltage the system allows to perform the initial charge in the shortest time period. Do not exceed the highest voltage listed for a given temperature. Do not exceed the maximum current(s) shown in Section 9.3.
TABLE A
INITIAL CHARGE
Ambient Temp.
25°C (77°F)
25°C (77°F)
Cell Voltage
2.35
2.40
7
Time Charge - Hours
48
24
NOTE: Time periods listed in Table A are for temperatures from 21°C (70°F) to 32°C (90°F); for temperatures 13°C (55°F) to 20.5°C (69°F), double the number of hours For temperatures other than 25°C (77°F) the following formula can be used to determine the recommended initial charge voltage per cell (VPC):
V corrected = V25°C - [(T actual - 25°C) x (0.003 V/°C)] or V corrected = V77°F - [(T actual - 77°F) x (0.0017 V/°F)]
Example at 29.4°C (85°F) and at 24 hr. initial charge
V corrected = 2.40 - (29.4-25) (0.003)
= 2.40 - 0.0132 = 2.387 VPC
Raise the voltage to the maximum value permitted by the system equipment, but do not exceed the maximum voltage listed for a given temperature. When charging current has tapered and stabilized (no further reduction for three hours), charge for the hours shown in Table A or until the lowest unit voltage ceases to rise. Correct charge time for the temperature at the time of stabilization. To determine the lowest volt­age unit, monitoring should be performed during the final 10% of the charge time.
SECTION 9 - OPERATION
.
9.0 FLOAT CHARGE
In this type of operation, the battery is connected in parallel with a constant voltage charger and the critical load circuits. The charger should be capable of maintaining the required constant voltage at the battery terminals and also supply the normal load where applicable. This sustains the battery in a fully charged condition and also makes it available to assume the emergency power requirements in the event of an AC power interruption or charger failure.
9.1 FLOAT VOLTAGES
Following is the float voltage range recommended for the RELAY GEL Battery System. Select the “volts per cell” (VPC) value within the range listed that will result in the bat­tery series string having an average volts per cell equal to that value.
RECOMMENDED FLOAT VOLTAGES: 77°F (25°C) = 2.25 VPC to 2.30 VPC
MAXIMUM CURRENT: 20A / 100 AH (20 hr rating to 1.75V@25C)
For temperatures other than 77°F (25°C) the following formula can be used to determine the recommended float charge voltage per cell:
V corrected = V25°C - [(T actual - 25°C) x (0.0055 V/°C)] or V corrected = V77°F - [(T actual - 77°F) x (0.003 V/°F)]
8
Minimum float voltage (temperature corrected) is 2.21 VPC. Temperature correction does not apply below this value. Maximum float voltage (temperature corrected) is 2.40 VPC. Temperature correction does not apply above this value.
Example
Modern constant voltage output charging equipment is recommended for the float charge method of operation for the batteries. This type of charger, properly adjusted to the recommended float voltages and following recommended surveillance procedures, will assist in obtaining consistent serviceability and optimum life.
After the battery has been given its initial charge (refer to Section 8), the charger should be adjusted to provide the recommended float voltages at the BATTERY TERMINALS.
Do not use float voltages higher or lower than those recommended. Reduced capacity or loss of battery life will result.
9.2 VOLTMETER CALIBRATION
Panel and portable voltmeters used to indicate battery float voltages should be accurate at the operating voltage value. The same holds true for portable meters used to measure individual cell/battery voltages. These meters should be checked against a standard every six months and calibrated when necessary.
At 18.3°C (65°F)
V corrected = 2.27 - (18.3-25) (0.0055)
= 2.27 + 0.037 = 2.307 VPC
9.3 RECHARGE
All batteries should be recharged as soon as possible following a discharge with constant voltage chargers. Recharge time should not exceed recommendations given in Section 8.0, Table A. However, to recharge in the shortest period of time, raise the charger output voltage to the highest value that the connected system will permit. Do not exceed 2.40 VPC. Maximum recharge current should be limited to 20A / 100 AH (20 hr rating to 1.75V@25C). The charger used should incorporate a current limit fea­ture. The maximum recommended charge current for the battery is as shown below:
Model
Relay Gel R12VU1 6.0
Relay Gel R12V22 10.0 Relay Gel R12V24 14.3 Relay Gel R12V27 17.2 Relay Gel R12V31 20.9
Current (Amps)
9
9.4 DETERMINING STATE OF CHARGE
If the normal connected load is constant (no emergency load connected), the following method can be used to determine the approximate state of charge of the battery. This state of charge can be identified to some degree by the amount of charging current going to the battery. When charging, the current read at the charger ammeter will be a combination of the load current plus the current necessary to charge the battery. A condition where the current remains constant for a period of three consecutive hours would reflect approximately 90 to 95% state of charge.
If the normal connected load is variable (e.g., telecommunications), the following method can be used to check the state of charge of the battery. With the battery on float and stabilized, measure the voltage across a pilot unit. If the voltage is stable for three consecutive hours, the battery is considered 100% charged.
9.5 EFFECTS OF TEMPERATURE
Temperature has a direct effect on the life of a battery. The design life of the battery is based on an average annual temperature of 25°C (77°F). As the temperature increases above 25°C (77°F), the life of the battery decreases. The chart below shows the effects of temperature.
Maximum Annual
Average Battery
Temperature
25°C (77°F) 30°C (86°F)
35°C (95°F) 40°C (104°F) 45°C (113°F) 50°C (122°F)
For example: If a battery has a design life of 10 years at 25°C (77°F), but the actual annual average battery temperature is 35°C (95°F), the projected life of the battery is calculated to be only 5 years [10 years - (10 years X 0.50) = 5 years].
Temperature records shall be maintained by the user in accordance with the maintenance schedule published in this manual. The battery temperature shall not be allowed to exceed the maximum temperature shown above. It is important to maintain the battery temperature as close to 25°C (77°F) to achieve the optimum service life from your battery.
Maximum
Battery
Temperature
50°C (122°F) 50°C (122°F) 50°C (122°F) 50°C (122°F) 50°C (122°F) 50°C (122°F)
Percent
Reduction
In Battery Life
0% 30% 50% 66% 75% 83%
10
9.6 EFFECTS OF FLOAT VOLTAGE
Float voltage also has a direct effect on the service life of your battery. A float voltage above the recommended limits reduces service life. The chart below shows the effects of float voltage (temperature corrected, see section 9.1) on battery life.
Temperature corrected 25°C (77°F)
Float voltage per cell
Minimum
2.25 2.30
2.31 2.35
2.36 2.40
For example: A battery has a design life of 10 years, but the actual annual average float voltage is 2.33 volts per cell. The projected life of the battery is calculated to be 5 years [10 years - (10 X 0.50) = 5 years].
Voltage records shall be maintained by the user in accordance with the maintenance schedule published in this manual. To obtain the optimum service life from the battery, it is important to make sure the battery’s float voltage is within the recommended range.
SECTION 10 - EQUALIZATION
10.0 EQUALIZING CHARGE
Maximum
Percent
Reduction
In Battery life
0% 50% 75%
Under normal operating conditions an equalizing charge is not required. An equalizing charge is a special charge given to a battery when non-uniformity in voltage has developed between units. It is given to restore all units to a fully charged condition. Use a charging voltage higher than the normal float voltage and for a specified number of hours, as determined by the voltage used.
The recharge parameters of Section 9.3 apply for this section also.
Non-uniformity of units may result from low float voltage due to improper adjustment of the charger or a panel voltmeter which reads an incorrect (higher) output voltage. Also, variations in unit temperatures greater than 3°C (5°F) in the series string at a given time, due to environmental conditions or battery arrangement, can cause low voltage batteries.
10.1 EQUALIZING FREQUENCY
An equalize charge should be given when either of the following conditions exist.
A. The float voltage of the pilot unit (or any unit for quarterly readings ) is less than
2.21 VPC.
B. A recharge of the battery is required in a minimum time following an emergency
discharge.
11
SECTION 11 - MAINTENANCE SCHEDULE
A pilot unit is selected in the series string to reflect the general condition of all units in the battery. The pilot unit should be the battery with the lowest voltage in the string following the initial charge. By measuring the pilot unit voltage, it serves as an indicator of battery condition between scheduled overall individual unit readings.
A complete recorded history of the battery operation is most desirable and helpful in obtaining satisfactory performance. Good records will also show when corrective action may be required to eliminate possible charging, maintenance or environmental problems.
The following data should be read and permanently recorded for review by supervisory personnel:
A. Upon completion of the initial charge and with the battery on float charge at the
proper voltage for one week, read and record the following:
1. Individual battery voltages
2. Battery string terminal voltages
3. Ambient temperature
B. Every 12 months, a complete set of readings as specified in Paragraph A above must
be done and all individual connections retorqued.
C. Whenever the battery is given an equalizing charge, an additional set of readings
should be taken and recorded as specified in Paragraph A above.
The suggested frequency of record taking is the absolute minimum to protect warranty. For system protection and to suit local conditions or requirements, more frequent readings (quarterly) are desirable.
Minimum Maintenance Schedule*
Item Action Interval
Refer to
Section
Installation Initial Charge Upon Installation 8.0
String Voltage Measure/Record Every 3 Months 9.1
Individual Voltages Measure/Record Every 12 Months 9.1
Pilot Unit Voltage Measure/Record Every 3 Months 11.0
Ambient Temperature Measure/Record Every 3 Months 9.5
Inter-Unit Connections
*Failure to adhere to these minimum maintenance schedules will void the battery’s warranty.
Inspect/Retorque
(Clean as Needed)
Every 12 Months 7.4
12
SECTION 12 - TAP CONNECTIONS
Tap connections should not be used on a battery. This can reduce battery life.
SECTION 13 - TEMPORARY NON-USE
An installed battery that is expected to stand idle for over 6 months should be treated as follows:
A. Give the battery an equalizing charge. Following the equalizing charge, open the
connections at the battery terminals to remove charger and load from the battery.
B. Every six months, temporarily connect battery to charger and give an equalizing
charge.
C. To return the battery to normal service, retorque all connections per Section 7.3 and
then re-connect the battery to the charger and return the battery to float operation.
D. If the battery is standing at an elevated temperature, corrections to the time period
to equalize charge should be corrected per Section 4.1.
SECTION 14 - UNIT CLEANING
Periodically clean unit covers to remove accumulated dust. If any unit or parts appear to be damp with electrolyte or show signs of corrosion, clean with a solution of baking soda and water or isopropyl alcohol, and re-examine within 30 days to determine if the condition re-occurs. If so, contact your local GNB representative.
Do not clean plastic parts with any solvents, detergents, mineral
CAUTION
spirits, or spray-type cleaners other than those mentioned here as these can cause crazing or cracking of the plastic materials.
13
A
Division of Exide Technologies
RELAY GEL BATTERY MAINTENANCE REPORT
Batt.
Batt.
WHEN ADVICE IS DESIRED, PLEASE FORWARD A DUPLICATE OF THIS REPORT TO YOUR GNB INDUSTRIAL POWER REPRESENTATIVE.
14
A Division of Exide Technologies
®
GNB Industrial Power – The Industry Leader.
GNB Industrial Power, a division of Exide technologies, is a global leader in network power applications including
communication/data networks, UPS systems for computers and control systems, electrical power generation and distribution systems, as well as a wide range of other industrial standby power applications. With a strong manufacturing base in both North America and Europe and a truly global reach (operations in more than 80 countries) in sales and service, GNB Industrial Power is best positioned to satisfy your back up power needs locally as well as all over the world.
GNB Industrial Power
USA – Tel: 888.898.4462 Canada – Tel: 800.268.2698
www.gnb.com
Based on over 100 years of technological innovation the Network Power group leads the industry with the most recognized global brands such as ABSOLYTE FLOODED CLASSIC®, MARATHON®, ONYX®, RELAY GEL®, SONNENSCHEIN symbolize quality, reliability, performance and excellence in all the markets served.
GNB Industrial Power takes pride in its commitment to a better environment. Its Total Battery Management program, an integrated approach to manufacturing, distributing and recycling of lead acid batteries, has been developed to ensure a safe and responsible life cycle for all of its products.
®
, and SPRINTER®. They have come to
®
, GNB
®
Loading...