F EJ0133 1 PARALLEL CHGR OPERATION w/ 2% LOAD SHARING
L
H EJ0592 1 HIGH DC VOLTAGE CHARGER SHUTDOWN
R EJ0141 1 COMMON ALARM RELAY CONTACTS
M
B
C
D
D
N
D EI5033 1 DRIP SHIELDS - STYLE-3 CABINET (EB0123)
D
D
GENERAL SPECIFICATIONS:ADDITIONAL FEATURES / OPTIONS / NOTES:
Regulation: + or - 0.5% no-load to full-load
Regulation: + or - 0.5% for + or - 10% AC line variation
Regulation: + or - 1% for combined load, line & temp. variations
Ambient Temperature Range: 0º C to 50º C
Relative Humidity: up to 95% without condensation
Altitude: up to 1,000m above sea level
EJ0093
EJ0097
EJ0869
EJ0131
EJ0096
EJ0141
EJ0967
EI5030/31
EI5032
EI5034
EI5035
1
CORE (BB####) A B C D E F G H J K L M N
SHT
#
FILTERED DC OUTPUT (30 mV RMS w/BATTERY)
BATTERY ELIMINATOR DC OUTPUT FILTERING
EJ5007 -00 WHITE CHARACTERS ON BLACK BACKGROUND
EJ5007 -10 BLACK CHARACTERS ON WHITE BACKGROUND
X
JH0002 -09 PARTS DATA PACKAGE PER MFG. SWITCHBOARD
X
JH0002 -07 COPY OF TEST DATA PER NEMA PE5-1985
JH0003 CUSTOM DRAWING PACKAGE CAD DISK
JH0002
JH0002
JH0002 -01 BURN-IN OR HEAT-RUN HOURS
JH0002
JH0004 -01 EXPORT PACKING PER FS0001-00
JH0004
JH0004
4
4
4
4
4
4/5
4
4
5
1
1
2
1
1
1
1
1
1
1/2
SURGE WITHSTAND FILTER (SWC) PER IEEE-472
200 kAIC AC FUSING (1PH - 2-POLE / 3PH - 3-POLE)
AC DC CKT BKR AUX CONTACTS
COPPER GROUND BUS BAR w/ LUG(S)
FUNGUS PROOFING PER CA0004-00SPECIAL NEMA CABINET TYPE
in RELAY RACK MOUNTING ASSY.
SPECIAL (FLOOR / WALL) MOUNTING ASSY.
CUSTOM TAG PLATE ENGRAVED FUNCTIONAL NAMEPLATES
EXTRA INSTRUCTION MANUALS
-06
-03
-00
-05
-10
INPUT VOLTAGE
FLOAT VOLTAGE
EQUALIZE VOLTAGE
1 - Serial Number and Core (BB####) calculated by factory
COMMON ALARM BUZZER
2% ACCURACY 3.5in AC AMMETER (1PH)
2% ACCURACY 3.5in AC AMMETER (3PH)
CURRENT LIMIT ALARM & IND. LIGHT (1PH / 3PH)
0-CENTER DC AMMETER FOR BATT/LOAD MONITOR
END OF DISCHARGE ALARM & INDICATOR LIGHT
CABINET HEATER STRIPS
OVER-TEMPERATURE ALARM w/ (BUZZER / IND.)
DC POWER ON INDICATOR LIGHT
4-20 mA TRANSDUCER Adc Vdc
HIGH AC RIPPLE ALARM w/ INDICATOR LIGHT
AC INPUT LIGHTNING ARRESTOR (1PH / 3PH)
VENT FAN CONTROL RELAY & IND. (FROM EQUALIZE)
BATTERY OPEN ALARM & IND LIGHT
EXTERNAL TEMP COMPENSATION PROBE (PB/NICD)
CERTIFIED TEST DATA PER NEMA PE5-1985
CERTIFICATE OF CONFORMANCE
IN-HOUSE INSPECTION BY OUTSIDE PERSONNEL
CUSTOM PACKING
EXTENDED WARRANTY PER JF5001-00
JF0026-00
Vac
Vdc
Vdc
IMPORTANT SAFETY INSTRUCTIONS
1) Before using the battery charger, read all instruction and cautionary markings on:
A) battery charger, B) battery, C) equipment connected to charger and battery
2) This manual contains important safety and operating instructions, and therefore should be filed
for easy access.
3) Do not touch any insulated parts of the battery charger, especially the input and output connections,
as there is the possibility of electric shock.
4) During normal operation, batteries may produce explosive gas. NEVER smoke, use an open flame,
or create arcs in the vicinity of the charger or battery.
5) Maintain at least 1ft (0.3m) clearance from all obstructions on all sides of the battery charger.
6) Keep area in front of battery charger clear for at least 4ft (1.3m).
7) Connect or disconnect the battery only when the battery charger is off to prevent arcing or burning.
8) De-energize all AC and DC inputs to the battery charger before servicing.
9) Do not operate battery charger if it has been damaged in any way. Refer to qualified service
personnel only.
10) Do not disassemble battery charger. Only qualified service personnel should attempt repairs.
Incorrect reassembly may result in explosion, electrical shock, or fire.
11) Do not install the battery charger outdoors, or in wet or damp locations unless specifically ordered
for that environment.
12) Remove all jewelry, watches, rings, etc. before proceeding with installation.
PLEASE READ AND FOLLOW
ALL SAFETY INSTRUCTIONS
i
TABLE OF CONTENTS
Page No.
SCR/SCRF BATTERY CHARGER SPECIFICATIONS (JF0026-00).......................... (inside front cover)
IMPORTANT SAFETY INSTRUCTIONS ................................................................................................i
TABLE OF CONTENTS......................................................................................................................ii-iii
4. Placing Charger in Service.................................................................................................................................3
5. Adjustments of Float & Equalizing Charge .......................................................................................................3
8. Normal Performance ..........................................................................................................................................4
9. Description of Operation....................................................................................................................................5
a. Power Transformer........................................................................................................................................5
b. Rectifier Section............................................................................................................................................5
c. Control Module .............................................................................................................................................5
d. Filter Section .................................................................................................................................................5
3. Testing of Components ......................................................................................................................................6
a. External Circuit Wiring.................................................................................................................................6
b. Power Transformer (T1)................................................................................................................................7
c. Circuit Breakers (CB1 / CB2) .......................................................................................................................7
d. Surge Suppressors (SS1 / SS2 / SS3 / SS4)...................................................................................................7
e. Rectifier Diodes (CR4 / CR5 / CR6).............................................................................................................7
f. SCR Diodes (SCR1 / SCR2 / SCR3).............................................................................................................8
g. Control Module (A1).....................................................................................................................................8
h. Current Sensing Resistor (SH1) ....................................................................................................................9
j. DC Voltmeter (M2).......................................................................................................................................9
k. DC Ammeter (M1)......................................................................................................................................10
m. Filter Capacitors (C1 / C2)..........................................................................................................................10
n. Internal Wiring ............................................................................................................................................10
SECTION IV - SYSTEM ADJUSTMENTS
1. Voltage Adjustments and Response.................................................................................................................11
a. Float Adjustment .........................................................................................................................................11
b. Equalize Adjustment...................................................................................................................................12
2. Current Limit Response and Adjustment.........................................................................................................13
a. Checks and Adjustments .............................................................................................................................13
b. Checks to Make if Malfunctioning..............................................................................................................13
2. Component Description - SCR/SCRF Series Battery Charger Options (Single Phase / Three Phase).......24-26
SECTION VII - TABLES / DIAGRAMS / FIGURES
Table A - Troubleshooting Chart..........................................................................................................................27
Parts List / Drawing Notes.................................................................................................................................... 62
iii
SECTION II
INSTALLATION AND OPERATION
1. SAFETY NOTICE
CAUTION! READ “IMPORTANT SAFETY INSTRUCTIONS” ON PAGE i.
There are dangerous voltages within the battery charger cabinet!
a. Only qualified personnel should attempt to adjust or service this equipment.
b. Refer to instruction manual for service procedures and CAUTION notes.
2. APPLICATION
Specifications: The silicon controlled rectifier is designed to maintain a system voltage within + or -
0.5% of the set value without exceeding its rated output current. It will maintain + or - 0.5% with input
voltage variations 10% above or below the rated input AC voltage and with 5% frequency variations.
The charger is designed, primarily, to operate only when connected to a battery load. It can be
operated as a battery eliminator into a resistive load up to full rated output at increased ripple. Filtered type
chargers will have a ripple content less than 30 mV RMS under steady state conditions with the charger
connected to a battery having an 8-hour Amp-Hour rating of at least 4 times the full load current rating of
the charger. Other connected loads such as DC-to-DC power supplies or inverters, may put ripple on the
battery appreciably above 30 mV.
Unfiltered chargers should not be used with critical loads such as communication systems, amplifiers
and instrumentation systems, but should only be used for non-critical applications such as engine cranking.
This charger can be used on any number of lead-acid, nickel-cadmium, or nickel-iron cells as long as
the desired float and/or equalize voltages are within the range of the charger.
3. INSTALLATION
a. Location: Select a clean, dry location for the charger. It may be located in the battery room, but not
over the battery, and must be mounted upright. The openings for ventilation in the top, bottom and sides of
the cabinet should not be obstructed, as they provide convection cooling and ventilation. Ambient
temperatures between 32° F and 122° F, and elevations up to 3,300 feet above sea level, will not affect the
performance of the charger. Operation at higher temperatures, or at higher elevations, is possible if the
ampere output is de-rated in accordance with published information, and if the charger is custom ordered for
these operating ambient conditions.
b. Wire Sizes AC: Wire sizes for the AC wiring may be selected by consulting the data on the
nameplate for input amperage. Local electrical or NEMA standards should dictate appropriate wire size.
Most codes specify that the AC wiring size must match the current rating of the input circuit breaker or
fuses.
c. Wire Sizes DC: The size of the charger leads should be selected to (a) carry the charger (ampere)
current rating, and also (b) provide less than 0.5 volt total drop at rated current in the loop or leads between
the charger and battery terminals. Choose the larger wire size that meets conditions (a) and (b). Do not
undersize. It is good practice to keep the DC leads as short as possible and to keep them together as a pair to
obtain low inductance. Likewise, it is good practice to avoid sharp bends and to run both DC leads together
if run in conduit.
d. Input Power: These chargers are nominal 208V, 240V, 480V (60 Hz) or 380/416V (50 Hz) AC
three phase. If the AC input data as supplied with the charger does not agree with the AC supply voltage at
the installation site, do not connect the charger to the AC line. The AC voltage must be within +/- 10% of
the rated input voltage of the charger. If not, consult your power company or the battery charger
manufacturer. These three phase input power chargers are not phase rotation sensitive, and thus any
combination of three phase input AC wiring may be used.
2
4. PLACING CHARGER IN SERVICE
a. With the AC and DC breakers OFF and the system in float mode, install the charger making AC
and DC connections, as described in Section II, 3, and in accord with local regulations as they apply.
b. After connecting the lead from the positive (+) battery terminal to the positive (+) terminal on the
charger and the lead from the negative (-) battery terminal to the (-) terminal on the charger, observe the
voltmeter. It should read the correct polarity and be approximately the battery open circuit voltage (this is
2.0 volts per cell for lead-acid batteries and 1.2 volts per cell for nickel cadmium batteries). For example, a
60-cell lead-acid battery should read about 2 x 60 cells = 120 volts. This is a check to indicate that all cells
are in a true series (none connected in reverse). The open circuit voltage should be about 8% to 10% below
the rated float voltage.
c. The charger can now be energized, by first closing the DC breaker to supply voltage for the control
circuits then closing the AC breaker. Set the charger to “float”. The AC power ON pilot light should light,
and the ammeter should indicate charger output current. It is to be expected that the meter may show up to
110% current rating of the charger; the 110% being the factory setting of the current limit control.
d. The factory preset float voltage adjustment value is listed on the inside front cover. When this
value is reached, the charger ammeter should show a slow decrease in current, eventually down to a
stabilized value. Please note that whenever a charger is in a current limit condition, the output voltage is
automatically reduced to a value below the set float or equalize voltage. The voltage will not increase to
normal value until the battery’s state of charge increases, causing the charger current to decrease to a value
equal to or less than the rated current.
e. The factory preset equalize voltage value is also listed on the inside front cover. Assuming this is
as desired, the Float/Equalize switch may be switched to “Equalize”, to check the charger performance at
this voltage value. If a Manual Equalize Timer (option) has been included, turn it clockwise to activate the
equalize charger mode. The charger ammeter may again go up to current limit until the equalizing charger
voltage is reached. The length of time required to reach this level depends on the state of charge of the
battery, and the ampere rating of the charger versus the battery Ampere-hour rating.
f. With the charger operating at the desired float and equalizing voltage values, the system can be
considered installed and ready for service.
5. ADJUSTMENTS OF FLOAT & EQUALIZING CHARGE (also see Section IV, 1)
a. Each adjustment is made by means of a potentiometer with a slotted shaft for a screwdriver. The
potentiometers are front-panel mounted and appropriately marked. A lock nut on each potentiometer is
provided and should be tightened after the proper adjustment is completed. This prevents any accidental
mis-adjustments of the settings. The voltage response may be slow if a rise in voltage adjustment is desired,
because the battery state of charger and connected load must be considered. Turning the shaft clockwise will
raise the voltage, and turning counter-clockwise will lower the voltage.
b. Since accuracy of measurement is important when setting float and equalizing voltages, a
precision portable VoltOhmmeter with at least 1% accuracy is recommended for these DC measurements. A
conventional VoltOhmmeter or analyzer such as the Simpson Model 260 is also satisfactory, but is not as
accurate.
c. Any setting of the float voltage or equalizing charger voltage should not be considered final until
the ammeter shows less than charger rated current, and voltage does not change after several hours of
operation.
6. MANUAL EQUALIZE TIMER (OPTIONAL)
a. This timer is provided to obtain a charge up to 72 hours, at a slightly higher value than the
ordinary float voltage. The timer may be used for recharging older batteries, or for a freshening charge on
new batteries. For a detailed explanation of operation see Section V (Customer Options).
3
7. MAINTENANCE
a. This charger is designed to require a minimum of maintenance. There are no rotating parts except
in the optional timer and all components have a nominally indefinite life with no expected aging effect. It
should be kept clean, dry and checked periodically to make sure all connections are tight. If necessary, dry
air may be used to blow dust out of the interior. In the event of any irregular operation, examine, and tighten
if necessary, all internal and external connections and check circuits for continuity (see schematic diagram
on page 28). If the difficulty cannot be remedied, contact the manufacturer.
8. NORMAL PERFORMANCE
a. Assuming that the charger has been operating in the float position, an indication of normal
performance can be obtained by setting the FLOAT/EQUALIZE switch in the equalize position (turn timer
off zero). Increased charge current will show on charger ammeter until the battery reaches the equalize
voltage. At this point the current should slowly decrease.
b. If the charger has been operating in the equalize voltage position, turn SW1 to FLOAT (turn the
timer manually to zero). The charger will indicate zero or little output current until the float voltage is
reached. At this point, the current should increase slowly to the system load value, (the battery is now
“floating” across the line with approximately equal input and output currents).
c. When operating normally, the current limit control will limit the maximum charger output current
to approximately 110% of the rated charge current. In case of a high DC current demand, the current limit
control will keep the charger output within safe values without tripping the DC circuit breaker or the AC
breaker.
4
9. DESCRIPTION OF OPERATION
There are four major sections of the SCR three-phase charger, which work together to produce
stable, regulated, filtered output. The functions of these four sections may be described as follows.
a. The Power Transformer (T1): This section includes T1 and its associated input
protection. Its purpose is basically to supply an AC voltage of the proper magnitude and capacity to the
rectifier section. It also supplies various other voltages used by the control unit and accessories. It is
connected to an AC source by means of a circuit breaker.
b. The Rectifier Section: This section consists mainly of the voltage regulating silicon
controlled rectifiers and the power rectifier diodes. It accepts the AC voltage from the transformer, rectifies
this voltage to DC, and controls the voltage’s magnitude so that the charger output is regulated at all times.
The firing angle of the SCRs is controlled by the action of the control module. Both the SCRs and the diodes
are protected from AC and DC surge voltages by means of the metal-oxide varistor surge suppressors.
c. The Control Module: This printed circuit board generates the three-phase phase-fired gate
signals that turn on the SCR diodes in response to the charging requirements of the battery load. The output
voltage of the charger is monitored by the voltage feedback circuit and advances or retards the phase angle
of the trigger pulses so that the output voltage is maintained essentially constant. This is accomplished by
comparing a small portion of the output voltage to a stable voltage reference. An error signal is created
proportional to the differential voltage. This error signal is then used to alter the phase angle of the SCR gate
trigger pulses in order to correct the output voltage. The load current is also monitored by the circuit so that
when its value exceeds an arbitrary value (110% rated current) the system is “phased back” to limit the
output current to no more than 110% of its rated value.
d. The Filter Section:
(1). Depending on the application, the charger may be unfiltered. In this case, one
filter choke, L1, is utilized not for filtering but for phase correction of the highly leading current-voltage
condition created by the batteries during the charging pulses. The batteries represent a very large capacitor in
shunt with a resistive load. This creates out-of-phase current problems for the SCR diodes causing nonuniform triggering problems particularly at low load currents. The single filter choke corrects this condition
and also aids the ratio of average current to RMS current flowing in the circuit.
(2). For filtered units, the objective is to remove the charging ripple at the battery
terminals. To accomplish this a "T" or "double-L" section filter consisting of inductors L1 and L2 and
capacitors C1 and C2 are used. C1 and C2 may consist of one or more individual capacitors. The degree of
filtering required dictates whether the "T" or "double-L" configuration is used. The "double-L" section filter
is normally used to reduce the ripple to 0.06% of nominal output voltage when the charger is operated as a
filtered eliminator.
5
SECTION III
TROUBLESHOOTING
1. CAUTION NOTICE
Before troubleshooting, always isolate and de-energize the charger by opening the AC circuit breaker
(CB1) and the DC circuit breaker (CB2). This avoids the possibility of high short circuit current damaging
the charger, tools, test equipment, or injuring personnel. NOTE: Circuit breaker terminals (CBx), printed
circuit boards (Ax) and terminals/terminal blocks (TB1, TB2, TB3, TB5 & TB15) have dangerous voltage
across them, even when both circuit breakers are open. After isolating the charger, check that the voltage
across the filter capacitors (C1/C2) is zero. Once charged, they will take several minutes to discharge if
bleeder resistor (R1) is open. If DC circuit breaker (CB2) is not provided, remove the DC fuses (F1/F2) in
order to isolate the charger from the battery. AFTER LOCATING THE CHARGER PROBLEM,
ALWAYS DE-ENERGIZE ALL AC AND DC CHARGER INPUTS AT THE POWER SOURCE
BEFORE SERVICING.
2. TROUBLESHOOTING PROCEDURE
a. When a charger is not operating properly, the cause must be determined by checking various
components until the fault is located.
b. The major components do not have to be checked in the order as listed in Section II, 9, since a charger
may exhibit a number of difficulties, each with different symptoms. In many cases, failure of one
component may cause another component or part to fail. Therefore, the following paragraphs treat major
components, functional circuits and parts individually (or by symptom). Together with serviceability
measurements and tests, the faulty part or component should be located.
c. Most of the following checks can be performed with an oscilloscope, a VoltOhmmeter (similar to a
Simpson Model 260) and an SCR tester.
d. Consult the trouble-shooting chart in Table A on page 27. When using the table, first locate the fault
symptom observed (in the left hand column) then follow the sequence for checking components in the
numerical order listed (1, 2, 3 etc.) for that particular symptom. Follow this sequence until the trouble is
located. After correcting the trouble, check the charger for normal performance as described in Section II, 8.
e. In addition to those symptoms listed in Table A, the following procedure should be followed for any
condition:
• Check voltage of the AC supply to insure that it is within 10% of the value of the
specified input voltage.
• Examine charger for any evident loose or improper connections, particularly at the
control unit, transformer and input/output terminal board.
• Check continuity of battery circuit by comparing voltage at charger terminals with total
of cell voltages.
• Check accuracy of voltmeter and ammeter on the charger.
3. TESTING OF COMPONENTS
a. External Circuit Wiring
1. When no line voltage exists between TB1 input terminals (L1 to L2 , L2 to L3 & L3 to L1), check
the AC line back to source.
2. With no output, or a low output, the external DC wiring may be at fault. Check the wiring
between charger and battery to see that it is properly installed. Make certain that terminals are tight and
clean, and that the DC wiring is free from grounds. The total operating voltage drop in the loop or leads
between the charger and battery terminals should never exceed 0.5 volt (at rated charge current), and
preferably should be kept considerably below this limit by using a sufficiently large wire size.
6
b. Power Transformer (T1)
1. With the AC and DC circuit breakers open or OFF, open the cabinet and carefully check the line voltage
across line terminals on TB1, terminals (L1 to L2, L2 to L3 & L3 to L1). If no AC voltage is indicated, refer to
Section III, 3, a, 1. Check the wiring connections to ascertain that the unit has the proper primary tap connections for
the line voltage indicated. Turn on the AC circuit breaker (CB1). Check that the voltage at the primary is the same as
that of the line. If this is not the case, CB1 or the wiring between it and T1 is open. In this case, proceed with checks
under Section III, 3, c, 1.
2. Check AC secondary voltage on T1 (see Table B below for expected voltage values). If secondary voltages
are much less than indicated or not balanced, then either T1 is at fault or the power regulating devices (SCR1, SCR2
or SCR3) are faulty.
TABLE B - SECONDARY VOLTAGE OF TRANSFORMER T1
Expected Voltages (AC) Leads or Locations
Approximately equal to float voltage X1 to X2, X2 to X3 and X3 to X1
Note: The "X" of Table B voltages should be measured as they terminate on the full-wave bridge
components. All other voltages may be measured at the end of the transformer leads. Where power
rectifier fuses are employed in the larger power chargers (see custom diagrams and parts list), these
fuses should also be checked, and replaced if unserviceable.
120 Vac Y1 to Y2, Y2 to Y3 and Y3 to Y1
c. Circuit Breakers (CB1/CB2)
1. AC Circuit Breaker (CB1): When an AC voltmeter of suitable range is connected between leads L1-L2, L2L3 & L3-L1 and indicates line voltage, but does not indicate when connected to the output terminals of CB1 when
closed, the circuit breaker is probably defective. De-energize the AC supply to the charger and remove the leads to the
circuit breaker. Use a volt-ohmmeter to check for continuity between the circuit breaker terminals with breaker
manually closed. Zero resistance should be indicated if the unit is operative. If unit checks OK, check performance by
measuring the AC voltage drop across each pole of the breaker. This voltage should be under 0.1 volt when the load
current is normal. If a higher voltage drop is found, replace the breaker.
2. DC Circuit Breaker (CB2): When the DC circuit breaker is suspected of being inoperative or at fault, a
similar test to that made for the AC breaker will determine the operating condition of the breaker.
3. If the polarity protection diode (CR1) is shorted, the battery will discharge into CR1, which will trip the DC
circuit breaker (CB2). Check CR1 with an ohmmeter (both polarities) for a shorted condition and replace if required.
d. Surge Suppressors (SS1/SS2/SS3/SS4)
1. The metal-oxide varistor (MOV) type of surge suppressor is used throughout these battery chargers instead
of the older selenium type. This is done for personnel safety. When a selenium device fails and arcs or burns, toxic
selenium fumes are given off, which are very poisonous if inhaled. The MOV type has a much sharper limiting
“knee” characteristic, and performs a better protection function. If an MOV surge suppressor fails during a highenergy transient, it may explode. This is an obvious failure and the part must be replaced.
2. If the suppressor is shorted, an ohmmeter check will indicate continuity. When the suppressor shows an
infinite resistance in both directions measured with it disconnected from the charger and has a normal appearance it
can be presumed to be in good operating condition.
e. Rectifier Diodes (CR4/CR5/CR6) - also see Section III, 3, f
1. In lower current three phase chargers, these diodes are part of an SCR-diode module, in which the SCR and
diode of each leg are contained in an assembly mounted on an electrically insulated heatsink plate. Three connections
(plus one SCR gate terminal) are available for checking. In higher current three phase chargers, individual diodes and
SCRs are used instead of modules. Check the diode portion of each bridge leg by disconnecting one terminal and
measuring the forward and reverse resistance in either of two ways:
a) Using an ohmmeter, use the Rx1 scale for the forward resistance. This should show approximately 5 to
10 ohms. The reverse resistance should be up in the thousands of ohms (probably 50,000 or more) measured with a
higher scale of the meter.
b) Connect the diodes in series with a 6 or 12-volt lamp across a DC source of the same voltage. The lamp
must require at least one-quarter Ampere. The lamp should light with nearly full brilliance with current flowing in the
forward direction and not at all in reverse. If it lights in both directions, the diode is shorted. If in neither direction, the
diode is open.
7
2. Note that semiconductors usually short in pairs in bridge circuits, seldom as single units, and it is rare that
all six semiconductors in a bridge are found defective. When diodes fail it usually is because of surge voltages.
Therefore, surge suppressors (SS1, SS2, SS3 & SS4) should also be checked to determine that they are operative
(refer to Section III, 3, d).
f. SCR Diodes (SCR1/SCR2/SCR3) - also see Section III, 3, e
1. These devices are either part of the SCR-diode modules or are individual components as described in
Section III, 3, e above. Power regulating devices (SCR1, SCR2 & SCR3) are silicon-controlled rectifiers, which
cannot be checked using the same method as used with rectifier diodes by forward and reverse resistance checks,
since the SCR will always show a high resistance until triggered.
2. The operation of the SCR can be checked with an oscilloscope. The control module assembly (A1)
produces the gate-firing voltage signal. The oscilloscope should be GROUND ISOLATED for these tests. This is
normally done, using a line isolation transformer, in which the secondary that powers the oscilloscope is
UNGROUNDED. Alternatively, a battery-powered portable oscilloscope can be used. The gate signal may be
checked on the control module (see Section III, 3, g) or where the twisted-pair trigger leads terminate on the SCRdiode module. The same signal should appear at both points. Absence of the signal indicates that the control module is
defective, not the SCR (see Section III, 3, g).
3. If the charger AC input breaker (CB1) trips immediately, and a shorted SCR is suspected, a simple check
with an ohmmeter can be made. Turn off CB1 and CB2. Connect to the anode and to the cathode, and adjust to the
direct reading scale of the ohmmeter. If a low resistance is observed, reverse the leads and again check the resistance.
If this reading is also low, the SCR is shorted and should be replaced.
4. An SCR can also be checked for operation with a Simpson Model 260 volt-ohmmeter. With the black lead
in common and red lead in +, put polarity switch to + DC. Connect the red lead to the anode and the black lead to the
cathode. The meter should now indicate high resistance above 50,000 ohms (when on the R x 10,000 scale). With the
leads connected as above, set the function switch to R x 1 and touch the gate to the anode. This should fire the SCR
and give a reading of approximately 5-20 ohms. This shows the SCR has been turned on. On very small SCRs, this
reading will hold after removing the gate lead. This is latched-on and can be unlatched by opening the cathode lead.
Larger SCRs will not stay on with the current available with Simpson meter. The Simpson may not have enough
current to gate or turn on extremely large SCRs (400 amp and up).
5. If the charger output is too high, unplug the control module and turn on the charger. With no gate signals
the charger should have zero output. If there is still current output, one or both SCRs are defective.
6. The above checks can be used to confirm that a suspected SCR is indeed bad. However, occasionally an
SCR might check OK in all these tests and still break down or fail in the charger circuit during normal operation. Any
SCRs suspected should be replaced.
g. Control Module PC Board Assembly (A1)
One preliminary note that should be kept in mind: The action of the overall feedback circuit controls the
battery charger output voltage so that the feedback voltage from the slider of “FLOAT ADJUST” potentiometer (R3)
to the control module board matches the 6.4 volt reference voltage on the module. Measure this voltage and if it is not
approximately 6.4 volts the feedback circuit or related circuits are not functioning. Proceed as follows using the
GROUND ISOLATED oscilloscope described in Section III, 3, f, 2 above. Make the following tests in the order
shown.
1. If the gate signals were not checked as described in Section III, 3, f, 2, do so at this time. If one or more of
the gate signals are absent when attempting to operate the charger in a normal manner, make the following checks.
Refer to FIGURE 1 on page 29 for component layout and test point locations on the trigger board. See schematic on
page 30 for related circuit diagram.
2. Check DC voltages at test point P10 [+12 VDC, +/- 0.5V]. If zero, check input and output to miniature
transformer TR1 [120V:12V AC] and check DC voltage at IC7, pin 1 [18 VDC]. Replace defective components. If
OK, proceed as follows.
3. Check three phase input voltages at resistors (R1, R2 & R3). The voltage should be 120 VAC between any
two resistors in three phase relationship. If not present, check J1 plug connections and voltages appearing between
terminal pins 1, 3 and 5 (also 120V - three phase).
Note: The following wave form tests must be made using the oscilloscope set with vertical sensitivity set
at 5V/CM and the horizontal time base set at 5mS/CM. Compare the waveforms observed with those
shown in FIGURE 2 on page 31 for the various test points indicated.
8
4. Check square wave pattern at test points A1, A2 and A3. Note the 120-degree (5.5 mS) delay between the
three patterns (scope synchronized to the 60 Hz AC line). If A1 pattern is missing, replace IC3. If A2 or A3 is
missing, replace IC4.
5. Check ramp pattern at B1, B2 and B3. Compare with those shown in FIGURE 2. Note that the exact wave
shape depends on the phase angle of SCR gates. The steeper the ramp the earlier in each half cycle the SCR is fired
and the higher the output of the charger. If waveform at B1 or B2 is abnormal or missing replace IC2. If B3 waveform
is missing replace IC1.
6. Check waveform at test points C1, C2 and C3. This comparator pulse generator produces rectangular
waveforms of varying lengths with the leading edge varying in position to a fixed-in-time trailing edge. Compare with
FIGURE 2. If C1 or C2 is missing, replace IC2. If C3 is missing, replace IC1.
7. Check waveform at test point H. This waveform should be a continuous string of very short pulses with
approximately 10V amplitude. This is the picket fence generator output. If missing, replace IC3, IC5 or IC6.
8. Check bursts of picket fence signal at test points D1, D2 and E3. Compare with FIGURE 2. If D1 or D3 is
missing, replace IC4. If D2 is missing, replace IC3.
9. Check amplified picket fence pulse trains at test points E1, E2 and E3. These pulse trains are similar to
those at D1, D2 and D3 of FIGURE 2. If E1 is missing replace Q1 or Q2. If E2 is missing, replace Q3 or Q4. If E3 is
missing, replace Q5 or Q6.
Note: The following check should be made only after completing steps 1 through 9 above. Chargers with
output ratings higher than 150 Adc may be supplied with an Auxiliary Gate Drive PC Board (A14)
triggering the phase-controlled SCRs. The A14 board intercepts the SCR gate lead wiring from the
control module (A1) as shown in drawing EH0617 on page 31. The A14 board converts the “picket
fence” pulse train (waveform similar to D1) from the control module to a DC gating signal for the main
SCRs. The A14 output will be a square wave approximately 1.5 Vdc in amplitude.
10. If a main SCR fails to turn on, trace the gate signal from the control module to A14, and from A14 to the
appropriate SCR. The AC gate signal should be approximately the same magnitude at both input and output of A14. If
an input gate signal has no corresponding output signal, replace A14.
11. If a main SCR fails to turn off, resulting in a high charger output voltage, disconnect SO14 plug from A14
board. If the main SCR now turns off, replace A14. If the main SCR remains on, the main SCR is defective and must
be replaced.
12. Check ripple waveform symmetry of the charger by connecting the oscilloscope ahead of the filter choke
(L1). Connection may be made across the bleeder resistor (R1). With the unit adjusted for about 66% output current,
observe to determine that the 360 Hz ripple pulses are of uniform amplitude. If not, slowly adjust the two balance
adjust potentiometers (R24 & R32) on the trigger board (A1). Note that phase #1 is not adjustable and is used as a
reference. Adjust the two potentiometers for the most uniform pattern yielding the lowest ripple voltage at the output
terminals. This adjustment may also be made using a sensitive AC voltmeter at the charger output terminals, and
adjusting for minimum RMS voltage indication (less than 30 mV for a filtered charger).
h. Current Sensing Resistor (SH1)
1. In light current chargers, the current sensing signal is taken directly across the DC ammeter. In chargers
with 50 Amp or higher output current, the sensing resistor is a meter shunt, which also serves as the shunt for the
panel ammeter. Use a portable precision digital voltmeter and measure the voltage drop across the current sensing
resistor. With a rated current output indicated on the panel ammeter, a nominal voltage drop of approximately 30mV
(in proportion to rated current) should be observed. If the voltage drop is higher or lower than the nominal indication,
replace the ammeter or shunt and recheck the voltage drop.
j. DC Voltmeter (M2)
1. The DC voltmeter is of the 2 percent accuracy type. It is connected across the charger output to the battery
and should indicate regardless of whether or not the charger is operating or the DC breaker is ON. If it does not, use a
precision voltmeter of the 1% accuracy type connected across the meter terminals. An indication on the test meter will
show that the panel meter is open. Check the wiring for an open circuit, or replace meter if circuit wiring is complete.
2. A shorted voltmeter will show no indication. Battery current through a shorted meter will cause a visible
indication such as smoke from burning wire insulation. Disconnect the charger from the battery and AC source and
replace the meter and damaged wiring.
3. If the meter calibration is in doubt, checking against a precision meter will determine if the panel voltmeter
is off calibration more than two percent.
9
k. DC Ammeter (M1)
1. The charger DC ammeter is connected in series between the charger output and battery. If open it
will indicate zero, or if shorted, it will also indicate zero. First be certain the connections are tight. If still no
indication, turn CB1 and CB2 breakers to OFF, disconnect the charger ammeter (and/or shunt) and
substitute a precision ammeter of suitable range. Be certain to make solid connections; clip contacts may not
carry sufficient current, or may make poor contact and cause the reading to be inaccurate.
2. A reverse-scale indication of the meter indicates the charger is inoperative or internally shorted,
and that the battery is discharging through the rectifier, or that the meter leads have been reversed. Turn
CB1 and CB2 to OFF and check wiring and meter connections. Then check meter operation, using a 1-1/2
Volt D-cell as the power source. Momentarily touch the D-cell terminals (with proper polarity) to meter
terminals and observe meter deflection.
m. Filter Capacitors (C1/C2) - (filtered chargers only)
NOTE: Capacitors C1 and C2 may consist of one or more parallel-connected capacitor units as
needed by the filtering requirements. C2 normally is used only in chargers with the filtered eliminator
option.
CAUTION: The filter capacitor is on the charger side of the blocking diode (CR2) and is NOT
charged by the battery when CB2 is turned ON. When the charger is turned "OFF" (CB1 opened) the
capacitor will hold a charge until discharged by bleeder resistor (R1). Capacitors C1 and C2 should always
be discharged before servicing in the event the R1 has opened and no longer serves as a bleeder.
1. Before attempting to check the output ripple, it should be determined that in all other respects the
charger is operating normally. Having determined this, the ripple may be checked as follows. Connect a
sensitive AC voltmeter (digital type preferred) to the battery terminals and measure the AC ripple voltage. If
it measures more than 30 milliVolts RMS check the following:
(a). That the battery connected to the output terminals of the charger has an Ampere-hour rating
of at least four times the rated capacity in amperes of the charger.
(b). The ripple is measured at the terminals of the battery.
(c). Check capacitors C1 and C2 as follows: Switch the VoltOhmmeter to the Rx100 scale and
connect the red lead to the capacitor plus terminal (marked by a red dot or plus sign) and the black lead to
the negative terminal. The meter should initially swing up scale toward zero Ohms then come back as the
capacitor charges. A reading of zero Ohms indicates a shorted capacitor while no initial swing means an
open capacitor. Either an open or shorted capacitor should be replaced.
n. Internal Wiring
1. Check internal wiring for obvious mechanical faults or wear. Follow the schematic diagram on
page 28 and check continuity with an ohmmeter to determine open connections. Check wiring against
ground also, and remove any grounds.
10
SECTION IV
SYSTEM ADJUSTMENTS
1. VOLTAGE ADJUSTMENTS AND RESPONSE
When abnormal output voltage exists (or no output current is present), and the previous checks in
Table A on page 27 “VOLTAGE ADJUST INEFFECTIVE” have been made without locating the fault,
switch the AC breaker (CB1) to OFF. Switch the DC breaker (CB2) to OFF or disconnect the battery and
proceed as follows:
Check the battery with a portable voltmeter of one percent accuracy to insure that it is not higher
than the rated float voltage. For proper operation, the open circuit voltage of the battery must be slightly
lower than the rated float voltage. If the battery voltage is higher than the float voltage range, check the
number and type of cells connected to the charger making certain the proper number and type of cells are
not exceeded. Close the DC breaker (CB2) or connect charger to battery. Close the AC breaker (CB1). If
battery voltage is now within the float voltage range or is slightly lower and some output current exists,
proceed with Section IV, 1, a, 2 below.
If the battery voltage is slightly lower or within the float voltage range, switch the charger to the
equalize mode. If still no output appears, or the potentiometer (R5) does not produce a rise from the
previous value, turn equalize charge control fully clockwise, and if still no voltage rise is obtained or no
output appears, proceed again with the check sequence in Table A trouble-shooting chart. If the voltage
increased or output was obtained when the charger switched, to evaluate proceed with the voltage
adjustments.
a. Float Adjustment
1. Since the charger must be operable for this adjustment, preceding checks in Section IV, 1
above must indicate a serviceable charger. Set switch (SW1) to “FLOAT”. Use a portable voltmeter of
one percent accuracy. Connect the battery supply leads to the battery and close the DC (battery) breaker
(CB2). Set the AC breaker (CB1) to "ON".
2. Since the EQUALIZE and FLOAT potentiometer control settings interact with each other, it is
always necessary to adjust the FLOAT control first and then the EQUALIZE control afterward. Never
finalize a voltage adjustment with the charger output in excess of 100% rated output current.
3. Turn the control clockwise, watching the response on the voltmeter. Clockwise rotation should
cause the charger output current to increase rapidly, while the voltage should rise slowly. The rate of
voltage rise depends upon whether the battery is fully charged, the size of any connected load, and the
size of the charger versus the size of the battery. After getting several volts response in battery voltage
rise, turn the FLOAT control counterclockwise. This should result in a rapid drop in charger output
current and eventually in a slow decrease in battery voltage. Now adjust the voltage for the desired float
setting and tighten the locknut on the potentiometer.
11
b. Equalize Adjustment
1. Since the equalize adjustment will not affect the float voltage adjustment and requires a higher
voltage it should always be made after the float voltage is determined. Use a portable voltmeter of one
percent accuracy as in the float adjustment. Set switch (SW1) to “EQUALIZE”. Close the DC (battery)
breaker (CB2). Set the AC breaker (CB1) to "ON".
2. In attempting to set the equalize voltage, one thing must be kept in mind. It will be impossible
to set the equalize voltage if the batteries are in a discharged condition. If fact, they must be at near fullcharge. This is to prevent the charger from going into a current limit condition. Current limit reduces the
charging voltage and no matter if the EQUALIZE potentiometer is increased to a full-clockwise position,
the charger voltage will not increase.
3. Therefore, it is suggested that the batteries be placed on equalize charge for several hours so
that the charger is no longer in current limit. This should be observed using the portable 1% accuracy
voltmeter and the charger panel ammeter. When the charging current falls below the 100% rated value of
charger current, observe the voltage and set carefully for the desired equalize voltage. If, upon
readjustment, the current again goes into current limit wait for the batteries to continue their charge
cycle. Continue this adjustment procedure until the desired voltage is reached and the current is less than
rated current. When the final setting is determined, tighten the lock nut on the EQUALIZE
potentiometer.
12
2. CURRENT LIMIT RESPONSE AND ADJUSTMENT
a. Checks and Adjustments: Make certain the charger leads are connected to the battery and that
the panel voltmeter indicates the proper polarity. Switch the DC breaker (CB2) to "ON" and AC breaker
(CB1) to "ON". The "AC ON" indicating light (DS1) should illuminate, indicating power has been
applied. With the charger in float mode, a float voltage charge should be indicated on the panel
voltmeter and the ammeter should show either a charge current, or practically none at all, depending on
the state of battery charge.
1. If the batteries are in a discharged condition, switching to the equalize mode will cause the
charger to automatically go into a current limit condition. If, however, the batteries are fully charged they
probably will not draw current in the current limit range. In order to cause this condition, it will be
necessary to connect additional load to the battery charger or battery bank. This can be resistive elements
or turning on the normal load of the installation. When current limiting is encountered, observe that the
charger voltage will be reduced below its set value by the current limit feedback signal. Observe that as
the current limit condition continues, the voltage will slowly increase as the batteries take on a charge.
Eventually the current will begin to decrease below the current limit value and continue to decrease to a
value less than 100% of rated output current. As the current decreases below 100% of rated output
current, the voltage will become constant at the equalize value and remain so.
2. To check the system response, turn the AC breaker (CB1) to "OFF" to simulate line voltage
failure. Charging current will return to zero on the instrument panel ammeter (M1), and the voltage
should reduce slightly. Place a load on the battery and discharge it heavily for a short period of time until
the voltmeter drops to float value or slightly lower. Return the AC breaker (CB1) to "ON" and observe
that charge ammeter again reads 110% of charge rate and voltage is less than the equalizing level. If
current is greater than, or less than 110% of rated charge, open the cabinet and locate the CURRENT
LIMIT potentiometer on the control trigger PC board (A1). Reference the component layout on page 29
and schematic on page 30. The CURRENT LIMIT is labeled R11 on single-phase control PC boards
(GK0058) and R65 on three-phase control PC boards (GK0048). Adjust this control for 110% charge
current. Repeat the AC circuit breaker (CB1) ON-OFF sequence listed above. If charge rate is still 110%
rated value for which it was set, close the cabinet. Restore the charger to float mode.
b. Checks to Make if Malfunctioning: If all of the above adjustments were attempted and a high
current persists, the current limit circuit on the control trigger board or the ammeter or shunt used for
current sense may be defective. The interconnecting wiring may also be faulty. Make the following
checks to isolate the fault.
1. Turn the current limit control on the control trigger PC Board (A1) to determine if it has any
effect on the high output current reading. This control is the potentiometer labeled R11 on single-phase
control PC boards (GK0058) and R65 on three-phase control PC boards (GK0048). If it does have an
effect, make the adjustment for 110% rated current for a current limit setting as described in paragraph
IV, 2, a, 2 above.
2. If no effect is noted, IC1 on the control trigger PC board (A1) may be defective. If so, replace.
3. Check the voltage generated across the ammeter (M1), or ammeter shunt (SH1) to determine
that sufficient voltage is available at rated current to activate the current-limit feedback amplifier. See
Section III, 2, h. Use a sensitive DC voltmeter and measure the voltage across the ammeter (M1) or
ammeter shunt (SH1). Measure the voltage from the "current limit" pin to the "control circuit reference"
pin, on the plug (SO1) of the control trigger PC board (A1). These pins are respectively pins #1 and #10
on single-phase control boards (GK0058) and pins #6 and #9 on three-phase control boards (GK0048). If
the sense voltage is not present at the control trigger PC board (A1), check the wiring. If the wiring is
satisfactory, proceed with the check sequence listed in Table A trouble shooting chart on page 27.
13
SECTION V
SCR/SCRF SERIES BATTERY CHARGER CUSTOMER OPTIONS
The following pages describe customer options available in SCR/SCRF Series battery chargers. The text
describes the basic operational philosophy and theory of operation. Block diagrams (or schematics) for these
options are shown in Section VIII, in numerical order of the "EJ####" specification number.
1. GROUND DETECTION CIRCUITS
Purpose: The purpose of a ground detector circuit is to indicate to the user when either the positive (+)
or negative (-) output terminal of the battery charger (or its connected load) is grounded. This is important
for many applications where a full floating system is required for operation or safety reasons. There are
several methods of indicating a grounded output terminal. These will be outlined below with an explanation
of how each works.
Descriptions:
a. POSITIVE / NEGATIVE GROUND INDICATOR LIGHTS (EJ0088)
The simplest form of a ground detection system is the two-lamp method. This utilizes two lamps of
voltage equal to the battery charger output voltage connected from the positive terminal to ground and from
negative terminal to ground. Under normal conditions, each bulb will have half-voltage applied and glow
dimly at quarter-brilliance. Upon a ground, the lamp indicating the grounded terminal will glow at full
brilliance. The other lamp will go out.
b. POSITIVE / NEGATIVE GROUND INDICATOR LIGHTS W/TEST SWITCH (EJ0089)
This is a variation of “EJ0088” above, so that the two lamps are not continuously connected in the
circuit. A double-pole, double-throw momentary center off switch (SW12) is utilized. Activating the SW12
down will connect the two lamps in series across the battery, with the center attached to chassis ground. This
performs as the two-lamp system (EJ0088) as described above. Activating the SW12 up serves to test the
lamps.
c. GROUND DETECTION SWITCH FOR DC VOLTMETER INDICATION (EJ0094)
This method uses the existing panel DC voltmeter (M2) and two double-throw switches (SW8/SW9)
to utilize the voltmeter in both functions. SW8 establishes the meter function (output voltage or ground
detection) and SW9 switches the voltmeter between (+) or (-) terminals to chassis ground, reversing the
meter polarity to maintain up-scale indications. The voltmeter, used in the ground detection mode, will
indicate the DC voltage potential between the corresponding output terminal and chassis ground. For cases
of partial grounds, the voltmeter will indicate the difference of the terminal DC voltage and the voltage of
the partial ground.
d. GROUND DETECTION ALARM RELAYS (EJ0086) - W/OPTIONAL INDICATOR LIGHTS
This method utilizes two DC relays which monitor the (+) and (-) terminal voltage to chassis ground
and will energize if the opposite polarity terminal is grounded. To insure that the relays will not energize on
half-voltage, when there is no ground present, series resistances are used to reduce the relay pull-in
sensitivity. However, once pulled in by a ground condition, the relays will not drop out when the ground is
removed because the drop out voltage of a DC relay is always less than the pull-in voltage. As a result, a
momentary “RESET” switch (SW3) must be activated to open the relays returning them to the “ready”
condition. Schematic EJ0086 shows the circuit diagram of this method. The panel lamps shown are a user
option that is available for front panel indication. The relay coil voltages, and series resistances will depend
on the output voltage of the battery charger.
14
2. AC POWER FAILURE ALARM RELAY (EJ0085) - WITH OPTIONAL INDICATOR LIGHT
Purpose: The purpose of this alarm is to notify the user that the AC input power to the battery charger
has been interrupted. A front panel "AC FAILURE" lamp is optional for local indication. Relay contacts are
provided for remote monitoring.
Description: The principle of operation utilizes the normally closed contacts of an AC relay (K1). K1 is
powered from the AC line at the primary of the transformer (T1). TM1, when energized, holds the normally
closed contacts open disabling the alarm indication. When the AC line fails or the AC circuit breaker (CB1)
is opened for any reason, the alarm contacts will close activating the alarm indicator. EJ0085 shows the
circuit with the optional panel indicator lamp and external relay connections for remote indication. The
indicator lamp must operate from the battery power since the AC line power is not available in an alarm
state. As a result, the indicator light operating voltage must match the battery DC voltage or must utilize a
series-dropping resistor to compensate for the difference in voltage between the battery and indicator lamp.
3. AC INPUT VOLTMETER (EJ0095/EJ0121) AND AMMETER (EJ0134/EJ0135) OPTIONS
Purpose: These options are to permit the user to monitor the input AC line voltage and line current to
the battery charger. This may be done for either single phase or three phase input power.
Descriptions:
a. Single phase AC: EJ0095 shows the connections to the ac voltmeter and EJ0134 shows the
connections to the AC ammeter. The ammeter is usually connected to the AC line via a current transformer
(CT1) if the line current is over 50 Amperes.
b. Three Phase AC: EJ0121 shows the connections to the ac voltmeter and EJ0135 and shows the
connections to the AC ammeter. Both show the connections utilizing a single meter, one to monitor the
three phase-to-phase voltages and one to monitor the three line currents. A two-pole, three position switch
(SW5) is used to switch the voltmeter from phase-to-phase to check all three input voltages. The ammeter
switch (SW6) is a special switch, which shorts all unused current transformer secondaries. Upon changing
switch position, it shorts the current transformer (CT1) secondary in use before transferring the ammeter to a
new position. This prevents very high voltage arcs when the secondary is open circuited.
CAUTION: NEVER OPERATE A CURRENT TRANSFORMER WITHOUT A SECONDARY
LOAD OR SHORT CIRCUIT ACROSS THE SECONDARY TERMINALS.
4. HIGH / LOW DC VOLTAGE ALARM RELAYS (EJ0083) - W/OPTIONAL INDICATOR LIGHTS
Purpose: The HIGH/LOW DC Voltage Alarm (HLVA) provides alarm indication for the DC system in
the event of a malfunction of the battery charger, which causes the battery voltage to rise or drop to a
dangerous level. Relay contacts and optional front panel lamps provide alarm indications.
Description: The HLVA printed circuit board consists of two independent operational amplifier circuits,
one monitoring the battery voltage for a high voltage condition and the other monitoring for a low voltage
condition.
The board obtains its operating voltage (12VDC) from the battery terminals and if required, an
externally mounted dropping resistor (R57).
There are two potentiometers on the HLVA PC board (A2). Viewed from the component side of the
board, the potentiometer near the top-left of the board is the LOW voltage alarm (LVA) threshold
adjustment. The right-hand potentiometer at the top of the board is the HIGH voltage alarm (HVA)
threshold adjustment.
15
If it is necessary to adjust the LVA threshold in the field, the user must load the battery bank and allow
the battery voltage to drop while decreasing the float voltage adjustment to the desired cut-off potential. The
LVA potentiometer is then adjusted so that the LVA relay is activated into the low voltage alarm condition.
Note that there is a delay time, up to 30 seconds before the relay operates once the threshold voltage is
reached. It will be necessary to raise and lower the battery voltage several times to ascertain that the
potentiometer setting is correct.
Similarly the battery bank will have to be charged at a high equalize rate in order to set the HVA
threshold. At the equalize rate the charger may go into a current limit condition, depending on the state of
charge, and it may be impossible to reach the desired high voltage alarm voltage. If this is the case, it will be
necessary to substitute a resistive load bank with paralleled capacitance in place of the batteries. Adjust the
output voltage of the charger by using the "EQUALIZE" potentiometer (R5) and then set the HVA
potentiometer accordingly.
It will be noticed that there is an operational delay time and a hysteresis zone (dead zone) between the
drop out voltage and the pull-in voltage of the alarm circuits. This is natural and desirable to prevent
chattering of the relays when the threshold voltage is reached.
The factory preset thresholds for alarm conditions are as follows unless otherwise specified:
LVA 2.00 volts/cell for LEAD ACID
1.14 volts/cell for NICKEL CADMIUM
HVA 2.40 volts/cell for LEAD ACID
Purpose: The Charger Failure Alarm provides an alarm indication whenever the charger output current
decreases to below 2% of rated current for more than 30 seconds. Alarm contacts are wired to TB3 terminals
19, 20 & 21 and an optional front-panel indicator (DS7) is available.
Description: Charger output current is sensed by means of an auxiliary winding on the main inductor
(L1). The CFA PC Board assembly (A3) detects the voltage signal from L1. When the voltage signal
indicates that the current has dropped to below 2%, an on-board relay switches to provide the alarm
indication. When the output current is restored to a value above 2%, the alarm will be automatically reset.
6. BATTERY DISCHARGING ALARM RELAY WITH INDICATOR LIGHT (EJ0120)
Purpose: The Battery Discharging Alarm indicates the condition when the battery is no longer receiving
adequate charging current from the charger and has become a source of current for the load. Alarm
indication is provided by a front panel lamp (DS10) and relay contacts. Alarm contacts are wired to TB3
terminals 22, 23 & 24.
Description: This is accomplished by monitoring the direction of current flow in a DC meter shunt
(SH3) connected in the main battery lead. When this current polarity changes from negative to positive the
alarm circuit is activated.
EJ0120 shows the connection diagram of the alarms. An op-amp voltage comparator senses when the
input signal from SH3 changes from negative to positive polarity. The op-amp output goes “high” and
activates the alarm.
The alarm board derives its power from the battery terminals. If necessary, voltage-dropping resistors are
used to properly match the battery voltage.
16
7. EQUALIZE TIMERS
Purpose: Equalize Timers are used to switch the charger into equalize charging mode for a set period of
time, when required by the batteries. "FLOAT" and "EQUALIZE" indicating lights mounted on the
instrument panel can be included with all timers to indicate the charging mode. There are three basic timers
described below. These Equalize Timers replace the standard "FLOAT/EQUALIZE" switch (SW1) featured
in the charger mainframe and referenced elsewhere in this manual.
To operate this 0-72 hour timer, turn the timer control knob (TM1) clockwise to the number of charge
hours desired. This will start an AC clock, driving two cams, which operate two contacts. One contact
provides AC to the clock motor, the other changes the voltage-sensing network to the higher equalizing
voltage. Upon completion of the time period, when the timer control knob reaches "0", the clock motor is
stopped and the voltage-sensing network is returned automatically to the float voltage value. Option EJ0096
features the aforementioned manual equalize timer, along with "FLOAT" and "EQUALIZE" indicating
lights. Option EJ0896 features the aforementioned manual equalize timer and indicator lights, along with a
manual "FLOAT/EQUALIZE" switch.
b. AC LINE FAILURE AUTO-EQUALIZE TIMER WITH INDICATOR LIGHTS (EJ0131)
The Auto-Equalize timer is designed to automatically provide an equalizing cycle when the ac input has
been interrupted longer then 10 seconds. The operation of this equalize timer is as follows. Toggle switch
(SW1) to the "AUTO/EQUALIZE" position, and the battery charger in the "FLOAT" mode: When the AC
power is interrupted for a period longer than 10 seconds and returns, the battery charger is placed in the
"EQUALIZE" charge mode for a pre-selected period of time (0 to 999 hours). The timer, now energized,
displays time remaining and completes the equalize charge period. Once the timer reaches "0" the charger
will switch to the "FLOAT" mode. The timer will shut its self down and remains ready to repeat the
operation for the same number of preset hours. The charger may also be returned to the "FLOAT" mode by
pushing the "FLOAT RESET" switch (SW11).
The schematic diagram (EJ0131) shows the circuit details. Relay (TM2) is a 10-second time-delay relay,
which latches itself closed 10 seconds after the AC power fails. When the AC power returns, the timer
(TM1) operates. As long as TM2 is latched closed, the charger is in "EQUALIZE" mode. When TM1 times
out, it opens the latch circuit of TM2 and returns the charger to "FLOAT" mode. The timer clutch then
disengages, and the timer (TM1) returns to start position. Placing switch (SW1) in the "EQUALIZE"
position overrides the timer function and manually puts the charger into "EQUALIZE" mode. "FLOAT" and
"EQUALIZE" indicating lights mounted on the instrument panel are standard, to indicate the charging mode.
c. PERCENT EQUALIZE TIMER WITH INDICATOR LIGHTS (EJ0084)
The “PERCENT” Equalizing Timer is used for certain types of batteries that required a period of
equalizing charge every 72 hours. The timer is an electro-mechanical timer whose dial reads from 0 to
100%, and whose drive motor rotates internal cams once every 72 hours.
If the operator sets the “percent” dial for 10%, for example, the timer will operate the cams such that the
EQUALIZE charge contacts will be closed for 7.2 hours (10%) out of the 72 hour continuously cycling
rotation period.
There is a manual "FLOAT/AUTO-EQUALIZE" switch (SW4), which interrupts the motor circuit when
the batteries are to be left in "FLOAT" charge.
"FLOAT" and "EQUALIZE" indicating lights mounted on the instrument panel are standard, to indicate
the charging mode. The timer is used to drive a DP-DT relay (K6). One set of the relay’s contacts control
the float/equalize charging while the other set of contacts control the indicating lights.
17
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.