A Fan Box has been designed to assist with the cooling of the PA Heatsink cast ing f or the
VHF EX7100 product range.
The Fan Box consists of a metal enclosur e with two (2) fan assemblies that f its over (and
is bolted to) the existing PA Heatsink. DC Supply for the fans is provided by the existing
DC input socket on the rear of the EX7100 Terminal.
1.0.1 Date of release
All VHF EX7100 Terminals produced aft er 1 May 2001 will include the Fan Box (Product
Code 61-8057-00002). It will be factory-fitted during the manufacturing process.
1.0.2 Terminal Mounting Considerations
The Fan Box fits snugly around the existing PA Heatsink casting and does not adversely
affect the overall width or depth of the EX7100 Terminal but does
affect the height .
The top of the Fan Box will be approximately 40mm above the top cover of t he EX7100
Terminal. However, as it is recommended that a gap of at least 2U (89mm) is left
above/below the EX7100 Terminal and any other equipment, this additional height should
not become a problem for standard 19” Rack mounting.
2.0 Removal Instructions
The following sections detail the steps necessary to rem ove the Fan Box to allow access
to the PA Heatsink casting.
2.0.1 Tools required
> M5 Short Arm Hex Wrench
> Medium sized insulated flat-blade screwdriver
2.0.2 Procedure
1) It is necessary to isolate the EX7100 Term inal f rom any mounting shelf prior to removal of
the Assembly.
(Depending on the leng ths of any antenna, telephone or DC power cables, it will probably
be necessary to remove these to allow unobstructed Terminal access)
2) Switch off the DC supply to the Terminal (if not already removed) and place the Terminal
on a clean, flat surface.
3) Refer to Figure 1 (overleaf) and remove the 2x M6 socket cap screws and washers from
the Fan Box Assembly using the Short arm Hex wrench. The removed screws and
washers should be put to one side for future r eplacem ent.
Figure 1: Assembly connected to the EX7100 Terminal
4) Remove the Fan Box DC supply cable from the rear of the EX7100 Terminal, taking
careful note of the existing wire connections f or future re-assembly (the BROWN wire is
connected to the +ve input and the BLUE wire is connected to the –ve input)
5) Carefully remove the Fan Box Assembly from the EX7100 Terminal. Access is now
available to the PA Heatsink casting.
6) Refer to Section 7 of t he EX7100 Technical Manual for further infor mation regarding the
replacement of the Heatsink casting and/or the PA Assembly.
7) Reverse the above-mentioned steps as required t o r e- assem b le t he Fan Box.
The following information outlines the mandatory regulations governing the installation
and operation of the Exicom EX7100 digit al radio link.
Adherence to this information is necessar y to ensure regulatory compliance.
1.0 General Requirements
This equipment shall be configured only with those assemblies as specified in the
Technical Manual and shall only be mounted as instructed.
1.0.1 Danger
The Modem/Controller module contains a lithium bat ter y. Ther e is a danger of explosion if
the battery is incorrectly replaced. Replace only with the same or equivalent type
recommended by the manufacturer.
Dispose of used batteries according t o the manufacturers instructions. Do not recharg e,
disassemble or incinerate.
Mandatory Regulations
1.0.2 Warning
This equipment must only be installed and maintained by service personnel.
1.0.3 Access to the Equipment
The EX7100 digital radio link should be installed in a location or environment that
prevents unauthorised access.
1.0.4 Equipment Port and Connector Classifications
The EX7100 digital r adio link contains various ports and connectors t hat are classified as
either Safety Extra Low Voltage (SELV) or T elecommunication Network Voltage (TNV) as
follows:
SELV TNV
> DC Power Input
> G.703 (3x ports)
> I/O
> Sync Data
> Line Interface Module Connector
> Control
> LMS
> Front Panel Test Pin Sockets
Connect SELV circuits on this equipment
The wire used for saf et y eart hing should be a minimum of 4mm2 and should preferably be
directly connected to an earthing stak e dr iven into t he ground
Refer to Section 2.8 of t he Technical Manual for specific instructions
2.0 Country-specific Regulations
The following sections detail any regulations that may be required by specific countries
and/or territories.
2.0.1 New Zealand Regulation - PTC 200
• “The grant of a Telepermit for any item of terminal equipment indicates only that
Telecom has accepted t hat the it em complies with minimum conditions f or connection
to its network. It indicates no endorsement of the product by Telecom, nor does it
provide any sort of warranty. Above all, it provides no assurance that any item will
work correctly in all respects with another item of Telepermitted equipment of a
different make or model, nor does it imply that any product is compatible with all of
Telecom’s network services.”
• “This equipment m ay not provide for the eff ective hand-over of a call to another device
connected to the same line.”
• “IMPORTANT NOTICE
Under power failure conditions, this device may not operate. Please ensure that a
separate telephone, not dependent on local power, is available for emergency use.”
• “Use of pulse dialling, when this equipment is connected to the same line as other
equipment, may give rise to bell tinkle or noise and may also cause a false answer
condition. Should such problems occur, the user should NOT contact the Telecom
Faults Service.”
• “Devices designed to respond to particular ringing cadences may not respond when
used with this equipment.”
• In the event of any problem with this device, it is to be disconnected and a CPE item
connected to one of its terminal ports m ay be connected directly in its place. T he user
should then arrange for the product to be repair ed. Should the matter be reported to
Telecom as a wiring fault, and the f ault be proven to be due to this product, a call-out
charge will be incurred.”
• “Note that the receive audio line level must not be more than 3dB higher than the
transmit audio line level. (for typical installations using short telephone cable lengths, it
is recommended that the receive audio line level is set for –3dBm)”
• “The maximum number of parallel CPE devices that can satisfactorily be operated on
a single port is two (2)”
• “This unit should be powered from a supply that is compliant with AS/NZS3260 and is
All rights reserved. This publication is copyrig ht.
No part of this work may be reproduced or copied in any form or by any means (electrical,
mechanical, photocopying, microfilm ing, recording or otherwise) without the written permission
of Exicom Technologies (1996) Ltd, Private Bag 50912, Porirua, New Zealand.
Confidentiality
This document contains confidential information which belongs to Exicom Technologies (1996)
Limited. All information is supplied to you in confidence on the basis that it must not be used by
you (except for product evaluation purposes) or disclosed to any person without Exicom
Technologies (1996) Limited’s prior written consent.
Any breach of the above obligation may be restrained by legal proceedings seeking remedies
including injunctions, damages and costs.
Disclaimer
Exicom Technologies (1996) Limited constantly seeks to improve quality and performance.
Therefore, specif ications and configurations are subject t o change without notice.
Product code: 61-8031-00002
EX7100 Technical Manual - Contents
Contents
Page
List of Figures
1 Introduction
1.1 General 1-1
1.2 Configuration 1-2
1.2.1 64 kbit/s digital “pipe” 1-2
1.2.2 Six low bit rate voice/fax/data channels 1-2
1.3 About this Manual 1-3
1.4 Terminology 1-3
1.5 EX7100 Specifications 1-4
1.5.1 System Parameters 1-4
1.5.2 Power, Mechanical and Environmental 1-4
1.5.3 Multi-channel Voice and Data Multiplexer 1-5
1.5.4 Data Channel 1-6
1.5.5 System Management 1-6
1.6 System Planning 1-7
2 Installation of Antenna and Equipment
2.1 General 2-1
2.2 Antenna Sites 2-1
2.3 Mounting the Antenna 2-2
2.3.1 Antenna Polarisation 2-2
2.3.2 Antenna Direction 2-3
2.3.3 Antenna Cable Grounding Kits 2-3
2.4 Positioning the EX7100 Terminal 2-4
2.5 Mounting the Terminal in the Rack 2-5
2.6 Cable Connections 2-5
2.6.1 General 2-5
RF Connection 2-5
DC Power Input 2-7
2.7 Terminal Type Specific Connections 2-8
2.7.1 Digital Data Terminal Connections 2-8
Synchronous Data V.35 2-8
3.4.1 Universal Parameters 3-3
Passwords 3-3
Changing the Time and Date 3-5
Operating Mode 3-5
Link ID 3-6
Terminal Descriptor 3-7
Changing the RF Channel Increment 3-7
Changing the Local Transmitter Frequency 3-8
Changing the Local Receiver Frequency 3-10
Transmitter RF Power Level 3-11
Interface Type 3-11
3.4.2 Data Terminal Parameters 3-12
Tx Data Clock Synchronisation 3-12
Sync Data Polarity 3-13
3.4.3 Exchange Terminal Parameters 3-14
Operating Mode 3-14
Channel Set-up 3-14
Payphone Metering Frequency 3-15
Transmit Audio Line Level 3-16
3.4.4 Subscriber Terminal Parameters 3-17
Ringer Frequency 3-17
Line Termination Impedance 3-17
Payphone Metering Frequency 3-18
Transmit Audio Line Level 3-19
Receive Audio Line Level 3-19
Telephone Loop Current 3-20
4 Monitoring and Diagnostics
4.1 General 4-1
4.2 Monitoring the EX7100’s Operation 4-1
4.2.1 RF Parameters 4-1
4.2.2 Power Supply Parameters 4-2
4.2.3 Framer Parameters 4-3
4.3 Monitoring a Remote Terminal 4-3
4.3.1 Setting up a Test Link 4-4
4.3.2 Closing the Test Link 4-5
4.3.3 Changing Operating Frequencies Remotely 4-5
4.4 EX7100 Internal Alarms 4-7
4.4.1 Acknowledging an Alarm 4-8
4.4.2 Setting Alarm Priorities 4-8
4.4.3 Link Up Time Alarm 4-9
4.4.4 Low RSSI Alarm 4-10
4.5 Diagnostic Tools 4-10
4.5.1 System Align Mode 4-10
4.5.2 Digital Loopbacks 4-11
Local Loopback 4-12
Remote Loopback 4-12
Enabling Digital Loopbacks 4-12
The EX7100 is a unique digital radio primarily designed to meet the requirements of
customers who require thin route communications, especially in remote and rural
locations, but also in urban areas where digital linking is required. It is an ideal solution
where copper wires are too expensive or difficult to install.
The EX7100 is a 64kbit/s dig ital radio that operates within a 25kHz RF channel. It has a
number of unique features including:
> On-demand operation,
> Automatic fax and modem data detection ( with inter nal multiplexer installed),
1
Introduction
> G.703 and Synchronous Data interface (V.35) t o connect to external devices,
> An optional internal six circuit, voice/fax/data, multiplexer,
> High system gain with 2 W att or 10 Watt power amplifier options,
> Inherent security through proprietary digital encoding,
> Robust design to operate in a variety of environmental condit ions.
1.2 Configuration
The EX7100 is a point to point, line of sight system available in two configurations as
detailed below:
1.2.1 64 kbit/s digital “pipe”
The 64kbps single channel config uration uses G.703 and/or synchronous data interfaces
(V.35), for connection to external OEM multiplexers, bridges, routers, LAN’s, etc. The
actual transmitted bit rate including system overheads is 68 kbit/ s, allowing a full 64 kbit/s
for the user.
This congifuration is also used to provide a full duplex repeater option, based on two
terminals back-to-back at G. 703 inter f ace. A r epeater enables t he user t o gr eatly increase
the distance between the end terminals
With the addition of an internal multiplexer/line interface card the EX7100 provides six,
low bit rate, voice/fax/data channels.
This option is designed to replicate six individual standard wireline telephone circuits and
caters for both 2-wire and 4-wire + E&M (with additional card) telephone operation. Line
drivers and ringers are integral to t he card, allowing telephone equipment to be situated
up to 5 kilometres fr om the terminal when used with external lightning protection.
Most equipment normally connected to telephone lines may be connected to each
channel of the EX7100, including payphone (12/16 kHz meter pulse or line reversal),
electronic funds transfer terminals, G3 fax and data traf fic at up to 9600bps.
Note that provision of voice/fax data tr affic requires external telephone modems at each
location. Modem/Fax data rate is limited to 9600bps.
The six-channel version of the EX7100 is available in two configur ations:
Exchange Terminal
Provides connection for six telephone circuits (either 2-wire or 4-wire +E&M) from the
PSTN. Using two exchange terminals, t he link may be config ured in software for Point-t oPoint Data terminal operation, providing six 9600bps data channels with 4-wire + E&M
interface.
Subscriber Terminal:
Provides connection for Subscriber equipment (2-wire), such as telephones, facsimile,
modem, etc.
Note: The telephone interface circuit boards within these terminals are specific to each
terminal type, i.e. an Exchange terminal cannot be linked as a Subscriber terminal,
or vice versa.
This Manual contains all the information necessary to enable installation and configurat ion
of an EX7100 as well as module and fault diagnosis information.
1.4 Terminology
The following terms and abbreviations are used throughout this manual:
BER Bit Error Rate,
BERT Bit Error Rate Test,
DSP Digital Signal Processing,
ESN Electronic Serial Number,
LCD Liquid Crystal Display
LED Light Emitting Diode,
LMS Link Management System,
LTF Line Terminating Frame,
MDF Main Distribution Frame,
PA Power Amplifier
POTS Plain O ld Telephone System
PSTN Public Switched Telephone Network
PSU Power Supply Unit,
RSSI Receive Signal Str ength Indication,
TCXO Temperature Controlled Crystal Oscillat or ,
VSWR Voltage Standing Wave Ratio.
This manual refers to “Exchange Terminal” and “Subscriber Terminal” however the
installation instructions apply equally to non-telephone, or Dat a, systems.
Digital Radio link planning is a complex procedure req uiring a study of each site and the
path between each site. Exicom T echnologies is able to assist in system planning if this is
required.
Specialist software packages are used by Radio System Engineers to determine path
losses and sources of interfering signals that may affect the reliability of the radio link.
(Unlike an FM signal, a digital radio signal is suscept ible to interf erence and f ades, similar
to those found on television broadcast systems)
The EX7100 is capable, under ideal circumstances, of providing communications over
paths of more than 50 kilom et r es.
However, the following considerations must be taken into account, which will assist in
determining the maximum link dist ance and system r eliability:
> Operating frequencies
> Free Space loss
> Terrain effects: Absorption and Reflection losses
> Antenna gain and position
> Cable losses
> Transmit power
> Receiver sensitivity
> Required fade margin
Further to these considerations, the system designer must be aware of factors at each
site, which may affect the reliabilit y of the radio link. These f act ors include:
> Access to a reliable power source.
> Antenna height.
> Access to a suitable grounding system.
> Lightning and surge protect ion
> Other radiating and receiving systems using t he site
EX7100 Technical Manual - Installation of Antenna and Equipment
Installation of Antenna and Equipment
2.1 General
2
Although EX7100 Radio Link terminals can be installed in any order, the following
sequence should be followed to ensure that minimum t im e is spent on installation.
> Install Exchange antenna (Section 2.3),
> Mount the Exchange terminal (Sections 2.4 and 2.5),
> Connect power, antenna and interface cables to the Exchange t er m inal (Section 2.6),
> Configure and test Exchange ter m inal ( Sect ion 3) ,
> Repeat the above steps for the installation of the Subscriber antenna, Subscriber
terminal and cabling (Sections 2.3 to 2.6 inclusive and Section 3) ,
> Final antenna alignment at Subscriber site ( Sect ion 2.11),
> Final antenna alignment at Exchange site (Section 2. 11) .
THIS EQUIPMENT MUST ONLY BE INSTALLED AND
MAINTAINED BY SERVICE PERSONNEL
WARNING
> Establish a test link to confir m oper at ion of system (Sections 4.3.1 and 4.3.2),
Note: Ensure that the correct terminal is dispatched to the appropriate site (Terminal
information can be found on a label on the side of the packing box).
2.2 Antenna Sites
Antenna sites for the EX7100 installat ion should have been chosen as part of the system
planning process (Refer to Section 1.6). If they have not been selected, contact your
Exicom International Supplier.
Radio path planning is a highly technical procedure and should only be performed by a
qualified person.
EX7100 Technical Manual - Installation of Antenna and Equipment
2.3 Mounting the Antenna
The antenna should be mounted high enough so that it is in "line-of-sight" with the
antenna at the other radio site (antenna heig ht may have been determined during system
planning). The antenna should be placed at least 10 m etres (VHF) or 3.5 metres (UHF)
from any metallic or conductive objects to avoid possible impaired operation of the
EX7100 link and fastened securely to protect against the effect s of strong winds.
When mounting the antenna, ensure it is pointing in the correct direction with the correct
polarisation. Final adjustments to t he antenna direction are made af ter both terminals are
installed. Refer to Section 2. 11 " Final Antenna Alignment".
2.3.1 Antenna Polarisation
The site plan should include details of antenna polar isation. If it doesn't, use t he following
information as a guide:
The antenna may be mounted with either vertical or horizontal polarisation. Figure 2.1
shows an antenna mounted with vertical polarisation (top) and horizontal polarisation
(bottom). In general, either polarisation can be used although each antenna must
identical polarisation.
have
Note: Vertical antenna polarisation is prefer red if the r adio link is to be used over a body
EX7100 Technical Manual - Installation of Antenna and Equipment
2.3.2 Antenna Direction
The site plan should include details of antenna direction. If it doesn't, use the following
information as a guide:
Refer to a map with the antenna sites marked. The antennas must point towards each
other in a straight line for the link to operate eff ectively. Take a compass bearing of each
antenna as shown in Figure 2.2. This is the direction the antenna should point towards
when mounted.
Figure 2.2: Antenna Direction
2.3.3 Antenna Cable Grounding Kits
To assist with lightning protection, coaxial cable grounding kits should be used at each
site. Grounding of the cable is recommended at the tower top, tower bottom and at the
entrance to the equipment shelter .
A range of grounding kits are available. Contact your Exicom International Supplier for
details.
EX7100 Technical Manual - Installation of Antenna and Equipment
Positioning the EX7100 Terminal
Before deciding on the position of the terminal, consider the following:
> The antenna coaxial cable should be as short as practical to m inimise transmission
losses,
> The EX7100 requires good ventilation to allow generated heat t o escape. Although
the maximum temperature environment f or the EX 7100 is +60°C, lower temperatur es
will assist with trouble-free operation, as is the case with most elect r onic equipment,
Always allow a gap of at least 2U
1
(89mm) above/below the terminal and any other
equipment,
> The EX7100 should be mounted close to a source of power, telephone wires (if
required) and the antenna cable. Note: Ensure that sufficient room for any cables
(including adequate bend radius etc) is present prior to positioning the terminal
> Access to a good earth is essential (separate t o m ains ear t h) r efer to Section 2.8,
> It may be necessary during the installation process (or subsequent servicing) to
access the rear panel of the term inal. Sufficient room should therefore be provided
around the terminal to allow access to any connections (such as the RS485 port that
may be used for PC control during test ing and set-up).
2
Ensure that the equipment racks are stable and capable o
supporting the weight of the EX7100 terminal before
equipment installation. Note t hat unsecur ed rack s may tip over,
causing damage to equipment or personal injury
WARNING
1
One U = 44.5 mm or 1 ¾ inch
2
Terminal depth of 425mm is measured from front panel handle to end of rear panel bracket. Additional
depth allowance may be required to cater for connecting cables etc.
EX7100 Technical Manual - Installation of Antenna and Equipment
2.5 Mounting the Terminal in the Rack
The EX7100 is compatible with the industry standard 19" rack system and occupies 3U1
(VHF) or 4U (UHF) of vertical space.
> Attach the handles to the EX7100 front panel using the handle kit supplied.
> Attach the front panel to t he r adio t erminal using the six screws supplied.
> Mount the terminal to the r ack using the f our front panel mounting points. Due to the
weight of the EX7100 terminal (approx. 15 kg), it is highly recommended that the
terminal be supported with the use of angled side rails. These rails are commonly
found in 19” racking systems (but are not
> Ensure that the terminal’s chassis ground is connected to the equipment rack’s
ground via the chassis earth screw terminal. (Refer to Section 2.8)
included with EX7100 terminals).
2.6 Cable Connections
2.6.1 General
Cable configuration is dependent on the variant of the terminal being installed, i.e. Data,
Exchange, or Subscriber. (Refer t o section 1.2)
However, there are some generic connections required, r egardless of variant type:
> The RF connection,
> The power supply connection,
> The earth connection.
RF Connection
VHF system
cable to the N-type socket mark ed ‘ANT’.
UHF system:
antenna’s coaxial cable to the N-type antenna socket on the lid of the terminal. If the
duplexer leads have been disconnected from RF connectors on the rear panel, it is
important they are reconnected correctly.
The connector marked thus: is connect ed to the Transmitter. (RF out) .
: The VHF EX7100 uses an internal duplexer Connect t he antenna’s coaxial
The UHF EX7100 uses an externally mounted duplexer. Connect the
The connector marked thus: is connect ed t o the Receiver. (RF in).
EX7100 Technical Manual - Installation of Antenna and Equipment
If the terminal’stransmitter frequency is higher t han it’s receiver frequency, the RF output
connector should be connected to the high-pass side of the duplexer.
If the terminal’str ansmitter frequency is lower than it’s receiver frequency, the RF output
connector should be connected to the low-pass side of the duplexer.
Figure 2.3 below shows the RF connections for a UHF duplexer.
Tx or RxTx or RxA ntenna
1234567
BRBP
Band Reject
Band Pas s
Filte r
(H PF)
A B C
High
4 Cavit y Duplex filter
D E F G
adjustment
High pass
Figure 2.3: UHF Duplexer Connections
Low
BPBR
Band Pas s
Band Reject
Filter
(LPF)
H I J
adjustment
low pass
A suitable lightning arrestor must
be installed at all
times in the coax cable between the EX7100 terminal
and the antenna.
EX7100 Technical Manual - Installation of Antenna and Equipment
The arrester must have a direct earth connect ion and must be mounted at either the base
of the antenna mast or where the coax cable enters the building. For further detail on
mounting the antenna, refer to the documentation that accompanies it.
Note: Ensure that any coaxial connectors exposed to the weather are adequately
protected with suitable weatherproof t ape that com pletely seals the connect or f rom
moisture.
DC Power Input
The EX7100 terminal is supplied with two variants of internal power supply:
> 10.8 VDC – 30 VDC Input
> 30 VDC – 60 VDC Input
If the terminal is to be powered by an existing DC power supply, ensure the voltage
supplied by the power supply system falls within one of the ranges detailed above.
Note: The terminal has a built-in sensing circ uit and will not operate if t he supply voltage
or polarity is incorrect.
NOTICE
Supply power to this equipment must be provided via an approved
power supply whose output voltages are in accordance with the
Safety Extra Low Voltages (SELV) limits as specified in IEC950.
Failure to operate this equipment with this type of power supply
would void safety approvals
DC Input cabling should be capable of carrying 15 Am ps @ 12V, 7.5 Amps @ 24V, and
4.0 Amps @ 48V. The maximum
Note: The terminal requires an external fuse (not supplied
permitted voltage drop in the cable is 200mV.
) within the DC Input cabling.
Fuse ratings vary depending on the nominal DC input voltage used:
Nominal DC Input Voltage Fuse Rating
12 V DC 60 Amp HRC type
24 V DC 30 Amp HRC type
48 V DC 20 Amp HRC type
HRC fuses should be used with a minimum current breaking capacity of 5000
Amps (as lead acid batteries are likely to be used to back up the DC supply)
EX7100 Technical Manual - Installation of Antenna and Equipment
Connect the power supply cable to the 3-way connector marked ‘- GND +’. The DC input
lines on this connector are floating and have no power connection to the chassis ground
(neither the positive nor the negative term inal is connected to the EX7100 chassis). This
enables the EX7100 to be powered from either a positive or negative ground supply.
The centre term inal of the DC input connector is connect ed to the EX7100’s chassis and
may be strapped to the side of the DC input t hat is at station ground potential.
2.7 Terminal Type Specific Connections
The EX7100 is supplied as one of three types, Data, Exchange, or Subscriber. (Ref er to
section 1.2). The interface connections to each terminal type are diff er ent.
Connection details for the three t er minal types are as follows:
2.7.1 Digital Data Terminal Connections
The EX7100 provides both synchronous Data, e.g . V.35 and CCIT T G.703 co-dir ectional,
digital interfaces. The terminal automatically detects the presence of a digital interface
card.
Selection of the interf ace req uired is m ade in soft ware using the front panel keypad. Refer
to Section 3.4.1 for configuration details.
Synchronous Data V.35
Once selected, the synchronous Data interface is m ade available on the DB15 connector
labelled ‘SYNC DATA’ on the ter minal’s rear panel. Detailed pin-out information can be
found in Appendix A.4.
Various adapter cables are available to cater for V. 35, RS-232 conversion. Contact your
Exicom International Supplier for det ails.
G.703
Once selected, the G.703 interface is made available on the DB15 connector labelled
‘G.703’ (for detailed pin-out information refer to Appendix A.3) and also on the pair of
BNC connectors labelled ‘G.703’, on the ter m inal’s r ear panel.
The DB15 connector provides a 120 Ohm co-directional interface, whereas the BNC
connectors provide a 75 Ohm co-directional interf ace. It should be noted that the arrows
alongside the BNC connectors indicate the data flow to and from the terminal.
2.7.2 Exchange Terminal Connections
The EX7100 Exchange terminal allows connection of six 2-wire telephone circuits; six 4wire+E&M telephone circuits, or six 4-wire+E&M data circuits (up to 9600bps).
All circuits are connect ed to t he terminal via the 50-way Champ connector, labelled ‘LINE INTERFACE’, on the terminal’s rear panel. (For detailed pin-out information refer to
Appendix A.6)
The Exchange Terminal may be supplied with a 3 or 10 metre cable that can be plugged
directly into this connector. The other end of this cable should be terminated into the
PSTN’s MDF. Contact your Exicom International Supplier for details.
EX7100 Technical Manual - Installation of Antenna and Equipment
Note: The EX7100 automatically detects the presence of an Exchange interface card.
The terminal is conf ig ured f or 2-wire or 4-wire+E&M, in software via the f ront panel
keypad. Refer to Section 3.4. 3 for configuration details.
The Exchange terminal may also be soft ware config ured, via the fr ont panel keyboard, as
a point to point Data terminal. Refer to Section 3.4.3 f or configuration details.
2.7.3 Subscriber Terminal Connections
The EX7100 Subscriber terminal provides six 2-wire telephone circuits for connection to
equipment such as telephones, payphones, EFT-POS t erminals, etc.
These circuits are accessed from the terminal via the 50-way Champ connector, labelled
‘LINE INTERFACE’, on the terminal’s rear panel. (For detailed pin-out information refer to
Appendix A.6)
The Subscriber terminal may be supplied with a 3 or 10 metre cable that can be plugged
directly into this connector. The un-terminated end of the cable may be either wired
directly to the user equipment, to an existing MDF, or to Exicom’s optional Line
Terminating Frame (LTF). Contact your Exicom International Supplier for details
Note: The EX7100 automatically detects the presence of a Subscriber inter face card.
The LTF is available with various connector options, as well as optional Primary Lightning
Protection circuitry. Contact your Exicom Int ernational Supplier for fur ther details.
2.8 Earthing the Terminal
The provision of a suitable earth f or the terminal is the responsibility of the installer. The
EX7100 has a screw terminal on the rear panel to connect the t er m inal to earth.
This will assist in preventing damage to the terminal from lightning strikes, particularly
strikes to the telephone cables. Protection from strikes to the antenna system may be
provided by fitting the recommended antenna lightning arrester.
For these protective measures to be effective, the system requires a good earth
connection. Mains earth is not
adequate, nor is a thin wire or any wire with bends or twists
in it.
The best earth connection is using a suitably heavy wire (e.g. >4 mm
connected straight to an earthing stake driven into the ground
If this is not possible, connect the ear t h cable t o the equipment rack ground system .
2.9 Other Rear Panel Connections
2
copper cable)
The EX7100 is f itted with several other rear panel connect ors as detailed below. Some of
these connectors will not be used for all applications, however descriptions of their
functions are detailed below.
Note: Detailed pin-out infor m ation can be found in Appendix A.
EX7100 Technical Manual - Installation of Antenna and Equipment
2.9.1 Control
A DB9 connector provides access to the internal RS-485 bus for future expansion of the
EX7100, and for back-to-back repeater connection. This connector will allow system
control of externally mounted interface cards that are yet to be developed. The Control
bus is not
user accessible.
2.9.2 LMS
A DB9 connector provides access to the internal RS-485 bus to allow daisy chaining of
multiple terminals and connection to an external Link Management device - ELMS. Refer
Appendix B-2.
2.9.3 I/O
A DB25 connector provides high and low priority alarm outputs, and six input/output
contacts for connection of non-latching externally generated site alarms that are sent
across the radio link when triggered.
Important Note: The I/O port is optically isolated. Details of maximum voltages and
currents are given in Appendix A.5. Failure to comply with this criteria may cause damage
to the I/O port.
External Site Alarms
The EX7100 provides the facility to connect up t o six non-latching external alar m contacts
which, when triggered, are sent across the radio link. Alarms may include: Site door
alarm, site fire alarm , or generator fuel low alarm.
When an external alarm cont act closes, the alarm is sent across the link, via the
engineering channel, and the corresponding output at all intermediate ter m inals ar e
triggered. An external alarm appear s on the front panel along with standard alarms.
Received
Burgla r Alarm
External output 0
goes low
Burgla r Alarm
External output 0
goes low
I/O
o o
o
o o
o
o o
EX7100
EXICOM
EX7100
EXICOM
2.9.4 RF
Allows connection to an externally mounted Duplexer, if required. (For example, UHF
Duplexer Type 8045)
EX7100 Technical Manual - Installation of Antenna and Equipment
2.10 Powering up the Terminal
2.10.1 General
Before powering up, ensure that all cables are connect ed correctly and that there is DC
power to the EX7100 terminal. Pay particular attention to the RF cable assembly,
ensuring all connections are tight.
The EX7100 on/off switch is located on t he r ear panel.
Note: This switch has an interlocking feature that prohibits accidental switch off. To
toggle the switch on or off you must pull the switch gently forward.
2.10.2 Procedure
Turn on the EX7100 terminal with the on/of f switch. The EX7100 will perform an internal
initialisation test, befor e set tling to its idle state.
Figure 2.5: EX7100 Front Panel Display - Initialisation Test
In this idle state, the f ront panel LCD will display:
initialising
■■■■■■■■■
Figure 2.6: EX7100 Front Panel Display – Idle State
Exicom EX7100
1 Jan 1210:01
Note: ‘Exicom EX7100’ is the factory default t erminal descriptor. This descriptor can be
any 16 character string , and may be changed at any time (Ref er to Section 3.4.1) .
If this descriptor was specified at time of order, the display will reflect that. For
example:
Figure 2.7: EX7100 Front Panel Display – Order Specified Terminal Descriptor
Exchange no 1
1 Jan 1210:01
If the Operating Mode is configured as ‘100%’ mode, the ‘Tx on’ LED will light and the
system will attempt to establish a link with the remote ter minal. This condition will continue
until a link has been established, indicated by the ‘Rx lock’ LED being lit.
If the Operating mode is configured as ‘on-demand’ the terminal will not turn on its
transmitter until a valid req uest is sent f r om the r elevant user int erf ace, e.g . t elephone of f hook.
EX7100 Technical Manual - Installation of Antenna and Equipment
It is now recommended that you proceed to Section 3 ‘Configuring the Terminal’, to
ensure that the EX7100 terminal has been configured for your specif ic applicat ion.
2.11 Final Antenna Alignment
2.11.1 General
This part of t he installation req uires t wo people, or one person with an analogue voltm eter
plugged into the terminals front panel monitoring point. The voltmeter leads need to be
long enough for the inst aller t o view the display while rotating the ant enna.
You will also need to refer to Section 3 of this Manual for instructions on using the
EX7100’s front panel.
Do not stand in front of the antenna, as electromagnetic radiation
may be hazardous to your health. Leave at least 1 metre between
the installer and the antenna as shown below
Figure 2.8: Antenna Alignment
2.11.2 Alignment Sequence
1) Set up a Test Link by following the
procedure outlined in Section 4.3.1.
2) Use the up and down arrow keys to
make sure the →→→→ is next to Antenna
Align and then press ‘Enter’
EX7100 Technical Manual - Installation of Antenna and Equipment
3) The local terminal’s transmitter will turn
off (Tx LED will go off), allowing the user
to adjust the antenna safely. T he r em ot e
Tx will remain on for up to 60 minutes.
RSSI is now displayed on the screen as
well as on the voltmeter inputs on the
front panel.
4) While one person watches the RSSI
level, the other should move the antenna
direction slightly until the RSSI level is at
its highest. This is the optim um antenna
alignment. Make sure you stand at least
one metre behind the active element
while taking a reading so as not to cause
interference. Tig hten the mounting bolts.
(Note: One person can do both tasks if a
voltmeter with long leads is connected to
the jacks on the front panel.
5) Press ‘Escape’. T he link will restart and
the menu will return to Antenna Align.
Press ‘Escape’ again then use the up
and down arrows to make sure the →→→→ is
next to End Remote Tests and then
press ‘Enter’.
RSSI: -95 DBM
■■■■■■■■■
RSSI: -90 dbm
■■■■■■■■■■■
Start tests
→end remote tests
This completes the installation of the terminal.
Repeat this “Final Antenna Alignment” procedure for the other ter minal.
EX7100 Technical Manual - Configuring the Terminal
3.1 General
In many cases, the terminal will have been configured in the factory, however it is
recommended that certain operating parameters be checked and corrected as required
before attempting to set-up a link.
The EX7100 is equipped with a powerful configuration, monitoring, and diagnostic, system
that may be accessed using the six-button keypad and LCD on the f ront panel. The front
panel also has four LED's that indicate the operating status of the terminal, as well as any
alarms being generated by the terminal.
3.2 Using the Keypad
3
Configuring the Terminal
The EX7100 six-button keypad allows the user to scroll through the user interface menu,
and then select, or change, the relevant parameters.
A password is required to allow access to the menu system. This password is ‘1111’, and
cannot be changed
operating parameters. This password may be changed at any time from the Exicom
default value of ‘1234’. Refer to Section 3.4.1 for details.
Direction Buttons
The four direction buttons provide up and down scrolling, as well as moving the cursor left
and right along any particular line.
Example: To change the default second level password from ‘1234’ to ‘2222’
(Refer to Section 3.4.1 for full details):
> Use the right arrow key to position the ↑↑↑↑ under the ‘1’.
> Press the up arrow key once to change the ‘1’ to a 2.
Exicom EX7100
1 Jan 1200.01
. A Second Level password is required to allow amendment of
Figure 3.1: EX7100 Front Panel Display and Keypad
> Press the right arrow key twice to position the ↑↑↑↑ under the ‘3’.
> Press the down arrow key once to change the ‘3’ to a 2.
> Press the right arrow key once to position the ↑↑↑↑ under the ‘4’.
> Press the down arrow key twice to change the ‘4’ to a 2.
> Press ‘Enter’ to accept changes.
EX7100 Technical Manual - Configuring the Terminal
Note: The user menu is not
a continuous loop. Once the cursor reaches the bottom of the
menu, you must use the up arrow to step back up to the top. Similarly, once the
cursor reaches the top of the menu you must use the down arrow to step back
down.
‘Enter’ Key
The ‘Enter’ key operates the same as a computer keyboard ‘Enter’ key. This will accept
any changes you have made to a parameter, or access the next menu level if available.
This will be indicated by a →→→→ symbol.
‘Escape’ Key
The ‘Escape’ key enables the user to back out of a menu location.
3.3 The User Interface Menu
The 16x2 digit display lets the user see two lines of the menu at once. As the user scrolls
up or down through the menu, the →→→→ symbol will indicate which line will b e selected if the
‘Enter’ key is pressed.
When viewing certain parameters, the LCD will give a numerical reading as well as a
graphical display. For example, an RSSI reading may look like this:
RSSI: -95 DBM
■■■■■■■
Figure 3.2: EX7100 Front Panel Display – RSSI Reading
3.4 Changing Parameters
This section is split into four areas:
Universal Parameters (refer to Section 3.4.1)
This section explains how to check and reconfigure certain oper ating parameters, which
are generic to all EX7100 terminals, whether Data, Exchange, or Subscriber.
Data Terminal Parameters (refer to Section 3.4.2)
This section explains how to check and reconfigure certain oper ating parameters, which
are specific to 64kbps Data terminals only.
Exchange Terminal Parameters (refer to Section 3.4. 3)
This section explains how to check and reconfigure the operation of certain parameters
that are specific to Exchange terminals only.
Note that an Exchange terminal normally connects t o the PST N or a PABX . W hen used in
conjunction with a Subscriber terminal the system provides six replacement telephone
circuits.
EX7100 Technical Manual - Configuring the Terminal
Two Exchange terminals may also be configured as a 4-wire Point to Point system. In this
mode, the system provides six, 4-wire trunked audio circuits with E & M wire control
signalling.
Subscriber Terminal Parameters (refer to Section 3.4.4)
This section explains how to check and reconfigure the operation of certain parameters,
which are specific to Subscriber terminals only.
3.4.1 Universal Parameters
Passwords.
EX7100 is protected by two levels of passwording.
The Low Level password is required to access the front panel menu system and is factory
fixed as ‘1111’. This cannot be changed by the user.
The High (or Second) Level password (required to change important operating
parameters) may be changed from the Exicom factory default setting of ‘1234’ to any fourdigit number.
Note 1: If the high level password is changed and the new password subsequently
forgotten, you will need to contact Exicom for a backdoor password.
Note 2: It is possible to disable either/both passwords as detailed below. It
should be noted however, that disabling the passwords will allow any
unauthorised person to change the terminal’s configuration.
Changing the Second Level Password.
1) From idle, press ‘Enter’
You will be asked to enter the password.
Note
this is the First Level password
which is factory fixed at ‘1111’
Use the arrow keys to enter ‘1111’, then
press ‘Enter’.
(Note: the up and down arrows increase
or decrease the number above the ↑↑↑↑
symbol)
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller.
Press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Passwords.
Press ‘Enter’
4) Use the up and down arrow keys to make
sure the → is next to Change Password.
Press ‘Enter’
EX7100 Technical Manual - Configuring the Terminal
4) You will be asked to enter the old Second
Level password. If this is still set to the
factory default value, use the arrow keys
to enter ‘1234’, then press ‘Enter’
5) You will be asked for the new
Second
Level password. Use the arrow keys to
change the old password to the required
new password and press ‘Enter’
6) You will be asked to confirm the new
password. Use the arrow keys to re-enter
the new Password, and press ‘Enter’
7) The new Second Level password is now
set. Press ‘‘Escape’’ until the display
returns to idle.
Disabling the Passwords.
1) From idle, press ‘Enter’
You will be asked to enter the password.
Note
this is the First Level password
which is factory fixed at ‘1111’
Use the arrow keys to enter ‘1111’, then
press ‘Enter’.
(Note: the up and down arrows increase
or decrease the number above the ↑↑↑↑
symbol)
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller.
Press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Passwords.
Press ‘Enter’
4) Use the up and down arrow keys to make
sure the → is next to ‘Disable Lo Lvl’, or
‘Disable Hi Lvl’.
Press ‘Enter’
5) You will be asked to enter the old
Second
Level password. If this is still set to the
factory default value, use the arrow keys
to enter ‘1234’, then press ‘Enter’
6) The password has now been disabled. To
re-enable the password, follow the same
process.
EX7100 Technical Manual - Configuring the Terminal
Changing the Time and Date.
The Time and Date should be changed to reflect local settings. Note that the date f ield
follows the UK format: DD/MM/YY.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the →→→→ is next to Set Time/Date.
Press ‘Enter’
4) The current time and date is displayed. As
in the example at the start of this section,
use the arrow keys to change the time and
date to the required local settings and then
press ‘Enter’
The new time takes effect when the ‘Enter’
key is pressed.
5) Press ‘‘Escape’’ unt il t h e display returns to
idle
Password ∗ ∗ 1 ∗
↑
→Controller
RF PARAMETERS
Operating mode
→set time/date
1201:01 01/01/98
↑
Operating Mode.
Ensure that this parameter is set to either:
> Terminal 100% (link is continually up),
> Terminal On Demand (link is up only with traffic),
> Repeater 100% (terminal configured as a repeater transmitting continually),
> Repeater On Demand (terminal configured as a repeater transmitting only with
traffic).
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller.
EX7100 Technical Manual - Configuring the Terminal
4) Use the up and down arrow keys to
choose the required operating mode and
then press ‘Enter’.
Note that the current setting is indicated by
an asterisk.
5) Press ‘‘Escape’’ unt il t h e display returns to
idle.
Link ID.
The Link ID is the identification number f or the link. There are 99 possible numbers from
1-99. (The factory default setting is 01)
Both terminals in the link must have the same Link ID setting. (If a repeater conf iguration
is used, see Section 8, all
terminals must have the same link ID).
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller and then
press ‘Enter’.
3) Use the up and down arrow keys until the
→→→→ is next to Change Link ID and then
press ‘Enter’.
4) Use the arrow keys to enter the required
link identification number (0-99)
Note: all term inals in a link must
have the
same Link ID (including repeaters).
Press ‘Enter’ to accept changes.
5) Press ‘Escape’ until the display returns to
idle.
→terminal 100%
term on demand
Password ∗ ∗ 1 ∗
↑
→Controller
rf parameters
Change password
→change Link id
Link id: 01
↑
Terminal Descriptor.
If required, a 16-character description of the terminal can be set. If changed from the
factory default setting, the terminal descriptor will be displayed on the front panel while the
user interface is idle, and will be displayed instead of the ESN when being accessed from
a remote location.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
Password ∗ ∗ 1 ∗
↑
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Controller.
EX7100 Technical Manual - Configuring the Terminal
3) Use the up and down arrows until the →→→→ is
next to Terminal Desc. Press ‘Enter’
4) Use the keypad to set the required
terminal description and then press ‘Enter’.
5) Press ‘Escape’ until the display returns to
idle.
Changing the RF Channel Increment.
The EX7100 provides RF Frequency increments of either 6.25 kHz (Exicom factory default
setting), or 5.0 kHz. Depending on the operating frequencies you require, it may be
necessary to change this setting to the other value.
Example: If your required frequencies are not divisible by 6.25 k Hz you will need to set the
channel increments to 5.0 kHz.
The procedure below is particular to a link at idle. If a link is alr eady established, or you
wish to change the channel increment remotely, the ‘Change Frequency’ command must
be used to action the changes. Refer to Section 4.3.3 for details.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to RF Parameters.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the →→→→ is next to Chan Increment.
Press ‘Enter’.
4) An asterisk (*) shows which increment
setting is currently in use. If required, use
the up and down arrow keys to toggle
between the two settings. Press ‘Enter’ to
accept the change.
5) If t he current operating frequencies are
incompatible with the new channel
increment, the terminal will display an
error message. The operating frequencies
will need to be adjusted as required to suit.
6) Press ‘Escape’ until the display returns to
idle.
EX7100 Technical Manual - Configuring the Terminal
Changing the Local Transmitter Frequency.
Ensure the Transmitter is set to operate on the required frequency.
Notes:
- This procedure is specific to a local
transmitter. To change the frequency of a
remote transmitter refer to Section 4.3.3.
- The EX7100’s front panel tuning range is limited. If a frequency change of more
than 100kHz
is required, it will be necessary to manually retune some parts of the
RF Section of the radio. Transmitter module re-tuning instructions are detailed in
Sections 7.3.3 (VHF) and 7.4.3 (UHF). Duplexer module re-tuning instructions are
given in Sections 7.9.3 (VHF) and 7.10.3 (UHF).
In addition, it may be necessary to replace the Duplexer module if a large chang e
in frequency is required. Refer Section 7.9.4 (VHF) and 7.10.5 (UHF).
Reserved Frequencies
- There are a number of internationally agreed frequencies that have been reserved
exclusively for Distress and Safety Communications.
It is therefore necessary to prevent transmission on the reserved frequencies (as
well as the frequencies one channel either side of the reserved frequencies)
Affected VHF frequencies
:
156.525 MHz (± 5 or 6.25 kHz) & 156.800 MHz (± 5 or 6.25 kHz)
Affected UHF frequency
:
406.000 MHz (± 5 or 6.25 kHz)
It is not possible to enter the above frequencies during the Tx frequency change
procedure outlined below (note that this only affects the Tx frequency procedure,
the Rx frequency procedure will allow selection of the frequencies but the
corresponding transmitter cannot be set)
1) The local transmitter must not be
transmitting. Setting the terminal to “Ondemand” operating mode will ensure the
transmitter is idle as long as there is no
data traffic .
From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Controller.
EX7100 Technical Manual - Configuring the Terminal
3) Use the up and down arrow keys to make
sure the → is next to Operating mode.
Press ‘Enter’.
4) Use the up and down arrow keys to make
sure the → is next to Term On Demand.
Press ‘Enter’. (The Tx On LED will
extinguish after 10 seconds).
5) Press ‘Escape’ to return to the main menu.
Select RF parameters and press ‘Enter’.
6) Use the up and down arrow keys to make
sure the →→→→ is next to Tx Frequency.
Press ‘Enter’
7) The current frequency setting is displayed.
Press ‘Enter’ to change the frequency.
8) You will be asked for the Second Level
password. Exicom’s factory default is
‘1234’. If the default password does not
give access, see your System Engineer as
the password may have been changed
(refer to Section 3.4.1 for details).
9) The current frequency is displayed. Using
the arrow keys, change the frequency to
the required setting. Press ‘Enter’
(Note: When the cursor is under the least
significant digit, the frequency will
increase/decrease by the channel
spacing).
The new frequency has now been set.
Press ‘Escape’ until the main menu is
displayed.
10) If required, repeat steps 3 and 4 to return
the terminal to 100% operation.
EX7100 Technical Manual - Configuring the Terminal
Changing the Local Receiver Frequency.
Ensure the Receiver is set to operate on the required frequency.
Notes:
- This procedure is specific to terminals in their idle state. To change the Rx
frequency while a link is established, see 4.3.3.
- The EX7100’s front panel tuning range is limited. If a frequency change of more
than 100kHz
is required, it will be necessary to manually retune some parts of the
RF Section of the radio. Receiver module re-tuning instructions are detailed in
Sections 7.7.3 (VHF) and 7.8.3 (UHF). Duplexer module re-tuning instructions are
given in Sections 7.9.3 (VHF) and 7.10.3 (UHF).
In addition, it may be necessary to replace the Duplexer module if a large chang e
in frequency is required. Refer Section 7.9.4 (VHF) and 7.10.5 (UHF).
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to RF Parameters.
Press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Rx Frequency.
Press ‘Enter’
4) The current frequency setting is displayed.
Press ‘Enter’ to change the frequency.
5) You will be asked for the Second Level
password. Exicom’s factory default is
‘1234’. If the default password does not
give access, see your System Engineer as
the password may have been changed
(refer to Section 3.4.1 for details).
6) The current frequency is displayed. Using
the arrow keys, change the frequency to
the required setting. Press ‘Enter’
(Note: When the cursor is under the least
significant digit, the frequency will
increment/decrement by the channel
spacing).
7) Press ‘Escape’ until the menu returns to
idle. The frequency change is now
complete.
EX7100 Technical Manual - Configuring the Terminal
Transmitter RF Power Level.
Ensure the transmitter power level is set as required. The power level is selectable in 3dB
steps (0.25W, 0.5W, 1W, and 2W for a 2Watt system, and 1.25W, 2.5W, 5W, and 10W for
a 10Watt system).
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrows until the →→→→ is
next to RF Parameters and then press
‘Enter’.
3) Use the up and down arrows until the →→→→ is
next to Tx Power and then press ‘Enter’.
Password ∗ 1 ∗ ∗ ↑
→Rf parameters
framer
rssi
→Tx power
4) The current Tx Power will be displayed.
Press the down key followed by ‘Enter’ to
change the power level.
8) You will be asked for the Second Level
password. Exicom’s factory default is
‘1234’. If the default password does not
give access, see your System Engineer as
the password may have been changed
(refer to Section 3.4.1 for details).
6) The new setting is now in effect.
Press ‘Escape’ until the display returns to
idle.
Interface Type.
Check that the terminal is set for either, G.703 (Codir or Contra), Synchronous Data,
Exchange, or Subscriber as required for connection to your external equipment. This may
be checked on the Framer menu location.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrows until the →→→→ is
next to Framer and then press ‘Enter’
Tx pwr: 2.5 W
→set rf level
Password 1 ∗ ∗ ∗ ↑
Password ∗ ∗ 1 ∗ ↑
Rf parameters
→framer
3) Use the up and down arrow keys to make
sure the → is next to Interface and press
EX7100 Technical Manual - Configuring the Terminal
4) Use the up and down arrow keys to make
sure the → is next to the required
interface type. Press ‘Enter’ to accept.
Note that the currently selected setting is
indicated by an asterisk.
5) Press ‘‘Escape’’ unt il t h e display returns to
idle.
3.4.2 Data Terminal Parameters
Transmit Data Clock Synchronisation.
For each digital interface, the 64kbps transmitted data may be synchronised to one of
three options. These are:
1) Sync to Rx: Synchronise to clock from incoming data: (slave operation),
3) Internal Ref: Synchronise to EX7100 internal clock (master operation).
→ G.703 codir
G.703 contra
The selection made will depend on the equipment being connected to the EX7100
terminal. Setting the clock synchronisation to ‘Sync to Rx’ will suit most applicat ions that
use external equipment as the clock source (Exicom factory default setting).
Note: The six channel version of the EX7100 uses automatic internal synchronisation,
and does not need to be configured.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Framer.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Tx Data Clock.
Press ‘Enter’.
4) Use the up and down arrows to select the
digital interface being used.
Press ‘Enter’.
5) Select the synchronisation source
required. Press ‘Enter’.
Note that the currently selected setting is
indicated by an asterisk.
EX7100 Technical Manual - Configuring the Terminal
Sync Data Polarity.
When using the synchronous data interface (e.g. V.35), the polarity of the clock signals
may become critical to the successful interfacing of EX7100 to external devices. Many
V.35 devices, especially those manufactured in North America, may have their clock
and/or data signals inverted. For this reason, EX7100 allows the user to select either
normal or inverted clock signals.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Framer.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Tx Data Clock.
Press ‘Enter’.
4) Use the up and down arrows to select the
sync data interface.
Press ‘Enter’.
5) Use the up and down arrow keys to make
sure the → is next to Tx Polarity or Rx
Polarity (as required)
Press ‘Enter’.
6) Select the polarity required. Press ‘Enter’.
Password ∗ ∗ 1 ∗
↑
Rf parameters
→framer
Interface
→Tx Data Clock
G.703
→Sync data
Clock source
→tx polarity
→normal
inverted
Note: Some V.35 devices also require that the Data signals be inverted. This may be
achieved by simply swapping the (+) and (-) legs of the Tx Data and/or Rx Data
connections.
EX7100 Technical Manual - Configuring the Terminal
3.4.3 Exchange Terminal Parameters
If a terminal contains an Exchange Int erface card, an Exchange menu becomes available
containing the following parameters:
Operating Mode.
An Exchange terminal can be supplied to operate either with a Subscriber terminal: as a
six-channel telephone system, or with another Exchange terminal: as a six-channel,
trunked point-to-point, 4-wire+E&M system. The latter mode enables the user to link
PABX or PSTN trunks using the E&M signal wires as control lines.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Exchange.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Operating Mode.
Press ‘Enter’.
4) Use the up and down arrow keys to select
the mode required. Press ‘Enter’.
Note that the currently selected setting is
indicated by an asterisk.
5) Press ‘Escape’ to back out of the menu.
Password ∗ ∗ 1 ∗
↑
PSU monitoring
→Exchange
→Operating mode
Channel setup
Point to point
→Ex to Sub
Channel Set-up.
Each of the six telephone circuits may be set for 2-wire, or 4-wire+E&M interface, and the
line impedance may be set for either 600 ohm s, 900 ohms, or complex (actual complex
impedance network required must be specified: factory standard = BT3), as required by
the PSTN or external device.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Exchange.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Channel Set-up.
EX7100 Technical Manual - Configuring the Terminal
4) Use the keypad to position the ↑ below the
channel number and use the up and down
arrow keys to select the required channel.
For each channel, use the same method to
select the interface and line impedance
required. Press ‘Enter’ to accept changes
to each channel.
5) When all channels have been checked/set,
press ‘Escape’ to exit menu.
Payphone Metering Frequency.
If Meter Pulse payphone operation (12kHz or 16kHz) may be enabled in pairs of channels.
Note that a channel with metering enabled will still operate with a standard telephone
circuit. Note also that line reversal payphone detection is automatic and does not need to
be configured from the front panel.
Ch:1 2W 600Ω ↑
Ch:2 4W 600Ω ↑
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Exchange.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Metering.
Press ‘Enter’.
4) Select ‘Frequency’ to set the metering to
either 12 or 16 kHz.
EX7100 Technical Manual - Configuring the Terminal
4) Use the keypad to set the correct Rx audio
line level for each channel. Press ‘Enter’ to
accept changes for each channel.
NB: All channel may be set to the same
value by selecting 'ALL’.
(Note: Within a terminal the Rx line level
should not be set higher than the Tx line
level. For typical applications with short
telephone cable runs, an Rx line level of
–3dbm is recommended)
3.4.4 Subscriber Terminal Parameters.
If a terminal is configured as a Subscriber Terminal, the following parameters should be
checked:
Ringer Frequency.
The EX7100 is able to be configured to provide either 18Hz or 25Hz ringing frequency.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Subscriber.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Ring.
Press ‘Enter’.
4) Use the up and down arrow keys to select
the ringing frequency required. Press
‘Enter’.
Note that the currently selected setting is
indicated by an asterisk.
5) Press ‘Escape’ to back out of the menu.
Ch: 1 lv: 0 dbm
↑
Password ∗ ∗ 1 ∗ ↑
PSU monitoring
→Subscriber
→ring
termination
→18hz
25hz
Line Termination Impedance.
Each of the six channels may have a line impedance of 600Ω, 900Ω, or complex (actual
complex impedance network must be specified: factory standard = BT3).
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
Password ∗ ∗ 1 ∗
↑
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Subscriber.
EX7100 Technical Manual - Configuring the Terminal
3) Use the up and down arrow keys to make
sure the → is next to Termination.
Press ‘Enter’.
4) Use the keypad to set the line impedance
for each channel. Press ‘Enter’ to accept
changes for each channel.
NB: All channels may be set the same by
selecting 'ALL’.
5) Press ‘Escape’ to back out of the menu.
Payphone Metering Frequency.
As for the Exchange Terminal, check that the correct payphone metering frequency is
selected (12 kHz or 16 kHz) for each channel pair. Note that line reversal detection is
automatic and does not need to be configured.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Subscriber.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Metering.
Press ‘Enter’.
4) Select ‘Frequency’ to set the metering to
either 12 or 16 kHz.
Select ‘Enable’ to turn on the metering
facility for each channel.
NB: All channels can be turned on or off by
selecting ‘ALL’.
5) Press ‘Escape’ to back out of the menu.
Ring
→termination
Ch: 1 600 Ω ↑
Password ∗ ∗ 1 ∗ ↑
PSU monitoring
→Subscriber
termination
→Metering
Frequency
→
Enable
Transmit Audio Line Level.
For each channel, the transmit audio line level is selectable in 0.5dB steps from
-15dBm to +3dBm.
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
Password ∗ ∗ 1 ∗
↑
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Subscriber.
EX7100 Technical Manual - Configuring the Terminal
Telephone Loop Current.
If the telephone cabling is excessively long, the loop current may need to be increased to
provide extra microphone and ringing current. The loop current m ay be set t o either 25mA
or 45mA, but should be left at 25mA if cabling is short.
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the → is next to Subscriber.
Press ‘Enter’.
3) Use the up and down arrow keys to make
sure the → is next to Loop Current.
Press ‘Enter’.
4) Use the keypad to set each channel to the
loop current required. Press ‘Enter’ to
accept changes for each channel.
EX7100 Technical Manual – Monitoring and Diagnostics
4.1 General
The EX7100 is equipped with a powerful monitoring and diagnostic system that may be
accessed using the six button keypad and LCD on the front panel. (Refer to Section 3.2
for information on how to use the Front Panel User Interface).
The front panel also has four LED's that indicate the operating status of the terminal, as
well as any alarms being generated by the terminal.
It is possible, via the front panel, to view how t he terminal is configured (refer to Section
3), monitor various operating parameters (Refer to Section 4.2), and set up the terminal to
generate and log alarms for those parameters that may potentially cause link failure.
4
Monitoring and diagnostics
This facility also allows the user to access any remote terminals within the local terminal’s
RF path. (Refer to Section 4.3 Monitoring a Remote Terminal). With the addition of the
optional ELMS (Exicom Link Management System) software, monitoring of multiple
terminals is possible (Refer to Appendix B.1).
4.2 Monitoring the EX7100’s Operation
The EX7100 User Interface allows the user to monitor the operation of the various
modules that make up the radio terminal.
This Section details the monitoring method for various parameters as follows:
Note: Many of the instructions listed are similar to the configuration instructions
previously given in Section 3. It is possible to view
having to actually change
4.2.1 RF Parameters
> Channel Increment
> Tx Frequency
> Rx Frequency
> Tx Power
it.
a changeable parameter without
> Tx Temperature (Displays the temperature of the Power Amplifier heatsink)
> RSSI
> Synthesiser Loop Volts (Displays the loop voltage of the Rx and Tx frequency
synthesisers – Refer RF alignment within Section 7 as required.
EX7100 Technical Manual – Monitoring and Diagnostics
4.3.1 Setting Up a Test Link
To perform remote monitoring it is necessary to set up a Test Link with the terminal to be
interrogated, even if a link is alr eady established due to normal traff ic. A test link ensures
that the radio link remains in place irrespective of whether there is traffic or not.
Refer to the menu tree diagram at the end of Section 3. Following the path:
Enter Password→Remote Tests→Start Tests→
• If a link is already established due to user traffic:
There will be a short delay while the
system checks for other terminals in the
RF path
1) A list of terminal ESNs
1
or terminal
descriptors (if set) found will be displayed
with the closest terminal at the top of the
list. Choose the required terminal and then
press ‘Enter’
→ please wait
getting chain
→ 12345678
23456789
• If a link is not already established:
1a) If any Link IDs in the path are unknown,
a Test Link can be established by
selecting Ignore Link ID: and then
pressing ‘Enter’.
1b) If all Link IDs in the path are known, a
Test Link can be established by selecting
Use Link ID: and then pressing ‘Enter’.
2) The link will take a few seconds to
establish a link.
3) A list of terminal ESNs
1
or terminal
descriptors (if set) found will be displayed
with the closest terminal at the top of the
list. Choose the required terminal and then
press ‘Enter’
The menu now displays the main menu of the remote terminal. All monitoring, diag nostic,
and configuration parameters are now available for that terminal. The menu layout looks
identical to that of a local terminal menu.
→ ignore link id
use link id:xx
Ignore link id
→ use link id: xx
Please wait
Setting up link
→ 12345678
23456789
1
If a terminals Terminal Descriptor has been changed from default (Refer to Section 3.4.1) it will be displayed instead of
EX7100 Technical Manual – Monitoring and Diagnostics
Note 1: If the remote terminal is unable to be contact ed, due to a faulty link or if another
user is accessing the terminal, a message will be displayed:
Couldn’t contact
Remote terminal
Note 2: When accessing a remote menu there will be a short delay between pressing a
key and the menu changing, due to the limited data speed of the engineering
channel.
4.3.2 Closing the Test Link
When you have finished the remote interrogation, you should close down the test link,
even if the link was already established (with data or telephone t raffic). If a test link is not
closed down manually it will be shut down automatically after 10 minutes.
1) Press the ‘Escape’ key until the menu
display is as shown. Use the up and down
Start tests
→end remote tests
arrow keys to make sure the →→→→ is next to
End Remote Tests and then press ‘Enter’.
2) If there is no telephone or dat a traffic using the system, the EX7100 will close down the link
(both the Tx and Rx LED’s will go out).
If there is telephone or data traffic using the system, the EX7100 will close down the test
link, but the link will continue to operate (both the Tx and Rx LED’s will remain on).
3) Press ‘Escape’ until the display returns to idle.
Important Note:
While a terminal is being remotely accessed, it will not be able to be accessed locally. The
remote terminal display will read:
Remote access
Keyboard locked
4.3.3 Changing Operating Frequencies Remotely
As previously discussed in Section 3.4.1, it is possible to configure an EX7100 terminal
remotely, with the process being identical to configuring a local terminal.
There is however, a slight change in process when changing the Operating Frequencies
or Channel Increment remotely, or locally with a link established.
Consider a link operating on Tx 450.000 MHz and Rx 455.000 MHz, with a requirement to
change this to Tx 450.050 MHz and Rx 455.050 MHz.
If we followed the procedure outlined in Section 3.4.1 for an idle terminal, the local
terminal’s frequencies would change but there would be no means of setting up a link with
the remote terminal, as the new local frequencies would no longer match the remote
terminal’s frequencies.
EX7100 Technical Manual – Monitoring and Diagnostics
Therefore, we would be unable to change the remote terminal’s frequencies unless we
visited the remote site. Similarly, if it were possible to change the remote terminals
frequencies, and an error was made in doing so, it would not be possible to remotely
access the terminal to amend the error.
For this reason, the EX7100 has a ‘smart’ Change Frequency command. If it is necessary
to change the frequencies of a working link, this procedure must be used.
This command allows the user to enter the new frequencies of all t he terminals in the RF
path, and then issue the command to change them all simultaneously. I f the link is unable
to be established on the new frequencies, the system automatically returns the link to the
original frequencies.
Important Note:
The EX7100’s front panel tuning range is limited. If a frequency change of more
than 100kHz is required, it will be necessary to manually retune some parts of the
RF Section of t he radio.
Transmitter module re-tuning instructions are detailed in Sections 7.3.3 (VHF) and
7.4.3 (UHF). Receiver module re-tuning instructions are detailed in Sections 7.7.3
(VHF) and 7.8.3 (UHF). Duplexer module re-tuning instructions are given in Secti ons
7.9.3 (VHF) and 7.10.3 (UHF).
In addition, it may be necessary to replace the Duplexer module if a large change in
frequency is required. Refer Sections 7.9.4 (VHF) and 7.10.5 (UHF).
Procedure:
A) Use the procedure detailed in Section 4.3.1 ‘Setting Up a Test Link’, to gain access to
the remote terminal’s menu system.
B) Use the procedure detailed in Section 3.4.1 ‘Changing the Local Transmitter
Frequency’ (steps 2-9), to change the remote terminal’s Tx frequency.
Note: Although the new frequency will be displayed, it will not actually change until the
Change Frequency command is given.
C) Use the procedure detailed in Section 3.4.1 ‘Changing the Receiver Frequency’, to
change the remote terminal’s Rx frequency.
Note: Althoug h the new frequency will be displayed, it will not actually change until the
Change frequency command is given.
D) If the link contains a repeater
, press the ‘Escape’ key until the list of terminal ESNs is
displayed. Select the most remote repeater terminal and repeat st eps B and C. Press
the ‘Escape’ key until the list of terminal ESNs is displayed. Select the other repeater
terminal and repeat steps B and C.
If the link does not contain a repeater, ignore this step.
E) Press the Escape key to back through the menu.
F) Use the up arrow key to make sure the →→→→ is next to RF Parameters, and press
EX7100 Technical Manual – Monitoring and Diagnostics
G) Repeat steps B and C. This will enter the Local Terminal’s new frequencies.
H) Repeat step E.
I) Use the down arrow key to make sure the →→→→ is next to Remote Tests. Press ‘Enter’.
J) Use the down arrow key to make sure the →→→→ is next to Change Freqs. Press ‘Enter’.
K) Enter the Second Level Password and press ‘Enter’.
The link will shut down briefly, and then attempt to set-up a link using the new frequencies.
If it is successful, the link will continue to operate using the new frequencies. If it is unable
to set-up a link (i.e. one or more frequencies is incompatible) the link will again shut down
briefly, then set-up the link using the old frequencies.
Note: If the frequency change is successful, the following message is displayed:
Change freqs ok.
Using new freqs
This message refers only to the local RF hop. If a multi-hop frequency change has
been attempted it is recommended that the user access the terminals again, to
check that the new frequencies are correct.
If the frequency change is unsuccessful, the following message is displayed:
Change freqs fail.
Using old freqs
The procedure will need to be repeated.
Note: Any traffic using the link during a Change Frequency command will be lost.
L) Use the Close Link procedure detailed in Section 4.3.2 to close down the Test Link.
4.4 EX7100 Internal Alarms
The EX7100 terminal generates the following internal alarms:
> Input Voltage (DC input voltage out of range: approx. 5% from shutdown voltages)
> Low RSSI (Adjustable alarm set point, refer to Section 4.4.4)
> Tx Power Drop (3dB drop below current menu setting)
> High VSWR
> High BER (Adjustable alarm set point, refer to Section 4.2.3)
> Modem Lock (Modems not synchronised)
> Synth Loss (Rx or Tx frequency not locked)
> Link Up Too Long
> Link Failed (Locally generated link failure)
EX7100 Technical Manual – Monitoring and Diagnostics
> Internal Voltage Rails (Internal voltage rails out of range: approx. ± 10%)
> Over Temperature Alarm (UHF 10 Watt system only, activates if Heatsink
temperature exceeds 60°C)
The user is able to assign either a high or a low priority to each of these alarms. When a
high priority alarm occurs, an opto-isolated output closes. When a low priority alarm
occurs, a second opto-isolated output closes. In either case, an alarm message is sent out
of the LMS port.
If a high priority alarm is triggered, a link set-up is attempted (if a link is not already in
place) and the alarm transported to the remote end. At the remote end, and any
intermediate repeater sites, the high priority output is act ivated and an alarm message is
sent out to the LMS port. At any site, the user is able to scroll through active local and
remote alarms via the front panel LCD.
When any alarm event occurs, local or remote, the alarm LED on the front panel flashes
red. When the user acknowledges the alarm using the front panel, the LED stops flashing
but continues to glow red.
1
4.4.1 Acknowledging an Alarm
To acknowledge an alarm, follow the menu path:
Enter Password→Alarms→Current Alarms
Use the up and down arrow keys to
scroll through the current alarms until t he
new alarm is displayed. This is
recognisable by the flashing * in the
bottom left corner.
Press ‘Enter’ to acknowledge the alarm.
When the alarm clears, the front panel LED extinguishes. If more than one alarm is
present at one time, the above conditions apply until all alarms are acknowledged, and
then cleared.
Alarm events (either activating or clearing of any local or remote alarm) are stored in a log.
Each entry includes a time and date stamp. The user is able to scroll through the alarm
log.
Note: The alarm log can hold 32 events. W hen the alarm log is full, the oldest alarm is
overwritten. In the event of a power failure, the alarm log will be lost.
4.4.2 Setting Alarm Priorities
To set Alarm Priorities (high or Low), follow the menu path:
Local alarm
‘*’ Low RSSI
Note: To view the time and date stamp of the
alarm toggle the left or right arrow key.
Enter Password→Alarms→Priorities
1
Any remote alarm(s) will be cleared whenever the link closes down, either by a user-action or a link failure.
EX7100 Technical Manual – Monitoring and Diagnostics
1) Press ‘Enter’. You will be given a list of all
alarms available within the terminal
2) Use the up and down arrow keys to select
the alarm you wish to set and then press
‘Enter’ to select.
3) The asterisk (*) indicat es which priority is
set for that alarm. Use the left and right
arrow keys to change the priority and then
press ‘Enter’ to accept the change.
4) Continue t o check/set the priorities for
each alarm and then press ‘Escape’ until
the display returns to idle.
4.4.3 Link Up Time Alarm
The EX7100 provides an alarm to indicate when the link has been up longer than the set
time limit. This may be useful in the case where a site is battery/solar powered and it is
necessary to know if the link is being held up for any reason.
The Link Up Time Alarm may be set for the following times:
Off, 1 Hour, 3 Hours, 6 Hours, 9 Hours, 12 Hours, 18 Hours, 24 Hours.
Alarm Log
→ Priorities
Low RSSI
→Tx Power drop
Tx power drop
* low High
To set the Link U p Time Alarm:
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Alarms and then
press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Link Up Time and
then press ‘Enter’.
4) Use the up and down arrow keys to
choose the required alarm time and then
press ‘Enter’ to accept.
Note that the currently selected option is
indicated by an asterisk.
5) Press ‘Escape’ until the display returns to
idle
EX7100 Technical Manual – Monitoring and Diagnostics
4.4.4 Low RSSI Alarm
The user may set an RF level (-40 dBm to -106 dBm) at which the Low RSSI Alarm will
trigger. To set this trigger point:
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys until the
→→→→ is next to RF Parameters and then
press ‘Enter’
3) Use the up and down arrow keys to
position the →→→→ next to RSSI and then
press ‘Enter’.
4) Press the down arrow key then press
‘Enter’.
5) Use the up and down arrow keys to
select the required alarm trigger point,
then press ‘Enter’.
The currently selected setting is indicated
by an asterisk.
6) Press ‘Escape’ until the display returns to
idle
Password ∗ ∗ 1 ∗
↑
→rf parameters
framer
→RSSI
Tx power
Rssi : -75dbm
→set alarm point
* -100 dbm
→-98 dbm
4.4.5 Over Temperature alarm
The UHF 10 Watt system requires fan assisted cooling, due to the extra heat generated
by the power amplifier. Two fans are controlled by the transmitter CPU. If the heatsink
temperature exceeds 45°C one fan will be turned on.
Every 40 hours (approx) the CPU will switch between the two fans to ensure an even
lifecycle. If the heatsink temperature continues to rise above 55°C, bot h fans will be turned
on simultaneously. If the heatsink temperature exceeds a maximum permitted level of
60°C, normally due to a total fan failure, an alarm will be generated.
4.5 Diagnostic Tools
4.5.1 System Align Mode
To enable the user to retune the EX7100’s RF section with the minimum of external test
equipment, the terminal may be put into an Align Mode.
In this mode, the internal modem is set to output fixed data patterns, with a constant AGC
level, and the transmitter is keyed on. The user is then able to retune the Transmitter
module as per the instructions in Section 7.
Note: Two modes can be used to retune the RF Modules.
EX7100 Technical Manual – Monitoring and Diagnostics
The ‘CW’ mode provides a carrier output only. This enables the user to verify the
transmitter operating frequency using a standard frequency counter.
The ‘DSBSC’ mode provides a double side band, suppressed carrier output, to enable the
user to adjust the transmitter carrier null, and also to measure Transmitter RF Power
(PEP).
1) Align Mode cannot be accessed if the link is established or the Transmitter is on.
Ensure this is not the case by setting the Terminal’s Operating Mode to “Ondemand”.
2) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
3) Use the up and down arrow keys to make
sure the →→→→ is next to Controller and then
press ‘Enter’
4) Use the up and down arrow keys to make
sure the →→→→ is next to Align Mode and then
press ‘Enter’.
5) Use the keypad to select the required
modulation and Tx power level, then press
‘Enter’.
6) Press ‘Escape’ to disable and exit out of
Align Mode.
Password ∗ ∗ 1 ∗
↑
→Controller
Rf Parameters
S/w version
→Align Mode
→mod: ∗ cw dsbsc tx: ∗ low norm
Key: MOD = Modulation.
CW = Carrier only.
DSBSC = Double side band at +/- 8kHz from carrier.
Tx = Transmit power level.
Low = Set to lowest menu setting.
Normal = Set to current user setting.
4.5.2 Digital Loopbacks
The EX7100 is able to loopback the 64kbps digital data in the following configurations:
EX7100 Technical Manual – Monitoring and Diagnostics
Local Loopback
In Local loopback mode, the transmit 64kbps digital data stream, from the user interface,
is looped within the framer to the receive 64kbps digital data stream, back to the user
equipment. This enables the user to check the interface between the EX7100 and the user
equipment.
Notes: Local loopback operates for both G.703 and Synchronous Data inputs.
Remote Loopback
In Remote Loopback mode, the received RF into the EX7100 terminal is looped to the
transmit RF line. This enables the user to check the radio path of the system.
Both loopbacks can be enabled for the local terminal as well as the remote terminal.
Enabling Digital Loopbacks
1) From idle, press ‘Enter’.
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Framer and then
press ‘Enter’.
3) Use the up and down arrow keys to make
sure the →→→→ is next to Loopback and then
press ‘Enter’.
4) Use the up and down arrow keys to
choose the required loopback and then
press ‘Enter’.
5) Use the keypad to enable the loopback
function.
Password ∗ ∗ 1 ∗
↑
RF parameters
→framer
ber
→loopback
local
→remote
off
→on
Note: Ensure that the loopback mode is disabled when testing is completed.
Warning: Digital loopbacks should only be used with the system set for G.703 or V.35
(sync data) input. Do not attempt to use the digital loopbacks when the
EX7100 interface is set to Exchange or Subscriber. Doing this may cause the
subscriber telephones to ring continuously.
EX7100 Technical Manual – Monitoring and Diagnostics
4.5.3 Analogue Loopbacks
The six channel telephone version of the EX7100 is equipped with the ability to loop back
the audio on each of the six analogue lines. This f unction is done within the digital audio
processing section of the line interface card and therefore is transparent to the interface
confi guration (2-wire or 4- wire+E&M).
LINE 1…6
LINE 1…6
Figure 4.4: Analogue Loopback Configurations
DSLAC
DSLAC
LOCAL
LOOPBACK
REMOTE
LOOPBACK
DSPs
Local Loopback
Each channel may be put into local loopback mode from the front panel of the EX7100
terminal. In this mode, the transmit audio (into the EX7100 terminal) is looped back to the
received audio (out of the terminal), within the DSLAC (Dual Subscriber Line Audio
Circuit) device.
The user is now able to send an analogue signal into the radio and monitor it across the
same line (using a suitable test instrument with built in hybrid network). It is possible to
perform a similar test using a standard telephone connected to the line, but due to echo
cancellation effects, the received audio will sound distorted.
This feature enables a technician to confirm that the EX7100 line interface circuitry is
operating correctly.
Remote Loopback
Each analogue channel may be put into remote loopback mode from the front panel of the
EX7100. In this mode, the received audio from the remote t erminal is looped back to the
transmit audio path.
From the remote terminal, a technician is able t o send a signal down the line and monitor
it from the same location (using suitable test equipment with built in hybrid network).
EX7100 Technical Manual – Monitoring and Diagnostics
This feature allows a technician to distinguish whether a fault is within the radio
equipment, or on the external telephone line.
Enabling Analogue Loopbacks
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Exchange/Subscriber
and then press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Loopback and then
press ‘Enter’.
4) Use the keypad to set the required
channel to the required loopback mode
and then press ‘Enter’ to accept.
5) Press ‘Escape’ until the display returns to
idle
Password ∗ ∗ 1 ∗
↑
Psu monitoring
→Subscriber
Loop current
→loopback
Ch: 1 off
↑
Note: During loopback testing the channel is not available to user traffic. Ensure that the
loopback mode is disabled when testing is complete.
4.6 Bit Error Rate Testing
4.6.1 General
At some time after installation of the EX7100, the user may wish to perform a bit error rate
test in order to confirm that the system is operating correctly.
A BER test may be performed on both configurations of EX7100: 64kbps data or
telephone.
Testing of a telephone system is possible by performing the test at the 64kbps digital level
using the G.703 or Synchronous data interface.
There are a number of levels of BER testing that may be performed on the EX7100 to
enable the user to pin-point the location of a potential fault.
A) End-to-End one direction test: This requires a Bit Error Rat e Tester (BERT) at both
ends of the link.
B) Full round-trip test: This may be perf ormed using a single BERT (capable of sending
and receiving simultaneously) utilising the remote digital loopback feature of the
EX7100.
C) Local Interface test: As per B) above, but utilising the local loopback feature of the
local EX7100 terminal.
It should be noted that the results obtained from a round trip test will produce a BER twice
that of a single direction test.
EX7100 Technical Manual – Monitoring and Diagnostics
Important Note:
During the BER test, the radio link will not be available to normal traffic.
o o
o
BE R TBE R T
EXICOM
o o
o
o o
EX7100
EX7100EX7100
EXICOM
Bit error rate
tester set to
transmit.
o o
o
o o
o
o o
EX7100
Bit error rate
tester set to
receive.
Figure 4.5: End-to-End Bit Error Rate Test
o o
o
BE R T
Bit error rate
tester set to
EXICOM
o o
o
o o
EX7100EX7100
EX7100
EXICOM
EX7100 set for
remote loopback
transmi t and
receive.
Figure 4.6: Round-Trip Bit Error Rate Test
o o
o
BE R T
Bit error rate
tester set to
EXICOM
EX7100 set for
local loopback
o o
o
o o
EX7100
EX7100
transmi t and
receive.
Figure 4.7: Local Interface Bit Error Rate Test
o o
o
o o
o
o o
EX7100
4.6.2 BER Testing an EX7100: End-to-End
A) Connect the BERT equipment to the digital interface port of both EX7100 terminals
(G.703, or Sync Data) as required.
B) Set the sending BERT equipment to provide the clocking source for the test.
C) Set the interfaces of both EX7100 terminals to match the interface of the BERT
equipment - G.703 or V.35 (sync data) - as follows:
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrows until the →→→→ is
next to Framer and then press ‘Enter’
3) Use the up and down arrow keys to make
sure the → is next to Interface and press
‘Enter.’
EX7100 Technical Manual – Monitoring and Diagnostics
4.6.3 BER Testing an EX7100: Round-Trip
A) Connect a BERT, set to send and receive simultaneously, to the local EX7100
terminal.
B) Follow steps B-E above to set the EX7100 terminals for the correct interface, clock
sync, and 100% operation.
C) Set the remote EX7100 terminal to Dig ital Rem ote Loopback mode by fir st setting up
a remote test link and accessing the remote terminal (refer to Section 4.3.1) then
following the procedure below:
1) From idle, press ‘Enter’
Use the arrow keys to enter the First Level
password ‘1111’ and then press ‘Enter’.
2) Use the up and down arrow keys to make
sure the →→→→ is next to Framer and then
press ‘Enter’
3) Use the up and down arrow keys to make
sure the →→→→ is next to Loopback and then
press ‘Enter’.
4) Use the up and down arrow keys to
choose the required loopback and then
press ‘Enter’.
5) Use the keypad to turn the loopback
function on.
Password ∗ ∗ 1 ∗
↑
RF parameters
→framer
ber
→loopback
local
→remote
off
→on
D) The BER test may now begin. Remember to disable the loopback, close the t est link,
and return the EX7100 terminals to their original configurations when finished.
4.6.4 BER testing an EX7100: Local Interface.
A) Connect a BERT, set to send and receive, to the local EX7100 terminal.
B) Set the EX7100 terminal to the correct interface and clock sync using the steps in
Section 4.6.2.
C) Using the instructions given earlier as a guide, set the EX7100 terminal to Digital
Local Loopback mode.
D) The BER test may now begin. Remember to disable the loopback and return the
terminal to its original configuration when finished.
EX7100 Technical Manual – Monitoring and Diagnostics
4.7 Networking EX7100 Terminals
4.7.1 General
It is possible to create a small network of EX7100 link s by connecting the management
channel of multiple terminals toge ther at a local site. This enables a user to monitor and
configure any other terminal in the network, from an ELMS conf igured PC, using the onboard remote diagnostic feature.
When combined with ELMS (Exicom Link Management System – refer to Appendix B) an
extensive alarm logging system can be established.
o o
o
o o
o
o o
EX7100
EX7100
o o
o
o o
o
o o
EX7100
EX7100
EXICOM
EXICOM
EXICOM
EX7100
EX7100
EXICOM
o o
o
o o
o
o o
EX7100
EX7100
o o
o
o o
o
EXICOM
o o
o o
o
o o
o
o o
EX7100
EXICOM
o o
o
o o
o
o o
EX7100
EXICOM
o o
o
o o
o
o o
EX7100
EX7100
EXICOM
Repeater
EX7100
o o
o
o o
o
o o
EX7100
EX7100
EX7100
o o
o
o o
o
o o
EX7100
EX7100
EXICOM
EXICOM
o o
o
o o
o
o o
EX7100
EX7100
o o
o
o o
o
o o
EX7100
EX7100
EXICOM
EXICOM
o o
o
o o
o
o o
EX7100
EX7100
Figure 4.8: Networking EX7100 terminals
4.7.2 Interconnection of Local Terminals.
Interconnection of each EX7100 terminal’s management channel is achieved by simply
daisy-chaining the RS-485 Bus which appears on the LMS port of each local terminal.
Cabling should be screened and pin-out information is detailed in Appendix A.1.
Note: The ELMS PC connects to terminal three using RS-232. The terminals
communicate with each other using RS-485
4.7.3 Accessing Bussed Terminals.
Using an ELMS configured PC, the user may access any local terminal, or the remote
terminal of any link. An instruction on how to use ELMS is provided within the program.
This chapter describes some methods of identifying problems with the EX7100 and
suggests possible solutions.
The EX7100 has powerful fault diagnosis tools built in. Internal alarm monitoring,
metering and configuration information are available on the front panel and at remote
terminals. Refer to Section 4 for more details on the use of t hese diagnostic tools.
5.2 Configuration Issues
Configuration problems ar e not normally an issue with links that are already in operation,
but an initial mis-configuration can prevent an EX7100 link from oper ating.
5
When changing modules within the EX7100, configuration problems can arise. This is
because the modules carry the configurat ion information relevant to them – e.g. the Line
Module carries line level and the other configuration variables relevant to the Line
Module. An exception is that all RF configuration parameters are carried on the
Transmitter module.
Symptoms Possible Causes How To Fix Additional Comments
Low transmit power, low RSSI and
Antenna or feeder fault . Replace faulty antenna and/or
poor VSWR
Duplexer faulty or out of
alignment.
Transmit and/or receive frequency
incorrect.
Low transmit power, VSW R &
Transmit power set low. Set terminal to the correct transmit
RSSI OK
Low transmit power, high bit error
rate, VSWR & RSSI OK.
Higher than usual bit error rate or
poor sensitivity, transmit power,
Faulty Transmitter module or
Power Amplifier module.
Transmitter or receiver may have
drifted off frequency.
RSSI & VSWR OK.
Low RSSI reading. Can be caused by low transmit
power, feeder and/or antenna
problems, antenna alignment and
receiver problems.
feeder.
Check, align or replace Duplex
Filter.
Set terminals to correct transmit
and receive frequencies.
power level.
See Sections 7.3 to 7.6.
Return to Exicom for alignment.
Refer to the appropriate sect ions
of this manual.
Low transmit power or poor
receiver sensitivity usually cause
problems in one direction only.
Feeder and antenna problems
effect both direct ions of the link.
The Terminal contains semi-conductor components that are
sensitive to electrostatic damage.
Electrostatic sensitive devices should only be stored and
transported inside electrically conductive static shielding
bags. Fault finding and module replacement must be
performed at “electrostatically safe work stat ions” where the
work bench surface; soldering iron and the operator are all
earthed to prevent the build up of harmful electrostatic
charges.
6.1 Procedure
To gain service access to any of the modules, the top or bottom covers must be removed
as follows:
1. Isolate the EX 7100 Terminal fr om the incoming DC supply by removing the DC input
wires from the rear panel terminal block. It may also be necessary to remove any
signalling and antenna cabling.
2. Remove either cover as required by removing the screws. Keep all screws in a safe
place for later replacement.
Warning: The VHF Duplexer module is attached to the under side
care must be tak en when removing this cover so as not to damage the RF
cabling connecting the duplexer to the modules within the ter m inal.
The UHF Duplexer and associated filters are attached to the outside
top cover. Before disconnecting the RF cables to the rear panel, care should
be taken to note the correct cable connect ion.
The EX7100 Terminal consists of the following Modules:
General (Non-RF) Modules
> Power Supply Module Type 2964,
> Modem/Controller Module Type 2966,
> Front Panel Type 2994,
RF Modules
7
Module Descriptions
> VHF Transmitter Module Type 8027 or
UHF Transmitter Module Type 8053,
UHF CPU Module Type 8044 (sub-module of UHF Tx Module Type 8053),
> VHF RF Power Amplifier Module Type 8028 or
UHF RF Power Amplifier Module Type 8048 (10 Watt),
> VHF Receiver Module Type 8029 or
UHF Receiver Module Type 8054,
> VHF Front-End Module Type 8018 (sub-module of VHF Rx Module Type 8029) or
UHF Front-End Module Type 8055 (sub-module of UHF Rx Module Type 8054),
> VHF Duplexer Module Type 8013 or
UHF Duplexer (& Filters) Module Type 8045,
Line Interface Modules: (pr esent in t he six channel variant only)
> Two wire 6-Channel Exchange Line Interface Module Type 2967,
Four wire Module Type 2967 (optional sub-module of Interface Type 2967),
> Two wire 6-Channel Subscriber Line Interface Module Type 2971,
> Isolated Power Supply Type 2990 (sub-module of each Line Interface module)
Refer to Figures 7.1 to 7.3 for module locations (Front Panel Type 2994 and Duplexer
modules are not shown).
Figure 7.3: UHF EX7100 Terminal with Bottom Cover Removed
7.2 Power Supply Module Type 2964
7.2.1 General
The Power Supply module (PSU) converts the incoming DC input from the rear panel to
the voltages needed to operate the circuitry within the EX7100 terminal.
The incoming supply may be positive earth, negative earth or floating (with no earth
connection).
Refer to Figure 7.4. The f irst stag e of t he power supply is an isolated “forward” converter.
This converts the incoming DC voltage to +24 volts, negative earth. The +24 volt supply is
used as required within t he EX7100 terminal and is used to supply a second stage “f lyback” converter that provides ±5 and ±15 volt output s.
1
Refer to Section 2, page 2-6 for IMPORTANT WARNINGS re the power supply
The PSU Measurement Board connected to t he Power Supply provides various metering
functions via the terminal’s f ront panel display (Refer to Sect ion 7.2.2 for details). This is
calibrated to the Power Supply and is considered an integral part of the Power Supply.
7.2.2 Testing and Fault Diagnosis
Note: Refer to Section 5 “Troubleshooting the EX7100” before reading this Section.
The module contains semi-conductor components that are
sensitive to electrostatic damage.
Electrostatic sensitive devices should only be stored and
transported inside electrically conductive static shielding
bags. Fault finding and module replacement must be
performed at “electrostatically safe work stat ions” where the
work bench surface; soldering iron and the operator are all
earthed to prevent the build up of harmful electrostatic
charges.
-15V
+5V
-5V
Isolation
Barrier
Flyback
Converter
General
Front panel diagnostics are available to measure the power supply’s input and output
voltages, and the input current.
To access the PSU Monitoring from idle:
1) From idle, press ‘Enter’
Use t he ar r ow keys to enter the First
Password ∗ ∗ 1 ∗ ↑
Level password ‘1111’ and then press
‘Enter’.
2) Use the up and down arrows until the →→→→ is
next to PSU Monitoring and then press
framer
→psu monitoring
‘Enter’
3) Use the up and down arrows to position
the →→→→ next to the required parameter and
4) Press t he ‘Escape’ key to back out of the
menu system.
The power supply can be considered to be operating satisfactor ily if the supply rails are
within the ranges specified within Table 7.1 below.
Front Panel Measurement Typical Reading Range
Input DC Voltage 10.8 to 30V (LV variant), 30 to 60V (HV variant)
+24 Volt Rail 22.8 to 25.2V
+15 Volt Rail 14 to 16V
-15 Volt Rail -14 to -16V
+5 Volt Rail 4.8 to 5.2V
-5 Volt Rail -4.7 to -5.3V
Input Current Up to: 9A (LV variant), 3A (HV variant)
Table 7.1: Typical Power Supply Measurement Ranges
If the display is not operating or the power supply rails are not within the expected
voltage, follow the steps outlined in Figur e 7. 5 overleaf.
Accessing the Power Supply
To gain service access to the power supply module, remove the bottom cover of the
terminal as described in Section 6.1.
Before commencing cover removal, switch the r ear panel power
switch off
electrolytic capacitors are discharged bef or e pr oceeding.
AND isolate the fused supply to the unit. Check that
Diagnosis
With the unit de-powered, check the power supply visually for signs of damage such as
burnt tracks, or components. If no damage is apparent, apply power to the t erminal and
check the voltages in Table 7.2.
Note: Measurements should be made with an isolated dig ital multi-meter to prevent the
possibility of injury to servicing personnel or damage to the terminal.
1 TB1 +ve terminal. T B1 - ve terminal. Input voltage ± 0. 5V.
2 10 A Fuse F1, bot h ends. Chassis Ground 22.8 to 25.2V.
3 2 A Fuse F2, both ends. Chassis Ground 14 to 16V.
4 1 A Fuse F3, both ends. Chassis Ground -14 to -16V.
5 5 A Fuse F4, both ends. Chassis Ground 4.8 to 5.2V.
6 250 mA Fuse F5, both ends. Chassis Gr ound -4.7 to -5.3V.
Fuse
Rating
Positive Probe Negative Probe Expected Voltage
Table 7.2: Typical Power Supply Test Point Voltages
7.2.3 Alignment
The Power Supply requires no alignment and has no user adjust m ents.
Two potentiometers ar e provided: RV301 & RV302. They are factory set to t he required
under-voltage and over-voltage shut down thresholds and should not be adjusted
The PSU Measurement board has factory set metering coefficients. These cannot be
adjusted in the field.
7.2.4 Module Replacement Procedure
.
1. Isolate the EX 7100 Terminal fr om the incoming DC supply by removing the DC input
wires from the rear panel terminal block.
2. Remove the bottom cover as described in Section 6.1.
3. Note the connector positions and the way that the cables ar e run (it is important that
all cables are replaced as they were initially run before the module replacement
procedure).
4. Disconnect t he remote on/off switch loom by unplugging SK301. Remove the wiring
loom plug from PL1 and remo ve the cable from SK6.
5. Loosen the screws of the terminal block TB1 and remove the DC input wires.
Caution: Remove the six f errite beads (two per wire) and keep in a safe place for
future replacement.
6. Check, using a multimeter, placed between the eart h (on TB1) and the fuse carriers
on the PCB, that the filter capacitors have safely discharged.
7. Remove the nine M3 screws and bushes from the heat-sink mounted
semiconductors. Keep them in a safe place.
8. Remove the six M4 screws and washers holding the PCB and keep them in a safe
place. Carefully lift the PCB out of its housing. Do not carry the PCB by the pr oject ing
semiconductors. The PCB can be safely carried by grasping T1 (the largest
transformer) or by holding it by the edges of the board.
9. Remove the thermal pads and the insulating bushes and discard them. Inspect the
new pads and bushes carefully for any foreign m atter. Small specks of dirt or metal
filings can cause the pad to be punctured when the semiconductors are clamped
down.
10. Carefully remove all foreign matter from the mating surfaces of the new Power
Supply’s semiconductors and the heat-sink contact area.
11. Align new pads with the holes in the heat-sink contact area. Place the new power
supply PCB in its cavity and alig n the boar d with its mounting holes. Replace the nine
semiconductor mounting screws and bushes. Do not fully tig ht en the screws.
12. Replace t he six M4 PCB mounting screws and washers. Tighten the screws caref ully
(do not over tighten as this can strip the internal screw threads). Tighten the
semiconductor mounting screws.
13. Using a multimeter, measure the resistance from the tab of each semiconductor to
the aluminium casting. All readings should be more than 400Ω (ensure that PL1 is
not plugged in when measuring). If any reading is lower, remove the heat-sink
components and check them all caref ully for the cause of the short circuit. Caution:
do not proceed with the installation until this insulation test has been passed
successfully or the power supply will be damaged.
14. Replace the six ferr ite beads (two per wire) on the main power cables and insert into
terminal block TB1. Ensure that the polarity is correct. Carefully tight en the screws of
the terminal block.
15. Re-connect the cable loom plug into PL1 and the cable into connect or SK6.
16. Re-connect the r emote on/ of f switch loom t o SK301. Ensure that all
cables are run as
they were prior to removal.
17. Inspect the EX 7100 terminal to ensure that it is free of foreign mater ial. Remove and
clean as required.
18. Connect the ant enna to the terminal. Check the external
DC supply fuse, to ensure it
is not blown and replace if required (refer to Section 2.6.1 for fuse types and ratings)
19. Apply power to the EX7100 rear panel and switch the terminal on. Measure the
output rails with a multimeter and verify that they are all within the specifications as
detailed in Table 7.1.
20. Replace the bottom cover, taking care to t ighten every screw. No screws should be
left over at the end of the job.
21. Re-install t he EX 7100 into its r ack and re- connect all necessary power, sig nalling and
antenna cabling.
The VHF Transmitter module accept s data f r om the Modem Controller module Type 2966
(via the VHF Receiver module Type 8029). This data is f iltered, modulated with a locally
generated carrier, amplif ied and then f iltered ag ain ready for am plificat ion by the VHF RF
Power Amplifier Module (PA) Type 8028.
A microcontroller on the Transmitter Module provides control and metering for the
Transmitter, PA, Receiver and Receiver Front-End (FE). The microcontroller on the
Transmitter module also stores configuration information for the Transmitter, Receiver
and RF PA modules.
Figure 7.6 below shows the connections between the RF modules and the
Modem/Controller module. This diagram should be referred t o when reading the VHF RF
module sections following.
Figure 7.7: VHF Transmitter Module in Place within an EX7100 Terminal
7.3.2 Testing and Fault Diagnosis
General
Note: Refer to Section 5 “Troubleshooting the EX7100” before reading this Section.
The Transmitter module provides control t o the Receiver module, t he Receiver Front-End
module and the Transmitter RF Power Amplifier. It collects measurements from all of
these modules and interacts with the Modem/Controller module.
For this reason, a faulty Transm itter module m ay cause symptoms that appear elsewhere
while faults elsewhere may cause symptoms to appear at the Transm it t er m odule.
The module contains semi-conductor components that are
sensitive to electrostatic damage.
Electrostatic sensitive devices should only be stored and
transported inside electrically conductive static shielding
bags. Fault finding and module replacement must be
performed at “electrostatically safe work stat ions” where the
work bench surface; soldering iron and the operator are all
earthed to prevent the build up of harmful electrostatic
charges.
The RF Power Amplifier module must not be run without a
50Ω load on its output. Failure to meet this condition may
damage the amplifier.
The RF devices used in the Power Amplifier module may
contain beryllium dioxide. These devices must not be broken,
ground, hammered or t ampered with in any way, and should
be disposed of in a safe manner as specified in local
environmental and safety legislation. If safe disposal is a
problem, they should be sealed in an appropriate container
and returned to Exicom for disposal. In this case, it is the
senders’ responsibility to ensure that all precautions are
taken to ensure safe delivery to Exicom.
Accessing the Transmitter Module
To gain service access to the Transmitter module, remove the bottom cover as per
Section 6.1.
Diagnosis
With the unit de-powered, check the Transmitter module visually for signs of damage
such as burnt tracks or components. Check that all connectors are fully mat ed and that
all socketed ICs are fully home. If no damage is apparent, apply power and follow the
steps outlined in Figure 7.8.