Exhausto RSHG12 Replacement of PDS

3000953-2010-09-10
Step by step procedure
GB
The Dungs PDS device has been replaced with the Honeywell PDS device for EXHAUSTO CDT chimney fans type RSHG, RSVG and RSG. This is how you replace existing PDS with the new PDS type.
1. Open the chimney fan and disconnect the cables to the PDS.
2. Remove the existing PDS with its bracket.
3. Mount the new PDS onto the bracket sup­plied and locate this assembly according to the drawing. Use the 2 self tapping screws supplied.
4. Locate tubes according to drawings. Use the silicon tubes supplied.
5. The connections to the motor are made as follows:
Blue cable to position 1 on the PDS (NC - normally closed)
Black cable to position 2 on the PDS (NO - normally open)
Brown cable to position 3 on the PDS (COM - common).
6. Recommission the system as per the control­ler installation instructions.
7. Please do not blow into the PDS to test for­working as this could damage it.
RSHG12
-
+
RSHG14
-
-
+
-
+
-
+
-
+
+
-
+
-
+
Items supplied with Item.no. 0500652:
Product code Description Unit Qt.
0502225 PDS Honeywell DPS200 single 1
1100327 Bracket for PDS (RSHG, RSVG and RSG) single 1
2000162 Self tapping screws 4,2 mm x 9,5 mm fzb single 2
2000335 Clear silicon tube ø8/ø4 (53004020) m 0,6
2001645 Cable shoe single 3
EXHAUSTO CDT A/S
C.F. Tietgens Boulevard 41 DK-5220 Odense SØ
Tel. +45 7010 2234 Fax +45 7010 2235 sales@exhausto-cdt.dk www.exhausto-cdt.dk
3000953-2010-09-10
+
-
-
+
-
+
+
-
RSVG 200 RSVG 250
RSVG 315
-
-
+
-
+
+
-
­+
+
-
+
+
-
-
+
RSG 133 RSG 133-K
RSG 125 RSG 150 RSG 200
2 / 2
Loading...