GeneralAll VEX units with EXact2 control have an integrated Modbus RTU interface, so they can
communicate with other modbus-enabled devices in the building.
Modbus communication that must operate via TCP/IP, must use a MTCP module or a
third party module. MTCP is a gateway that coverts data between the Modbus RTU and
the Modbus TCP protocol. MTCP acts as a Modbus/TCP slave on an Ethernet network.
Start-up and
commissioning
Warning! Switch off power to the unit before opening the doors. If the unit has
Specialist
knowledge
MonitoringThe most important parameters for monitoring daily operations can be set.
AlarmsAll alarms can be monitored and accessed via modbus. All alarms can be saved on the
Data collectionPost-commissioning, the set points on the ventilation system must to be optimised. It is
If communication is implemented via a Modbus network, it works in parallel with the
unit's HMI panel. That is, settings made via the HMI panel can be changed via the modbus network and vice versa. The latest change made will be the valid change.
been stopped via the HMI panel, it can be started later via the modbus
network.
Certain settings require specialist knowledge and therefore cannot be set directly via the
Modbus network. EXHAUSTO recommends commissioning is carried out by qualified
professionals, directly via the HMI panel.
If the unit is monitored from a main workstation, the screen display used for monitoring
should be kept as simple as possible, so that it is manageable for the user.
main workstation (PC) to give an overall view of the installation. There may be up to 16
current alarms listed on the "Current list" in the EXact2 control Menu 4.5. All 16 alarm
register addresses are listed at the back of this instruction.
See "EXact2 Control System Basic Instructions" for a description of the alarms.
advisable to have the temperature and airflow curves and other operating values available. These values can be read from the unit via the modbus network and must be logged and saved on the main workstation (PC).
6/108
3003977-2019-08-29.fmAssembly
Main station
- Overview
- Data collection
- Alarm processing
Heating
- Control of heating
installation
Lights
- Control of
lights
Ventilation
- Control of
ventilation
Motion sensor
- Switch on ventilation
- Switch on lights
- Set point for temperature ventilation/heating
Gateway
RD12919GB-01
1.1.1 Interaction with other technical installations
Interaction with
other technical
installations
To achieve comfort and the most energy-efficient operation, the VEX unit is designed to
interact with other technical installations, e.g. heating installations, motion sensors and
window switches.
There are a wide range of components available on the market for this purpose, also for
altering or expanding the installation at a later date.
2.Assembly
2.1 Mechanical assembly
2.1.1 Factory fitted
If MTCP is ordered as factory fitted, no mechanical assembly is necessary. MTCP is
located in the control system box on the unit. (Photo: example VEX240).
7/108
3003977-2019-08-29.fmAssembly
11
22
Snap ONSnap OFF
RD12918-01
2.1.2 Retrofitting of MTCP - general
When MTCP-AS is ordered for retrofitting, the module must be mounted on a DIN rail in
the control system box. See the following sections for locations on the various VEX models. The accompanying shield terminal block must always be fitted to shield the cables
on the MTCP module cable.
The MTCP module is mounted on the DIN rail as shown on the illustration:
2.1.3 Retrofitting of MTCP in a VEX320C/330C
(A) Mount the
module on the DIN
rail and mount the
shield terminal
block
8/108
3003977-2019-08-29.fmAssembly
2.1.4 Retrofitting of MTCP in a VEX330H
(A) Mount the
module on
the DIN rail
(B) Mount the
shield terminal
block
2.1.5 Retrofitting of MTCP in a VEX308
(A) Mount the
module on
the DIN rail
Mount the shield
terminal block
2.2 Electrical assembly
2.2.1 Factory fitted
If MTCP is ordered as factory fitted, no mechanical assembly is necessary. All of the internal connections have been made and tested.
9/108
3003977-2019-08-29.fmAssembly
2.2.2 Retrofitting EXact2
X1, X2, X3TerminalSignal description
X1: Power supply1+24 VDC
20 VDC (chassis)
1Do not connect
2Do not connect
X2: Modbus
(RS-485)
3Do not connect
4Do not connect
50 VDC (chassis)
6Do not connect
7Do not connect
8RS485 + (A)
9RS485 - (B)
1TD+ (Transmit data +)
2TD- (Transmit data -)
X3: Ethernet
3RD+ (Receive data +)
4Not in use
5Not in use
6RD- (Receive data -)
7Not in use
8Not in use
10/108
3003977-2019-08-29.fmAssembly
The Ethernet is connected to the front of
the MTCP module. It
is not itself connected
to the EXact control
board
2.2.3 Description of network type, speed, topology, etc.
•EXact2 Modbus uses the Modbus RTU protocol over the RS-485 bus topology
with 120 ohms termination resistors in every termination point. The modules
have built-in termination resistors.
•MTCP uses Modbus over the TCP protocol over the Ethernet network.
TerminationCheck that the termination resistor is connected via jumper JP2 on the webserver.
2.2.4 Connection to Ethernet network
11/108
3003977-2019-08-29.fmOperation
3.Operation
3.1 LED indicators - signal explanation
LED
no.:
Function
1Module statusGreen/red OffNo supply voltage to MTCP
2Network statusGreen/red OffNo supply voltage to MTCP or there is no
Display
option
LED signalDescription
GreenMTCP functioning correctly
Flashing greenMTCP on standby.
Flashing redA minor fault has been detected.
RedA serious internal fault has been detected.
Contact service.
Flashing green/red
GreenAt least one Ethernet/IP address is active.
Flashing greenNo active Ethernet/IP address.
Flashing redAt least one active Ethernet/IP connection
RedMTCP has detected a shared IP address is
Flashing green/red
Self-test running.
shared IP address for the MTCP.
expired.
already in use.
Self-test running.
3Network linkGreenOffMTCP is not connected to Ethernet network.
GreenMTCP is connected to Ethernet network.
4ActivityGreenFlashing greenData packs received or sent
5Subnet status
(Modbus RTU)
6MTCP statusGreen/red OffNo supply voltage to MTCP
Green/red OffNo supply voltage to MTCP
Flashing greenSubnet is not active.
GreenSubnet is active.
RedStopped.
Flashing green/red
GreenInitialising.
Flashing greenConfiguration OK.
12/108
Faulty/invalid configuration.
3003977-2019-08-29.fmOperation
3.2 Configuration of EXact2 control via HMI/Web server
3.2.1 Activation of BMS function
Activate communication between the EXact2 control and the MTCP module by:
StepAction
1Enter the BMS menu via the HMI panel Menu 3.5 (code 1111)
2Select ”MTCP”
3Wait approx. 2 minutes until the "MTCP" settings are activated.
CheckCommunication between the EXact2 control and the MTCP module
is active, when LED no. 1on the MTCP module is green
3.3 Configuration of the MTCP module IP address.
3.3.1 Network parameters
The standard MTCP configuration is as follows:
IP address: 192.168.1.190
Gateway: 192.168.1.1
Subnet mask: 255.255.255.0
DHCP: Disabled
3.3.2 Setting of network parameters
If desired, the IP address can be changed via the MTCP module's built-in Web server.
Change the IP
address
StepAction
1Connect the PC and the MTCP to a local network
2Set the PC to an IP address in the same subnet as the MTCP module
(default subnet: 192.168.1.xxx)
3Access the MTCP start page by entering the MTCP IP address in the URL
address field (default IP address: 192.168.1.190)
4The network parameters can be changed on the start page. Contact your
local network administrator to get the necessary network information.
OverviewThis table gives an overview of the most common register addresses. See appendix A
at the end of this instruction for the complete list of variables and for more information.
Register
address
00070008HOLDING 10100010%Unsigned Airflow set point.
00080009HOLDING 110035010
00090010HOLDING 1010000 1l/sUnsigned Fixed airflow set point:
00150016HOLDING 1011Unsigned Control mode:
01040105INPUT10100010%Unsigned Extract air fan speed:
01070108INPUT10100010%Unsigned Supply air fan speed:
01150116INPUT1011
01160117INPUT1071
01350136INPUT1065535 1
Register
no.
Modbus
type
SizeMin.Max.ScaleUnitTy peDescription
This register sets the airflow set point.
The value is only used if register 0015=0.
°C
°C
°C
°C
Unsigned Temperature set point:
This register is used to set the temperature set point to the supply air or room
temperature regulator, depending the
configuration.
This register sets the airflow set point for
the extract air air fan or supply air fan,
when using air regulation method 4 or 3.
This register holds the value for the control mode of the Unit.
Value: 0=Manual
Value: 1=Weekly plan
This register indicates the fan speed.
This register indicates the fan speed.
Unsigned Airflow regulator status:
This register indicates the state of the airflow regulator.
State: 0 = Off, 1 = On
Unsigned Airflow regulator mode:
This register indicates the state of the airflow regulator.
Val ue:
0 = OFF
1 = Starting
2 = Dampers opening
3 = Extract air fan starting
4 = Supply air fan starting
5 = Unit is running
6 = Unit is stopping but is doing post
ventilation
7 = Dampers are closing
Unsigned Current active alarm 1 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
14/108
3003977-2019-08-29.fmModbus functions
Register
address
01360137INPUT1065535 1
01370138INPUT1065535 1
01380139INPUT1065535 1
01390140INPUT1065535 1
01400141INPUT1065535 1
01410142INPUT1065535 1
01420143INPUT1065535 1
01430144INPUT1065535 1
01440145INPUT1065535 1
01450146INPUT1065535 1
01460147INPUT1065535 1
01470148INPUT1065535 1
01480149INPUT1065535 1
01490150INPUT1065535 1
01500151INPUT1065535 1
Register
no.
Modbus
type
SizeMin.Max.ScaleUnitTy peDescription
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Unsigned Current active alarm 2 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 3output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 4 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 5 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 6 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 7 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 8 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 9 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 10 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 11 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 12 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 13 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 14 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 15 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
Unsigned Current active alarm 16 output:
The register shows there is an active
alarm. See also EXact2 control menu 4.5
"Current List".
15/108
3003977-2019-08-29.fmModbus functions
Register
address
01600161INPUT1041
01730174INPUT10101
01740175INPUT10100010%Unsigned Heating unit 1 set point:
01750176INPUT10100010%Unsigned Heat recovery unit set point:
01760177INPUT10100010%Unsigned Cool recovery unit set point:
01770178INPUT10100010%Unsigned Cooling unit set point:
01870188INPUT1-700150010
01910192INPUT1-700150010
01940195INPUT1-700150010
01950196INPUT1-700150010
01980199INPUT1-700150010
01990200INPUT1-700150010
02000201INPUT1-700150010
Register
no.
Modbus
type
SizeMin.Max.ScaleUnitTy peDescription
°C
°C
°C
°C
°C
°C
°C
°C
°C
SignedActive profile:
This register indicates which profile is
active.
Val ue:
0 = Off
1 = Comfort
2 = Standby
3 = Economy
Unsigned Temparature regulator mode:
This register indicates the current mode
of the temperature regulator.
Value 0 = Automatic. Automatic switching between heating, recovery and
cooling.
Value 4 = Night cooling active.
Value 6 = Unit is in Master OFF.
Value 10 = Cooling recovery is active.
Value 13 = Unit has been temporarily
forced into Economy mode (during
start-up only).
Value 255 = Non-initialised value
(during power-up only).
This register indicates the set point for
heating unit 1.
This register indicates the set point for the
heat recovery unit.
This register indicates the set point for the
cool recovery unit.
This register indicates the set point for the
cooling unit.
SignedSupply air temperature sensor:
This register indicates the value of the
current active outdoor air temperatur sensor.
SignedOutdoor air temperature sensor:
This register indicates the value of the
current active outdoor air temperatur sensor.
SignedExhaust air temperature sensor:
This register indicates the value of the
exhaust air temperatur sensor.
SignedExtract air temperature sensor:
This register indicates the value of the
current active extract air temperatur sensor.
SignedReturn pipe temperature heating coil 1:
This register indicates the temperature on
the internal return pipe on water heating
coil 1 (TE-RPT).
SignedReturn pipe temperature external heating
coil 1:
This register indicates the temperature on
the external return pipe on water heating
coil 1 (TE-RPT-X).
SignedSupply pipe temperature heating coil 1:
This register indicates the temperature on
the internal supply air pipe on water heating coil 1 (TE-SPT).
16/108
3003977-2019-08-29.fmModbus functions
4.3 Example of control of system
4.3.1 Control of airflow, supply air temperature and manual mode/timer program
Setting the
airflow
Setting the supply
air temperature
StepAction
1Set the unit to manual mode:
Set the register address 0015 to "0".
2Set the register address 0007 to a value between 0 and 100%.
The value 0% will stop the unit.
StepAction
1Set the unit to manual mode:
Set the register address 0015 to "0".
2Set the register address 0008 to a value between 10 and 35°C.
NB: The temperature set point may be limited by other settings and
functions.
Timer programSet the register address 0015 to "1", if the unit must return to the timer program.
17/108
3003977-2019-08-29.fmDK - Produktinformation
1.DK - Produktinformation
1.1 MTCP’s anvendelse på VEX/CX-aggregater med EXact2
GenereltAlle VEX-aggregater med EXact2-styring kan leveres med Modbus RTU interface for
kommunikation med andre Modbus enheder i bygningen, såfremt aggregatet er forsynet
med en webserver.
Skal Modbus kommunikationen køre via TCP/IP, kan/skal der anvendes et MTCP modul.
MTCP er en gateway, som konverterer data mellem Modbus RTU og Modbus TCP protokollen. MTCP optræder på Ethernet netværket som en Modbus/TCP slave.
Opstart og
indregulering
Advarsel! Afbryd spændingsforsyningen til aggregatet, inden lågerne åbnes.
Specialistkendskab
OvervågningTil overvågning af daglig drift stilles de vigtigste driftsparametre til rådighed.
AlarmTil overvågning af alarmer stilles alle alarmpunkter til rådighed via modbus.
Hvis der er kommunikation via et modbus-net, virker dette parallelt med aggregatets
HMI-panel. Det vil sige, at indstillinger foretaget på HMI-panelet kan ændres via modbus-nettet og omvendt. Den sidst foretagede ændring vil være gældende.
Hvis aggregatet er stoppet på HMI-panelet kan det senere blive startet
via modbus-netværket.
Visse indstillinger, som kræver specialistkendskab, kan ikke indstilles direkte via modbus-netværket. EXHAUSTO anbefaler, at idriftsættelse foretages af faguddannede folk,
direkte på aggregatets HMI-panel.
Hvis anlægget overvåges fra en hovedstation, anbefales det, at skærmbilleder,
der anvendes til overvågning, holdes så simple som muligt for at bevare overblikket.
Alle alarmer kan gemmes på en hovedstation (PC), og giver et fælles overblik over
installationen. Der kan være op til 16 aktuelle alarmer på listen i EXact2-styringen menu
4.5 “Aktuel liste”. Se registeradresselisten bagerst i denne vejledning for at se de tilsvarende 16 registrenumre for alarmerne.
For beskrivelse af alarmer se “EXact2 Automatik Basisvejledning”.
DataopsamlingNår et ventilationssystem efter idriftsættelsen skal optimeres med hensyn til setpunkter,
er det til stor gavn at have trendkurver for temperaturer, luftmængder og andre driftsværdier. Disse værdier kan hentes fra aggregatet via modbus-nettet, og skal logges og gemmes på en hovedstation (PC).
18/108
3003977-2019-08-29.fmMontage
Hovedstation
- oversigtsbillede
- dataopsamling
- alarmhåndtering
Varm e
- styring af
varmeinstallation
Beslysning
- styring af
belysning
Ventilation
- styring af
ventilation
Bevægelsesmelder
- start af ventilation
- start af belysning
- setpunkt for temperatur vent./varme
Gateway
RD12919DK-01
1.1.1 Samspil med andre tekniske installationer
Samspil med
andre tekniske
installationer
For at opnå komfort og energimæssig optimal drift, er det en fordel at VEX-aggregatet
har et samspil med andre tekniske bygningsinstallationer - f.eks. varmeinstallationer,
bevægelsesmeldere eller vindueskontakter.
På markedet findes der et stort antal komponenter, som kan sikre dette samspil, også
hvis installationen senere skal ændres eller udbygges.
2.Montage
2.1 Mekanisk montage
2.1.1 Fabriksmontage
Hvis MTCP er bestilt som fabriksmonteret, skal der ikke laves nogen montage.
MTCP er placeret i automatikboksen på aggregatet. (Foto: eksempel VEX240)
19/108
3003977-2019-08-29.fmMontage
11
22
Snap ONSnap OFF
RD12918-01
2.1.2 Eftermontage af MTCP - generelt
Når MTCP-AS er bestilt for eftermontage, skal MTCP modulet monteres på DIN skinnen
i automatikboksen, se de følgende afsnit for placering i de forskellige VEX-modeller.
Den medleverede skærmbøjle skal altid monteres for at skærme MTCP-modulets kabel.
MTCP modulet monteres på DIN-skinnen som vist på illustrationen:
2.1.3 Eftermontage af MTCP i en VEX320C/330C
(A) Monter modulet på DIN-skinnen
og monter skærmbøjle
20/108
3003977-2019-08-29.fmMontage
2.1.4 Eftermontage af MTCP i en VEX330H
(A) Monter modulet på DIN-skinnen
(B) Monter
skærmsbøjle
2.1.5 Eftermontage af MTCP i en VEX308
(A) Monter modulet på DIN-skinnen
Monter skærmbøjle
2.2 Elektrisk montage
2.2.1 Fabriksmontage
Hvis MTCP er bestilt som fabriksmonteret, skal der ikke laves nogen montage.
Alle interne forbindelser er udført og testet.
21/108
3003977-2019-08-29.fmMontage
2.2.2 Eftermontage EXact2
X1, X2, X3KlemmeSignalbeskrivelse
X1: Power supply1+24 VDC
20 VDC (stel)
1Må ikke forbindes
2Må ikke forbindes
X2: Modbus
(RS-485)
3Må ikke forbindes
4Må ikke forbindes
50 VDC (stel)
6Må ikke forbindes
7Må ikke forbindes
8RS485 + (A)
9RS485 - (B)
1TD+ (Transmit data +)
2TD- (Transmit data -)
X3: Ethernet
3RD+ (Receive data +)
4Ikke i brug
5Ikke i brug
6RD- (Receive data -)
7Ikke i brug
8Ikke i brug
22/108
3003977-2019-08-29.fmMontage
Ethernet tilkobles på
forsiden af MTCP
modulet. Ikke på selve EXact styringens
print.
2.2.3 Beskrivelse netværkstype, hastighed, topologi mm.
•EXact2 Modbus anvender Modbus RTU protokollen over RS485 i bus topologi
med 120 ohms termineringsmodstand i hvert endepunkt. Termineringsmodstanden er indbygget i modulerne.
•MTCP anvender Modbus over TCP protokollen over Ethernet netværk.
EndetermineringKontroller at termineringsmodstanden er tilkoblet, dette gøres via jumper JP2 på
webserveren.
2.2.4 Tilslutning til ethernet netværk
23/108
3003977-2019-08-29.fmDrift
3.Drift
3.1 LED indikator - signal forklaring
LED nr.Funktion
1Modul statusGrøn/rødSlukketMTCP er uden spændingsforsyning.
2Netværks statusGrøn/rødSlukketMTCP er uden spændnigsforsyning eller der
Mulig
visning
LED signalBeskrivelse
Lyser grønMTCP fungerer korrekt.
Blinker grønMTCP er i standby.
Blinker rødEn mindre intern fejl er detekteret.
Lyser rødEn større intern fejl er detekteret.
Kontakt service.
Blinker Grøn/rødSelvtest er i gang.
er ikke tildelt nogen IP adresse til MTCP.
Lyser grønMindst en EtherNet/IP forbindelse er aktiv.
Blinker grønDer er ingen aktive EtherNet/IP forbindelser.
Blinker rødMindst en aktiv EtherNet/IP forbindelse er
udløbet.
Lyser rødMTCP har detekteret at den tildelte IP
adresse allerede er i brug.
Blinker grøn/rødSelvtest er i gang.
3Netværks linkGrønOffMTCP er ikke tilkoblet Ethernet netværk.
GrønMCTP er tilkoblet et Ethernet netværk.
4AktivitetGrønBlinker grønData pakker er modtaget eller sendt.
5Subnet status
(Modbus RTU)
6MTCP statusGrøn/rødOffMTCP er uden spændingsforsyning
Grøn/rødOffMTCP er uden spændingsforsyning
Blinker grønSubnet er ikke aktivt.
Lyser grønSubnet er aktivt.
Lyser rødEr stoppet.
Blinker grøn/rødKonfiguration mangler eller er invalid.
GrønInitialisering er i gang.
Blinker grønKonfiguration er ok.
24/108
3003977-2019-08-29.fmDrift
3.2 Konfiguration EXact2-styring via HMI/Webserver
3.2.1 Aktivering af BMS funktion
Aktivere kommunikationen mellem EXact2-styringen og MTCP modulet på følgende
måde:
TrinHandling
1Gå ind i BMS men uen, via HMI-panelets men u 3.5 (kod e 1111)
2Vælg ”MTCP”
3Vent ca. 2 minutter indtil ”MTCP” indstillingerne er aktiveret.
KontrolKommunikationen mellem EXact2-styringen og MTCP modulet er
aktiv, når LED nr. 1på MTCP modulet lyser grønt
3.3 Konfiguration af MTCP modulets IP adresse.
3.3.1 Netværksparametre
Som standard er MTCP konfigureret med følgende netværksparametre:
IP adresse: 192.168.1.190
Gateway: 192.168.1.1
Subnet mask: 255.255.255.0
DHCP: Disabled
3.3.2 Indstilling af Netværksparametre
Ønskes der ændret på IP adressen kan det gøres via MTCP modulets indbyggede webserver.
Ændre IP adresse
TrinHandling
1Forbind PC og MTCP til et lokal netværk
2Instil PC’en til en IP adresse i samme subnet som MTCP modulet (default
subnet: 192.168.1.xxx)
3Gå ind på MTCP start side, ved at skrive MTCP’s IP i URL adresse boksen
(default IP adresse: 192.168.1.190)
4Fra start siden kan netværksparametrene ændres. Kontakt den lokale net-
værks administrator for den nødvendige netværks informationer.
Værdi 0 = Automatik. Automatisk skift
mellem varme, genvinding og køl.
Værdi 4 = Natkøl aktiv.
Værdi 6 = Aggregat er i Master OFF.
Værdi 10 = Kølegenvinding er aktiv.
Værdi 13 = Aggregat er midlertidig tvunget i Economy. (Kun under opstart)
Værdi 255 = Ikke initialiseret værdi.
(Kun under power up)
Dette register viser setpunkt for varmeflade
1
Dette register viser setpunkt for varmegenvindingsenhed
Dette register viser setpunkt for kølegenvindingsenhed
Dette register viser setpunkt for køleaggregat
SignedTemperaturføler - tilluft
°C
SignedTemperaturføler -udeluft
°C
SignedTemperaturføler - afkast
°C
SignedTemperaturføler - fraluft
°C
SignedTemperaturføler - returvand - varmeflade 1
°C
SignedTemperaturføler - returvand - varmeflade 1
°C
SignedTemperaturføler -fremløb - varmeflade 1
°C
Dette register viser den målte temperatur på
den aktuelle temperaturføler
Dette register viser den målte temperatur på
den aktuelle temperaturføler
Dette register viser den målte temperatur på
den aktuelle temperaturføler
Dette register viser den målte temperatur på
den aktuelle temperaturføler
Dette register viser den målte temperatur på
returrøret i varmefladen (TE-RPT)
Dette register viser den målte temperatur på
returrøret fra varmeflade (koldeste sted)
(TE-RPT-X)
Dette register viser den målte temperatur på
fremløbsrøret i varmeflade (TE-SPT)
28/108
3003977-2019-08-29.fmModbus funktioner
4.3 Eksempel på styring af anlæg
4.3.1 Styring af luftmængde, tilluftstemperatur og manuel mode/urprogram
Indstilling af
luftmængden
Indstilling af
tillufttemperaturen
TrinHandling
1Sæt aggregatet i manuel mode:
Indstil register adressen 0015 til “0”.
2Sæt register adressen 0007 til en værdi mellem 0 og 100%.
Værdien 0% standser aggregatet.
TrinHandling
1Sæt aggregatet i manuel mode:
Indstil register adressen 0015 til “0”.
2Sæt register adressen 0008 til en værdi mellem 10 og 35°C.
Bemærk: Temperatursetpunktet kan været begrænset af andre
indstillinger og funktioner.
UrprogramSæt register adressen 0015 til “1”, hvis aggregatet skal tilbage på urprogram.
29/108
3003977-2019-08-29.fmDE - Produktinformation
1.DE - Produktinformation
1.1 Verwendung von MTCP bei VEX/CX-Geräten mit EXact2
AllgemeinAlle VEX-Geräte mit EXact2-Automatik verfügen über eine integrierte Modbus RTU-
Schnittstelle zur Kommunikation mit anderen Modbus-Einheiten im Gebäude.
Falls die Modbus-Kommunikation über TCP/IP erfolgen soll, kann/muss ein MTCPModul benutzt werden.
MTCP ist ein Gateway zum Konvertieren von Daten zwischen dem Modbus RTU- und
dem Modbus TCP-Protokoll. MTCP erscheint im Ethernet-Netzwerk als Modbus/TCPSlave.
Inbetriebnahme
und Einregelung
Achtung! Vor dem Öffnen der Türen ist die Spannungsversorgung zum Gerät zu
Spezialistenkenntnisse
ÜberwachungZur Überwachung des täglichen Betriebs werden die wichtigsten Betriebsparameter zur
AlarmZur Überwachung von Alarmen werden alle Alarmpunkte über den Modbus zur
Bei Kommunikation über ein Modbusnetz funktioniert dies parallel zum HMI-Panel des
Geräts. Das heißt, dass am HMI-Panel vorgenommene Einstellungen über das
Modbusnetz geändert werden können und umgekehrt. Die zuletzt vorgenommene
Änderung ist maßgeblich.
unterbrechen. Falls das Gerät am HMI-Panel abgeschaltet wurde, lässt
es sich später über das Modbusnetzwerk einschalten.
Gewisse Einstellungen erfordern eingehende Fachkenntnisse und lassen sich nicht
direkt über das Modbusnetzwerk einstellen. EXHAUSTO empfiehlt, dass die
Inbetriebnahme von geschulten Personen direkte am HMI-Panel des Geräts
vorgenommen wird.
Verfügung gestellt.
Wird die Anlage von einer Haupteinheit überwacht, wird empfohlen, die
Überwachungsfenster so einfach wie möglich zu gestalten, um den Überblick zu
bewahren.
Verfügung gestellt.
Alle Alarme können in der Haupteinheit (PC) gespeichert werden, und sie geben einen
Gesamtüberblick über die Installation. Die Liste in Menü 4.5 “Aktuelle Liste” in der
EXact2-Automatik enthält bis zu 16 aktuelle Alarme. Die entsprechenden 16
Registernummern für die Alarme entnehmen Sie bitte der Registeradressenliste hinten
in dieser Anleitung.
Die “EXact2 Automatik Basisanleitung” enthält eine Beschreibung der Alarme.
Erfassung von
Daten
Bei der Optimierung der Sollwerte eines Lüftungssystems nach der Inbetriebnahme ist
es von großem Vorteil, Trendkurven für Temperaturen, Luftmengen und sonstige
Betriebswerte zur Verfügung zu haben. Diese Werte können über das Modbusnetz vom
Gerät abgerufen werden und müssen geloggt und in einer Haupteinheit (PC)
gespeichert werden.
30/108