Exhausto EXact2 Product Information

EXHAUSTO A/S
Odensevej 76 DK-5550 Langeskov
Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk
Main station
- Overview
- Data collection
- Alarm processing
Heating
- Control of heating installation
Lights
- Control of
Ventilation
- Control of ventilation
Motion sensor
- Switch on ventilation
- Switch on lights
- Set point for temperature ventilation/heating
Gateway
Building Management Systems MTCP (Modbus TCP) EXact2
1. GB - Product information
1.1 MTCP applied to VEX/CX units with EXact2...................................................... 6
1.1.1 Interaction with other technical installations.................................................. 7
2. Assembly
2.1 Mechanical assembly .......................................................................................... 7
2.1.1 Factory fitted ................................................................................................. 7
2.1.2 Retrofitting of MTCP - general ...................................................................... 8
2.1.3 Retrofitting of MTCP in a VEX320C/330C.....................................................8
2.1.4 Retrofitting of MTCP in a VEX330H ............................................................. 9
2.1.5 Retrofitting of MTCP in a VEX308................................................................. 9
2.2 Electrical assembly.............................................................................................. 9
2.2.1 Factory fitted ................................................................................................. 9
2.2.2 Retrofitting EXact2 .....................................................................................10
2.2.3 Description of network type, speed, topology, etc. .....................................11
2.2.4 Connection to Ethernet network.................................................................. 11
3. Operation
3.1 LED indicators - signal explanation.................................................................12
3.2 Configuration of EXact2 control via HMI/Web server..................................... 13
3.2.1 Activation of BMS function ......................................................................... 13
3.3 Configuration of the MTCP module IP address. ............................................. 13
3.3.1 Network parameters ...................................................................................13
3.3.2 Setting of network parameters .................................................................... 13
4. Modbus functions
4.1 Description of Modbus codes...........................................................................14
4.2 List of most used Modbus registers ................................................................ 14
4.3 Example of control of system........................................................................... 17
4.3.1 Control of airflow, supply air temperature and manual mode/timer program 17
1. DK - Produktinformation
1.1 MTCP’s anvendelse på VEX/CX-aggregater med EXact2...............................18
1.1.1 Samspil med andre tekniske installationer.................................................. 19
2. Montage
2.1 Mekanisk montage.............................................................................................19
2.1.1 Fabriksmontage .......................................................................................... 19
2.1.2 Eftermontage af MTCP - generelt .............................................................. 20
2.1.3 Eftermontage af MTCP i en VEX320C/330C .............................................. 20
2.1.4 Eftermontage af MTCP i en VEX330H ....................................................... 21
2.1.5 Eftermontage af MTCP i en VEX308 ..........................................................21
2.2 Elektrisk montage.............................................................................................. 21
2.2.1 Fabriksmontage .......................................................................................... 21
2.2.2 Eftermontage EXact2 ................................................................................. 22
2.2.3 Beskrivelse netværkstype, hastighed, topologi mm. ..................................23
2.2.4 Tilslutning til ethernet netværk ....................................................................23
3. Drift
3.1 LED indikator - signal forklaring ......................................................................24
3.2 Konfiguration EXact2-styring via HMI/Webserver .......................................... 25
3.2.1 Aktivering af BMS funktion ......................................................................... 25
3.3 Konfiguration af MTCP modulets IP adresse. .................................................25
3.3.1 Netværksparametre ....................................................................................25
3.3.2 Indstilling af Netværksparametre................................................................. 25
4. Modbus funktioner
4.1 Beskrivelse af Modbus funktions koder .......................................................... 26
4.2 Liste over mest brugte Modbus registre ......................................................... 26
4.3 Eksempel på styring af anlæg ..........................................................................29
4.3.1 Styring af luftmængde, tilluftstemperatur og manuel mode/urprogram ......29
2/108
1. DE - Produktinformation
1.1 Verwendung von MTCP bei VEX/CX-Geräten mit EXact2 ..............................30
1.1.1 Integration mit anderen technischen Installationen .....................................31
2. Montage
2.1 Mechanische Montage....................................................................................... 31
2.1.1 Werksmontage ...........................................................................................31
2.1.2 Nachmontage von MTCP - allgemein ........................................................32
2.1.3 Nachmontage von MTCP in Geräten vom Typ VEX320C/330C ................. 32
2.1.4 Nachmontage von MTCP in Geräten vom Typ VEX330H .......................... 33
2.1.5 Nachmontage von MTCP in einem VEX308-Gerät ....................................33
2.2 Elektrische Montage.......................................................................................... 33
2.2.1 Werksmontage ...........................................................................................33
2.2.2 Nachmontage EXact2 ................................................................................34
2.2.3 Beschreibung von Netzwerktyp, Geschwindigkeit, Topologie u.a.m.. ........ 35
2.2.4 Anschluss an Ethernet-Netzwerk ................................................................ 35
3. Betrieb
3.1 LED-Anzeiger - Signalerläuterung....................................................................36
3.2 Konfiguration der EXact2-Automatik über HMI/Webserver ........................... 37
3.2.1 Aktivierung der BMS-Funktion ....................................................................37
3.3 Konfiguration der IP-Adresse des MTCP-Moduls...........................................37
3.3.1 Netzwerkparameter ....................................................................................37
3.3.2 Einstellung von Netzwerkparametern.......................................................... 37
4. Modbusfunktionen
4.1 Beschreibung von Modbus-Funktionscodes .................................................. 38
4.2 Liste über die gängigsten Modbus-Register................................................... 38
4.3 Beispiel für Regelung der Anlage .................................................................... 41
4.3.1 Regelung von Luftmenge, Zulufttemperatur und
manuellem Modus/Uhrprogramm ........................................................................ 41
1. NO - Produktinformasjon
1.1 MTCP-bruk på VEX/CX-aggregater med EXact2 .............................................42
1.1.1 Samspill med andre tekniske installasjoner ................................................ 43
2. Montage
2.1 Mekanisk montage.............................................................................................43
2.1.1 Fabriksmontage .......................................................................................... 43
2.1.2 Ettermontering av MTCP - generelt ............................................................ 44
2.1.3 Ettermontering av MTCP i en VEX320C/330C............................................ 44
2.1.4 Ettermontering av MTCP i en VEX330H .................................................... 45
2.1.5 Ettermontering av MTCP i en VEX308 ....................................................... 45
2.2 Elektrisk montering ........................................................................................... 45
2.2.1 Fabrikksmontering ......................................................................................45
2.2.2 Ettermont
2.2.3 Beskrivelse av nettverk
2.2.3 Tilkobling til Ethernet-nettverk.....................................................................47
3. Drift
3.1 LED indikator - signalforklaring .......................................................................48
3.2 Konfigurasjon EXact2-styring via HMI/webserver ..........................................49
3.2.1 Aktivering av BMS-funksjon ....................................................................... 49
3.3 Konfigurasjon av MTCP-modulens IP-adresse. .............................................. 49
3.3.1 Nettverksparametre ....................................................................................49
3.3.2 Innstilling av nettverksparametre.................................................................49
4. Modbus-funksjoner
4.1 Beskrivelse av Modbus-funksjonskoder ......................................................... 50
4.2 Liste over de mest brukte Modbus-registrene................................................ 50
4.3 Eksempel på styring av anlegg ........................................................................53
4.3.1 Styring av luftmengde, tilluftstemperatur og manuell modus/urprogram .... 53
ering EXact2 ............................................................................... 46
stype, hastighet, topologi mm. .............................. 47
3/108
1. SE – Produktinformation
1.1 MTCP-användning på VEX-/CX-aggregat med EXact2 ................................... 54
1.1.1 Samverkan med andra tekniska installationer.............................................55
2. Montering
2.1 Mekanisk montering ..........................................................................................55
2.1.1 Fabriksmontering ........................................................................................ 55
2.1.2 Eftermontering av MTCP - allmänt ............................................................. 56
2.1.3 Eftermontering av MTCP i en VEX320C/330C............................................ 56
2.1.4 Eftermontering av MTCP i en VEX330H .................................................... 57
2.1.5 Eftermontering av MTCP i en VEX208........................................................ 57
2.2 Elektrisk montering ........................................................................................... 57
2.2.1 Fabriksmontering ........................................................................................ 57
2.2.2 Eftermontering EXact2 ............................................................................... 57
2.2.3 Beskrivning av nätverkstyp, hastighet, topologi m.m. ................................ 58
2.2.4 Anslutning till Ethernet-nätverk.................................................................... 59
3. Drift
3.1 Lysdiodindikator – förklaring till signaler ....................................................... 60
3.2 Konfiguration av EXact2-styrning via manöverpanel/webbserver................ 61
3.2.1 Aktivering av BMS-funktionerna ................................................................. 61
3.3 Konfiguration av MTCP-modulens IP-adress.................................................. 61
3.3.1 Nätverksparametrar ....................................................................................61
3.3.2 Inställning av nätverksparametrar ............................................................... 61
4. Modbus funktioner
4.1 Beskrivning av Modbus funktionskoder..........................................................62
4.2 Lista över mest använda Modbus-register...................................................... 62
4.3 Exempel på styrning av anläggning.................................................................65
4.3.1 Styrning av luftmängd, tilluftstemperatur och manuellt läge/tidursprogram 65
1. NL - Productinformatie
1.1 MTCPgebruik voor VEX/CX-units met EXact2................................................. 66
1.1.1 Samenspel met andere technische installaties ........................................... 67
2. Montage
2.1 Mechanische montage ...................................................................................... 67
2.1.1 Fabrieksmontage ........................................................................................ 67
2.1.2 Namontage van MTCP - algemeen ............................................................ 68
2.1.3 Namontage van MTCP in de VEX320C/330C............................................. 68
2.1.4 Namontage van MTCP in de VEX330H ..................................................... 69
2.1.5 Namontage van MTCP in de VEX308 ........................................................69
2.2 Elektrische montage..........................................................................................69
2.2.1 Fabrieksmontage ........................................................................................ 69
2.2.2 Namontage EXact2 .................................................................................... 70
2.2.3 Beschrijving type netwerk, snelheid, topologie e.d. .................................... 71
2.2.4 Aansluiting op Ethernet netwerk..................................................................71
3. Bedrijf
3.1 LED indicator - verklaring signalen..................................................................72
3.2 Configuratie EXact2 regeling via HMI/webserver ........................................... 73
3.2.1 Activering van BMS functie ........................................................................ 73
3.3 Het IP adres van de MTCP module configureren............................................ 73
3.3.1 Netwerkparameters ....................................................................................73
3.3.2 Instellen van netwerkparameters ................................................................73
4. Modbus functies
4.1 Beschrijving van de Modbus functiecoden .....................................................74
4.2 Lijst van meest toegepaste Modbus registers................................................ 74
4.3 Voorbeeld van het regelen van de installatie..................................................77
4.3.1 Regelen van het luchtdebiet, de toevoerluchttemperatuur
en de handbediening/het klokprogramma ........................................................... 77
4/108
1. FI – Tuotetietoja
1.1 MTCP käyttö VEX/CX-laitteissa, joissa on EXact2..........................................78
2. Asennus
2.1 Mekaaninen asentaminen ................................................................................. 79
2.2 Sähköasennus.................................................................................................... 81
3. Käyttö
3.1 LED-ilmaisin – signaalien selitykset ................................................................ 84
3.2 EXact2-ohjauksen konfigurointi HMI:n/webpalvelimen kautta ...................... 85
3.3 MTCP-moduulin IP-osoitteen konfigurointi..................................................... 85
4. Modbus-toiminnot
4.1 Modbus-toimintokoodien kuvaus.....................................................................86
4.2 Luettelo tavallisimmista Modbus-rekistereistä ............................................... 86
4.3 Koneen ohjausesimerkki...................................................................................89
1.1.1 Toiminta yhdessä muiden teknisten laitteiden kanssa ................................ 79
2.1.1 Tehdasasennus ..........................................................................................79
2.1.2 MTCP:n jälkiasennus ................................................................................. 80
2.1.3 MTCP-jälkiasennus VEX320C/330C-laitteistoon ........................................ 80
2.1.4 MTCP-jälkiasennus VEX330H-laitteistoon ................................................. 81
2.1.5 MTCP-jälkiasennus VEX308-laitteistoon .................................................... 81
2.2.1 Tehdasasennus ..........................................................................................81
2.2.2 Jälkiasennus EXact2 .................................................................................. 82
2.2.3 Verkkotyypin, nopeuden, topologian jne. kuvaus. ......................................83
2.2.4 Kytkentä Ethernet-verkkoon........................................................................83
3.2.1 BMS-toiminnon aktivointi ............................................................................ 85
3.3.1 Verkkoparametrit ........................................................................................ 85
3.3.2 Verkkoparametriasetukset........................................................................... 85
4.3.1 Ilmamäärän, tuloilmalämpötilan ja manuaalisen tilan/ajastimen ohjaus ..... 89
1. Appendix - Complete list of Registers - in English
1.1 Appendix............................................................................................................. 90
5/108
3003977-2019-08-29.fm GB - Product information
1. GB - Product information
1.1 MTCP applied to VEX/CX units with EXact2
General All VEX units with EXact2 control have an integrated Modbus RTU interface, so they can
communicate with other modbus-enabled devices in the building. Modbus communication that must operate via TCP/IP, must use a MTCP module or a third party module. MTCP is a gateway that coverts data between the Modbus RTU and the Modbus TCP protocol. MTCP acts as a Modbus/TCP slave on an Ethernet network.
Start-up and commissioning
Warning! Switch off power to the unit before opening the doors. If the unit has
Specialist knowledge
Monitoring The most important parameters for monitoring daily operations can be set.
Alarms All alarms can be monitored and accessed via modbus. All alarms can be saved on the
Data collection Post-commissioning, the set points on the ventilation system must to be optimised. It is
If communication is implemented via a Modbus network, it works in parallel with the unit's HMI panel. That is, settings made via the HMI panel can be changed via the mod­bus network and vice versa. The latest change made will be the valid change.
been stopped via the HMI panel, it can be started later via the modbus network.
Certain settings require specialist knowledge and therefore cannot be set directly via the Modbus network. EXHAUSTO recommends commissioning is carried out by qualified professionals, directly via the HMI panel.
If the unit is monitored from a main workstation, the screen display used for monitoring should be kept as simple as possible, so that it is manageable for the user.
main workstation (PC) to give an overall view of the installation. There may be up to 16 current alarms listed on the "Current list" in the EXact2 control Menu 4.5. All 16 alarm register addresses are listed at the back of this instruction. See "EXact2 Control System Basic Instructions" for a description of the alarms.
advisable to have the temperature and airflow curves and other operating values avai­lable. These values can be read from the unit via the modbus network and must be log­ged and saved on the main workstation (PC).
6/108
3003977-2019-08-29.fm Assembly
Main station
- Overview
- Data collection
- Alarm processing
Heating
- Control of heating installation
Lights
- Control of lights
Ventilation
- Control of ventilation
Motion sensor
- Switch on ventilation
- Switch on lights
- Set point for temperature ventilation/heating
Gateway
RD12919GB-01
1.1.1 Interaction with other technical installations
Interaction with other technical installations
To achieve comfort and the most energy-efficient operation, the VEX unit is designed to interact with other technical installations, e.g. heating installations, motion sensors and window switches. There are a wide range of components available on the market for this purpose, also for altering or expanding the installation at a later date.
2. Assembly
2.1 Mechanical assembly
2.1.1 Factory fitted
If MTCP is ordered as factory fitted, no mechanical assembly is necessary. MTCP is located in the control system box on the unit. (Photo: example VEX240).
7/108
3003977-2019-08-29.fm Assembly
11
22
Snap ON Snap OFF
RD12918-01
2.1.2 Retrofitting of MTCP - general
When MTCP-AS is ordered for retrofitting, the module must be mounted on a DIN rail in the control system box. See the following sections for locations on the various VEX mo­dels. The accompanying shield terminal block must always be fitted to shield the cables on the MTCP module cable.
The MTCP module is mounted on the DIN rail as shown on the illustration:
2.1.3 Retrofitting of MTCP in a VEX320C/330C
(A) Mount the module on the DIN rail and mount the shield terminal block
8/108
3003977-2019-08-29.fm Assembly
2.1.4 Retrofitting of MTCP in a VEX330H
(A) Mount the module on the DIN rail (B) Mount the shield terminal block
2.1.5 Retrofitting of MTCP in a VEX308
(A) Mount the module on the DIN rail Mount the shield terminal block
2.2 Electrical assembly
2.2.1 Factory fitted
If MTCP is ordered as factory fitted, no mechanical assembly is necessary. All of the in­ternal connections have been made and tested.
9/108
3003977-2019-08-29.fm Assembly
2.2.2 Retrofitting EXact2
X1, X2, X3 Terminal Signal description
X1: Power supply 1 +24 VDC
2 0 VDC (chassis) 1 Do not connect 2 Do not connect
X2: Modbus (RS-485)
3 Do not connect 4 Do not connect 5 0 VDC (chassis) 6 Do not connect 7 Do not connect 8 RS485 + (A) 9 RS485 - (B) 1 TD+ (Transmit data +) 2 TD- (Transmit data -)
X3: Ethernet
3 RD+ (Receive data +) 4 Not in use 5 Not in use 6 RD- (Receive data -) 7 Not in use 8 Not in use
10/108
3003977-2019-08-29.fm Assembly
The Ethernet is con­nected to the front of the MTCP module. It is not itself connected to the EXact control board
2.2.3 Description of network type, speed, topology, etc.
EXact2 Modbus uses the Modbus RTU protocol over the RS-485 bus topology with 120 ohms termination resistors in every termination point. The modules have built-in termination resistors.
MTCP uses Modbus over the TCP protocol over the Ethernet network.
Termination Check that the termination resistor is connected via jumper JP2 on the webserver.
2.2.4 Connection to Ethernet network
11/108
3003977-2019-08-29.fm Operation
3. Operation
3.1 LED indicators - signal explanation
LED no.:
Function
1 Module status Green/red Off No supply voltage to MTCP
2 Network status Green/red Off No supply voltage to MTCP or there is no
Display option
LED signal Description
Green MTCP functioning correctly
Flashing green MTCP on standby.
Flashing red A minor fault has been detected.
Red A serious internal fault has been detected.
Contact service.
Flashing green/red
Green At least one Ethernet/IP address is active.
Flashing green No active Ethernet/IP address.
Flashing red At least one active Ethernet/IP connection
Red MTCP has detected a shared IP address is
Flashing green/red
Self-test running.
shared IP address for the MTCP.
expired.
already in use.
Self-test running.
3 Network link Green Off MTCP is not connected to Ethernet network.
Green MTCP is connected to Ethernet network.
4 Activity Green Flashing green Data packs received or sent
5 Subnet status
(Modbus RTU)
6 MTCP status Green/red Off No supply voltage to MTCP
Green/red Off No supply voltage to MTCP
Flashing green Subnet is not active.
Green Subnet is active.
Red Stopped.
Flashing green/red
Green Initialising.
Flashing green Configuration OK.
12/108
Faulty/invalid configuration.
3003977-2019-08-29.fm Operation
3.2 Configuration of EXact2 control via HMI/Web server
3.2.1 Activation of BMS function
Activate communication between the EXact2 control and the MTCP module by:
Step Action
1 Enter the BMS menu via the HMI panel Menu 3.5 (code 1111) 2 Select ”MTCP” 3 Wait approx. 2 minutes until the "MTCP" settings are activated.
Check Communication between the EXact2 control and the MTCP module
is active, when LED no. 1on the MTCP module is green
3.3 Configuration of the MTCP module IP address.
3.3.1 Network parameters
The standard MTCP configuration is as follows: IP address: 192.168.1.190 Gateway: 192.168.1.1 Subnet mask: 255.255.255.0 DHCP: Disabled
3.3.2 Setting of network parameters
If desired, the IP address can be changed via the MTCP module's built-in Web server.
Change the IP address
Step Action
1 Connect the PC and the MTCP to a local network 2 Set the PC to an IP address in the same subnet as the MTCP module
(default subnet: 192.168.1.xxx)
3 Access the MTCP start page by entering the MTCP IP address in the URL
address field (default IP address: 192.168.1.190)
4 The network parameters can be changed on the start page. Contact your
local network administrator to get the necessary network information.
13/108
3003977-2019-08-29.fm Modbus functions
4. Modbus functions
4.1 Description of Modbus codes
MTCP module supports
Function Description
03 Read Holding Register 04 Read Input Register 16 Write Multiple Registers
4.2 List of most used Modbus registers
Overview This table gives an overview of the most common register addresses. See appendix A
at the end of this instruction for the complete list of variables and for more information.
Register address
0007 0008 HOLDING 1 0 1000 10 % Unsigned Airflow set point.
0008 0009 HOLDING 1 100 350 10
0009 0010 HOLDING 1 0 10000 1 l/s Unsigned Fixed airflow set point:
0015 0016 HOLDING 1 0 1 1 Unsigned Control mode:
0104 0105 INPUT 1 0 1000 10 % Unsigned Extract air fan speed:
0107 0108 INPUT 1 0 1000 10 % Unsigned Supply air fan speed:
0115 0116 INPUT 1 0 1 1
0116 0117 INPUT 1 0 7 1
0135 0136 INPUT 1 0 65535 1
Register no.
Modbus type
Size Min. Max. Scale Unit Ty pe Description
This register sets the airflow set point. The value is only used if register 0015=0.
°C
°C
°C
°C
Unsigned Temperature set point:
This register is used to set the tempera­ture set point to the supply air or room temperature regulator, depending the configuration.
This register sets the airflow set point for the extract air air fan or supply air fan, when using air regulation method 4 or 3.
This register holds the value for the con­trol mode of the Unit. Value: 0=Manual Value: 1=Weekly plan
This register indicates the fan speed.
This register indicates the fan speed.
Unsigned Airflow regulator status:
This register indicates the state of the air­flow regulator. State: 0 = Off, 1 = On
Unsigned Airflow regulator mode:
This register indicates the state of the air­flow regulator. Val ue:
0 = OFF 1 = Starting 2 = Dampers opening 3 = Extract air fan starting 4 = Supply air fan starting 5 = Unit is running 6 = Unit is stopping but is doing post ventilation 7 = Dampers are closing
Unsigned Current active alarm 1 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
14/108
3003977-2019-08-29.fm Modbus functions
Register address
0136 0137 INPUT 1 0 65535 1
0137 0138 INPUT 1 0 65535 1
0138 0139 INPUT 1 0 65535 1
0139 0140 INPUT 1 0 65535 1
0140 0141 INPUT 1 0 65535 1
0141 0142 INPUT 1 0 65535 1
0142 0143 INPUT 1 0 65535 1
0143 0144 INPUT 1 0 65535 1
0144 0145 INPUT 1 0 65535 1
0145 0146 INPUT 1 0 65535 1
0146 0147 INPUT 1 0 65535 1
0147 0148 INPUT 1 0 65535 1
0148 0149 INPUT 1 0 65535 1
0149 0150 INPUT 1 0 65535 1
0150 0151 INPUT 1 0 65535 1
Register no.
Modbus type
Size Min. Max. Scale Unit Ty pe Description
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Unsigned Current active alarm 2 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 3output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 4 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 5 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 6 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 7 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 8 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 9 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 10 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 11 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 12 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 13 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 14 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 15 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
Unsigned Current active alarm 16 output:
The register shows there is an active alarm. See also EXact2 control menu 4.5 "Current List".
15/108
3003977-2019-08-29.fm Modbus functions
Register address
0160 0161 INPUT 1 0 4 1
0173 0174 INPUT 1 0 10 1
0174 0175 INPUT 1 0 1000 10 % Unsigned Heating unit 1 set point:
0175 0176 INPUT 1 0 1000 10 % Unsigned Heat recovery unit set point:
0176 0177 INPUT 1 0 1000 10 % Unsigned Cool recovery unit set point:
0177 0178 INPUT 1 0 1000 10 % Unsigned Cooling unit set point:
0187 0188 INPUT 1 -700 1500 10
0191 0192 INPUT 1 -700 1500 10
0194 0195 INPUT 1 -700 1500 10
0195 0196 INPUT 1 -700 1500 10
0198 0199 INPUT 1 -700 1500 10
0199 0200 INPUT 1 -700 1500 10
0200 0201 INPUT 1 -700 1500 10
Register no.
Modbus type
Size Min. Max. Scale Unit Ty pe Description
°C
°C
°C
°C
°C
°C
°C
°C
°C
Signed Active profile:
This register indicates which profile is active. Val ue:
0 = Off 1 = Comfort 2 = Standby 3 = Economy
Unsigned Temparature regulator mode:
This register indicates the current mode of the temperature regulator.
Value 0 = Automatic. Automatic swit­ching between heating, recovery and cooling. Value 4 = Night cooling active. Value 6 = Unit is in Master OFF. Value 10 = Cooling recovery is active. Value 13 = Unit has been temporarily forced into Economy mode (during start-up only). Value 255 = Non-initialised value (during power-up only).
This register indicates the set point for heating unit 1.
This register indicates the set point for the heat recovery unit.
This register indicates the set point for the cool recovery unit.
This register indicates the set point for the cooling unit.
Signed Supply air temperature sensor:
This register indicates the value of the current active outdoor air temperatur sen­sor.
Signed Outdoor air temperature sensor:
This register indicates the value of the current active outdoor air temperatur sen­sor.
Signed Exhaust air temperature sensor:
This register indicates the value of the exhaust air temperatur sensor.
Signed Extract air temperature sensor:
This register indicates the value of the current active extract air temperatur sen­sor.
Signed Return pipe temperature heating coil 1:
This register indicates the temperature on the internal return pipe on water heating coil 1 (TE-RPT).
Signed Return pipe temperature external heating
coil 1: This register indicates the temperature on the external return pipe on water heating coil 1 (TE-RPT-X).
Signed Supply pipe temperature heating coil 1:
This register indicates the temperature on the internal supply air pipe on water hea­ting coil 1 (TE-SPT).
16/108
3003977-2019-08-29.fm Modbus functions
4.3 Example of control of system
4.3.1 Control of airflow, supply air temperature and manual mode/timer program
Setting the airflow
Setting the supply air temperature
Step Action
1 Set the unit to manual mode:
Set the register address 0015 to "0".
2 Set the register address 0007 to a value between 0 and 100%.
The value 0% will stop the unit.
Step Action
1 Set the unit to manual mode:
Set the register address 0015 to "0".
2 Set the register address 0008 to a value between 10 and 35°C.
NB: The temperature set point may be limited by other settings and functions.
Timer program Set the register address 0015 to "1", if the unit must return to the timer program.
17/108
3003977-2019-08-29.fm DK - Produktinformation
1. DK - Produktinformation
1.1 MTCP’s anvendelse på VEX/CX-aggregater med EXact2
Generelt Alle VEX-aggregater med EXact2-styring kan leveres med Modbus RTU interface for
kommunikation med andre Modbus enheder i bygningen, såfremt aggregatet er forsynet med en webserver. Skal Modbus kommunikationen køre via TCP/IP, kan/skal der anvendes et MTCP mo­dul. MTCP er en gateway, som konverterer data mellem Modbus RTU og Modbus TCP pro­tokollen. MTCP optræder på Ethernet netværket som en Modbus/TCP slave.
Opstart og indregulering
Advarsel! Afbryd spændingsforsyningen til aggregatet, inden lågerne åbnes.
Specialist­kendskab
Overvågning Til overvågning af daglig drift stilles de vigtigste driftsparametre til rådighed.
Alarm Til overvågning af alarmer stilles alle alarmpunkter til rådighed via modbus.
Hvis der er kommunikation via et modbus-net, virker dette parallelt med aggregatets HMI-panel. Det vil sige, at indstillinger foretaget på HMI-panelet kan ændres via mod­bus-nettet og omvendt. Den sidst foretagede ændring vil være gældende.
Hvis aggregatet er stoppet på HMI-panelet kan det senere blive startet via modbus-netværket.
Visse indstillinger, som kræver specialistkendskab, kan ikke indstilles direkte via mod­bus-netværket. EXHAUSTO anbefaler, at idriftsættelse foretages af faguddannede folk, direkte på aggregatets HMI-panel.
Hvis anlægget overvåges fra en hovedstation, anbefales det, at skærmbilleder, der anvendes til overvågning, holdes så simple som muligt for at bevare overblikket.
Alle alarmer kan gemmes på en hovedstation (PC), og giver et fælles overblik over installationen. Der kan være op til 16 aktuelle alarmer på listen i EXact2-styringen menu
4.5 “Aktuel liste”. Se registeradresselisten bagerst i denne vejledning for at se de tilsva­rende 16 registrenumre for alarmerne. For beskrivelse af alarmer se “EXact2 Automatik Basisvejledning”.
Dataopsamling Når et ventilationssystem efter idriftsættelsen skal optimeres med hensyn til setpunkter,
er det til stor gavn at have trendkurver for temperaturer, luftmængder og andre driftsvær­dier. Disse værdier kan hentes fra aggregatet via modbus-nettet, og skal logges og gem­mes på en hovedstation (PC).
18/108
3003977-2019-08-29.fm Montage
Hovedstation
- oversigtsbillede
- dataopsamling
- alarmhåndtering
Varm e
- styring af varmeinstallation
Beslysning
- styring af belysning
Ventilation
- styring af ventilation
Bevægelsesmelder
- start af ventilation
- start af belysning
- setpunkt for temperatur vent./varme
Gateway
RD12919DK-01
1.1.1 Samspil med andre tekniske installationer
Samspil med andre tekniske installationer
For at opnå komfort og energimæssig optimal drift, er det en fordel at VEX-aggregatet har et samspil med andre tekniske bygningsinstallationer - f.eks. varmeinstallationer, bevægelsesmeldere eller vindueskontakter. På markedet findes der et stort antal komponenter, som kan sikre dette samspil, også hvis installationen senere skal ændres eller udbygges.
2. Montage
2.1 Mekanisk montage
2.1.1 Fabriksmontage
Hvis MTCP er bestilt som fabriksmonteret, skal der ikke laves nogen montage. MTCP er placeret i automatikboksen på aggregatet. (Foto: eksempel VEX240)
19/108
3003977-2019-08-29.fm Montage
11
22
Snap ON Snap OFF
RD12918-01
2.1.2 Eftermontage af MTCP - generelt
Når MTCP-AS er bestilt for eftermontage, skal MTCP modulet monteres på DIN skinnen i automatikboksen, se de følgende afsnit for placering i de forskellige VEX-modeller. Den medleverede skærmbøjle skal altid monteres for at skærme MTCP-modulets kabel.
MTCP modulet monteres på DIN-skinnen som vist på illustrationen:
2.1.3 Eftermontage af MTCP i en VEX320C/330C
(A) Monter modu­let på DIN-skinnen og monter skærm­bøjle
20/108
3003977-2019-08-29.fm Montage
2.1.4 Eftermontage af MTCP i en VEX330H
(A) Monter modu­let på DIN-skinnen (B) Monter skærmsbøjle
2.1.5 Eftermontage af MTCP i en VEX308
(A) Monter modu­let på DIN-skinnen Monter skærmbøjle
2.2 Elektrisk montage
2.2.1 Fabriksmontage
Hvis MTCP er bestilt som fabriksmonteret, skal der ikke laves nogen montage. Alle interne forbindelser er udført og testet.
21/108
3003977-2019-08-29.fm Montage
2.2.2 Eftermontage EXact2
X1, X2, X3 Klemme Signalbeskrivelse
X1: Power supply 1 +24 VDC
2 0 VDC (stel) 1 Må ikke forbindes 2 Må ikke forbindes
X2: Modbus (RS-485)
3 Må ikke forbindes 4 Må ikke forbindes 5 0 VDC (stel) 6 Må ikke forbindes 7 Må ikke forbindes 8 RS485 + (A) 9 RS485 - (B) 1 TD+ (Transmit data +) 2 TD- (Transmit data -)
X3: Ethernet
3 RD+ (Receive data +) 4 Ikke i brug 5 Ikke i brug 6 RD- (Receive data -) 7 Ikke i brug 8 Ikke i brug
22/108
3003977-2019-08-29.fm Montage
Ethernet tilkobles på forsiden af MTCP modulet. Ikke på sel­ve EXact styringens print.
2.2.3 Beskrivelse netværkstype, hastighed, topologi mm.
EXact2 Modbus anvender Modbus RTU protokollen over RS485 i bus topologi med 120 ohms termineringsmodstand i hvert endepunkt. Termineringsmodstan­den er indbygget i modulerne.
MTCP anvender Modbus over TCP protokollen over Ethernet netværk.
Endeterminering Kontroller at termineringsmodstanden er tilkoblet, dette gøres via jumper JP2 på
webserveren.
2.2.4 Tilslutning til ethernet netværk
23/108
3003977-2019-08-29.fm Drift
3. Drift
3.1 LED indikator - signal forklaring
LED nr. Funktion
1 Modul status Grøn/rød Slukket MTCP er uden spændingsforsyning.
2 Netværks status Grøn/rød Slukket MTCP er uden spændnigsforsyning eller der
Mulig visning
LED signal Beskrivelse
Lyser grøn MTCP fungerer korrekt.
Blinker grøn MTCP er i standby.
Blinker rød En mindre intern fejl er detekteret.
Lyser rød En større intern fejl er detekteret.
Kontakt service.
Blinker Grøn/rød Selvtest er i gang.
er ikke tildelt nogen IP adresse til MTCP.
Lyser grøn Mindst en EtherNet/IP forbindelse er aktiv.
Blinker grøn Der er ingen aktive EtherNet/IP forbindelser.
Blinker rød Mindst en aktiv EtherNet/IP forbindelse er
udløbet.
Lyser rød MTCP har detekteret at den tildelte IP
adresse allerede er i brug.
Blinker grøn/rød Selvtest er i gang.
3 Netværks link Grøn Off MTCP er ikke tilkoblet Ethernet netværk.
Grøn MCTP er tilkoblet et Ethernet netværk.
4 Aktivitet Grøn Blinker grøn Data pakker er modtaget eller sendt.
5 Subnet status
(Modbus RTU)
6 MTCP status Grøn/rød Off MTCP er uden spændingsforsyning
Grøn/rød Off MTCP er uden spændingsforsyning
Blinker grøn Subnet er ikke aktivt.
Lyser grøn Subnet er aktivt.
Lyser rød Er stoppet.
Blinker grøn/rød Konfiguration mangler eller er invalid.
Grøn Initialisering er i gang.
Blinker grøn Konfiguration er ok.
24/108
3003977-2019-08-29.fm Drift
3.2 Konfiguration EXact2-styring via HMI/Webserver
3.2.1 Aktivering af BMS funktion
Aktivere kommunikationen mellem EXact2-styringen og MTCP modulet på følgende måde:
Trin Handling
1 Gå ind i BMS men uen, via HMI-panelets men u 3.5 (kod e 1111) 2 Vælg ”MTCP” 3 Vent ca. 2 minutter indtil ”MTCP” indstillingerne er aktiveret.
Kontrol Kommunikationen mellem EXact2-styringen og MTCP modulet er
aktiv, når LED nr. 1på MTCP modulet lyser grønt
3.3 Konfiguration af MTCP modulets IP adresse.
3.3.1 Netværksparametre
Som standard er MTCP konfigureret med følgende netværksparametre: IP adresse: 192.168.1.190 Gateway: 192.168.1.1 Subnet mask: 255.255.255.0 DHCP: Disabled
3.3.2 Indstilling af Netværksparametre
Ønskes der ændret på IP adressen kan det gøres via MTCP modulets indbyggede web­server.
Ændre IP adresse
Trin Handling
1 Forbind PC og MTCP til et lokal netværk 2 Instil PC’en til en IP adresse i samme subnet som MTCP modulet (default
subnet: 192.168.1.xxx)
3 Gå ind på MTCP start side, ved at skrive MTCP’s IP i URL adresse boksen
(default IP adresse: 192.168.1.190)
4 Fra start siden kan netværksparametrene ændres. Kontakt den lokale net-
værks administrator for den nødvendige netværks informationer.
25/108
3003977-2019-08-29.fm Modbus funktioner
4. Modbus funktioner
4.1 Beskrivelse af Modbus funktions koder
MTCP modulet understøtter
Funktion Beskrivelse
03 Read Holding Register 04 Read Input Register 16 Write Multiple Registers
4.2 Liste over mest brugte Modbus registre
Overblik Denne tabel giver et overblik over de mest anvendte register adresser. Den komplette
liste med yderligere informationer findes som Appendix bagerst i denne vejledning.
Register address
0007 0008 HOLDING 1 0 1000 10 % Unsigned Luftmængde setpunkt
0008 0009 HOLDING 1 100 350 10
0009 0010 HOLDING 1 0 10000 1 l/s Unsigned Konstant luftmængde setpunkt
0015 0016 HOLDING 1 0 1 1 Unsigned Styrings-metode:
0104 0105 INPUT 1 0 1000 10 % Unsigned Ventilatorhastighed, fraluftsventilator
0107 0108 INPUT 1 0 1000 10 % Unsigned Ventilatorhastighed,tilluftsventilator
0115 0116 INPUT 1 0 1 1 Unsigned Status, luft-regulering
0116 0117 INPUT 1 0 7 1 Unsigned Indstilling, luftregulering
0135 0136 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 1
Register nr.
Modbus­type
Size Min. Max. Scale Unit Typ e Beskrivelse
I dette register indstilles luftmængde set­punkt. Værdien anvendes kun hvis register 0015 = 0
Unsigned Temperatur setpunkt
°C
I dette register indstilles setpunkt for tilluft­temperatur eller rumtemperatur - afhængig af konfigurering
I dette register indstilles setpunkt for luft­mængde for fralufts- eller tilluftsventilator, når luftmængdereguleringsmetode 3 eller 4 anvendes
I dette register indstilles værdien for sty­rings-metode. Værdi: 0=Manuel Værdi: 1=Ugeplan
Dette register viser ventilatorhastigheden
Dette register viser ventilatorhastigheden
Dette register viser status for luftregulering 0 = OFF, 1 = ON
Dette register viser status for luftregulering
Værdi 0 = OFF Værdi 1 = Starter Værdi 2 = Spjæld åbner Værdi 3 = Fraluftsventilator starter Værdi 4 = Tilluftsventilator starter Værdi 5 = VEX kører Værdi 6 = VEX er stoppet men kører efterløb Værdi 7 = Spjæld lukker
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
26/108
3003977-2019-08-29.fm Modbus funktioner
Register address
0136 0137 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 2
0137 0138 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 3
0138 0139 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 4
0139 0140 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 5
0140 0141 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 6
0141 0142 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 7
0142 0143 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 8
0143 0144 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 9
0144 0145 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 10
0145 0146 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 11
0146 0147 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 12
0147 0148 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 13
0148 0149 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 14
0149 0150 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 15
0150 0151 INPUT 1 0 65535 1 Unsigned Aktuel alarm - alarm 16
Register nr.
Modbus­type
Size Min. Max. Scale Unit Typ e Beskrivelse
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
Registeret viser at der er en aktiv alarm, se også EXact2 styringen menu 4.5 “Aktuel liste”.
27/108
3003977-2019-08-29.fm Modbus funktioner
Register address
0160 0161 INPUT 1 0 4 1 Signed Aktuelt indeklimaniveau
0173 0174 INPUT 1 0 10 Unsigned Metode til temperaturregulering
0174 0175 INPUT 1 0 1000 10 % Unsigned Varmeflade 1
0175 0176 INPUT 1 0 1000 10 % Unsigned Varmegenvindingsenhed
0176 0177 INPUT 1 0 1000 10 % Unsigned Kølegenvindingsenhed
0177 0178 INPUT 1 0 1000 10 % Unsigned Køleaggregat
0187 0188 INPUT 1 -700 1500 10
0191 0192 INPUT 1 -700 1500 10
0194 0195 INPUT 1 -700 1500 10
0195 0196 INPUT 1 -700 1500 10
0198 0199 INPUT 1 -700 1500 10
0199 0200 INPUT 1 -700 1500 10
0200 0201 INPUT 1 -700 1500 10
Register nr.
Modbus­type
Size Min. Max. Scale Unit Typ e Beskrivelse
Dette register viser det aktuelle indeklima­niveau:
Værdi 0 = ventilator stoppet Værdi 1 = Komfort Værdi 2 = Standby Værdi 3 = Økonomi
Dette register viser den aktuelle metode:
Værdi 0 = Automatik. Automatisk skift mellem varme, genvinding og køl. Værdi 4 = Natkøl aktiv. Værdi 6 = Aggregat er i Master OFF. Værdi 10 = Kølegenvinding er aktiv. Værdi 13 = Aggregat er midlertidig tvun­get i Economy. (Kun under opstart) Værdi 255 = Ikke initialiseret værdi. (Kun under power up)
Dette register viser setpunkt for varmeflade 1
Dette register viser setpunkt for varmegen­vindingsenhed
Dette register viser setpunkt for kølegenvin­dingsenhed
Dette register viser setpunkt for køleaggre­gat
Signed Temperaturføler - tilluft
°C
Signed Temperaturføler -udeluft
°C
Signed Temperaturføler - afkast
°C
Signed Temperaturføler - fraluft
°C
Signed Temperaturføler - returvand - varmeflade 1
°C
Signed Temperaturføler - returvand - varmeflade 1
°C
Signed Temperaturføler -fremløb - varmeflade 1
°C
Dette register viser den målte temperatur på den aktuelle temperaturføler
Dette register viser den målte temperatur på den aktuelle temperaturføler
Dette register viser den målte temperatur på den aktuelle temperaturføler
Dette register viser den målte temperatur på den aktuelle temperaturføler
Dette register viser den målte temperatur på returrøret i varmefladen (TE-RPT)
Dette register viser den målte temperatur på returrøret fra varmeflade (koldeste sted) (TE-RPT-X)
Dette register viser den målte temperatur på fremløbsrøret i varmeflade (TE-SPT)
28/108
3003977-2019-08-29.fm Modbus funktioner
4.3 Eksempel på styring af anlæg
4.3.1 Styring af luftmængde, tilluftstemperatur og manuel mode/urprogram
Indstilling af luftmængden
Indstilling af tillufttemperaturen
Trin Handling
1 Sæt aggregatet i manuel mode:
Indstil register adressen 0015 til “0”.
2 Sæt register adressen 0007 til en værdi mellem 0 og 100%.
Værdien 0% standser aggregatet.
Trin Handling
1 Sæt aggregatet i manuel mode:
Indstil register adressen 0015 til “0”.
2 Sæt register adressen 0008 til en værdi mellem 10 og 35°C.
Bemærk: Temperatursetpunktet kan været begrænset af andre indstillinger og funktioner.
Urprogram Sæt register adressen 0015 til “1”, hvis aggregatet skal tilbage på urprogram.
29/108
3003977-2019-08-29.fm DE - Produktinformation
1. DE - Produktinformation
1.1 Verwendung von MTCP bei VEX/CX-Geräten mit EXact2
Allgemein Alle VEX-Geräte mit EXact2-Automatik verfügen über eine integrierte Modbus RTU-
Schnittstelle zur Kommunikation mit anderen Modbus-Einheiten im Gebäude. Falls die Modbus-Kommunikation über TCP/IP erfolgen soll, kann/muss ein MTCP­Modul benutzt werden. MTCP ist ein Gateway zum Konvertieren von Daten zwischen dem Modbus RTU- und dem Modbus TCP-Protokoll. MTCP erscheint im Ethernet-Netzwerk als Modbus/TCP­Slave.
Inbetriebnahme und Einregelung
Achtung! Vor dem Öffnen der Türen ist die Spannungsversorgung zum Gerät zu
Spezialisten­kenntnisse
Überwachung Zur Überwachung des täglichen Betriebs werden die wichtigsten Betriebsparameter zur
Alarm Zur Überwachung von Alarmen werden alle Alarmpunkte über den Modbus zur
Bei Kommunikation über ein Modbusnetz funktioniert dies parallel zum HMI-Panel des Geräts. Das heißt, dass am HMI-Panel vorgenommene Einstellungen über das Modbusnetz geändert werden können und umgekehrt. Die zuletzt vorgenommene Änderung ist maßgeblich.
unterbrechen. Falls das Gerät am HMI-Panel abgeschaltet wurde, lässt es sich später über das Modbusnetzwerk einschalten.
Gewisse Einstellungen erfordern eingehende Fachkenntnisse und lassen sich nicht direkt über das Modbusnetzwerk einstellen. EXHAUSTO empfiehlt, dass die Inbetriebnahme von geschulten Personen direkte am HMI-Panel des Geräts vorgenommen wird.
Verfügung gestellt. Wird die Anlage von einer Haupteinheit überwacht, wird empfohlen, die Überwachungsfenster so einfach wie möglich zu gestalten, um den Überblick zu bewahren.
Verfügung gestellt. Alle Alarme können in der Haupteinheit (PC) gespeichert werden, und sie geben einen Gesamtüberblick über die Installation. Die Liste in Menü 4.5 “Aktuelle Liste” in der EXact2-Automatik enthält bis zu 16 aktuelle Alarme. Die entsprechenden 16 Registernummern für die Alarme entnehmen Sie bitte der Registeradressenliste hinten in dieser Anleitung. Die “EXact2 Automatik Basisanleitung” enthält eine Beschreibung der Alarme.
Erfassung von Daten
Bei der Optimierung der Sollwerte eines Lüftungssystems nach der Inbetriebnahme ist es von großem Vorteil, Trendkurven für Temperaturen, Luftmengen und sonstige Betriebswerte zur Verfügung zu haben. Diese Werte können über das Modbusnetz vom Gerät abgerufen werden und müssen geloggt und in einer Haupteinheit (PC) gespeichert werden.
30/108