eWON eWON500 User Manual

User Guide
eWON500™
The Programmable Gateway

PURPOSE

ACT’L produces a complete range of Ethernet/Internet
gateways also known as “Programmable Industrial Routers” (PIR). See our website http://www.ewon.biz information about the eWON™ range.
The eWON500™ can be used as a programmable gateway: The eWON500™ becomes the interface between a proprietary serial protocol and a ModbusTCP Supervisor.
The eWON500™ can transform your old serial-only device to an Up-to-date Ethernet SCADA ready device.
to get further
ver 1.0
9/11/05
The goal of the current document is to teach you how to correctly configure the eWON500™ as a Programmable Gateway to address a wide range of various serial devices.
eWON500™ is just out of the box, you have already powered it ON (12-24VDC) and connected its Ethernet cable.
Every eWONs™ are shipped with the pre configured IP address 10.0.0.53 and adm/adm as User Name/Password.
• Enter http://10.0.0.53 in the address bar from your Internet Explorer (refer to the eBuddy User Guide if you need to change the eWON™ IP address and subnet mask)
• Enter adm (User Name)/adm (Password) then Enter
You are now navigating on your eWON500™!
Page 1
User Guide
eWON500™
The Programmable Gateway
ver 1.0
9/11/05

eWON500™ is a programmable gateway

Programmable gateway - What you can do with

Communicating with serial devices

The eWON500™ has been designed to enable communication with any serial device (RS232 or RS485)
A programmable gateway is used to enable the supervision of a
proprietary communication protocol, following those 2 principles:
• The eWON500™ is designed
The protocol from this device will be partially or totally coded in the eWON500™
• The significant data from the device will be published on the Ethernet link through the
eWON500™ Memory Tags, either with the ModbusTCP protocol or with the SNMP protocol
The serial protocols that are used on those devices are either ASCII (text) or binary.
We will only explain the case of the ASCII protocol which is more didactic and visual.
to communicate through its serial port with a device.
any device that embeds a serial port and

The serial protocols communication modes

The communications with serial devices use principally 2 operating modes:
• The
Question-Answer mode
Automatic sending of messages (at regular intervals or not)
You will find in this document some examples to illustrate those two operating modes.

The eWON500™ embeds a programming language

Main characteristics from the eWON500™ BASIC language

The programming language used in the eWON is the BASIC*, which is an interpreted language using a very simple syntax. However, this language embeds all the basic instructions and functions that can be found in a programming language, and also specific eWON500™ functions, such as the ability to read Tags, to program alarms, to manage schedule tasks,..
* The document
eWON™ web site http://www.ewon.biz detailed practical learning of the eWON500™ BASIC language.
Programming eWON : Learning by examples you can download on the
(Support/Documentation/How-to...) will provide you a
Page 2
User Guide
eWON500™
The Programmable Gateway
ver 1.0
9/11/05

eWON500™ serial port special features

¤ The serial ports can be configured in RS232 or RS485 by means of a dip switch. You have
just to configure the switches according to the illustrations below:
RS232
All switches OFF
RS485 dipswitch panel configuration
WITH polarization
dipswitch panel configuration
RS485 dipswitch panel configuration
WITHOUT polarization
¤ The eWON500™ BASIC language manages the serial port configuration, that means that the
serial port CANNOT BE USED by any IO server at the same time!!
¤ The eWON500™ BASIC instructions listed below are dedicated to operations on the serial
port. You will find exhaustive information on the eWON500™ BASIC instructions in the eWON™ User Guide you can download from the eWON™ web site: http://www.ewon.biz (Support/Documentation/User guides).
OPEN “com:1...” Opening the COM port
CLOSE Closing the COM port
PUT Writing on the COM port
GET Reading on the COM port
¤ There is no way to know the number of characters present in the incoming buffer from the
serial link.
Page 3
User Guide
eWON500™
The Programmable Gateway
ver 1.0
9/11/05
Question/Answer Protocol
Below are detailed the steps required to code a program sending a “question” on the serial port and waiting for an “answer”:
1 Serial port initialization gosub InitSerial_QA 2Sending a question Q$=”CMD”:gosub SendQuestion 3 Waiting for a delay tset 4,2 + ontimer 4 Reading the answer+displaying goto ReadAnswer
5goto 2
Rem --- eWON start section: SERIAL_QA Rem --- eWON user (start) InitSerial_QA: Open "com:1,9600,8n1n" For Binary Input As 1 ontimer 1,"goto Question" tset 1,10 return CloseSerial: Close 1 return Question: Q$ = "??"+chr$(13) gosub SendQuestion end SendQuestion: rem flush the serial input buffer A$ = GET 1 A$="" rem send the Question Q$ to serial put 1,Q$ rem Wait 2 seconds before read the input buffer rem set a timer handler and a timer of 2 seconds Ontimer 4,"goto ReadAnswer" tset 4,2 return ReadAnswer: rem stop the timer4 tset 4,0 rem read the serial input A$ = GET 1 rem process the Answer a% = len(A$) print time$;" RxLen: ";a% print "Rx: ";A$ SerialTag@ = VAL(A$) end Rem --- eWON user (end) End
COM ports special features:
- always 'binary' The serial ports are always Input/Output even when opened with Input (input/output does not exist)
Initialiazing a timer to send the Question every 10 seconds
End of the initialization process (QA mode)
Question = “??” + CR
We first empty the read buffer prior to send the question
The question is sent on the serial port
Initializing a timer to wait for the answer
Stop the timer to read only once when timer expires
Reading the entire input buffer (default: 2048 bytes max)
Displaying the answer in ScriptControl
If the answer represents a numeric value, it has to be converted prior to be assigned to a Tag
To test this Program, insert a Gosub InitSerial_cont in the init_section.
Page 4
User Guide
eWON500™
The Transparent Gateway
Spontaneous Protocol
The device moreoften sends fix length messages in this functionning mode
1 Serial port initialization gosub InitSerial_Cont
2 Reading the input buffer goto GetSerial
3 Waiting for a delay
4 Reading the answer+displaying gosub ProcessBuffer
5goto 2
Rem --- eWON start section: SERIAL_cont Rem --- eWON user (start) InitSerial_cont: Rem open the COM port Open "com:1,9600,8n1n" For Binary Input As 1 B$="" rem Set a timer handler Ontimer 4,"goto GetSerial" Rem and the set the timer to 2 seconds Tset 4,2 return end GetSerial: rem read the input buffer A$ = Get 1 rem add characters in a buffer B$=B$+A$ a% = len(B$) rem wait for receive 16 characters If (a%<16) Then print "buff: ";B$ Goto EndGetSerial Else If a%>16 Then rem extract the 16 first char C$=B$(1 To 16) rem keep the remainding char B$=B$(17 To) Else rem buffer holds exactly 16 characters C$=B$ B$="" Endif Endif Print time$;" ";C$ gosub ProcessBuffer EndGetSerial: End ProcessBuffer: rem extract the value of a substring and assign it to Tag If (C$(1)="N") Then SerialValue@ = VAL(C$(8 To 16)) Else Print Time$;" unknown message" Print C$ Endif return Rem --- eWON user (end) End Rem --- eWON end section: SERIAL_cont
COM ports special features:
- always 'binary'
- The serial ports are always Input/Output even when opened with Input (input/output does not exist)
The GetSerial procedure will be called every 2 seconds
Reading the entire input buffer (default: 2048 bytes max) Concatenation from the characters
Testing that the complete message has been received
Extraction of the 16 first characters in C$
C$ contents the message Message processing procedure call End from the GetSerial procedure
ver 1.0
9/11/05
To test this Program, insert a Gosub InitSerial_cont in the init_section.
Page 5