EWC Controls UZC-8 User Guide

Page 1
®
TECHNICAL BULLETIN
Forced Air Zone Controls
Model UZC4 Zone Control
The UZC4 Zone Control System allows you to easily upgrade an inefficient single zone HVAC system, into an Automated, Multi-zone, Energy saving, Comfort producing, Safety Minded, HVAC system. With Superior design, Intuitive firmware, Building Code Compliant support, Simple setup options, and Easy to understand wiring, the UZC4 Zoning system is the Designer/Contractors dream. Combined with Patented EWC motorized dampers and practically any Off-the­shelf Conventional or Heat Pump style Thermostats,
EWC has set a New Industry Standard in Large Residential and Commercial HVAC Air Zoning Systems.
Zone Capacity
Compatible HVAC Systems
Compatible Thermostats
Automatic Heat/Cool Changeover
Status LED
System LEDs
Damper LEDs
Operating Power
TB-221
P/N 090375A0221 Revision I
Universal
FA
FA 24V 24V
RESET
MXR MXC M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2
The main module controls four air zones using 24 vac motorized air dampers and may be expanded up to 20 zones, using
ZXM2 Expansion Modules. See page 23.
The UZC4 will Control 2, 3 & 4 stage Conventional, GeoThermal or Dual Fuel Heat pumps, without the need for dual fuel kits. Also single or multi-stage Gas, Oil, & Hydronic HVAC systems, with single or two stage cooling and Constant or Variable speed fan systems.
Compatible with most Off the shelf 1 or 2 stage Conventional Heat/Cool or Heat
M1
M6 M4 M2 M1
M6 M4 M2 M1
NC NO
C
G
Y2
Y1
O
B
W1
W2
E
RC
RH
RC LINK
W
E
Box Contents
Pump Therm ostats. All Mech anical, Digital/Electronic, Dual Mode, and Internet Compatible Thermostats that operate on 24vac. Battery powered or Power robbing thermostats that draw less than 20 ma of current are also compatible. Zone 1 will accept One Zone Mode, Carbon Dioxide Safety and Auxiliary/Dehumidify mode inputs. See pages 9-11 & 14-17 for details.
The UZC4 Zo ne system features auto m a t ic chan g e o ver from a n y
Manual and Automatic Thermal Circuit Breakers
thermostat allowing for individual zone comfort from the HVAC system.
The STATUS LED pulses as a steady heart beat to indicate active Micro­processor status.
On board Multi-colored LED’s will illuminate to indicate system status, HVAC system mode, and active / inactive zone identification. See page 22 for details.
Damper 1 thru Damper 20 green LEDs
Operating Conditions
will indicate which zone dampers are demanded to energize Open or Closed.
INPUT VOLTAGE: 19-30VAC 60 Hz
Transformer 40-100VA MAX. NEC Class
2.
CURRENT DRAW: Max 22VA @ 24VAC. OVER-CURRENT PROTECTION: 4.0
amp or 100VA.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Copyright © 2004-2009 EWC Controls All Rights Reserved
Indoor Fan Control
Leave this bulletin on the job site for future reference!
J1
HVAC ZONE CONTROl SYSTEM
TB1
JMP1
R
D1
C
TB2
CB1
F1
K1
Z O
4
N E
K2
TB3
Z O
3
N E
K3 K4
TB4
Z O
2
N E
TB5
K5
Z O
1
N E
TB6
O A
D M P R
K7
TB7
E B
K8
D
A
TB8
U X
K9
R L Y
K10 K11
TB9
H V A C
S
K12 K13
Y S T E
M
JMP3
K14
RH
CONTROLS INC. Englishtown, NJ
C
28
40
35
37
42
34
C54
R20
R19
HP
SYSTEM
>
HP
DF
< >
OFF
FAN PRG
<
PURGE
90
s
<
STAGES
OAS
<
OFF
50
<
OFF
SAS
<
FAN
GAS
<
TSTAT
HC
>
1
CS#
<
RV
O
<
OFF
<
RA
AUX RLY
<
RAS
OFF
<
0
RA LMT
<
FAN CTRL
ANY
<
STATUS OAS SAS RAS
ZONE ZONE
ZONE
ZONE
DMPR
BYPASS AUX RELAY FAN COMPRESSOR2
COMPRESSOR1 REV
EMERGENCY
C53
CONV
%
>
>
ZDL
R48
C17
Y1
R50
SW1
LIMIT
LIMIT LIMIT
4 3 2 1
VALVE
COOLING
LIMIT
R2
>
>
R
> > >
>
2
B
>
>
>
TIMER RESET
OPEN
OPEN
OPEN
OPEN
43
GAS
>
180
TMR
>
ON ON HYDRO
HP
ON
>
ON
+10
U14
U19
OPENOA
DMPR
R52
R53
R54
R55
R63
21
14
7
OFF
STAGING
OAS
TIMER
R1
C1
C2
D2
LED19
GROUND FAULT
JMP2
D3
R5
D4
R6
D5
R7
D6
R8
D7
R9
D8
R10
D9
R11
D10
R12
D11
R13
D12
R14
D13
R15
D14
W1 HEAT
W2 HEAT
R16
D15
R17
D16
R18
140
130
46
120
49
110
52
1ST
STAGE
HEATING
LIMIT
R3
R21
R22
BANK1
R29 R30
ON
s
DA
Z
1
>
U1
R31 R32 R33 R34 R35 R36
BANK2
R37 R38 R39 R40 R41 R42 R43 R44
C8
C7
U15
R47
C10C9C11
C12
C13
C14
C15
C18
R49
C19
C22
R58
C21
R51
CPU
RESET
U17
U18
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED11
LED12
LED13
LED14
LED15
LED16
LED17
LED18
Z1
R56
R57
R60
R61
26
150
19
160
12
170
5
STAGE
MULTI
DIFFERENTIAL
R4
R23
D17
R24
D18
R25
D19 D20
R26
D21
R27 R28
D22
R50
R45
C3
R46
D23
U2
C4
U3
C5
U4
C6
U5
C16
J2
U6
C20
U7
SW2
C23
U8
C24
U9
C52
R135
R134
UZC4
33
40
47
R64
HEAT
R65
S
R66
E
C25
R67
R69
R71
R75
R77
R79
R83
R85
R87
R91
R93
R95
R99
R101
R103
R107
R109
R111
R112
R115
R117
R119
R120
R123
R125
R126
R127
R128
R129
R130
R133
SW3
R68
R70
R72
R73
R74
R76
R78
R80
R81
R82
R84
R86
R88
R89
R90
R92
R94
R96
R97
R98
R100
R102
R104
R105
R106
R108
R110
R113
R114
R116
R118
R121
R122
R124
R130
R132
N
C26
S O
C27
R S
TB11
C28
T
C29
S T
C30
A T 4
C31
C32
TB12
C33
T S
C34
T
A
C35
T
C36
3
C37
TB13
C38
T
C39
S T A T
C40
2
C41
C42
TB14
C43
T S
C44
T
C45
A
T 1
C46
C47
C48
C49
C50
C51
EMERGENCY
NORMAL
* UZC4 Zone Control Panel * Supply Air Sensor * Technical Bulletin TB219 * Mounting Hardware
The main UZC4 module has a Manual Reset circuit breaker with a Ground Fa ult In dica tor t hat p rote cts al l connected modules and thermostat circuitry. All modules have separate damper motor Thermal Breakers too. They protect the damper motor circuitry from shorts in the field wiring. The breakers will not protect against shorts in the HVAC system wiring.
CAUTION: When the thermal
breaker is tripped it will get quite hot. To reset the breaker: Shut off
power to the panel. Find and repair the short. Restore the 24VAC power.
TEMPERATURE: -20° to 160°F (-29° to 71°C)
HUMIDITY: 0% - 95% RH Non-Condensing.
The UZC4 allows constant operation of the Indoor Fan by Thermostat #1 only, or by each individual thermostat. When controlled by thermostat #1, All Zone dampers will respond. When controlled individually, Zones not calling for continuous fan will close.
TB10
TB15
Figure 1.
SAS SAS OAS OAS RAS RAS
C W1 W2 O Y1 Y2 R G
C W1 W2 O Y1 Y2 R G
C W1 W2 O Y1 Y2 R G
C W1 W2 O Y1 Y2 R G
ONE ZONE AUX R
CO CO
1
E
B
E
B
E
B
E
B
2
2
Page 2
UZC4 STANDARD FIRMWARE AND HARDWARE FEATURES
Indoor Fan Control During Heating
Built-In Timer Settings
Definitions are explained below
*Short Cycle Timer
*Changeover Timer
*Inter-stage Timer
*Opposite Mode Delay Timer
*Staging Timer / OAS
21
14
7
OFF
MULTISTAGE
Timer / OAS
28
35
42
OFF or 7 to 42 minutes or 7 to 42 degrees F.
Use when Timer or Outside Air Changeover is required. See Page 7
*Supply/Return Air Limit Delay Timer
2
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
A dip switch is provided to enable automatic fan operation in heat mode. Useful for straight electric heat or hydronic heat applications. NOTE: Fan mode is automatically set when Heat Pump is selected.
The panel has built-in delay timers that insure safe & reliable operation.
*Short Cycle Timer
*Changeover Timer *Inter-stage Timer
*Opposite Mode
3 minutes - Fixed. 4 minutes - Fixed.
2 minutes - Fixed.
20 minutes - Fixed.
Delay Timer
*Staging Timer OAS Setting
*Supply / Return
7 to 42 minutes or 7 to 42 ° F
3 minutes - Fixed.
Air Limit Delay Timer
When all zone demands are satisfied, the panel will not resume the same mode operation for a minimum of 3 minutes.
When a demand to Change Over has been honored. A 4 minute delay timer prevents the system from rapidly changing between Heat to Cool, or Cool to Heat mode.
2 minute time delay that occurs between thermostatic demands to stage up or down.
A 20 minute delay must expire, or all act i ve zone( s) m ust sat i sf y, bef or e t h e U ZC 4 w i ll h o n o r a t h e r m o s t a t d e m a n d t o c h a n g e o v e r t o t h e opposite mode of system operation. The delay is fixed & cannot be changed or defeated.
The STAGING TIMER sets the amount of continuous & cumulative call time in 1st stage, before second stage heat or cool is energized. Also applies to 3rd & 4th stage heat. NOTE: The potentiometer also serves as the 2nd or 3rd stage Heat,
Outside Air Changeover Setting.
The UZC4 can inhibit 2nd or 3rd stage heat based on Time or Outside Air Temperature. All staging scenarios depend upon the type of thermostat used. See page 5 & 7 for details.
NOTE: An Optional OAS Sensor is required to use the OAS feature. NOTE: Y2 Output defaults to 30 minutes, if OAS is chosen and single stage thermostats are used.
The time delay of 3 minutes must expire before the UZC4 will re­energize heat or cool mode. This occurs when the processor detects the supply or return air temperature is higher or lower than the Heat/Cool limit settings.
Cooling and Heating Limit Controls
The operational sequence of the limit controls depends upon the dip switch settings chosen on the UZC4 main module. Multistage Heat Pump sequence will differ from Conventional Gas/Electric.
43
40
37
34
COOLING LIMIT
130
120
110
1st STAGE
HEAT LIMIT
19
12
5
MULTI STAGE HEAT
DIFFERENTIAL
Example: Hi Temp. limit=130 Plus M. stg T= 40
New limit F = 170°
Timer Reset BUTTON
CPU Reset BUTTON
Emergency Heat Switch
140
26
TIMER RESET
SYSTEM RESET
NORM
46
52
150
170
33
40
47
EM
49
160
Press & Hold the SYSTEM RESET button for 5 seconds. That will reset the Main & Expansion modules on a UZC4 Zoning System.
NOTE: A three minute startup delay
occurs whenever the CPU Reset button is pushed, upon any initial power up, or when a power failure has occurred.
An On-Board Switch is provided that allows the user to set the system to the Emergency heat mode. This switch is shown in the NORMAL position.
NOTE: An Emergency terminal is also provided at every Thermostat terminal b l o c k , a l l o w i n g H e a t P um p Thermostats to be connected to every zone.
Th e Ad j ust a ble C ool i ng L i mi t potentiometer sets the supply air temperature at which the 1st & 2nd stage cooling is cycled off and the fan continues to run, allowing the coil to warm up.
Th e Adj u sta b le H e a ti n g L imi t potentiometer sets the 1st or 2nd stage heat supply air temperature, at which the heating is cycled off and the fan continues to run, allowing the heat exchanger or coil to cool down.
The Adjustable Mul tistage H eat differential potentiometer sets the 2nd and/or, 3rd, & 4th stage heat supply air temperature, at which the heating is cycled off and the fan continues to run, allowing the heat exchanger or coil to cool down. NOTE: Allows the supply air sensor to be installed in the supply air plenum, regardless of the coil/heat exchanger configuration. Allows the installer to fine tune virtually any multistage heating system!
Momentarily pressing the TIMER RESET button will clear any Active
Time Delay. This enables you to test and certify the installation faster. NOTE: Do not use sharp objects to press the button. Use your finger tip or the eraser head of a pencil.
Page 3
UZC4 ADVANCED FIRMWARE AND HARDWARE FEATURES CONTINUED
*FIRE ALARM INTERLOCK FEATURE
Building Code Compliant Support
Fire Alarm Activation Over-rides ALL functions and features
All Connected Dampers will close and the HVAC system will shut down
*Demand Based Ventilation
CO2 MONITOR FRESH AIR INTERFACE FEATURE
Building Code Compliant Support
This feature is not affected by Heat/Cool Operations
Fire Alarm Activation Over-rides this feature
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
The UZC4 includes a Fire Alarm system interlock feature.
Wire the UZC4 into your building Fire Alarm system, and achieve full HVAC system shutdown, and Closure of all Duct dampers, in the event of Fire Mode Activation.
The circuit is normally closed and must open to activate this mode. A Fail Safe dry contact is required on the Fire Alarm System.
When the Fire alarm system resets to normal, the UZC4 will also resume normal operation. Clip the on-board jumper and wire as shown on page 17.
The UZC4 includes a Carbon Dioxide and Fresh Air interface feature.
Wire the UZC4 up to a separate
&
CO2 Monitor with auxilary dry contacts. When the CO2 Monitor activates, the UZC4 will open a fresh air damper connected to it’s OA damper terminal block, and start the HVAC system fan.
The circuit is normally open and must close to activate this mode. A normally open dry contact is required on the C02 Monitor or Fresh air Timer or Other Device.
When the CO2 monitor resets to a normal CO2 level, the UZC4 will close the fresh air /auxilary damper.
Other external dry contact devices can be connected to the CO2 terminals such as a Manual Switch, Enthalpy Control, or ClockTimer. See page 16.
NO T E: Co o li ng & He at i ng operations are not affected by activation of this feature. NOTE: Activation of the Fire Alarm Interlock feature will over-ride the CO2 Monitor feature.
AUXILARY or DeHUMIDIFY INTERFACE RELAY
Enhanced Comfort Solution
Auxiliary “dry” SPDT output
This feature is affected by Heat/Cool Operations
Fire Alarm Activation Over-rides this feature
ELECTRONIC BYPASS DAMPER SUPPORT FEATURE
Enhanced Airflow Solution
Fire Alarm Activation Over-rides this feature
The UZC4 includes an Auxiliary Interface Input and SPDT action Dry Contact Output. This allows
the Installer to connect various Aux i lia r y co n trol s suc h as Humidify or DeHumidify controls. Simply connect the Controlled Device or Circuit to the “Output” dr y c on ta ct s a nd ac hi ev e integrated control without 3rd party isolating relays.
See Page 14 and 15 for example control and wiring solutions.
The Auxiliary input logic can be field selected as (DA) Direct Acting to humidify or (RA) Reverse Acting to Dehumidify.
The UZC4 activates a unique algorithm to rapidly de-humidify the home without over-cooling it. See page 14.
The UZC4 includes support for an Electronic Bypass Damper.
Wire up a EWC Model “EBD” Bypass Damper to ach ieve precise control of the HVAC system static pressure and bypass damper operations.
Wire up the Model “EBD” damper as shown on page 17.
The UZC4 defaults the Bypass Damper to the “Open” position during “IDLE” periods. It will also maintain that position for 45 seconds; at the start of any thermostat demand for Heating, Cooling, or Fan only Operation.
The 45 second time delay allows a constant or variable speed fan to start in a “Quiet Mode” and does away with noisy air duct velocities upon system startup.
A Latent cooling effect is also achieved by using this feature.
After 45 seconds the UZC4 will release control of the system static pressure to the EBD diaphragm control and a gradual increase in sy st em st at ic pr es su re i s achieved. NOTE: The UZC4 will not
resume control of the “EBD”, until the next “IDLE” period begins.
3
Page 4
UZC4 ADVANCED FIRMWARE AND HARDWARE FEATURES CONTINUED
RETURN AIR MONITORING FEATURE
Enhanced HVAC System Safety and Energy Savings Solution
Note: If this feature is “Enabled” but the “RAS” is not connected or is not detected; The “RAS” LED will blink rapidly as a warning and The UZC4 will not allow RAS operations to occur.
Note: When the Return Air sensor detects a return air temperature between the Stage Up Value and the Stage Down Value, the “RAS” LED will blink slowly as a warning. The UZC4 will also hold at the current staging until the system status changes sufficiently to allow a stage up or down.
The UZC4 includes a RETURN AIR TEMPERATURE SENSING feature.
Connect an OPTIONAL Return Air Sensor (#RAS) to the UZC4 and achieve the ability to STAGE DOWN the HVAC system if the return air temperature exceeds the return air temperature limit set points. Set the “RAS” Dipswitch #6 to the “ON” position, and choose either (0) or (+10) at the “RA LIMIT” Dipswitch # 7. Both switches are located on the Dipswitch Bank#2.
The UZC4 will now monitor the return air temperature and allow Stage up, or if necessary Stage Down the cooling or heating operation to maintain a return air temperature within the following values. As stated above, choose either (0) to accept the default return air limit values for your particular HVAC system or choose (+10) to offset the default values 10 degrees higher. Note: The (+10) offset applies to heating operations only. The default
return air temperature limit set points for cooling operations cannot be offset.
RETURN AIR LIMITS DURING HEATING CYCLE FOR HEAT PUMPS ONLY:
Default (0) set points:
If the Return Air temperature is:
80 degree F. or below, Stage Up is allowed. 105 degree F. or above, Stage Down is forced.
Default (+10) set points:
If the Return Air temperature is:
90 degree F. or below, Stage Up is allowed. 115 degree F. or above, Stage Down is forced.
RETURN AIR LIMITS DURING HEATING CYCLES FOR GAS, OIL, STRAIGHT ELECTRIC:
Default (0) set points:
If the Return Air temperature is: 80 degree F. or below, Stage Up is allowed.
115 degree F. or above, Stage Down is forced. Default (+10) set points:
If the Return Air temperature is:
90 degree F. or below, Stage Up is allowed. 125 degree F. or above, Stage Down is forced.
RETURN AIR LIMITS DURING COOLING CYCLES FOR ALL HVAC SYSTEM TYPES:
Default (0) set points:
If the Return Air temperature is:
65 degree F. or above, Stage Up is allowed. 55 degree F. or below, Stage Down is forced. Default +10 applies to heating operations only.
The Return Air Sensing Feature cannot cycle the 1st stage equipment off-line. It can only force a
4
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Stage Down when the equipment is in 2nd stage cool or 2nd, 3rd, or 4th stage heat, and the selected return air set points above have been exceeded. The Supply Air Sensing feature is the only monitor that can cycle the 1st stage equipment off-line.
A three minute delay will occur after a forced stage down. If a stage up demand is present, the UZC4 will allow the stage up to re-occur when the three minute delay has expired and the return air temperature is back to normal.
The UZC4 will automatically adapt to the “GAS,OIL,ELECTRIC” set points when a Heat Pump system stages up to Fuel or Auxiliary mode.
This powerful feature will enhance the efficiency of your Zoned HVAC system and protect the equipment from excessive bypass temperatures during low load conditions.
Page 5
UZC4 ADVANCED FIRMWARE AND HARDWARE FEATURES CONTINUED
MODULE TO MODULE FACTORY POWER WIRING
The UZC4 includes Factory Power Wiring on all expanded systems. The 24 vac power to the expansion modules is fed through the bus cable. The bus cable feeds power to all module processors & thermostats. Damper Motor
terminal blocks are isolated and powered separately. This simplifies your wiring,
reduces the chances of polarity reversal and allows more connected dampers per zone.
DIRECT DUAL FUEL COMPATIBLE FIRMWARE
The UZC4 is fully compatible with Dual Fuel Heat Pumps, and other Hybrid HVAC systems. Dual Fuel kits are not required. Select staging based on Adjustable Time Delay, an Optional Outside Air temperature Sensor, or allow the thermostats to control staging. The intelligent firmware does the rest.
* 7 TO 42 MINUTE STAGE UP TIME DELAY SETTINGS
RAPID DE-HUMIDIFY FIRMWARE
The UZC4 will perform a unique de-humidify function when a demand to de-humidify is detected at the Auxilary Input terminal. The UZC4 will energize the Emergency heat relay to activate one electric strip bank at the same time the Y1 cool is active, so long as the demand to de-humidify is detected. This
powerful feature will rapidly de-humidify your home, and tempers (reheats) the supply air to prevent over-cooling. See Page 14 for details.
CO2 DEMAND BASED VENTILATION SUPPORT
The UZC4 includes support for Demand Based Ventilation Control scenarios. Designed to help meet or exceed local building codes and ASHRAE ventilation standards. Simply connect your CO2 Monitor and a Fresh Air damper to the UZC4.
*ZONE DEMAND LIMITING FEATURE
* 7 TO 42 DEGREE F. OUTSIDE AIR CHANGEOVER
* MULTI- STAGE HEAT ADJUSTABLE LIMIT CONTROL
* ELECTRONIC BYPASS DAMPER SUPPORT
* AUXILARY MULTI-FUNCTION SUPPORT RELAY
THERMOSTATIC DEMAND STAGE UP ON ALL ZONES
The UZC4 is the first Zone Control System to allow 4 stage thermostats to be connected to all zones
* STATUS LED’s ARE INCLUDED ON ALL MODULES
*ONE ZONE MODE SETBACK CAPABILITY
* SIMPLIFIED WIRING AND SYSTEM SETUP
* FIRE ALARM INTERFACE
The UZC4 is capable of numerous staging sequences depending on the type of HVAC system being controlled, the type of thermostats connected, and the programmed staging sequence you desire.
As always you can still control a multi-stage HVAC system using inexpensive single stage thermostats and sequence the staging by on-board adjustable time delay, or by using an optional outdoor air sensor (OAS) and sequence the staging via an outdoor air set point.
You can still control a state of the art multi-stage Heat Pump using single or two stage conventional thermostats and sequence the staging by time delay or outside air set point.
You can choose to control most any multi-stage Heat Pump or Conventional HVAC system with OEM multi-stage thermostats on all zones. The UZC4 can be programmed to stage up or down based on the thermostat inputs from each zone. The UZC4 allows a level of versatility that has never before been offered by any zoning company. You can choose to install 3 or 4 stage thermostats on the largest zones, 2 stage thermostats on medium sized zones and single stage thermostats on the small zones.
To achieve staging via thermostatic demand only; Choose (TMR) Timer setting on Dipswitch #5 Bank 1 And then set the Multi-Stage Timer setting to (0) Zero. Setting the Timer to zero disables Timed Staging and the UZC4 will stage up or down only when the thermostat(s) demand it.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
5
Page 6
Selecting the Options Using the DIP Switches
***FS = Factory Settings
RECORD YOUR DIP SWITCH
SETTINGS HERE
Programming and setting up the UZC4 is very easy! Check the Switch Legend and refer to the following pages for an explanation of each dip switch function and choose your settings. Some functions may
not apply to your application. Use a pencil to fill in the square & record your settings. If the settings get
changed later on, you will have a record of the original settings. NOTE: When you choose “HP” at switch #1, Bank 1, the fan mode is automatically set for you. There is no need to move switch #8, Bank1. Leave it in the “GAS” factory setting.
RECORD YOUR DIP SWITCH
SETTINGS HERE
Bank1
Bank2
SWITCH LEGEND
HP < SYSTEM > GAS
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
1
1
2
2
3
3
4
4
5
5
FS
DF < HP > CONV FS
FS OFF < FAN PRG > ON
90s < PURGE > 180s FS OAS < STAGES > TMR FS FS OFF < 50% R > ON
FS OFF < SAS > ON FS GAS < FAN > HYDRO
HC < TSTATS > HP
FS
FS1 < CS# > 2
FS O < RV > B FS OFF < ZDL > ON
RA < AUX RLY > DA FS
6
6
7
7
8
8
FS OFF < RAS > ON FS 0 < RA LIMIT > +10
ANY < FAN CTRL > Z1 FS
Detailed explanations of each Dip Switch Function are included on the following pages. Please study and familiarize yourself with all of the functions and features, prior
to activating the Zoned HVAC system. Not all features will apply to your application.
The UZC4 comes from the factory pre-set to operate a 2 stage Heat Pump using heat pump thermostats to control the staging.
Failure to properly set all dip switches to the correct and/or desired positions will result in improper operation of the controlled HVAC System.
Please read and study the entire Technical Bulletin and if necessary, Call the EWC Technical Support Hotline when assistance is required.
Leave this Technical Bulletin with the Home or Building Owner for future reference.
CONTINUED ON NEXT PAGE...
6
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Page 7
Selecting the Options Using the DIP Switches - BANK1
HP < SYSTEM > GAS
1
Choose the type of HVAC system you want to control. Select HP, if your system is any type of heat pump. Select GAS, if your system is a any type of Gas / Oil furnace, or any straight Electric furnace or Hydronic (hot water / steam) heating system.
DF < HP > CONV
2
If you chose “HP” at switch #1, then choose the type of Heat Pump you want to control. Select DF, if your system is a Dual Fuel heat pump with Gas or Oil furnace backup heat. Select CONV, if your system is a Conventional heat pump with Electric resistance backup / supplemental heat. Also applies to Ground source / Geothermal heat pumps with Electric backup heat.
OFF < FAN PRG > ON
3
Select ON, if you want the UZC4 to force the indoor blower ON at the end of a heat/cool call to assist the zone purge cycle. Selecting OFF will allow the HVAC system to operate the indoor blower, without interference from the UZC4.
90S < PURGE > 180S
4
Select 90S or 180S, if you want the zone dampers to hold position for 90 seconds or 180 seconds at the end of any heat or cool call. This allows the HVAC system to purge the remaining hot or cold air, into the zone(s) that were calling for it.
OAS < STAGES > TMR
5
Select OAS, if you want to delay multi-stage operations based on the outside air temperature sensor. Select TIMER, if you want to
delay stage up based on the adjustable on-board timer. Both features are very useful when using single stage thermostats on all zones.
NOTE1: Y2/W2 stage up defaults to a 30 minute delay, when OAS is chosen. NOTE2: An optional Outside Air Sensor (Part#OAS) is required
to use the OAS feature. NOTE3: Thermostat demands to stage up, will always over-ride the Timer or OAS staging operations, Unless the 50% rule has been enabled, or the Return Air temperature limit has been exceeded. NOTE4: Thermostatic demands to Stage Down will be honored unless the Timer is also in use. NOTE5: Disable the Timer by setting to OFF, and the UZC4 will obey Stage up & Stage down
demands via the thermostats only!
OFF < 50% RULE > ON
6
Select OFF, if you do not want to inhibit two stage compressor cooling operations based on the total number of zones calling.
Select ON, if you want to inhibit 2nd stage cooling compressor based on the total number of zones calling. Half or more of the total number of thermostats must be calling or stage up will not occur. NOTE 1: In All Modes, the 50% rule occurs between Y1 and Y2. NOTE2: In Gas mode
the 50% rule occurs between W1 &W2. NOTE3: If Dual Fuel or OAS has been selected, the 50% rule applies to cooling only. Heating stage up will not be affected by this setting. Emergency mode is never affected by the 50% rule.
OFF < SAS > ON
7
Select OFF, if you do not want to use the Supply air sensor included with the UZC4 Zone Control system. Select ON, if you want to use the included Supply air sensor. Refer to the data sheet included with the Supply air sensor for
installation details. Refer to page 2 for details on Supply air Sensing Limit Controls and settings. Mount the Supply Air Sensor in the discharge duct and/or plenum.
GAS < FAN > HYDRONIC
8
Select GAS, if your HVAC system is a gas or oil forced air furnace. Select HYDRONIC, if your HVAC system has a hot water / steam coil, or straight electric heat with no indoor blower support. Useful when you need the indoor blower to run automatically in heat mode, just like it does in cool mode. NOTE: When you select HP on dip switch #1, the indoor fan mode is automatically set for you. If so, then leave this switch in the factory GAS setting.
CONTINUED ON NEXT PAGE...
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
7
Page 8
Selecting the Options Using the DIP Switches - BANK2
1
HC < TSTAT > HP
Select the type of thermostats you want to use. Select HC, if your thermostats are the standard Heat/Cool type. Select HP, if your thermostats are Heat Pump types. NOTE1: You cannot mix thermostat types. NOTE2: You do not need HP thermostats to control a Heat Pump. NOTE3: Thermostat demands to stage up, will always over-ride the Timer or OAS staging operations, unless the 50% rule has been enabled. NOTE4: Thermostatic demands to stage down will be honored unless the Timer is in use.
IMPORTANT NOTE: The UZC4 Zone Control System allows Heat Pump or Conventional Multi-Stage
thermostats to be wired to all Zones!
Thermostat demands to stage up, will always over-ride any programmed staging operation. The UZC4 will remain in Multi-stage mode until that terminal is de-energized. If this occurs in dual fuel mode or emergency mode, the UZC4 will stay in that mode until all Heating demands are satisfied. On the next heating cycle, the UZC4 will attempt to activate 1st stage heat unless, Emergency Mode is still active, or the outdoor temperature is low and OAS / DF has been selected. This comfort over-ride feature provides true versatility to your zoning system, and gives the homeowner comfort control capability over the system.
1 < CS# > 2
2
Choose the number of Condensing Unit Stages you want to control. Select , if your CU has a Y1 connection only. Select 2, if your CU has a Y1 & Y2 connection. NOTE1: This feature must be set correctly for proper Timed & Outdoor Air Sensor staging operations. NOTE2: Thermostat demands to stage up, will always Over-ride the Timer & OAS staging operations, unless the 50% rule has been enabled, or the Return air temperature limit has been exceeded. NOTE3: All stage up Operations depend upon the correct setting of this switch.
3
O < RV > B
Choose the type of Reversing Valve you want to control. Select O , if your heat pump reversing valve energizes in cooling and defaults to heat mode. Select B, if your reversing valve energizes in heating and defaults to cool mode. NOTE: The UZC4 will hold the “O” output or the “B” output continuously, even during idle periods, until a thermostatic demand to change modes is detected.
NOTE: Proper setting of this switch is critical. The reversing valve will not function properly if this switch is not set correctly.
1
OFF < ZDL > ON
4
Select ON and the UZC4 will limit HVAC operations based on the total number of zones calling for conditioned air.
16% or 1/6 of the total number of zones (rounded up) must be calling for the same mode of operation, or the UZC4 will not activate the HVAC system. This feature only activates at 8 or more zones. Demand Limiter feature. NOTE: Zone 1 is not affected by this feature. Zone 1 demands are always honored. ZDL example: A zone system has 20 total zones and the ZDL feature is active; At least 4 zones must be calling for the same mode of operation (Heat or Cool) or the UZC4 will not activate the HVAC system. 18zone=3, 16zone=3, 14zone=3, 12zone=2, 10zone=2, 8zone=2.
5
RA < AUX RLY > DA
Select the control signal type you need, in order to activate your preferred Auxilary Relay function. Acting) for De-Humidification Control, or Choose DA (Direct Acting) for Humidification Control, depending on the control input signal you require. Then connect your controlled device or circuit to the SPDT dry output contacts and achieve integrated control without the need for 3rd party relays or specialty relays. If this feature is not used, the switch must be in the DA position.
See Pages 14-16 for further information.
6
OFF < RAS > ON
If you connect an OPTIONAL Return Air Sensor to the UZC4, then Select ON, and Choose to use the default set points
for Return Air Temperature Limit Operations, or choose to Offset those set points by 10 degrees higher at the next Dip Switch.
Refer to the data sheet included with the Return air sensor for installation details. return air duct as close to the Blower intake as possible, or in the blower cabinet. Read page 4 for Operational details.
7
0 < RA LIMIT > +10
If you connect an OPTIONAL Return Air Sensor and switch on the “RAS” switch above; then choose “0” to accept the
default set points for Return Air Temperature Limits, or choose “+10” to Offset the default set points 10 degrees higher.
Refer to the data sheet included with the Return air sensor for installation details. page 4 for Operational details.Read
Select OFF if you do not want to utilize the Zone
Choose RA (Reverse
Mount the Return Air Sensor in the
8
ANY < FAN CTRL > Z1
Select which thermostat(s) can activate a demand for Continuous Fan Operation. Choose “ANY”, and the UZC4 will
honor any thermostat demand to activate continuous fan, and only the dampers connected to that zone will open. All others will close. Choose “Z1”, and the UZC4 will honor a demand to activate continuous fan from zone 1 only. All connected dampers on all zones will open. Demands to activate continuous fan from any other thermostat will be ignored. NOTE: Continuous Fan Operations will only occur when there are no active or pending heat or cool operations.
8
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Page 9
INSTALLATION INSTRUCTIONS and THERMOSTAT WIRING
Installation should be performed by qualified personnel only. Follow local & national electrical & mechanical codes. Use multi-conductor 18 awg solid copper conductors. Wire number to number or letter to letter on each control or device.
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24-30vac. DO NOT USE OTHER VOLTAGES! USE CAU T I ON TO AVOID E L ECTR I C S H OCK O R EQUIPMENT DAMAGE.
Mount the panel housing in a convenient location close to the Air Handler. Mounting hardware is provided. Use the knockouts provided on the panel housing as entryways into the housing. Strain relief fittings can be used if desired. Use care and do not damage the circuit board
when making wire connections. NOTE: The 24 vac power required to operate a UZC4 system must be supplied by a separate transformer. WARNING! DO NOT use the 24 vac power supply from the HVAC manufacturer’s equipment.
NOTE: Unlike previous UZC series zone control systems, the UZC4 supplies power to all connected expansion modules. This improved design simplifies the installation wiring and reduces the possibility of polarity reversal or incorrect transformer phasing. The UZC4 does allow you to isolate and power up the damper terminal block separately for greater versatility.
CONVENTIONAL 2 HEAT / 1 COOL THERMOSTAT
MODEL EWT-3707
MODEL EWT-3707
W2
O
B
W1
C
*
ANY ZONE T’STAT
C
W1/E
W2
O/B
Y1
Y2
R
G
Common wire not required if batteries are used.
*
Figure 4.
Model EWT-3707: Configured for typical 2 stage Gas or Electric heating system with 1 stage cooling.
Y1
R
G
L
E
POWER WIRING
Line
A single 24vac, 40va UL Listed transformer can power the UZC4 Main module with one damper on each zone. A total of four zones and four dampers. See page 19 for more load and transformer data.
Voltage
PROVIDE
MEANS OF
DISCONNECT
TRANSFORMER
24vac, 40 - 100va
UL LISTED
Figure 2. UZC4 Power wiring Supply
TYPICAL 1 HEAT / 1 COOL THERMOSTAT WIRING
MODEL EWT-3707
ANY ZONE T’STAT
B
C
W1/E
W2 O/B Y1 Y2 R G
Common wire not required if batteries are used.
*
Figure 3.
Model EWT-3707: Configured for 1 heat 1 cool (SS1 mode). Typical Gas, Oil or Hydronic System.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
MODEL EWT-3707
C
W1
W2
*
O
Y1
UZC4
Main Module
FA
FA
24 V 24 V
R - Hot C - Common
R
E
G
R
C
L
CONVENTIONAL 2 HEAT / 2 COOL THERMOSTAT
TOUCHSCREEN THERMOSTAT
MODEL EWT-3102
R
S1
S2
L
C
W1
W2
E
Y1
Y2
G
*
ANY ZONE T’STAT
C
W1/E
W2
O/B
Y1 Y2
R
G
Common wire not required if batteries are used.
*
Figure 5.
All of the preceding diagrams reflect conventional (N on - He a t P u m p ) t h er m os t a t s, c on t ro l l i ng conventional HVAC systems. However, the equipment being controlled does not have to be the conventional type. A heat pump system can be controlled using conventional thermostats. But you cannot control a conventional system using heat pump thermostats.
Model EWT-3102 : Configured for typical 2 stage Gas or Electric heating system with 2 stage cooling.
9
Page 10
THERMOSTAT WIRING CONTINUED
ANY ZONE T’STAT
Figure 6.
TOUCHSCREEN THERMOSTAT
MODEL EWT-3102
S1
S2
L
C
W2
E
O/B
Y1
R
Y2
G
*
**
C
W1/E
W2
O/B
Y1
Y2
R
G
Model EWT-3102: Configured for 2 heat 1 cool heat pump (HP1 mode). See thermostat instructions for further details.
Common wire not required if batteries are used.
*
Field installed jumper.
*
*
ANY ZONE T’STAT
Figure 8.
TOUCHSCREEN THERMOSTAT
MODEL EWT-3102
S2
S1
L
C
W2
E
O/B
Y1
R
Y2
G
*
**
C
W1/E
W2
O/B
Y1
Y2
R
G
Common wire not required if batteries are used.
*
Field installed jumper.
*
*
Model EWT-3102: Configured for 3 heat 2 cool heat pump (HP2 mode). See thermostat instructions for further details.
WIRELESS THERMOSTAT: RECIEVER MODULE
MODEL EWT-3900
C
ANY ZONE T’STAT
Figure 7.
B
C
W1/E
W2
O/B
Y1
Y2
R
G
Model EWT-3900: Wireless Thermostat.
O
Y2W1 W2 Y1
Configured for 2 heat 2 cool (MS2 mode). See Thermostat instructions for further details.
WIRELESS THERMOSTAT: RECIEVER MODULE
MODEL EWT-3900
C
R
G
ANY ZONE T’STAT
B
O
R
Y2W1 W2 Y1
G
C
W1/E
W2
O/B
Y1
Y2
R
G
Figure 9.
Model EWT-3900 Wireless Thermostat: Configured for 3 heat 2 cool heat pump (HP2 Mode). See thermostat instructions for further Details.
10
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Page 11
WIRING FOR RADIANT FLOOR HEAT
HEAT PUMP MODE WITH DE-HUMIDIFICATION
ANY ZONE T’STAT
Figure 10.
MODEL EWT-3611
W
RH
G
C
W1/E
W2
O/B
Y1
Y2
R
G
C
RC
Y
To Radiant floor / Baseboard heat zone valve or pump relay
Wiring a split circuit thermostat to operate a Radiant floor heating or Baseboard heating Hydronic system. The UZC4 controls the cooling only, in this type of configuration.
WIRING FOR “ONE ZONE” MODE
ZONE 1
T'STAT
Figure 12.
C
W1/E
W2
R
Carrier Bryant
THERMIDISTAT 2 Heat 1 Cool HEAT PUMP CONFIGURATION
Y1 / W2
O/W2
W / W1
C
Y / Y2
R
R
DHUM
G
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
CO2 CO2
Refer to Dehumidify Operations on page 14.
Wiring for typical 2 stage Heat,1 stage cool Heat Pump. Diagram reflects De-humidification terminal wired to the Auxilary input. For auxilary output wiring see page 14. Auxilary Relay Dip Switch #5, Bank #2, should be set to Reverse Acting. (RA)
ZONE 1
T'STAT
Figure 11.
Commercial Grade
Thermostat
C
W1/E
W2
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
CO2
CO2
Wiring for automatic activation of “One Zone” mode using a commercial grade thermostat in Zone 1. Program or wire the thermostat to Energize (close contact) the One Zone Terminal and setback the temperature when the building is
Unoccupied....When the building is Occupied, the
thermostat will de-energize (open contact) the One Zone Terminal.
ZONE THERMOSTAT #1
UNOCC / OCC
C
W2W1
RY
G
ANY ZONE T’STAT
Figure 13.
MODEL IZT-250
INTERNET THERMOSTAT
O
CB
W1 W2
Y1
Y2
RC
RH
G
C
W1/E
W2
O/B
Y1
Y2
R
G
Model IZT-250 Internet Thermostat: Configured for 2 heat 2 cool. See thermostat instructions for further details.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
11
Page 12
HVAC SYSTEM WIRING
Single Transformer Gas/Oil Systems 1 or 2 Stage Heat
OUTDOOR
CONDENSING
UNIT
Y C
Figure 14. Single transformer Gas / A/C system.
Typical gas / oil system with A/C.
A jumper wire between Rc and Rh is provided. There is no need to install a jumper.
GAS/OIL
Furnace
1or2 STAGE
G
Y2
Y1
W1
W2
C
R
UZC4
G Y2 Y1
O
B
W1 W2
E
RC RH
RC/RH LINK
Conventional 4 Stage Heat Pump with a “B” Type Reversing Valve
Typical heat pump system wiring with electric resistance backup heat. Wire up the reversing valve to either O or B, depending on your system type. Applies to air cooled or geothermal / ground source systems.
AIR HANDLER
WITH 1 0R 2 STAGE
ELECTRIC RESISTANCE
HEAT PUMP
2 STAGE
H V A C
­S Y S T E M
Y2
Y
B
X / W
C R
Diagram reflects a Heat Pump with a “B” type Reversing Valve NOT a neutral or Common terminal designated as “B”.
BACKUP HEAT
G
Y2
Y
B
W
W2
C
R
UZC4
G Y2 Y1
O
B
W1 W2
E
RC RH
RC/RH LINK
H V A C
­S Y S T E M
Two Transformer Oil/ Hydro Systems
OUTDOOR
CONDENSING
UNIT
Y C
Oil / Wood Burner
Primary Control
Boiler Control
Zone Valve
Pump Control
Terminals
Wiring diagram for a typical oil burner, hydronic zone / Air handler with A/C. Cut the Rc / Rh link on the UZC4 Panel for systems requiring isolation.
TYPICAL FAN
CENTER
TERMINAL
*W
BLOCK
W*
Y
G
C
R
*
TT
ISOLATION TERMINALS
OR WIRES
*
or
or
or
T
T
UZC4
G
H
Y2
V A
Y1
C
O
-
B
S
W1
Y
W2
S T
E
E
RC
M
RH
RC/RH LINK
*
Cut Rc/Rh Jumper
Figure 15. Two transformer Oil or Hydronic / A/C system.
* Note: Your Air Handler may include a W terminal. That
means it may have it’s own isolation circuit. If you can confirm this, simply connect the W1 terminal to the W terminal on the air handler. Do not cut the Rc / Rh jumper. Wire up your Oil Burner, Pump Control, or Hydronic Zone valve to the isolation terminals or wires provided in the air handler. (follow dashed lines)The fan is controlled via time delay relay inside the air handler, or set the UZC4 “FAN “ Dip Switch to the “HYDRO” position.
12
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Figure 16. Conventional Heat Pump System
Dual Fuel Heat Pump with “O” Type Reversing Valve
HEAT PUMP
1 STAGE
Y
O
Wout
W
C R
Hi Efficiency Heat Pump with built-in Outside Air Changeover Capability. The Heat Pump makes the decision to run the Furnace. Note that the UZC4 can still operate the furnace in Emergency Mode!
GAS OR OIL
FORCED AIR
FURNACE
BACKUP HEAT
G
Y
O
W
C
R
UZC4
G
Y2
Y1
O
B
W1 W2
E
RC RH
RC/RH LINK
H V A C
­S Y S T E M
Figure 17. Single stage heat pump and single stage furnace.
Note that a Conventional & Dual fuel heat pump could wire up more or less the same. The difference is how staged heat operates. In a Conventional system, the indoor fan & the compressor continues to run when stage up occurs. In a Dual Fuel system, the indoor fan & the compressor shuts down when stage up occurs. The UZC4 will perform these functions automatically. All you have to do is set the dip switches to the correct settings. Select DF or CONV at dip switch #2, Bank 1. Choose to activate 2nd stage heat by TIMER or by OUTSIDE AIR TEMPERATURE. (Optional Sensor Required) You can also use Multi-stage thermostats in any or all Zones. When the thermostat stage up heat demand is satisfied, the UZC4 will stage down, unless DF/OAS has been selected and the outdoor temperature is lower than the OAS changeover setting. In that case the system will continue in FUEL mode, until all heating demands are fully satisfied. Your Heat Pump may be capable of making
these decisions without the aid of the UZC4, in which case you may elect to wire your system as shown in figure 17.
Page 13
SYSTEM WIRING CONTINUED
Typical A/C Split System 2 stage heat 2 stage cool
Typical 2 stage gas or straight electric furnace with 2 stage cooling. Choose “Timer” or “Outside Air Sensor” to delay 2nd stage, or use 2 stage T-stats on all zones.
2 STAGE
OUTDOOR
CONDENSING
UNIT
Y2 Y1
C R
* “R” wire may
not be required on your Outdoor Condensing Unit
2 STAGE GAS
FURNACE
G
Y2
Y1
W1
W2
C
R
*
G
Y2
Y1
W1
W2
C
R
UZC4
G
Y2
Y1
O
B
W1 W2
E RC RH
RC/RH LINK
H V A C
­S Y S T E M
Note that you can route a Common wire back to the “System” terminal block, but it should never be connected! Use it as a TEST point while troubleshooting. It should be marked as such and remain capped off when not in use!
HVAC system with OEM Voltage Control Circuitry
Some HVAC manufacturers are designing HVAC Systems with 5 - 18 vdc control circuits. Standard 24 vac thermostats will not work on these systems. These systems can only be controlled with their own thermostat. But the SYSTEM connections on a UZC4 are all dry contacts! Virtually any HVAC low voltage control circuit can be connected and controlled. All you have to do is ask the manufacturer which numbered terminals correspond to the standard terminals.
Theoretical diagram only shown below.
OEM Geothermal or Ground Source Packaged Heat Pump. 3 stage heat & 1 stage cool with “O” type reversing valve.
UZC4
G
6 5
4 3
2
1
Y2
Y1
O
B
W1 W2
E RC RH
RC/RH LINK
H V A C
­S Y S T E M
Figure 18. Single transformer 2 Stage Heat / AC system
High Efficiency Heat Pump. 3 or 4 Stage Heat and 2 Stage Cool
High Efficiency
HEAT PUMP
2 STAGE
Y2
Y1
O
W
C
W1 Out
W2 Out
Y2 Out
R
X/L
LUXAIRE High Efficiency “Acclimate” Heat Pump System. Refer to Mfr’s data for specific equipment dip switch settings and logical program settings. Set up the UZC4 to control the staging based on “Time” with single stage Conventional Thermostats. Or you can install 3 stage Heat Pump Thermostats on all zones.
Variable Speed
FURNACE OR AIR HANDLER
WITH 1 0R 2 STAGE
BACKUP HEAT
UZC4
G
Y2
Y1
O
C
W/W1
W2
Y2/Y
R
HUM
X/L
G Y2 Y1
O
B
W1 W2
E
RC RH
RC/RH LINK
Optional Humidistat See Mfr’s Data
Figure 19. 3 or 4 Stage High Efficiency Heat Pump System
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Figure 20. OEM system with 5 - 18 vdc control circuit.
IMPORTANT NOTES:
HEAT PUMP EMERGENCY OPERATIONS:
Any Thermostat can demand Emergency Mode!
When emergency mode is activated, the UZC4 will energize the “E” output terminal and the “W1” terminal. The “W2” terminal will also energize after a 3 minute delay. There is no need to jumper the “E” terminal to the “W” terminals. The UZC4 does this to ensure that the Emergency backup system energizes, regardless of which terminal it is connected to. In fact, the design of the UZC4 encourages you to separate up to three (3) electric strip banks, preventing large in-rush currents
H V A C
­S Y S T E M
when all banks are tied together. This will also reserve at least one bank dedicated for Emergency mode and De­humidify/Reheat operations . Make sure that you have correctly selected either “Dual Fuel” or “Conventional” Heat Pump to obtain the proper staging operations for your particular system.
Warning: All of the wiring diagrams provided are general in nature and may not perfectly match your particular application. This is due to differences in the HVAC Mfr’s terminal designations and functions! Variations on these diagrams and other System or Thermostat applications are available b y contacting the EWC Technical Support Hotline, or visit our web site at www.ewccontrols.com
13
Page 14
SYSTEM WIRING CONTINUED - Specialty Applications
The Auxiliary Feature can be used to activate DeHumidify Operations on Variable or Constant Speed HVAC Systems.
The UZC4 can be set up to control DeHumidify operations on most any H e a t P u m p o r Con ven t ion al H VAC system. The UZC4 will also activate a unique De hu mi di fy C o n tr ol Algorithm when the De­humidify demand is d e t e c t e d . W h e n a separate control calls for Dehumidification, the UZC4 will activate “Y1”, “G” and the Auxiliary Relay, to signal the Air Handler to slow the fan down. The UZC4 WILL ALSO e n e r g i z e t h e ( E ) E m e r g e n c y o u t p u t terminal to REHEAT the cold discharge air and Rapidly Dehumidify the home. Energizing the “E” during this cycle prevents over-cooling the home. A common Customer complaint with the DeHumidify cycle in these HVAC systems.
NOTE1: The UZC4 will n o t a c t i v a t e dehumidify operations unless the “Y1” (cool) signal is also detected at Zone 1. NOTE2: A cooling or h e a t i n g d e m a n d detected at any other zone can cause a delay to activate or will te rm in a te th e D e­Humidify operations.
NOTE3: Dehumidify can only be achieved In (RA) Reverse acting mode.
14
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Using the UZC4’s Auxiliary Feature to control Dehumidify Operations
Variable Speed
AIR HANDLER
with 1 or 2 stage Heat
1 or 2 STAGE
HEAT PUMP
Y2
Y1
O
W
C
R
Figure 21.
Wiring for typical 4 stage Heat,2 stage cool Heat Pump. Diagram reflects De-humidification terminal wired to the Auxiliary output (NC) Normally Closed terminal. Auxiliary Relay Dip Switch #5, Bank #2, should be set to (RA) Reverse Acting when using the type of control shown below.
ZONE 1
T'STAT
C
AND
DEHUMIDIFICATION
CAPABILITY
DH
G
Y2
Y1
O
W1
W2
C
R
HUM
THERMIDISTAT 3 Heat 2 Cool HEAT PUMP CONFIGURATION
Carrier Bryant
R
UZC4
NC NO
C
G
Y2
Y1
O
B
W1 W2
E RC RH
RC/RH LINK
R
A U X R L Y
H V A C
­S Y S T E M
W1/E
W2
C
W / W1
O/W2
Y1 / W2
Y / Y2
R
G
DHUM
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
CO2
This type of control uses (RA) reverse acting logic to signal De-humidify demands.
CO2
Figure 22.
Wiring for typical 3 stage Heat,2stage cool Heat Pump. Diagram reflects De-humidification terminal wired to the Auxiliary input. Auxiliary Relay Dip Switch #5, Bank #2, should be set to (RA) Reverse Acting. Contact EWC Controls Technical support or visit our web site for additional diagrams and alternate control methods to achieve De-humidification.
Page 15
SYSTEM WIRING CONTINUED - Specialty Applications
Using the UZC4’s Auxiliary Feature to control Fan Speed
UZC4
Variable Speed
1 or
2 STAGE
CONDENSOR
Y2
Y1
C
R
FURNACE
with 1 or 2 stage Heat
DS/BK
G
Y2
Y1
O
W1
W2
C
R
HUM
NC NO
C
G
Y2
Y1
O
B
W1 W2
E RC RH
RC/RH LINK
Figure 23.
Wiring for typical 2 stage Heat,2 stage cool Gas Furnace.. Diagram reflects DS/BK terminal wired to the Auxiliary output (NC) Normally Closed terminal. Auxiliary Relay Dip Switch #5, Bank #2, should be set to (RA) Reverse Acting when using the type of control shown.
A U X R L Y
H V A C
­S Y S T E M
ZONE 1
T'STAT
C
W1/E
W2
C
2 Heat 2 Cool
Thermostat
W1
W2
Y1
Y2
R
G
The Auxiliary Feature can also be used to Control the Fan speed based on the Number of Zones calling.
The UZC4 can be set up to control the fan speed on most any variable speed air handlers or furnaces during cooling operations. The UZC4 will lower the fan speed when 25% or less of the total zones are calling for cooling. When this occurs the UZC4 will activate the Auxiliary relay output which will de-energize the DS/BK terminal on the Forced air unit resulting in the blower running at a lower speed.
NOTE 1: A jumper is required across the R terminal on zone 1 and the AUX R terminal. N O T E 2 : O t h e r conf igura tions are available. Contact Technical Support for further information.
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
JUMPER REQUIRED
CO2
CO2
Figure 24.
Wiring for typical 2 stage Heat, 2 stage cool Thermostat. Diagram reflects AUX R terminal wired with a jumper to the R terminal. Auxiliary Relay Dip Switch #5, Bank #2, should be set to (RA) Reverse Acting.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
15
Page 16
SYSTEM WIRING CONTINUED - Specialty Applications
The Auxiliary Feature can be used to control Humidify Operations on any HVAC System.
Set the Auxiliary relay Dip Switch to Direct Acting and connect a dry contact Humidity Control to the “R” and “AUX R” terminals. When the UZC4 detects a demand to Humidify, it w i l l e n e r g i z e t h e Auxiliary Output Relay. The Au xil i ary rel a y contacts are dry, so you can connect and control most any humidifier you want. These drawings show an Ultra-Zone 072000 Smart Humidistat connected to the Auxiliary Input, and an S2000/S2020 Steam Humidifier connected to the Auxiliary Output. Refer to the Technical Bulletins on the Ultra­Zone S2000/S2020 and t he 0 7 2 00 0 S m a r t Humidistat for additional details. The UZC4 humidit y control logic allows a Humidity demand to occur at any time. There is no need for a Heating demand to occur first. Bear this in mind when field wiring your system. Yo u m a y h a v e t o interlock your Humidifier to run during a heating c a l l o n l y ! S t e a m Humidifiers can run at any time and do not r e q u i r e a h e a t i n g demand to occur first.
N O T E : H u m i d i f y operations can only be achieved in (DA) Direct acting mode.
16
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Using the UZC4’s Auxiliary Feature to control Humidify Operations
S2000/S2020 STEAM HUMIDIFIER
RG1 G2 H H
UZC4
NC NO
2 STAGE
1 or
CONDENSING
UNIT
G
Y2
Y1
C
R
“R” WIRE MAY NOT
BE REQUIRED ON
YOUR CONDENSING
UNIT!
Figure 25.
Wiring for typical 2 stage Heat,2 stage cool conventional HVAC System. Diagram reflects Humidification terminal wired to the Auxiliary output (NO) Normally Open terminal. Auxiliary Relay Dip Switch #5, Bank #2, should be set to Direct Acting. (DA)
ZONE 1
T'STAT
Variable or Constant Speed
with 1 or 2 stage HEAT
1 or 2 stage COOL
C
W1/E
Y2
Y1
W1
W2
C
R
FURNACE
and
C
2 Heat 2 Cool CONFIGURATION
Y1
W1
W2
Y2
C
G
Y2
Y1
O
B
W1 W2
E RC RH
RC/RH LINK
R
G
A U X R L Y
H V A C
­S Y S T E M
W2
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
CO2
CO2
Figure 26.
Wiring for typical 2 stage Heat,2 stage cool Conventional HVAC System. Diagram reflects a Direct Acting Humidification control wired to the Auxiliary input. Dip Switch #5, Bank #2, should be set to Direct Acting. (DA) Refer to the Ultra-Zone 072000 Tech. Bulletin.
To OAS
OD OD C R H H
Ultra-Zone 072000 HUMIDISTAT
Auxiliary Relay
Page 17
SYSTEM WIRING CONTINUED - Specialty Applications
The UZC4 features a CO2 Monitoring interlock system that will activate a Fresh Air Damper and the indoor Fan on the HVAC system in response to a Separate CO2 Mon itor. Thi s po w erfu l feature allows Demand Based Ventilation of a large h o m e o r c o m m e r c i a l building, based on the daily occupancy levels. Demand
Based Ventilation saves energy, reduces over­ventilation, and optimizes air quality in the building.
Wire up the UZC4 to a separate CO2 Monitor with auxilary dry contacts as shown. Also install and wire up a fresh air damper as shown.
Set the PPM trip threshold on the CO2 Monitor per the Mfr’s. Instructions or local requirements.
Upon activation, the UZC4 will open the Fresh Air Damper and Start the Indoor Fan if it is not already running. The UZC4 will continue the ventilation process, until the CO2 Mo n it or r e s et s. O th er devices can be connected to the CO2 terminals such as a Clock Timer, Manual Switch or Enthalpy Control.
NOTE: Cooling & Heating operations are not affected by activation of this feature.
NOTE: Activation of the Fire Alarm Interlock Feature will over-ride (shutdown) the fresh air ventilation process.
Using the UZC4’s CO2 Feature to satisfy Building Fresh Air Ventilation Codes
EWC Controls Spring Return Motor Actuator
MA-ESR
NC NO C M M
This Damper Actuator is wired to Power OPEN and Spring CLOSE
UZC4
M6 M4 M2 M1
M6 M4 M2 M1
NC
NO
C
O A
D M P R
E B D
A U X R L Y
Power OPEN & Power CLOSE
Figure 27.
This diagram reflects the UZC4 OA DMPR Output terminals wired to an UltraZone Spring Closed type damper. When the UZC4 detects a Ventilation Demand, it will energize the damper open and force the Indoor Fan to run. The UZC4 will stay in this mode until the CO2 Monitor detects an acceptable CO2 level in the building.
ZONE 1
T'STAT
Figure 28.
This diagram reflects the UZC4 CO2 terminals wired to the (NO) normally open contacts of a third party device. The circuit is normally open and the contacts must close to activate this feature. This feature operates regardless of all other functions except the FIRE Mode interlock.
dampers can also be used.
Commercial Grade
C
W1/E
W2
O/B
Y1
Y2
R
G
ONE ZONE
AUX R
CO2 CO2
ZONE THERMOSTAT #1
C
Thermostat
RY
W2W1
G
CO2 Monitor
C NC NO
UNOCC / OCC
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
17
Page 18
SYSTEM WIRING CONTINUED - Specialty Applications
The UZC4 has a “FIRE” interlock feature that allows the UZC4 to satisfy HVAC Fire Co de i n Re si de nt ia l & C o m m e r c i a l b u i l d i n g s . Coordinate with the Fire S y s te m s Co n t r ac t o r t o interlock the UZC4 into the building Fire Alarm system as shown and cut the Jumper 1. When properly interlocked to the buildings Fire A larm system, the UZC4 becomes an integral part of the Fire Safety System. If the Fire Alarm system activates, the UZC4 will shutdown the controlled HVAC system and force all connected dampers to t h e c l o s e d p o s i t io n s , effectively isolating the duct work and the Fan system. This action will reduce the spread of smoke advancing through the building assisted by Fan and Duct systems that are not interlocked with a Fire Alarm system, or equipped with the capability to do so.
Using the UZC4’s “FIRE Interlock” Feature to satisfy Building Fire Codes
UZC4
FIRE ALARM SYSTEM
CUT
JMP1
FA
NC C NO
To Line Voltage Provide over current protection
Separate 24vac
Figure 29.
Transformer
This diagram reflects the UZC4 Fire Alarm Output terminals wired to a FIRE ALARM System with a Fail Safe, Normally Open Dry Contact. The circuit is normally closed and must OPEN to activate the UZC4 FIRE MODE. Be sure to cut the Jumper 1 resistor when you interlock the UZC4 to the Fire Alarm System. When the UZC4 activates Fire Mode, the HVAC System will shutdown and all connected dampers will close to Isolate & Compartmentalize the HVAC Duct System. The Fire Alarm System must reset to NORMAL before the UZC4 will allow HVAC Operations to resume.
FA
24V 24V
RESET
MXR MXC
M6 M4 M2 M1
R C
CB1
The UZC4 has a set of dedicated terminals to power up and control an (EBD) Electronic Bypass Damper. The UZC4 will assume control of the EBD and force it to the OPEN position during the Idle periods, Short cycle delays or Changeover delays. It will also maintain that open position for 45 seconds at the start of any th er mo st at d em an d fo r Heating, Cooling, or Fan only operation. After 45 seconds the UZC4 will release control of the EBD, resulting in a smooth gradual increase in static pressure. The 45 second st ar t u p d el ay al lo ws a Constant speed fan to start in a “Quiet Mode” eliminating air noise upon system startup. It also eliminates hunting on variable speed systems and it enhances the latent cooling capacity of any HVAC system.
18
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Using the UZC4’s “ON BOARD BYPASS DAMPER SUPPORT”
“EBD” Motor
6
4
1
Pressure Control Wiring Compartment
RED
GREEN
WHITE “COMMON” WIRE
NC
C
NO
WIRE
NUT
UZC4
M6 M4 M2 M1
M6 M4 M2 M1
NC
NO
C
O A
D M P R
E B D
A U X R L Y
Field Wiring =
Figure 30.
Wire up the “EBD” straight to the UZC4 to obtain integrated Bypass Damper operational support via the UZC4’s bypass firmware. The UZC4 defaults the bypass damper open during idle periods and releases control to the EBD 45 seconds after the Fan starts. This action results in a smooth, quiet startup and gradual increase in static pressure.
Factory Wiring =
Page 19
DAMPER WIRING AND CONFIGURATION
Note: All zone dampers default to the "OPEN" position after a purge delay has occurred. Dampers also default “OPEN” during changeover & short cycle delays, and when all zone demands are satisfied, and no signals are detected from the thermostats.
REFERENCE THESE DIAGRAMS PRIOR TO INSTALLATION AND POWER WIRING. DOING SO WILL SAVE TIME AND LABOR ON THE JOB SITE.
ZONE MODULE DAMPER MOTOR TERMINAL BLOCK DESIGNATION & FUNCTION
Terminal M6 Terminal M4 Terminal M2 Terminal M1
24vac to Close a damper(s)
24vac to Open a damper(s)
Constant 24vac HOT
Common 24vac
M6 M4 M2
M1
Z O N E
2 Wire Spring Return Motor Wiring
EWC Controls Spring Return Motor Wiring
MA-ESR
Either one Not both
NC NO C M M
Auxilary SPDT End Switch Dry Contacts Rated for 24vac only
A Spring Open Damper is wired to M1 & M6 A Spring Close Damper is wired to M1 & M4
Figure 34.
Multiple MA-ND & MA-URD Damper Wiring on a Single Zone
.
{
M6 M4 M2 M1
Z O N E
.
Figure 31.
All Models MA-ND & MA-URD Damper Wiring
6 4 1
Patented Optical Damper Motor Actuators
Figure 32.
M6 M4 M2 M1
Z O N E
All Models SMDL & BMDL Damper Wiring
4 2 1
Patented Optical Damper Motor Actuators
Figure 33.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
M6 M4 M2 M1
Z O N E
6 4 1
M6 M4 M2 M1
Z O N E
6 4 1
Multiple dampers
wired to operate
6 4
together on a single
zone
1
Figure 35.
On all these dampers and most older style dampers, including competitor’s dampers, always wire up number to number. Contact EWC Controls Technical Support when you are on the job site for assistance with damper wiring. NOTE: Some older style dampers cannot be wired in parallel. Do not overload your transformer!
19
Page 20
DAMPER WIRING, DAMPER TESTING AND POWER SUPPLY SOLUTIONS
Unlike previous models, the UZC4 series allows “Damper Motor Power Isolation” on the Main and Expansion modules. The Main Module’s motor blocks can be isolated only if necessary, but the Expansion module motor blocks must be powered by a separate transformer. This advanced design provides automatic 2.5amp over-current protection for each Expansion module motor block and allows a maximum 60va transformer to be connected. This means that you can directly connect a theoretical maximum of 12 Genuine ND/URD dampers to a single 2 zone expansion module. Now you no longer have to isolate & power up multiple dampers using field installed relays. The Expansion modules provide the isolation for you. See the diagram below for typical wiring solutions for dampers.
Typical damper power wiring for a ZXM2 Expansion Module.
A single damper on the first expansion zone
and three dampers on the next. Your
actual number of dampers per zone may vary.
C
6 4 1
H
Separate 24 vac Transformer 60va MAX
L2
To Line Voltage Provide over current protection
L1
ZXM2 MODULE
MXR
6 4 1
THERMAL CIRCUIT BREAKER
6 4 1
MXC
D M P R
F1
M6 M4 M2
M1
D
6 4 1
Figure 36.
Genuine ND and URD dampers wired in series or parallel configuration. NOTE: Some
older style dampers and competitor’s dampers cannot be paralleled and must be
isolated or wired in tandem. Contact EWC Controls Technical Support for assistance.
M P R
M6 M4 M2
M1
UZC4 Recommended Power Solutions
ND / URD’s @ 3.5 - 5 va per damper
4
40va
6
40va
8
50va
Number of Zones
Non-inherently current limiting transformers must have field provided over-current protection on the secondary 24 vac output. The table values provided pertain to genuine ULTRAZONE Dampers and Competitors typical 24 vac Spring loaded dampers. Included in these VA load ratings are the correct number of thermostats, the UZC4 Zone System, and a 5% field factor. Spring loaded dampers draw higher currents & require more power.
Number of Dampers Directly Connected to Main Module
1
-
4
10 12
14
ones
Z
1-
50va 60va
60va
4
16 18 20
ones
Z
75va
75va 75va
1-
4
Use class 2 UL
Listed 1585
inherently
current limiting
transformers
only!
TE S T I NG D AM P E R MOTORS
ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should
Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close
RDN / SMDL / BMDL Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminals 2 and 4. Damper should Open. Remove 24vac hot from terminal 4. Damper should Close.
SR / ESR Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Close. Remove 24 vac hot. Damper should Open.
SR / ESR Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals. Damper should Open. Remove 24vac hot. Damper should Close.
20
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Spring Types @ 8 - 10 va per damper
4
40va
6
50va
8
50va
Number of Zones
Number of Dampers Directly Connected to Main Module
Zone
s
1-
60va
60va 75va
4
16 18 20
ones
Z
75va
100va
100va
1- 4
1-
4
10
12
14
Page 21
UZC4 FEATURES AT A GLANCE
Fire Alarm Interlock Terminals and Cuttable Link
Polarized Power Input Terminals
Resettable Circuit Breaker with LED fault indicator
4.0 amp
ISOLATING DAMPER POWER TERMINAL BLOCK, BREAKER & CUTTABLE LINK
Rugged Damper Motor Terminal Blocks
Outside Air Damper Terminal Block
Electronic Bypass Damper Terminal Block
Multi Function Auxilary Terminal Block
Isolated HVAC System Terminal Block
On-Board System Rc/Rh Link
FA
FA 24V 24V
RESET
MXR MXC
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
M6 M4 M2 M1
NC NO
C
G
Y2
Y1
O
B
W1
W2
E
RC
RH
RC LINK
W
E
Rugged 10 pin Expansion Header
Protective header cap not shown for clarity
J1
HVAC ZONE CONTROL SYSTEM
JMP1
TB1
R C
TB2
TB3
CB1
F1
K1
Z
O
4
N
E
K2
Z
O
3
N
E
TB4
K3 K4
Z
O
2
N
E
TB5
K5
Z
O
1
N
E
TB6
O A
D M
P
R
TB7
K7
E
B
K8
D
TB8
A U X
K9
R
L
Y
K10 K11
TB9
H
V A C
S
K12 K13
Y S T E
M
JMP3
RH
K14
CONTROLS INC. Englishtown, NJ
C
33
40
47
R65
R66
R68
R70
R72
R73
R74
R76
R78
R80
R81
R82
R84
R86
R88
R89
R90
R92
R94
R96
R97
R98
R100
R102
R104
R105
R106
R108
R110
R112
R113
R114
R116
R118
R120
R121
R122
R124
R126
R128
R130
R132
SW3
Easy Setup 16 Switch Bank
UZC4
14
D
R64
S E
C25
N S
C26
O
C27
R S
TB11
C28
T
C29
S T
C30
A T 4
C31
C32
TB12
C33
T S
C34
T
A
C35
T
C36
3
C37
TB13
C38
T
C39
S T A T
C40
2
C41
C42
TB14
C43
T S
C44
T
C45
A
T 1
C46
C47
C48
C49
C50
C51
EMERGENCY
TB10
TB15
SAS SAS OAS OAS RAS RAS
C W1 W2 O Y1 Y2 R G
17 18
C W1 W2 O Y1 Y2 R G
C W1 W2 O Y1 Y2 R G
C W1 W2 O Y1 Y2 R G
ONE
ZONE
AUX R
CO CO
E
B
E
B
E
B
E
B
2
2
Supply, Outside, & Return Air Sensor Terminal Blocks
Rugged & Versatile Thermostat Terminal Blocks
Multi Functional Zone 1 Thermostat Terminal Block
User Friendly Adjustable Multi-function Potentiometers
21
14
7
OFF
TIMER
C1
D1
C2
D2
28
STAGING
OAS
R1
C54
D24
LED19
GROUND FAULT
35
42
R52
43
40
37
34
R19
COOLING
LIMIT
R2
C53
R20
46
49
52
R21
SWITCH LEGEND
JMP2
HP
SYSTEM
>
HP
DF
< >
D3
OFF
<
90
s
<
OAS
<
OFF
<
OFF
<
GAS
<
HC
1
CS#
<
RV
O
<
OFF RA
<
OFF
<
0
RA LMT
<
ANY
<
STATUS
OAS
SAS
R10
D9
R11
D10
R12
D11
R5
D4
R6
D5
R7
D6
R8
D7
R9
D8
RAS
ZONE
R13
ZONE
D12
ZONE ZONE
OA DMPR
R14
BYPASS
D13
AUX RELAY
FAN
COMPRESSOR2
R15
COMPRESSOR1
D14
REV W1 HEAT
W2 HEAT
EMERGENCY
R16
D15
R17
D16
R18
>
CONV
FAN PRG
PURGE
>
STAGES
R
%
50
>
ON
SAS
>
HYDRO
FAN
>
TSTAT
>
>
2
>
B
>
ZDL
>
<
AUX RLY
RAS
ON
>
>
FAN CTRL
R48
C17
Y1
R50
SW1
TIMER RESET
LIMIT LIMIT
LIMIT
4
OPEN
3
OPEN
2
OPEN
1
OPEN
DMPR
VALVE ‘O’
GAS
ON
>
180
TMR
>
ON
HP
ON
DA
>
+10
>
U14
U19
OPEN
R52
R53
R54
R55
R63
s
Z
1
C8
R47
C10C9C11
U1
C21
120
110
C18
130
U15
C12
U18
HEATING
R22
C13
R58
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED11
LED12
LED13
LED14
LED15
LED16
LED17
LED18
140
1ST
BANK1
BANK2
C14
R51
STAGE
R3
C7
C15
150
160
170
LIMIT
D17 D18 D19 D20 D21 D22
R29 R30 R31 R32 R33 R34 R35
D23
R36
R37 R38 R39 R40 R41 R42 R43 R44
J2
R49
C19
SW2
C22
CPU
RESET
U17
Z1
R56
R57
R60
R61
R50
R45
R46
C3
12
MULTI
C52
R134
19
5
26
STAGE
DIFFERENTIAL
R4
R67
R23 R24
R69
R25 R26 R27
R71
R28
R75
R77
R79
U2
C4
R83
U3
R85
C5
U4
R87
C6
U5
R91
C16
R93
U6
R95
C20
U7
R99
C23
U8
R101
R103
C24
U9
R107
R109
R111
R115
R117
R119
R123
R125
R127
R129
R135
R130
R133
HEAT
NORMAL
Figure 37.
Heavy duty 10 amp contact rated relays
Bright System Status LED’s
On-Board Emergency Switch
21
Page 22
UZC4 LED FUNCTION AND DESCRIPTION
GREEN
RED
RED
RED
GREEN
GREEN
GREEN
GREEN
GREEN
GREEN
ORANGE
UZC4 LED’s
POWER
OAS
SAS
RAS
The SAS LIMIT LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP LIMIT. LED will blink rapidly to indicate a malfunctioning Supply Air Sensor.
The RAS LIMIT LED illuminates solid to indicate that the Return Temperature has exceeded the chosen set point. LED will blink rapidly to indicate a malfunctioning Return Air Sensor.
ZONE 4 OPEN
ZONE 3 OPEN
ZONE 2 OPEN
ZONE 1 OPEN
OA DMPR OPEN
BYPASS DMPR
AUX RELAY
The UZC4 is equipped with 18 LED’s which indicate system operation and status. Familiarize
yourself with the LED’s definitions, in order to quickly determine the system status and mode of
operation.
The POWER LED pulses as a steady heart beat to indicate proper Microprocessor operation.
The OAS LIMIT LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point. LED will blink rapidly to indicate a malfunctioning Outdoor Air Sensor.
ZONE 4 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
ZONE 3 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
ZONE 2 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
ZONE 1 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
The OA DMPR OPEN LED will illuminate solid to indicate that the Outside Air damper is energized open in response to the CO2 detector or other device to provide demand based ventilation.
The BYPASS DMPR LED will illuminate solid to indicate that the Bypass damper(s) is being forced to the Open position. Occurs during idle, short cycle and changeover periods.
The AUX RELAY LED will illuminate solid to indicate that the Auxilary relay is being energized in response to a demand, to start a function such as Humidify or De-humidify.
GREEN
YELLOW
YELLOW
ORANGE
RED
RED
RED
RED
FAN
The FAN LED will illuminate solid to indicate a demand for fan operation, during COOLING, HEATING, PURGE, or CONTINUOUS FAN operations.
COMPRESSOR 2
COMPRESSOR 1
REV VALVE ’O’
W1 HEAT
W2 HEAT
EMERGENCY
GROUND FAULT
The REV VALVE ‘O’ LED will illuminate solid to indicate that the reversing valve on a heat pump system is being energized to the COOL position. The LED will be out during heating mode on a heat pump.
The W1 LED illuminates solid to indicate 1st stage of HEATING is energized in a conventional HVAC system. Or the W1 LED illuminates solid to indicate the 1st stage of Auxiliary or Backup heat is energized in a heat pump system. (3rd stage heat) Also illuminates during Emergency mode.
The W2 LED illuminates solid to indicate 2nd stage of HEATING is energized in a conventional HVAC system. Or the W2 LED illuminates solid to indicate the 2nd stage of Auxiliary or Backup heat is energized in a heat pump system. (4th stage heat) Also illuminates during Emergency mode.
The EMERGENCY LED illuminates solid to indicate all stages of Auxiliary, Backup, and Standby Heat have been energized and Compressor 1 and 2 have been locked out. This is done in response to a demand from any Heat Pump thermostat connected to any zone. It can also be activated via the On-board Emergency switch. When Emergency mode is activated, the W1 & W2 LED’s will also illuminate.
The GROUND FAULT LED illuminates when the Circuit Breaker Trips due to an electrical short in the thermostat field wiring or possibly in the main module damper field wiring. The electrical short must be located and repaired before the circuit breaker can be reset to normal.
The COMPRESSOR 2 LED illuminates solid to indicate the 2nd stage compressor is energized.
The COMPRESSOR 1 LED illuminates solid to indicate the 1st stage compressor is energized.
22
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Page 23
ZXM2 FEATURES AT A GLANCE
POLARIZED ISOLATING DAMPER POWER TERMINAL BLOCK &
2.5 amp BREAKER
Rugged Damper Motor Terminal Blocks with ZONE ID blocks
Heavy duty 10 amp contact rated relays
ZXM2
MXR
MXC
D
M6
M
M4
P
M2
R
6
D
M6
M
M4
P R
M2
5
M1
TB1
TB2
TB3
R1
R3
R5
F1
K1
R2
R4
J1
Z1
R9
R10
R7
C3
R8
U1
SW1
CTS 206-4
D4
C8
O
N
12 34
0
A
1
>
>
0
A
2
>
>
0
A
4
>
>
8
0
A
>
>
LED1
C2
Y1
D2
R12
R13 R14 R15
R6
C1
R16
C4
U2
C9
C5
U3
R24
C6
U4
C12
C7
U5
R32
D5
C15
R17
R25
R33
R18
C10
R26
C13
R34
C16
R19
R27
R35
R20
C11
R28
C14
R36
C17
R21
R29
R37
R22
R30
R38
R23
R31
TB5
R39
STATUS
D3
K2
D1
R11
U6
6
DMPR
5
J2
LED2
LED3
R40
C18
R41
R42
C19
R43
R44
C20
R45
R46
R47
TB4
D6
C
E
W1 W2 O Y1 Y2 R G
D7
D8
B
6
T S T
A
T
Rugged & Versatile Thermostat Terminal Blocks
C
E
W1 W2 O Y1 Y2 R G
D9
B
5
T S T A T
FIELD ZONE ID Blocks
Rugged 10 pin Expansion Header
Bus Cable not shown for clarity
4 Switch ZONE ADDRESS Bank
Bright STATUS LED and DAMPER LED’S with ZONE ID blocks
The ZXM2 Expansion Module for the UZC4 series is pictured above. A total of eight (8) ZXM2’s can be connected to the UZC4 to create a 20 ZONE system! The modules are housed and linked together via a factory supplied 10 conductor BUS CABLE and a unique Expansion Header Card. The
UZC4 expands by connecting factory assembled Expansion Systems such as the ZXM2A, ZXM4A and ZXM6A that are pre-wired and configured for you at the factory. The UZC4 connects to these housed
expansion assemblies via a flexible 20” long bus cable. Each Expansion module has a set of address switches that must be set properly to allow the UZC4 to recognize each expansion module in the correct order. Note the
“STATUS” LED provided on every Expansion Module to indicate active micro-processor operation. There are also two “DAMPER” LED’s provided to indicate which damper(s) are energized open or closed. Next to each Damper and Thermostat terminal block is a blank
white square, where the “Zone Number” can be written to easily identify it as a new expanded zone. These blocks will be filled in for you at the factory when a UZC 6 zone, 8 zone, 10 zone or higher has been ordered. The ZXM2 address switches will also be factory set for you. Note the same multi-input thermostat terminals are supplied on the ZXM2 as are supplied on the UZC4 Main Module. Most Important of all is to note the MXR & MXC
Damper Motor Power Input Block. The ZXM2 Expansion Module is powered via the Bus Cable from the UZC4, but the power for the
dampers must be provided by a separate transformer and is isolated from the module. This allows great freedom to connect as many dampers
as the 2.5 amp thermal breaker can handle. See page 19 for damper motor power supply details. Make sure to read the ZXM2 Technical Bulletin for
the proper cabling scenarios and zone address settings for your system or refer to the chart on the right.
All Expansion module Dip switch banks must be set correctly for proper zone address identification. The 1st expansion module would be zones 5 & 6. The 2nd expansion module would be zones 7 & 8. The 3rd expansion module would be zones 9 & 10. And so on up the line for a total of 20 zones.
The switches are set for you at the factory unless you are expanding the system in the field. It is a good idea to check them anyway.
Expansion Panel No.
8
7
6
5
4
3
2
1
Dip Switch Settings
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
N
CTS 206-4
O
12 3 4
O
12 3 4
O
12 3 4
O
12 3 4
O
12 3 4
O
12 3 4
O
12 3 4
O
12 3 4
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
23
Page 24
T R O U B L E S H O O T I N G
SYMPTOM
LED’S are responding properly but
HVAC system is malfunctioning.
LED’s are not responding properly
and HVAC system is malfunctioning.
LED’s illuminate and HVAC system
functions normally but dampers do
not respond.
LED’s do not illuminate and HVAC
system does not respond.
DETECTING 24vac SHORTS
HVAC system not responding and
UZC4 LED’s are Off.
Dampers not responding and THE
UZC4 LED’s are Off or On.
ISOLATING 24vac SHORTS
F1 circuit breaker protects the UZC4 and all connected modules. Reacts to a short in the damper motor or thermostat component and field wiring.
SOLUTIONS
Check HVAC system wiring for proper connections. Check HVAC system wiring for shorts/miswiring. Check HVAC System. Check HVAC System technical documentation and Mfr’s Technical Support.
Check HVAC system wiring for shorts/miswiring. Check HVAC system wiring for proper connections. Check HVAC thermostat for proper connections. Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
Check damper motor wiring for proper connections. Check damper motor 24vac transformer voltage/fuse/UZC4 circuit breaker. Check damper motor wiring for shorts/miswiring. Refer to Technical Bulletin for correct Setup/Wiring.
REFER TO THE DAMPER MOTOR TESTING PAGE 8
Check HVAC/UZC4 system transformer supply voltage. Check HVAC/UZC4 system 24vac transformer voltage/fuse/UZC4 circuit breaker. Check the Fire Alarm system. The UZC4 will not operate if the fire alarm is active and the interlock is used. 24vac can be read across an open FA circuit.
CHECK YOUR WIRING
SYMPTOMS: Modules, Motors or both will not function
If 24vac short has occurred, 24vac will be present at the UZC4 Module Input terminals R & C; but 24vac will not be present at the Thermostat R&C terminals. The Ground Fault LED is illuminated!
SOLUTIONS: Remove 24vac power from UZC4 and reset the manual circuit breaker or allow
the thermal breaker to cool off. Find and repair short(s) in damper and/or thermostat field wiring. Restore 24 vac power.
Disconnect the wire(s) from the ‘R’ terminals on the UZC4 thermostat terminal blocks , and the “M2/M4/M6’’ terminals on the UZC4 damper motor terminal blocks. Restore power. If the short is no longer present, Ohm out the thermostat and damper field wiring for shorts/misconnections. Replace or repair wires as necessary. Restore power. Module(s) will resume operation.
TE STI NG C ONV EN TIO NA L TH ERM OS TATS
During a demand for heating, the thermostat should apply a 24vac hot signal to the W1 and or W2 terminals.
During a demand for cooling, the thermostat should apply a 24vac hot signal to the Y1, Y2 and G terminals.
During a continuous fan demand, the thermostat should apply a 24vac hot signal to the G terminal.
Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires separation of these circuits.
Use the (C) Common terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats.
You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is connected there.
TECHNICAL SUPPORT
EWC Controls provides superior toll free Troubleshooting Support for the UZC4 when you are on the job site!
Call 1-800-446-3110 Monday - Friday 8am to 5pm East Coast Time. Otherwise call 1-732-446-3110 for information on the UZC4 and other ULTRA-ZONE products.
When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy.
24
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- [email protected]
Loading...