Everwarm EWPO2430PV, EWPO2430NV Installation And Operation Instructions Manual

INSTALLATION AND OPERATION INSTRUCTIONS
PFS
US
P126345-01
UNVENTED (VENT-FREE) GAS LOG HEATER
REMOTE CONTROL READY BURNER SYSTEM
MODELS
EWPO2430NV AND EWPO2430PV,
FOR USE WITH:
P/N 126345-01 Rev D 11/2016
®
EWPO18R, EWPO24R, EWPO30R AND
EWLCT18R, EWLCT24R, EWLCT30R LOG SETS
REPORT NO. F09-129
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Appliances
This is an un-vented gas-fired appliance. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
WARNING:
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department. — Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
Thank you for your purchase. We appreciate your business!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety information.
Following these safety, care, and operation instructions will help ensure many years of dependable and enjoyable service from your appliance.
Please read and understand these instructions before installing or operating.
SAFETY
TABLE OF CONTENTS
Safety ............................................................................................. 2
Product Identification ..................................................................... 4
Optional Remote Control Accessories ............................................ 4
Local Codes ................................................................................... 4
Commonwealth of Massachusetts Requirements........................... 4
Unpacking ...................................................................................... 4
Product Features ............................................................................ 4
Air for Combustion and Ventilation ................................................ 5
Installation ..................................................................................... 7
Operation .................................................................................... 17
Inspecting Burners ....................................................................... 19
Cleaning and Maintenance ........................................................... 19
Troubleshooting ........................................................................... 21
Specifications ............................................................................... 24
Service Hints ................................................................................ 24
Technical Service ......................................................................... 24
Replacement Parts ....................................................................... 24
Wiring Diagram ............................................................................ 25
Parts ............................................................................................ 26
Accessories .................................................................................. 30
Warranty ...................................................................................... 31
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assis­tance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory­built fireplace or in a listed ventless firebox enclo­sure. It is design-certified for these installations in accordance with ANSI Z21.11.2. Exception: Do not install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale,
from the manufacturer
WARNING: This product contains and/or generates chemicals known to the state of California to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide poi-
soning resemble the flu, with headaches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
2
cuiheat.com 126345-01D
SAFETY Continued
WARNING: Any change to this heater or its controls
can be dangerous.
WARNING: Do not use a blower insert, heat ex­changer insert or other accessory not approved for use with this heater.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when run­ning heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shutdown. Allow surface to cool before touching.
Carefully supervise young children when they are in the room with heater. When using the hand-held remote accessory, keep selector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before running heater.
Keep the appliance area clear and free from combus­tible materials, gasoline and other flammable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in your
building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
4. This heater shall not be installed in a bedroom or bathroom, un­less installed as a vented appliance. See Installing Damper Clamp Accessory for Vented Operation, Page 9. This gas log set may not be installed as a vented appliance in a bedroom or bathroom in the Commonwealth of Massachusetts.
5. Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and distribute soot within the house. Inspect chimney flue for damage. If damaged, repair flue and firebox before operating heater.
6. Do not burn solid-fuel in a masonry or UL127 factory-built fire­place in which a vent-free room heater is installed.
7. If fireplace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside fireplace will cause glass to burst. Make sure there are no obstructions across openings of fireplace.
8. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, Page 20.
9. Before using furniture polish, wax, carpet cleaner or similar prod­ucts, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation, Page 5. If heater keeps shutting off, see Troubleshooting, Page 22.
11. Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been exposed to or under water. Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped (dime-sized or larger).
15. Turn heater off and let cool before servicing, installing or repairing. If optional remote control is used, make sure the selector switch is in the OFF position. Only a qualified service person should install, service or repair heater.
cuiheat.com126345-01D
3
SAFETY Continued
COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS
16. If optional remote control is used, make sure the selector switch is in the OFF position when you are away from home for long periods of time.
17. Operating heater above elevations of 4,500 feet may cause pilot outage.
18. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
19. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Six Piece Log Set
(7 pc. for 30" models)
Piezo Igniter
Base Assembly
Flame Adjustment Knob
Figure 1 - Product Identification
Control Knob
OPTIONAL REMOTE CONTROL ACCESSORIES
There are four optional controls that can be purchased separately for:
• wall switch
• wall thermostat
• hand-held ON/OFF remote
• hand-held thermostat remote
See Accessories, Page 31. The wall thermostat or thermostat remote may not be used where
vented decorative listing is required.
These appliances are approved for installation in the US state of Massachusetts if the following additional requirements are met:
Un-vented Room Heaters shall be installed in accordance with 527 CMR 30.
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.
The individual manual shut-off must be a T-handle type valve.
Un-vented appliances may NOT be installed in bedrooms or bathrooms.
A working smoke detector must be installed in the area where vent-free appliances are installed.
Seller of un-vented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
UNPACKING
CAUTION: Do not remove data plates from grate assembly. Data plates contain important warranty and safety information.
1. Remove logs and heater base assembly from cartons. NOTE: Do not pick up heater base assembly by burners. This could
damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied to logs and heater for shipment.
3. Check appliance for any shipping damage. If appliance is damaged, promptly inform dealer where you purchased the appliance.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realis­tic flames. This heater is designed for vent-free operation with flue damper closed. It has been tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters. This heater may also be oper­ated as a vented decorative (ANSI Z21.60) product by opening the flue damper.
LOCAL CODES
Install and use appliance with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
25 West 43rd Street, 4th floor
New York, NY 10036
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02169-7471
4
cuiheat.com 126345-01D
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent­free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo Igniter. This system requires no matches, batteries or other sources to light heater.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes. Read the following instructions to ensure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materi­als, increased insulation and new construction methods help reduce heat loss in homes. Homeowners apply weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, homeowners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, some fireplaces, clothes dryers and some fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will ensure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on Pages 5 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where: a. walls and ceilings exposed to the outside atmosphere have a
continuous water vapor retarder with a rating of one perm (6 x
-11
10
kg per pa-sec-m2) or less with openings gasketed or sealed
and
b. weather stripping has been added on openable windows and
doors and
c. caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, be­tween wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.
If your home does not meet all three criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA54 allows two methods for determining whether the space in which the heater is being in­stalled is confined or unconfined space. The standard method defines
a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appli­ances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space. Where the air infiltration rate of a structure is known, the Known Air Infiltration Rate Method may be used. Follow The National Fuel Gas Code, ANSI Z223.1/NFPA 54 to use this method to determine if the space is confined or unconfined.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space Using the Standard Method
Use this work sheet to determine if you have a confined or uncon­fined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =__________cu. ft. (volume of space) Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/ Hr the space can support.
_______ (volume of space) x 20 = (Maximum Btu/Hr the space
can support)
Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace ________Btu/Hr Gas water heater* ________Btu/Hr Gas furnace ________Btu/Hr Vented gas heater ________Btu/Hr Gas fireplace logs ________Btu/Hr Other gas appliances* + ____Btu/Hr Total = _______Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws
combustion air from the outdoors and vents to the outdoors.
Example: Gas water heater 40,000 Btu/Hr Vent-free fireplace + 33,000 Btu/Hr Total = 73,000 Btu/Hr
cuiheat.com126345-01D
5
AIR FOR COMBUSTION AND VENTILATION Continued
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Outlet Air
Ventilated Attic
Outlet A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_____ Btu/Hr (maximum the space can support) _____ Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used) The space in the above example is a confined space because the actual
Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
B. Vent room directly to the outdoors. See Ventilation Air From
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no ad­ditional fresh air ventilation.
Btu/Hr (actual amount of Btu/Hr used)
extra space provides an unconfined space, remove door to adjoin­ing room or add ventilation grills between rooms. See Ventilation
Air From Inside Building.
Outdoors.
unconfined.
Figure 2 - Ventilation Air from Inside Building
WARNING: If the area in which the heater may be operated does not meet the required volume for indoor combustion air, combustion and ventilation air shall be provided by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the out­doors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
6
Figure 3 - Ventilation Air from Outdoors
cuiheat.com 126345-01D
INSTALLATION
NOTICE: This heater is intended for use as supple­mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must install
heater. Follow all local codes.
NOTICE: State or local codes may only allow operation of this appliance in a vented configuration. Check your state or local codes.
WARNING: If optional remote control is used, make sure the selector switch is in the OFF position before installing heater.
WARNING: Before installing in a solid fuel burn­ing fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue and firebox may create and distribute soot within the house. Inspect chimney flue for damage. If damaged, repair flue before operating heater.
WARNING: Never install the heater
• in a bedroom or bathroom unless installed as a vented appliance, see page 11
• in a recreational vehicle
• where curtains, furniture, clothing or other flam­mable objects are less than 36" from front and 42" from top of heater; for side clearances see Figure 4
• in high traffic areas
• in windy or drafty areas
IMPORTANT: Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, page 5.
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install log set. Call dealer where you purchased log set for proper type fireplace.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rating plate. Field conversion is not permitted.
INSTALLATION AND CLEARANCES FOR VENT-FREE OPERATION
MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE MATERI-
ALS
Side Wall 16", Ceiling 42", Front 36"
WARNING: Seal any fresh air vents or ash clean­out doors located on floor or wall of fireplace. If not, drafting may cause pilot outage or sooting. Use a heat­resistant sealant. Do not seal chimney flue damper.
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall cov­erings or operating heater where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
cuiheat.com126345-01D
LOG SIZING REQUIREMENTS
Log
Size
Height Depth Front Width Rear * Width
18" 17" 13.5" 24" 20.5" 24" 17" 13.5" 28" 20.5"
30'' 17'' 13.5'' 32'' 26''
* Measured at 13.5" depth.
Minimum Firebox
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from floor, ceiling and adjoining wall.
Carefully follow these instructions. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace or listed vent­free firebox.
7
INSTALLATION Continued
MINIMUM CLEARANCES FOR SIDE COMBUSTIBLE MATERIAL, SIDE WALL AND CEILING
A. Clearances from the side of the fireplace cabinet to any combus-
tible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf, etc. is made of combus-
tible material and protrudes 3-1/2" from the wall. This combustible material must be 4" from the side of the fireplace cabinet (see
Figure 4).
NOTE: When installing your gas logs into a manufactured firebox,
follow firebox manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42".
NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fire­place opening is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, Page 9.
Noncombustible
Material Distance (A)
12" or more Noncombustible material okay. Between 8" and 12" Install fireplace hood accessory
Less than 8"
Requirements for Safe Installation
(GA6050).
Noncombustible material must be ext ended to at least 8". See Between 8" and 12", above. If you cannot extend material, you must operate heater with flue damper open.
Example
*
*Minimum 16 inches from Side Wall
Figure 4 - Minimum Clearance for Combustible to Wall
MINIMUM NONCOMBUSTIBLE MATERIAL CLEARANCES Clearances if Not Using Mantel
NOTE: If using a mantel proceed to If Using Mantel. If not using a mantel, follow the information on this page.
You must have noncombustible material(s) above the fireplace open­ing. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncom­bustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (for all models). See Figure 5 for minimum clearances.
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.)
Above Fireplace
If Using Mantel
You must have noncombustible material(s) above the fireplace open­ing. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" Models Only). Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See
Figure 5, and Figures 6 and 7 (Page 9) for minimum clearances. IMPORTANT: If you cannot meet these minimum clearances, you
must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, Page 9.
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
8
cuiheat.com 126345-01D
Minimum Noncombustible Material
Minimum Non­Combustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
Mantel Shelf
12"
(A)
18" 20" 22"
24"
2 ½"
6"
8"
10"
INSTALLATION Continued
Minimum Noncombustible Material
8" Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to Underside of Mantel
Hood (GA6050 or GA6053)
Top of Fireplace Opening
Underside of Mantel Shelf
Mantel Shelf
Combustible Material
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances Without Using Hood
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Fol­low all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
• operate the logs only with the flue damper open
• raise the mantel to an acceptable height
• remove the mantel
FLOOR CLEARANCES
The fireplace's required clearances to combustibles must be main­tained. Consult your fireplace manufacturer's installation instructions for minimum clearances. If permitted by the fireplace installation instructions, combustible material may be installed up to the bottom edge of the fireplace face (see figure 8).
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
NOTE: To avoid heat-related finish damage, we recommend the use of high temperature paint (rated 175° F or higher) on the underside of the mantel.
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.
Figure 7 - Minimum Mantel Clearances When Using Hood
Figure 8 - Minimum Fireplace Clearances If Installed at Floor
Level
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
NOTE: When used as a vented heater, appliance must be installed only in a solid-fuel burning fireplace with a working flue and constructed of noncombustible material.
For Massachusetts Residents Only: Installation of this vented gas log set in the Commonwealth of Massachusetts requires the damper be permanently removed or welded in the fully open position.
If your heater is a manually-controlled model, you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.
1. The fireplace does not meet the clearance to combustibles require­ments for vent-free operation.
2. State or local codes do not permit vent-free operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, Page 31). This will ensure vented operation (see Figure 9, page 10). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
cuiheat.com126345-01D
9
INSTALLATION Continued
Damper Clamp
Damper
Damper Clamp
Damper
Manufactured FireplaceMasonry Fireplace
Figure 9 - Attaching Damper Clamp
See chart for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
Area of Various Standard Round Flues
Diameter Area
5" 20 sq. in. 6" 29 sq. in. 7" 39 sq. in. 8" 51 sq. in.
Chimney
Height
6' to 15' 39 sq. in.
15' to 30' 29 sq. in.
Minimum Permanent
Flue Opening
Damper
Installation Items Needed
• hardware package (provided with heater)
• approved flexible gas hose and fittings (if allowed by local codes)
(not provided)
• sealant (resistant to propane/LP gas, not provided)
• electric drill with 3/16" drill bit (metal or masonry as applicable)
• flathead screwdriver
• pipe wrench
1. Connect approved flexible gas hose to gas control fitting in heater
(see Figure 10).
IMPORTANT: Hold gas fitting with wrench when connecting flexible
gas hose.
2. Locate two masonry screws in hardware package.
3. Place heater base in fireplace.
4. Place logs in their proper position on heater base (see Installing
Logs, starting on Page 14).
5. Center heater base and logs front-to-back and side-to-side in fireplace.
6. Carefully remove logs without moving heater base.
7. Mark screw locations through one hole on each side of the mounting bracket (see Figure 11). If installing in a brick-bottom fireplace, mark screw locations in mortar joint of bricks.
Flexible Gas Hose (if allowed by local codes)
Fitting
INSTALLING HEATER BASE ASSEMBLY
WARNING: You must secure this heater to fire­place floor. If not, heater will move when you adjust controls. Moving heater may cause a gas leak or log misplacement.
WARNING: If installing in a sunken fireplace, special care is needed. You must raise the fireplace floor to allow access to heater control panel. This will ensure adequate air flow and guard against sooting and controls being damaged. Raise fireplace floor with noncombustible material. Make sure material is secure.
CAUTION: Do not pick up heater base assembly by burners. This could damage heater. Only handle base assembly by grates.
IMPORTANT: Make sure the heater burners are level. If heater is not level, heater will not work properly.
Figure 10 - Attaching Flexible Gas Hose to Heater
8. Remove heater base from fireplace. If installing optional control accessories, do so at this time. Follow all directions provided with accessory.
9. Drill holes at marked locations using 3/16" drill bit.
10. Attach base assembly to fireplace floor using two masonry screws (in hardware package).
Masonry Screw
Mounting Bracket
Figure 11 - Attaching Base to Fireplace Floor
10
cuiheat.com 126345-01D
INSTALLATION Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pres­sure regulator.
WARNING: A qualified service person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect propane/LP fireplace directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and propane/LP supply.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench * An equipment shutoff valve with 1/8" NPT tap is an acceptable al­ternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer. For propane/LP units, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing rain or sleet.
Propane/LP Supply Tank
External Regulator
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diam­eter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 13).
IMPORTANT: Install equipment shutoff valve in an accessible loca­tion. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
Equipment Shutoff Valve With 1/8" NPT Tap*
Approved Flexible Gas Hose (if allowed by local codes)
PROPANE/LP
From External Regulator (11" W.C.** to 14" W.C. Pressure)
NATURAL
From Gas Meter (5" W.C.** to10.5" W.C. Pressure)
Vent Pointing Down
Figure 12 - External Regulator With Vent Pointing Down
WARNING: Never connect natural gas fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
cuiheat.com126345-01D
3” Minimum
Pipe
Cap
Nipple
Gas Control
* Purchase the optional equipment shutoff valve from your dealer. ** Minimum inlet pressure for purpose of input adjustment.
Figure 13 - Gas Connection
Sediment Trap
Tee Joint
CAUTION: Avoid damage to gas control. Hold gas fitting with wrench when connecting it to gas piping and/or fittings.
11
Loading...
+ 25 hidden pages