UNPACKING THE PRODUCT ........................................................................................................................... 12
What’s in the box? ........................................................................................................................................12
ELEMENTS OF THE UPS - REAR PANEL ....................................................................................................... 13
HOW IT WORKS ................................................................................................................................................. 14
TOWER VERSION UPS INSTALLATION ........................................................................................................ 25
Installation of the UPS with a battery module ..............................................................................................26
RACK VERSION UPS INSTALLATION ........................................................................................................... 28
Installation of the UPS with a battery module ..............................................................................................31
DISCONNECTING THE BATTERY MODULE ................................................................................................ 32
FIRST START-UP OF THE UPS ......................................................................................................................... 33
STARTING UP THE UPS UNIT (power supply from the mains) ....................................................................... 34
STARTING THE UPS UP FROM THE BATTERY (cold start) ......................................................................... 34
SWITCHING THE UPS OFF ............................................................................................................................... 34
REPLACING THE UPS UNIT'S INTERNAL BATTERY ............................................................................ 36
REPLACING THE BATTERY IN THE UPS ...................................................................................................... 37
REPLACING THE BATTERIES IN THE BATTERY MODULE ...................................................................... 39
COMMUNICATION WITH PC ....................................................................................................................... 42
COMMUNICATION USING RS232 OR USB HID DEVICES .......................................................................... 42
Thank you for purchasing the EVER POWERLINE RT PLUS UPS system. This UPS
unit has been designed and engineered to provide the highest standard of protection
against power failure. We hope that the purchased UPS unit will meet your
expectations.
This manual contains all relevant information to ensure correct and safe operation of
the unit. Please read this manual carefully and thoroughly prior to using the EVER
POWERLINE RT PLUS unit. This will help you operate the unit correctly and safely.
The POWERLINE RT PLUS units were designed for computer servers, small
computer networks, workstations and other electrical, electronic ad IT systems. With
the universal rack / tower housing, the UPS orientation can be changed quickly.
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
4
GENERAL FEATURES OF THE UPS UNIT
The POWERLINE RT PLUS UPS units are ON-LINE (VFI) class devices, designed to
work with equipment supplied from ~ 230 VAC single-phase electric power mains.
They provide energy for practically any device whose power rating is not greater than
the UPS unit's power rating.
Alongside their excellent performance and reliability, the POWERLINE RT PLUS
UPS units offer a number of other advantages:
Output active power is equal to apparent power (PF=1).
On-line operation with real double conversion, sine wave output voltage
(ensuring top quality VFI-SS-111 parameters).
The universal rack / tower housing, thanks to which the UPS orientation can be
changed quickly. The LCD's rack / tower mode selection is done via software,
with buttons located on the UPS panel.
Availability of the ECO mode – further improves the efficiency of the power
supply system (through the ability to differentiate between periods with varying
degrees of safeguards).
HID USB communication interface - the UPS can operate with other devices
without the necessity to install software
Scalability (extension) of autonomous operation time thanks to the ability of
connecting up to 10 battery modules to the UPS
Manageable outputs - customized operation for specific needs of the more
demanding receivers.
Back-up time prediction - for determining the UPS autonomous operation (in
back-up mode) in real time, through PowerSoft.
The color LCD display grants the user complete control over the UPS.
The Start-on-battery function enables the UPS to be started even if power from
the mains is not available ("Cold start").
LAN filter (10/100 Base-T) – for protecting the network card against power
surges.
EVER POWERLINE RT PLUS UPS Operating Manual
5
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
Remote Emergency Power Off (Remote EPO) functionality which interrupts
power supply from the UPS output to loads in extreme situations or in
emergency (e.g. fire).
Remote On/Off (ROO) function for remotely starting and shutting down the UPS,
The unit's battery charging system with temperature compensation additionally
protects the built-in batteries, prolongs their life and consequently leads to
reduced maintenance costs.
The battery can be replaced by the user.
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
6
CAUTION! Before starting the procedures described in this manual,
please read the general safety instructions (including the instructions
found in this document), health & safety information, environmental
protection information and legal regulations that may apply. Always
observe the instructions and recommendations found in these
documents.
CAUTION! The user is strictly forbidden from performing any repairs, as
this would constitute a health hazard and may result in death. Any
repairs and replacement of batteries should be conducted only by
qualified service technicians properly authorized pursuant to the valid
legal regulations (after the warranty period, users are allowed to replace
batteries – the procedure specified in the instruction must be
unconditionally observed).
CAUTION! The unit should be operated and stored in conditions
complying with the requirements set in the specification (technical
documentation).
CAUTION! The device is completely disconnected from the mains only
when the power lead is removed from the mains socket (the plug is
removed from the mains socket).
CAUTION! The unit is equipped with an internal power source (batteries)
or it may operate in combination with a fixed, external source of power
(battery modules). Dangerous voltage may be present at the output
terminal(s), even if the unit has been disconnected from the mains.
CAUTION! The user should place warning labels on all remotely
installed primary isolation switches in order to warn electrical service
technicians that the circuit is powered by a UPS unit. The following (or
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General considerations
EVER POWERLINE RT PLUS UPS Operating Manual
7
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
equivalent) text should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS
CIRCUIT.
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements, unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the
unit's electrical connections must remain covered (with applicable
covers). Failure to observe this requirement may create hazard
potentially resulting in injury or death for persons who touch such
connectors. It may also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may
cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! The POWERLINE RT PLUS UPS units are not intended to
work directly with medical equipment, life-supporting equipment or any
other equipment that may have effect on health.
CAUTION! The POWERLINE RT PLUS UPS units may only be installed
and maintained by suitably qualified service technicians.
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working
and handling electrical equipment up to 1 kV voltage.
B) Installation information and requirements
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
8
CAUTION! Before connecting any cables or making any connections
within the UPS unit or in the electrical system, make sure there is no
dangerous voltage on electrical terminals and cables in the system.
CAUTION! The UPS may only be connected to a power system with
indicated rated voltage, with a suitable grounding connection installed.
The facility's electrical system to which the UPS unit is connected must
be fitted with overload and short-circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS
unit's input side, and only TN-S configuration is allowed on the UPS
unit's output side.
CAUTION! No extension cords should be used for connecting the UPS
unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be
completely dry before installation and operation. The acclimatization time should
be at least 2 hours.
UPS units and battery packs must not be installed in humid environment.
UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads,
cables, connectors, sockets and plugs, as well as that of the unit itself.
The unit must be connected to a power circuit with a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
EVER POWERLINE RT PLUS UPS Operating Manual
9
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
To reduce the risk of electric shock (in case the grounding cannot be checked),
the unit must be disconnected from the mains before installation or connecting to
other equipment. The power lead may only be reconnected after making all
required connections.
The electric system's grounding conductor leads the leakage current away from
the receivers. The leakage currents of all loads connected to the UPS unit's
output are combined in the UPS unit's power lead. The summary leakage current
may trigger protective devices (RCD) and result in disconnecting power to the
loads.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when
touching two surfaces with different electrical potentials.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in
emergency, the UPS unit from the connected loads regardless of the mode in
which the UPS is operating.
To minimize the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected
overcurrent protection. Additionally, the breaker should feature at least a 3 mm
insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All instructions must be executed step by step. If any problems emerge when
executing the instructions given in this document, please contact EVER service
support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective
grounding.
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
10
There may be voltage on the UPS unit's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in
the unit's internal batteries and/or battery packs).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
WARNING: This is a C2 category UPS. For commercial and industrial use in
secondary environment. Additional precautions or limitations in installation may be
required to prevent the emission of interferences.
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Only qualified service
technicians may perform maintenance works.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from
the mains (from terminals of the electrical power supply), parts inside the UPS
unit remain connected to the batteries, which may create hazards. Disconnect the
battery and/or battery packs before carrying out any servicing and/or
maintenance. Make sure there is no dangerous voltage on the DC circuit internal
elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.
CAUTION - Risk of electric shock! Dangerous voltage may be present between
the battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
- remove jewelry, watches, rings and other metal items,
- only use tools with insulated handles.
When replacing the battery, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
Always dispose of used batteries according to relevant instructions.
WARNING: Disposing of batteries in a fire may result in explosion.
WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and
parameters.
EVER POWERLINE RT PLUS UPS Operating Manual
11
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
E) Transport and packaging requirements
Exercise particular care when transporting the equipment, due to its heavy weight.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be
recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the battery has not been recharged. In such
cases always contact service support.
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
12
CAUTION! The product is supplied with the batteries connected.
CAUTION! Water vapor may condensate on the UPS unit's elements if
packaging is removed from the device in low temperatures. Do not install
the UPS until its interior and housing are completely dry (electric shock
risk).
TECHNICAL DESCRIPTION
UNPACKING THE PRODUCT
The UPS unit must be properly examined upon delivery or handover. Although the
product is carefully packaged, the appliance could have been damaged due to
shocks experienced during transport. Should any product damage be discovered, the
carrier or the vendor must be notified immediately, and a protocol must be made,
with photos of the damage.
Keep the packaging for future transport operations.
What’s in the box?
Check carefully the contents of the packaging. The packaging should contain:
- the UPS unit,
- tower type supports (2 pcs) for installing the unit vertically,
- 1 x USB cable,
- 1 x RS232 cable,
- a warranty card,
- a user's guide.
Depending on the UPS unit:
POWERLINE RT PLUS 1000
- 1 x power cord CEE 7/7 - IEC 320 C13 10 A,
- 2 x power cords IEC C13 - IEC C14 10 A.
POWERLINE RT PLUS 2000
- 1 x power cord CEE 7/7 - IEC 320 C19 16 A,
- 2 x power cords IEC C13 - IEC C14 10 A.
POWERLINE RT PLUS 3000
- 1 x power cord CEE 7/7 - IEC 320 C19 16 A,
- 2 x power cords IEC C13 - IEC C14 10 A.
- 1 x power cord IEC C19 - IEC C20 16A.
EVER POWERLINE RT PLUS UPS Operating Manual
13
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
1. Input circuit
automatic fuse
2. Controlled output sockets
IEC 320 C13 (10 A)
3. Non-controlled output sockets
IEC 320 C13 (10 A)
4. SNMP card's compartment
5. External battery modules
terminal
6. Fan
7. EPO/ROO connector.
8. USB communication interface
9. RS232 communication interface
10. RJ45 / RJ11 telecommunication
filter
11. RJ45 / RJ11 port – battery
module detection
12. Power socket:
IEC 320 C14 (10 A)
POWERLINE RT PLUS 1000
IEC 320 C20 (16 A)
POWERLINE RT PLUS 2000
POWERLINE RT PLUS 3000
13. Automatic fuses
of output circuits
14. Output socket
IEC 320 C19 (16 A)
Fig. 1: View of the rear panel of POWERLINE RT PLUS 1000
Fig. 2: View of the rear panel of POWERLINE RT PLUS 2000
Fig. 3: View of the rear panel of POWERLINE RT PLUS 3000
ELEMENTS OF THE UPS - REAR PANEL
Figures 1 - 3 present the elements found in rear panels of POWERLINE RT PLUS
units.
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
14
1. Fuse compartment cover
2. Cover of the battery module
output terminal
3. Cover of the battery module input
terminal
4. RJ45 / RJ11 port – battery
module detection
5. Output socket supplying power to
the internal charger of the
consecutive battery module
6. Socket supplying power to the
internal charger of the
consecutive battery module
7. Air vents / fan
Fig. 4: View of the rear panel of the battery module for
POWERLINE RT 1000
Fig. 5: View of the rear panel of the battery module for
POWERLINE RT 2000 - 3000
1. Start button (ON)
2. Shut down button (OFF)
3. Confirmation button (ENTER)
4. Exit button (ESC)
5. LCD display
Fig. 6: View of the front panel of the POWERLINE RT PLUS 1000 unit
BATTERY MODULE DESIGN – REAR PANEL
Figures 4 - 5 present the elements found in rear panels of battery modules for
POWERLINE RT PLUS units.
HOW IT WORKS
The UPS unit comes with an LCD display with four buttons. Fig. 6 shows front panel
elements of the POWERLINE RT PLUS unit, along with their description. Table 1
presents the description of the buttons of the control panel and Table 2 presents the
description of audio signals indicating the unit's various operation states.
EVER POWERLINE RT PLUS UPS Operating Manual
15
www.ever.eu
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
Button
Function
Description
ON
Switching the unit on
logically
When the UPS is not on logically (not operating in back-up or normal mode),
press and keep the button depressed for over 1 second to switch the unit on
logically.
Battery test start
Press and keep the button depressed for over 5 s to start the battery test. The
function is only available in the mains, ECO or inverter (frequency converter)
mode.
"Cold start". Starting
the UPS without the
mains voltage.
To start the UPS up when there is no voltage in the mains press and keep this
button depressed for over 1 s.
OFF
Switching the unit off
logically
When the UPS is on logically, press and keep the button depressed for over 1 s
to switch the unit off logically (power supply to receiver's connected to the UPS's
output is switched off).
ENTER
Access the UPS
unit's main menu
Press and keep this button depressed for over 5 s to enter the unit's main menu.
The function is only available in the bypass or standby mode.
Scrolling the menu
up
Press this button quickly to navigate to the next menu.
Confirming the
current setting and
exiting the menu.
Press and keep this button depressed for over 5 s to exit the menu and to confirm
the currently entered setting.
ESC
Changing the
parameter's value
Press the button shortly to change the value of the edited parameter, without
saving it.
Exiting the menu
without saving the
changes.
Press and keep this button depressed for over 5 s to exit the menu without
confirming the currently entered changes.
Switching the sound
signal on / off
Press and keep the button depressed for over 5 s to switch the sound signal on /
off.
This applies to sound signals if the UPS operates in the backup mode or low
battery condition is reported. Sound signals are active in the remaining cases
(despite previous deactivation).
ENTER
+
ESC
Bypass mode on / off
When the UPS operates in the mains mode, press ENTER and ESC
simultaneously and keep these buttons depressed for over 5 s to switch the unit
from the mains mode to the bypass mode or from the bypass mode to the mains
mode.
ON
+
ENTER
Rack / Tower mode
Press simultaneously and keep depressed the ON and ENTER buttons for over 5
s to change the LCD orientation (Tower / Rack).
Table 1. Functions of the control panel buttons
EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
www.ever.eu
16
Event
Sound signal
Operation modes: MAINS,
ECO, STANDBY, INVERTER
No sound signal
BACKUP (battery) mode
Sound signal every 10 s. Can be activated / deactivated through menu 009 or
through PowerSoft. The sound signal is activated every second as the battery
keeps discharging.
BYPASS mode
Sound signal every 20 s. Can be activated / deactivated through menu 009 or
through PowerSoft.
Sound signal every second. Sound signals are active if overload, overheating
or EPO triggered are detected, despite previous deactivation.
Table 2. Sound signals for specific states of the UPS unit
LCD DISPLAY ICONS
The front panel of the UPS unit presents useful information on the current functional
state of the UPS unit: the operation mode, the input and output voltage values, the
load level, the battery charge level, alarms and messages.
Figure 7 shows the display panel. Table 3 presents the description of information
icons that may be shown on the LCD display depending on the UPS unit's operation
mode.
Fig. 7: LCD display screen with information icons
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.