Ever Power Systems POWERLINE 11 series Instruction Manual

POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
TABLE OF CONTENTS
TABLE OF CONTENTS........................................................................................................................................ 2
INTRODUCTION .................................................................................................................................................. 3
GENERAL INFORMATION ................................................................................................................................. 3
PURPOSE OF THE POWER SUPPLY............................................................................................................. 3
General features of the battery back-up .................................................................................................................. 3
UPS STRUCTURE................................................................................................................................................. 4
FRONT PANEL................................................................................................................................................. 4
REAR PANEL ................................................................................................................................................... 6
SAFETY AND HEALTH INSTRUCTIONS ......................................................................................................... 7
TRANSPORT .................................................................................................................................................... 7
ELECTRIC SAFETY......................................................................................................................................... 7
INSTALLATION.................................................................................................................................................... 9
UNPACKING .................................................................................................................................................... 9
INSTALLATION OF THE BATTERY BACK-UP ........................................................................................ 10
CONNECTING THE BATTERY BACK-UP ................................................................................................. 10
Input / Output Installation..................................................................................................................................... 11
FIRST START ................................................................................................................................................. 11
DESCRIPTION OF THE BACK-UP'S OPERATION......................................................................................... 12
GENERAL INFORMATION .......................................................................................................................... 12
ZERO MODE (“00” MODE)........................................................................................................................... 12
“BYPASS” MODE (“01” MODE)................................................................................................................... 13
MAINS OPERATION MODE (“02” MODE)................................................................................................. 13
BACK-UP (BATTERY) OPERATION MODE (“03” MODE) ...................................................................... 14
STORAGE CELLS TEST MODE (“04” MODE) ........................................................................................... 14
“SERVICE BYPASS” OPERATION MODE...................................................................................................... 15
EMERGENCY MODE......................................................................................................................................... 15
SAFEGUARDS................................................................................................................................................ 16
Against overloads.................................................................................................................................................. 16
Against shorting.................................................................................................................................................... 16
EPO....................................................................................................................................................................... 17
COMMUNICATION BETWEEN THE UPS AND A COMPUTER................................................................... 17
RS232 COMMUNICATION ........................................................................................................................... 17
WinPower SOFTWARE INSTALLATION .................................................................................................... 18
Installation on computers with Windows.............................................................................................................. 18
CONFIGURING THE BATTERY BACK-UP'S PARAMETERS.................................................................. 18
INSTALLATION AND CONFIGURATION OF THE POWERSOFT PERSONAL SOFTWARE .............. 19
Installation on computers with Windows.............................................................................................................. 19
Installation on computers with Linux/Unix .......................................................................................................... 20
Software updates................................................................................................................................................... 21
ADDITIONAL REMARKS.................................................................................................................................. 22
BATTERY BACK-UP AND POWER GENERATORS ................................................................................. 23
STORAGE, MAINTENANCE ........................................................................................................................ 23
DISPOSAL....................................................................................................................................................... 23
TECHNICAL PARAMETERS............................................................................................................................. 24
INSTALLATION GUIDELINES .................................................................................................................... 24
TECHNICAL DATA ....................................................................................................................................... 25
DIAGNOSTICS OF ERRORS REPORTED BY UPS ......................................................................................... 26
INFORMATION REGARDING REGULATIONS AND WARRANTY............................................................ 27
DECLARATION OF CONFORMITY............................................................................................................ 27
WARRANTY................................................................................................................................................... 27
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
INTRODUCTION
Thank you for purchasing the EVER POWERLINE battery back-up. It belongs to
the latest series of state-of-the-art power supply devices designed to work with servers, computer networks, as well as data processing systems. EVER POWERLINE series UPS was designed so as to meet all your expectations for protection against power loss. The following manual contains information on operating the device and safety rules. Familiarising yourself in detail with the manual prior to using the EVER POWERLINE UPS will help you operate the device correctly.
GENERAL INFORMATION
PURPOSE OF THE POWER SUPPLY
POWERLINE series battery back-ups are ONLINE-class (VFI) devices designed for work with equipment powered by monophase ~230V mains.
WARNING! POWERLINE battery back-ups were not designed to work with medical equipment, in particular life and/or health support devices.
General features of the battery back-up
POWERLINE battery back-ups consist of the following functional units:
rectifier unit with PFC (power factor correction),
accumulator charger,
accumulator unit in a battery module
inverter manufactured in high-frequency IGBT technology,
automatic bypass system,
manual (service) bypass system,
microchip control system with measurement units.
The input inverter converts the AC energy into an internal DC bus. The power factor correction (PFC) system enables a radical reduction of interference transmitted to the power system. The DC bus is the basic power source for the inverrter creating a nominal AC true sine wave used to power the receivers. An independent charger is responsible for charging the accumulator. Its distinctive feature is a very low
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
alternating charging current component, which considerably prolongs the accumulators’ life. Microchip control system (DSP) enables precision and reliability of the whole power supply system.
The automatic bypass system increases the overall system security. In the event of a failure of the inverter, the current from the mains will be provided directly to the load. Thus, the automatic bypass system becomes an additional, passive safeguard of the load.
Additional function of manual connection of the bypass enables a complete switch of the load power supply to mains and thus conducting servicing or maintenance work. Internal electronic circuits (excluding the secured manual bypass system) can be started by input breaker.
UPS STRUCTURE
FRONT PANEL
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
No.
Symbol
Name
Description
1
SELECT
If the unit is in BYPASS mode or zero mode (STANDBY), pressing this button allows you to configure the unit’s parameters: output voltage, frequency, BYBASS mode options. To approve the selection, press ENTER (2)
2
ENTER
If the unit is in BYPASS mode, parameters set by means of the SELECT key may be approved by pressing ENTER.
3
OFF
When the power supply is regular, pressing the OFF button causes the unit to switch to BYPASS mode and turns off the inverter. If the BYPASS mode option is available, the outlet is powered from the BYPASS line
4
ON
Turns the unit on Deactivates sound alarms.
5
-
LCD
LCD
Display
Description
Input
Input voltage value
Input voltage frequency Indicates excessively high input voltage; not displayed if the voltage is regular
Indicates excessively low input voltage; not displayed if the voltage is regular
Output
Output voltage value
Output voltage frequency
Load
Unit load in W or VA Indicates short-circuit of the unit’s output Indicates unit overload
Storage cells
Storage cells voltage value Charge level of storage cells Indicates overload of the storage cells; the unit will switch to battery mode Indicates that the storage cells are discharged; the unit will soon switch off
Mode/Error/Warning
Displays the unit’s mode, error codes and warnings
Inverter
Indicates the operational status of the inverter
Bypass
Indicates the operational status of the BYPASS circuits
Output voltage, frequency, BYBASS mode option
If the unit is in STANDBY or BYPASS mode, one of the four output voltage values may be selected
If the unit is in STANDBY or BYPASS mode, one of the two input voltage frequency values may be selected
If the unit is in STANDBY or BYPASS mode, one of the two BYPASS mode options may be selected
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
REAR PANEL
Rear panel view of POWERLINE 6-11 and POWERLINE 10-11 back-ups
1 – Cover of the power supply and receiver grid connections 2 – Cover of the servicing BYPASS switch 3 – Input safeguard 4 – Parallel port (optional) 5 – Expansion card (optional) 6 – RS232 communications port 7 – Fans 8 – EPO connector
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
SAFETY AND HEALTH INSTRUCTIONS
TRANSPORT
Due to the significant weight of the devices, special care must be taken during
transport;
do not handle heavy equipment by yourself;
storage and operation of the device should take place in conditions conforming to
its specification.
WARNING! Transport, installation and maintenance of POWERLINE back-ups may be conducted only by qualified personnel.
ELECTRIC SAFETY
Never work alone in conditions that may be hazardous to health and/or life;
even a momentary shorting of a strong current may lead to severe burns;
before connecting the device to the mains inspect the condition of power leads,
plugs and sockets, as well as the condition of the device itself;
To minimise the risk of electric shock, in cases when there is no way of verifying
the earthing, the device should be disconnected from the mains before installation or connection of other equipment to the back-up – reconnect the power cord only after all connections are made;
in order to avoid the risk of electric shock when connecting and disconnecting
signal cables and touching two surfaces with differing electric potential, if possible use only one hand;
The device must be connected to an installation with a protective circuit; Failure
to comply with the above can result in electric shock;
The installation must enable a complete disconnection of the power supply from
the UPS, e.g. by switching an “S” breaker;
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
The device receiving the current must be connected with an appropriate circuit
protection (manual cut-out or circuit breaker);
The device is equipped with an earthing cable which siphons the earth leakage
current to the receivers (e.g. computer hardware). This should be taken into consideration with residual current safeguards;
WARNING! The receiver line of the emergency power supply should be equipped with a remote emergency power off (EPO), located near the main power switch and appropriately marked.
WARNING! Users are forbidden to carry out any maintenance activities, as they may lead to injury or death. Any repairs and replacement of batteries should be conducted only by a qualified representative of the technical support.
WARNING! The battery back-up is disconnected from the mains only when the power cord is removed from its socket.
WARNING! Since the device is equipped with internal power source (batteries) the output may provide current even though the device itself is not connected to the mains.
WARNING! POWERLINE battery back-ups were not designed to work with medical life support devices.
POWERLINE 11 series UPS – Instruction Manual
2011/07/22
www.ever.eu
INSTALLATION
WARNING! Before installing the battery back-up you must obligatorily familiarise yourself with the safety and health measures provided in the previous chapter.
UNPACKING
Please inspect the battery back-up upon receipt. Although the product is packed very carefully it could have sustained damage from shock during transport. Should you find any damages, please inform the carrier or seller immediately.
WARNING
! The device is delivered with its accumulator connected.
The battery back-up is packed in a manner enabling safe transport (including by forklift truck). To unpack the device:
carefully cut the protective bands,
slide the cardboard cover off,
remove the foam safeguards,
according to H&S instructions, remove the battery back-up from the wooden
transport pallet (this may require assistance),
place the back-up in the installation location using the transport castors,
block the castors.
Keep the packaging for future transportation of the device. Verify the contents of the package, which should include:
the battery back-up,
1 RS232 communication cable,
Instruction manual on CD,
warranty card.