EverHot 211220 Owner's Manual And Installation Instructions

This water heater must be installed and serviced by a qualified person.
Please leave this guide with the householder.
Owners Guide
and
Installation Instructions
Solar Storage Tank
WARNING: Plumber – Be Aware
Use copper pipe ONLY. Plastic pipe MUST NOT be used.
It is a requirement of a solar water heater installation that all pipe work be in copper
and not plastic, due to the effects of high water temperatures and pressures.
PATENTS
This water heater may be protected by one or more patents or registered designs.
TRADE MARKS
®
Registered trademark of Rheem Australia Pty Ltd.
™ Trademark of Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure accuracy in preparation of this publication.
No liability can be accepted for any consequences, which may arise as a result of its application.
WARNING: Plumber – Be Aware
The solar hot and solar cold pipes between the solar storage tank and the solar collectors MUST BE
of copper. All compression fittings must use brass or copper olives.
The full length of the solar hot and solar cold pipes MUST BE insulated.
The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating application and capable
of withstanding the temperature of the water generated by the solar collectors under stagnation conditions
The specification of the chosen insulation material should be checked with the insulation manufacturer prior to installation as different materials may vary in temperature tolerance.
be at least 13 mm thick, however thicker insulation may be required to comply with the
requirements of AS/NZS 3500.4
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar hot and solar cold pipe work
be fitted up to and cover the connections on both the solar storage tank and the solar collectors.
Note: Failure to observe these requirements increases the risk of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or where it may be in contact with a metal roof, may lead to freeze damage. The system has NO WARRANTY for freeze damage if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions.
The insulation is essential to assist in providing freeze protection, will offer corrosion protection to a metal roof against water runoff over the copper pipe, assist in avoiding accidental contact with the solar pipe work as high temperature water can flow from the solar collectors to the solar storage tank and also reduce pipe heat losses.
The insulated copper pipe work:
should be fixed at suitable locations to prevent or reduce the possibility of noise from water
hammer and vibration from occurring
is not to be placed or installed in contact with plastic pipe work.
Likewise, plastic pipe work is not to be placed or installed in contact with the insulated copper pipe work after the solar circuit is installed.
Plastic pipe MUST NOT be used, as it will not withstand the temperature and pressure of the water
generated by the solar collectors under stagnation conditions. The solar collectors can generate extremely high water temperatures up to 150°C and high water pressure of 1000 kPa. Plastic pipe cannot withstand these temperatures and pressures and MUST NOT be used. Failure of plastic pipe can lead to the release of high temperature water and cause severe water damage and flooding.
The highest point of the solar cold pipe and solar hot pipe must be where they connect to the solar
collectors, to avoid the possibility of air locks occurring in the system. There must be a continuous fall in the pipe work between the solar collectors and solar storage tank. Horizontal runs of pipe work are acceptable and may be installed.
A non return valve MUST BE installed on the cold water line to the solar storage tank AFTER the
cold water branch to a temperature limiting device.
The pressure applied to the solar circuit and solar collectors during a pressure test of a direct open
circuit system MUST NOT exceed 1000 kPa, otherwise damage may result to the solar collectors. Refer to “Pressure Testing” on page 34.
3
CONTENTS
HOUSEHOLDER – We recommend you read pages 4 to 19.
The other pages are intended for the installer but may be of interest.
About Your Water Heater ............................................................................................................ 4
Regular Care .............................................................................................................................. 11
Water Supplies........................................................................................................................... 14
Save A Service Call ................................................................................................................... 17
Installation – Solar Storage Tank............................................................................................. 20
Installation – Solar Collectors .................................................................................................. 31
Installation – Solar and Gas Booster Connections................................................................ 35
Connections – Plumbing .......................................................................................................... 41
Connections – Electrical ........................................................................................................... 44
Commissioning.......................................................................................................................... 45
Draining The Solar Collectors .................................................................................................. 49
Draining The Water Heater ....................................................................................................... 49
Warranty ..................................................................................................................................... 51
4
ABOUT YOUR WATER HEATER
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable water. Its use in an application other than this may shorten its life.
MODEL TYPE
Your Everhot® solar 211 220 water heater is designed for the solar collectors to be roof mounted and the vitreous enamel lined solar storage tank to be installed at ground or floor level, remotely from the solar collectors. The solar storage tank is suitable for installation either outdoor or indoor and with one or two HBT 200 solar collectors. If an in-series gas booster is mounted to the solar storage tank, then it is suitable for outdoor installation only.
The system is not suitable for installation above 400 metres altitude.
The system has a level of freeze protection designed to guard the system against damage from freeze conditions (refer to “Freeze Protection” on page 7). The system must be installed with the full length of the solar hot and solar cold pipes insulated to offer protection against freeze damage (refer to
“Pipe Work and Insulation” on page 6). Freeze conditions occur below 6°C.
The system has NO WARRANTY for freeze damage when installed above 400 metres altitude or if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions (refer to “Terms of the Everhot
Warranty on page 51). Note: The Everhot warranty against freeze damage
applies only to systems installed in Australia.
This solar water heater is designed to be installed with an Everhot continuous flow 274 020 or 271 026 model in-series gas booster mounted onto the storage tank or installed remotely.
The solar water heater may be installed with another suitable type of remotely installed in-series continuous flow or storage booster. If the in-series water heater is other than an Everhot continuous flow 274 020 or 271 026 model in­series gas booster, then the references to the in-series gas booster in this guide may not be applicable to the installation.
For information relating to the function and operation of the in-series water heater, refer to the Owners Guide and Installation Instructions supplied with the water heater.
SOLAR OPERATION
The Everhot solar open circuit system has its vitreous enamel lined solar storage tank installed at ground or floor level, remotely from the solar collectors.
As the sun heats the water in the solar collectors the increase in temperature activates the circulator. The circulator then moves the water from the solar collectors through an insulated copper pipe to the solar storage tank. The circulator switches on whenever the water in the solar collectors is hotter than the water in the tank. Cooler water from the solar storage tank is circulated to the solar collectors to be heated by the sun‟s energy.
This process continues while solar energy is available and until the water in the solar storage tank reaches a temperature of 70°C to 80°C.
Automatic safety controls are fitted to the water heater to provide safe and efficient operation.
ABOUT YOUR WATER HEATER
5
MAINS PRESSURE
The water heater is designed to operate at mains pressure by connecting directly to the mains water supply. If the mains supply pressure in your area exceeds that shown on page 23, a pressure limiting valve must be fitted. The supply pressure should be greater than 350 kPa for true mains pressure operation to be achieved. A minimum water supply pressure of 200 kPa is required to enable the solar circulator and solar circuit system to operate effectively.
HOW HOT SHOULD THE WATER BE?
The solar control unit will circulate water through the solar collectors until a temperature of 70°C to 80°C is reached in the solar storage tank. During periods of low solar energy gain, the continuous flow in­series gas booster will boost the water temperature automatically to its preset outlet temperature setting, or to the temperature setting of another type of in-series booster water heater.
The factory preset outlet temperature setting of the in-series gas booster is:
274 020 and 271 026 models 60°C
Note: The preset outlet temperature setting of a continuous flow in­series gas booster cannot be adjusted by the householder. The setting can only be adjusted by the installer, Rheem Service or their nearest Accredited Service Agent.
Note: AS 3498 requires that a water heater provides the means to inhibit the growth of Legionella bacteria in potable water. If this water heater is installed with an in-series continuous flow gas booster, then this requirement of AS 3498 can be satisfied provided the booster is energised, its preset outlet temperature setting is 70°C or higher and a remote temperature controller is not used.
If this water heater is installed with an in-series storage booster, then this requirement of AS 3498 can be satisfied provided the storage booster is energised and its thermostat setting is 60°C or higher.
Warning: Temperature controllers must not be fitted to the in-series water heater as part of a solar water
heater system because water at a temperature much higher than the controller setting can be delivered.
HOTTER WATER INCREASES THE RISK OF SCALD INJURY
This water heater can deliver water at temperatures which can cause scalding. Check the water temperature before use, such as when entering a shower or filling a bath or basin, to ensure it is suitable for the application and will not cause scald injury.
We recommend and it may also be required by regulations that an approved temperature limiting device be fitted into the hot water pipe work to the bathroom and ensuite when this water heater is installed. This will keep the water temperature below 50°C at the bathroom and ensuite. The risk of scald injury will be reduced and still allow hotter water to the kitchen and laundry.
WARNING
This water heater is only intended to be operated by persons who have the experience or the knowledge and the capabilities to do so. This water heater is not intended to be operated by persons with reduced physical, sensory or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere with the water heater.
This water heater uses 240 V AC electrical power for operation of the control systems and the electrically operated components. The removal of the front cover will expose 240 V wiring. It must only be removed by a qualified person.
The power lead from the solar controller must be plugged into a weatherproof electrical outlet if installed outdoors. Take care not to touch the power plug with wet hands.
Care should be taken not to touch the pipe work connecting the solar storage tank and the solar collectors. Very high temperature hot water can be generated by the solar collectors under certain conditions and flow through the pipe work from the solar collectors to the solar storage tank.
typical maximum
temperature from solar gain
maximum recommended
supply temperature to
bathrooms and ensuites
ABOUT YOUR WATER HEATER
6
SAFETY
This water heater is supplied with a thermostat, an over temperature energy cut-out, temperature sensors and a combination temperature pressure relief valve. These devices must not be tampered with or removed. The water heater must not be operated unless each of these devices is fitted and is in working order.
The operation of the over-temperature cut-out on the thermostat indicates a possibly dangerous situation. If the over-temperature cut-out operates, it must not be reset and the water heater must be serviced by a qualified person.
If the power supply cord or plug to the solar storage tank is damaged, it must be replaced by a qualified person in order to avoid a hazard. The power supply cord and plug must be replaced with a genuine replacement part available from Rheem. Phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
Warning: For continued safety of this water heater it must be installed, operated and maintained in
accordance with the Owner‟s Guide and Installation Instructions.
The Everhot warranty can become void if relief valves or other safety devices are tampered with or if the installation is not in accordance with these instructions.
PIPE WORK AND INSULATION
The solar hot and solar cold pipe work between the solar storage tank and the solar collectors and between the solar storage tank and a remote in-series water heater (if one is installed) MUST BE of copper.
The full length of the solar hot and solar cold pipes MUST BE insulated. The insulation must:
be of a closed cell type or equivalent, suitable for a solar water heating application and capable of
withstanding the temperature of the water generated by the solar collectors under stagnation conditions
be at least 13 mm thick, however thicker insulation may be required to comply with the requirements of
AS/NZS 3500.4
be weatherproof and UV resistant if exposed
extend through any penetrations in the eaves, ceiling and roof
cover valves and fittings in the solar hot and solar cold pipe work
be fitted up to and cover the connections on both the solar storage tank and the solar collectors.
Note: Failure of these requirements to be observed increases the risk of freeze damage.
Uninsulated pipe work, including concealed in cavities and roof spaces or where it may be in contact with a metal roof, may lead to freeze damage. There is NO WARRANTY for freeze damage if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions.
The insulation is essential to assist in providing freeze protection, will offer corrosion protection to a metal roof against water runoff over the copper pipe, assist in avoiding accidental contact with the solar pipe work as high temperature water can flow from the solar collectors to the solar storage tank and also reduce pipe heat losses.
Plastic pipe MUST NOT be used, as it will not withstand the temperature and pressure of the water generated by the solar collectors under certain conditions (refer to Warning on page 33).
ABOUT YOUR WATER HEATER
7
FREEZE PROTECTION
The system has a level of freeze protection designed to guard the system against damage from freeze conditions. The system must be installed with the full length of the solar hot and solar cold pipes insulated to offer protection against freeze damage (refer to “Pipe Work and Insulation” on page 6). Freeze conditions occur below 6°C.
The system has NO WARRANTY for freeze damage when installed above 400 metres altitude or if the solar hot and solar cold pipes are not insulated in accordance with the installation instructions (refer to “Terms of
the Everhot Warranty” on page 51). Note: The Everhot warranty against freeze damage applies only to
systems installed in Australia.
The anti freeze control is designed to recirculate a small amount of water from the solar storage tank through the solar pipe work and solar collectors during periods of low temperatures. This is to prevent the water inside the pipe work and collectors from freezing.
Additional freeze protection is provided by the anti-freeze heating unit, which is for heating the water at the bottom of the solar storage tank at times of low cold water temperature. The anti-freeze heating unit provides additional energy to the water to assist in the prevention of freezing in the solar pipe work and solar collectors. The anti-freeze heating unit is controlled by the solar controller and will only be energised when the water temperature is low and the circulator activates in the frost mode. The water temperature is monitored by the cold sensor.
If the water temperature at the bottom of the solar storage tank is less than 10°C when the circulator activates in the frost mode, the anti-freeze heating unit will be energised and will heat the water by a few degrees. The anti-freeze heating unit will be de-energised when either the frost mode is shut down or the water temperature is increased to 15°C.
It is essential the electrical circuit to the solar storage tank is continually turned on if there is a risk of freezing. The Everhot warranty does not cover damage caused by freeze conditions when the electrical circuit to the solar storage tank is turned off or interrupted.
An over temperature energy cut out is incorporated in a thermostat which is mounted on the solar storage tank behind the front cover.
Notes:
If it is necessary to switch the power off to the solar control unit and there is a risk of freezing, then it is
necessary to have your plumber drain the solar collectors and solar flow and return pipe work.
The freeze protection system will be rendered inoperable if electrical power is not available at the solar
control unit. Damage caused by freezing due to no power at the solar control unit, is not covered by the Everhot warranty.
The system is not covered for freeze damage above 400 metres altitude.
Refer to “Terms of the Everhot Warranty” on page 51.
ABOUT YOUR WATER HEATER
8
SOLAR MONITOR
A solar monitor is located on the front of the top cover and houses both a green and a red LED.
The green LED, marked “Solar”, indicates the current operational mode of the solar water heater and the red LED, marked “Attention”, indicates a fault mode.
The green LED will emit either a constant glow or a series of flashes, with a 2 second interval between each series.
The red LED will emit a series of flashes, with a 2 second interval between each series, only if there is a particular fault condition with the system.
The operational modes are:
Flashes
Operational Modes
solid green
(remains on)
Standby mode
green
slow pulse
Standby mode (power on for less than 48 hours)
green
rapid pulse
Circulating water through collectors
3 x green
Circulating water through collectors (power on for less than 48 hours)
no green
(remains off)
Power outage or call for service
If the power supply to the solar control unit is on and the green LED is off or the red LED is flashing, this indicates there may be a fault with the water heater. The red LED may emit up to six flashes in each series of flashes.
Notes:
If the system is in standby mode with the green LED emitting either a constant glow or slow pulsing
flashes (circulator is off) and the solar storage tank is full of hot water, the red LED may simultaneously emit a constant glow if solar radiation is still being received by the solar collectors. This does not indicate a fault. The red LED will go out when the temperature in the solar collectors decreases.
During periods of high solar radiation and the circulator activates after having been off (the green LED
will emit either a rapid pulse or a series of three flashes), it is possible the red LED may simultaneously emit a rapid pulse for a period of up to ten (10) minutes. This does not indicate a fault.
If the red LED continues to emit a rapid pulse for longer than ten (10) minutes, or emits a series of flashes, then count the number of flashes and phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
PRECAUTIONS
Where damage to property can occur in the event of the water heater leaking, the water heater must be installed in a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4 and all local codes and regulatory authority requirements.
The water heater must be maintained in accordance with the Owner‟s Guide and Installation Instructions.
Refer to “Regular Care” on page 11 and to “Anode Inspection and Replacement” on page 15.
If this water heater is to be used where an uninterrupted hot water supply is necessary for your application or business you should ensure that you have back up redundancy within the hot water system design. This should ensure the continuity of hot water supply in the event that this water heater were to become inoperable for any reason. We recommend you seek advice from your plumber or specifier about your needs and building back up redundancy into your hot water supply system.
ABOUT YOUR WATER HEATER
9
BLEEDING THE SOLAR COLLECTORS
It is necessary to purge air from the collector circuit:
When the water heater is to be turned on and the solar collectors and solar hot and solar cold pipes
have been drained.
After maintenance has been conducted on the pipe work and air has entered the system.
If the circulator appears not to be circulating water around the system.
Warning: Bleeding the solar collectors should be conducted in the morning, within three hours of sunrise, when the water temperature inside the solar collectors is lower.
To purge air from the collector circuit:
Ensure the water heater is full of water and all of the hot
taps are turned off.
Using a flat blade screwdriver, open the bleed valve (if it
is not already open) fitted above the solar hot water (from collector) inlet of the solar storage tank (see diagram).
The mains pressure will force water to flow from the tank
and through the pipe work and solar collectors, expelling air from the collector circuit through the bleed valve. This is evidenced by spurting of water from the drain line connected to the bleed valve.
Warning: Exercise care to avoid any splashing of water, as water discharged from the solar collectors may be of a very high temperature.
Close the bleed valve when water runs freely from the
drain line.
TO TURN OFF THE WATER HEATER
If you plan to be away from home for a few nights, we suggest you leave the water heater switched on.
If it is necessary to turn off the water heater:
Switch off the electrical supply at the power outlet to the solar storage tank (refer to note below).
Close the cold water isolation valve at the inlet to the water heater.
Refer to the Owner‟s Guide and Installation Instructions supplied with the in-series water heater for the
procedure to turn off the in-series water heater.
Note: If there is a risk of freezing conditions, the electrical supply to the solar storage tank should not be switched off unless the solar collectors are drained, otherwise damage could result (refer to “Freeze
Protection on page 7).
ABOUT YOUR WATER HEATER
10
TO TURN ON THE WATER HEATER
Open the cold water isolation valve fully at the inlet to the water heater.
If the solar collectors and solar hot and solar cold pipes have been drained, it will be necessary to bleed
the collector circuit (refer to “Bleeding the Solar Collectors” on page 9).
If the electrical supply to the water heater has been switched off:
Switch on the electrical supply at the power outlet to the solar storage tank.
The power outlet must be switched on for the solar control system to operate and solar gain to be achieved and for the anti-freeze heating unit to operate and offer additional freeze protection.
HOW DO I KNOW IF THE WATER HEATER IS INSTALLED CORRECTLY?
Installation requirements are shown on pages 20 and 30. The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with Standards AS/NZS 3500.4, AS/NZS 3000 and all local codes and regulatory authority
requirements.
In New Zealand, the installation must also conform with Clause G12 of the New Zealand Building Code.
Warning: Temperature controllers must not be fitted to the in-series water heater as part of a solar water
heater system because water at a temperature much higher than the controller setting can be delivered.
Refer also to “Pipe Work and Insulation” on page 6.
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Plumbing Industry Commission. This water heater must be installed by a licensed person as required by the Victorian Building Act 1993.
Only a licensed person will give you a Compliance Certificate, showing that the work complies with all the relevant Standards. Only a licensed person will have insurance protecting their workmanship for 6 years. Make sure you use a licensed person to install this water heater and ask for your Compliance Certificate.
DOES THE WATER CHEMISTRY AFFECT THE WATER HEATER?
The water heater is suitable for most public water supplies, however some water chemistries may have detrimental effects on the water heater, its components and fittings. Refer to “Water Supplies” on page 14.
If you are in a known harsh water area or you are not sure of your water chemistry, have your water checked against the conditions described on pages 14 to 16.
HOW LONG WILL THE WATER HEATER LAST?
The water heater is supported by a manufacturer‟s warranty (refer to page 51). There are a number of
factors that will affect the length of service the water heater will provide. These include but are not limited to the water chemistry, the water pressure, the water temperature (inlet and outlet) and the water usage pattern. Refer to “Precautions” on page 8.
GOING ON HOLIDAYS
It is not necessary to switch off the electrical supply at the power outlet to the solar control unit. Refer to “To
Turn Off The Water Heater” on page 9. Also if the system is not used for a period in excess of 2 weeks it is
recommended the solar collectors be covered.
11
REGULAR CARE
MINOR SIX MONTH MAINTENANCE
It is recommended minor maintenance be performed every six months by the dwelling occupant.
The minor maintenance includes:
Operate the easing lever on the temperature pressure relief valve. It is very important you raise and
lower the lever gently. Refer to “Temperature Pressure Relief Valve” on page 12.
Warning: Exercise care to avoid any splashing of water, as water discharged from the drain line will be hot. Stand clear of the drain line‟s point of discharge when operating the valve‟s lever.
Operate the easing lever on the expansion control valve (if fitted). It is very important you raise and
lower the lever gently. Refer to “Expansion Control Valve” on page 12.
Check the drain line from the safe tray (if one is installed) is not blocked.
MAJOR FIVE YEAR SERVICE
It is recommended a major five year service be conducted on the water heater.
If this water heater is installed with an integrated or remotely installed in-series Everhot continuous flow gas booster, then for the booster‟s safe and efficient operation, it is recommended a five year service be conducted on the gas booster. Another type of in-series booster may have its own recommended service schedule. Refer to the Owner‟s Guide and Installation Instructions supplied with the booster.
Warning: Servicing of a water heater must only be carried out by qualified personnel. Phone Rheem
Service or their nearest Accredited Service Agent.
Note: The five year service and routine replacement of any components, such as the anode and relief valves, are not included in the Everhot warranty. A charge will be made for this work. Only genuine replacement parts should be used on this water heater.
The major service includes the following actions:
Replace the temperature pressure relief valve.
Inspect and flush the expansion control valve (if fitted). If required, replace the valve.
Inspect and if required, replace the anode.
If the anode is not replaced, it should be replaced within three years of this service (refer to “Anode
Inspection and Replacement” on page 15).
Check the electric heating unit for excessive calcium build up or corrosion and replace if necessary.
Check the solar control unit for correct operation.
Flush and bleed the solar collectors.
Clean the collector glass.
Visually check the unit for any potential problems.
Inspect all connections.
Check the drain line from the safe tray (if one is installed) is not blocked.
Note: The solar storage tank may need to be drained during this service. After the completion of the service, the solar storage tank will take some time to reheat the water by solar gain.
REGULAR CARE
12
TEMPERATURE PRESSURE RELIEF VALVE
This valve is near the top of the water heater and is essential for its safe operation. It is possible for the valve to release a little water through the drain line during each heating period. This occurs as the water is heated and expands by approximately 1/50 of its volume.
Continuous leakage of water from the valve and its drain line may indicate a problem with the water heater (refer to “Temperature
Pressure Relief Valve Running” on page 18).
Warning: Never block the outlet of this valve or its drain line for any
reason.
Operate the easing lever on the temperature pressure relief valve once every six months. It is very important you raise and lower the lever
gently.
DANGER: Failure to do this may result in the water heater cylinder
failing, or under certain circumstances, exploding.
Warning: Exercise care to avoid any splashing of water, as water
discharged from the drain line will be hot. Stand clear of the drain line‟s point of discharge when operating the valve‟s lever.
If water does not flow freely from the drain line when the lever is lifted, then the water heater must be checked. Phone Rheem Service or their nearest Accredited Service Agent to arrange for an inspection.
The temperature pressure relief valve should be replaced at intervals not exceeding 5 years, or more frequently in areas where there is a high incidence of water deposits (refer to “Water Supplies” on page 14).
EXPANSION CONTROL VALVE
In many areas, including South Australia, Western Australia and scaling water areas, an expansion control valve is fitted to the cold water line to the water heater. The expansion control valve may discharge a small quantity of water from its drain line during the heating period instead of the temperature pressure relief valve on the water heater.
Operate the easing lever on the expansion control valve once every six months. It is very important you raise and lower the lever gently. The expansion control valve should be checked for performance or replaced at intervals not exceeding 5 years, or more frequently in areas where there is a high incidence of water deposits.
COLLECTOR GLASS
Ensure the glass on your solar collectors is free of dust, salt spray or any other matter, which may reduce the effectiveness of the solar collectors. If the collector glass becomes dirty, hose down or if the solar collectors are accessible, wash the collector glass with water and a soft brush when the solar collectors are cool.
Have any trees trimmed which may shade the solar collectors.
Rheem solar collectors have passed the AS/NZS 2712 requirements for resistance to hailstone damage, so it is not normally necessary to fit a guard to a collector. Stone Guards are available to provide a level of protection to the collectors against vandalism or accidental damage. Refer to your local Solar Distributor for details.
water
heater
drain
line
lift until water
flows from the
drain line –
lower gently
REGULAR CARE
13
FLUSHING THE SOLAR COLLECTORS
It may be necessary to flush the solar collectors if there is sediment in the water supply. This should be conducted in the morning, within three hours of sunrise, when the water temperature inside the solar collectors is lower.
Open a hot water tap and allow the water to run for five (5) minutes prior to flushing the solar collectors.
Close the hot tap.
Wait a further five (5) minutes before attempting to flush the solar collectors.
This will assist in the transfer of any high temperature water in the solar collectors to the solar storage tank.
Warning: Exercise care, as water discharged from the solar collectors may be of a very high temperature.
To flush the solar collectors, follow the procedure “Bleeding the Solar Collectors” on page 9, allowing the
water to flow from the bleed valve drain line for five minutes before closing the bleed valve.
It is recommended to flush the solar collectors every five years. This will assist in keeping the solar collectors, solar cold pipe and solar hot pipe clear of sediment (refer to “Major Five Year Service” on page 11).
14
WATER SUPPLIES
This water heater must be installed in accordance with this advice to be covered by the Everhot warranty.
This water heater is manufactured to suit the water conditions of most public reticulated water supplies. However, there are some known water chemistries which can have detrimental effects on the water heater and its operation and / or life expectancy. If you are unsure of your water chemistry, you may be able to obtain information from your local water supply authority. This water heater should only be connected to a water supply which complies with these guidelines for the Everhot warranty to apply.
CHANGE OF WATER SUPPLY
The changing or alternating from one water supply to another can have a detrimental effect on the operation and / or life expectation of a water heater cylinder, a temperature pressure relief valve, a heating unit and a solar collector in a direct solar water heater system.
Where there is a changeover from one water supply to another, e.g. a rainwater tank supply, bore water supply, desalinated water supply, public reticulated water supply or water brought in from another supply, then water chemistry information should be sought from the supplier or it should be tested to ensure the water supply meets the requirements given in these guidelines for the Everhot warranty to apply.
ANODE
The vitreous enamel lined cylinder of the water heater is only covered by the Everhot warranty when the total dissolved solids (TDS) content in the water is less than 2500 mg/L and when the correct colour coded anode is used. If an incorrect colour coded anode is used in the water heater, any resultant faults will not be covered by the Everhot warranty. In addition, the use of an incorrect colour coded anode may shorten the life of the water heater cylinder.
The correct colour coded anode must be selected and fitted to the water heater in accordance with the following advice and the Anode Selection chart on page 14 for the Everhot warranty to apply to the water heater cylinder.
Total Dissolved Solids
Anode colour code
0 – 40 mg/L
Green
40 – 150 mg/L
Green or Black
150 – 400 mg/L
Black
400 – 600 mg/L
Black or Blue
600 – 2500 mg/L
Blue
2500 mg/L +
Blue (no cylinder warranty)
The changing of an anode must be carried out by a qualified person.
Note: Some water analysis reports may state the conductivity of the water rather than the level of total dissolved solids. Conductivity, measured in microsiemens per centimetre (µS / cm), is directly proportional to the TDS content of the water. TDS, in mg / L, is approximately 70% of the conductivity in µS / cm.
CONDUCTIVITY - µS/cm
TOTAL DISSOLVED SOLIDS & CONDUCTIVITY
(vitreous enamel lined water heater cylinder)
40 150 400 600
TOTAL DISSOLVED SOLIDS (TDS) - mg/L
ANODE SELECTION
warranty applies to a vitreous enamel lined water heater cylinder if the
correct coloured anode is used for the TDS / conductivity level of water
2500
3570
no warranty
applies
to a vitreous enamel lined water heater
cylinder
Blue
Black
Green
60 215 570 860
0
0
Blue
WATER SUPPLIES
15
ANODE INSPECTION AND REPLACEMENT
The anode installed in a vitreous enamel lined steel water heater cylinder will slowly dissipate whilst protecting the cylinder. The life of the cylinder may be extended by replacing the anode.
If the anode is not replaced during a five year service (refer to “Major Five Year Service” on page 11) then the maximum time after installation when the anode should be replaced is 8 years.
For water supplies which are either softened, desalinated or where the water supply may alternate between a water tank and a reticulated public supply or another supply, it is recommended the anode be replaced within 5 years of installation.
CAUTION
If the water supply has a TDS greater than 150 mg/L and a green anode has not been changed to a black anode, or if the TDS is greater than 600 mg/L and the anode has not been changed to a blue anode, there is the possibility the anode may become overactive and hydrogen gas could accumulate in the top of the water heater during long periods of no use.
If, under these conditions, the water heater has not been used for two or more weeks the following procedure should be carried out before using any electrical appliances (automatic washing machines and dishwashers) which are connected to the hot water supply.
The hydrogen, which is highly flammable, should be vented safely by opening a hot tap and allowing the water to flow. There should be no smoking or naked flame near the tap whilst it is turned on. Any hydrogen gas will be dissipated. This is indicated by an unusual spurting of the water from the tap. Once the water runs freely, any hydrogen in the system will have been released.
SATURATION INDEX
The saturation index is used as a measure of the water‟s corrosive or scaling properties.
In a corrosive water supply, the water can attack copper parts and cause them to fail.
Where the saturation index is less than –1.0, the water is very corrosive and the Everhot warranty does not apply to a copper sheathed heating unit or to a solar collector in a direct solar water heater system. A corrosion resistant heating unit must be used for the Everhot warranty to apply to the heating unit.
In a scaling water supply calcium carbonate is deposited out of the water onto any hot metallic surface.
Where the saturation index exceeds +0.40, the water is very scaling. An expansion control valve must be fitted on the cold water line after the non-return valve to protect and for the Everhot warranty to apply to the temperature pressure relief valve and water heater cylinder. Solar collectors in a direct solar water heater system should be covered when the water heater is not intended to be used for more than two weeks.
Where the saturation index exceeds +0.80, the Everhot warranty does not apply to a standard watts density heating unit or to a solar collector in a direct solar water heater system. A low watts density heating unit must be used for the Everhot warranty to apply to the heating unit.
Water which is scaling may be treated with a water softening device to reduce the saturation index of the water.
Refer to the Saturation Index chart on page 16.
Contact Rheem Service or their nearest Accredited Service Agent if a replacement heating unit is required.
Refer to the cold water connection detail on page 41 for the position of the expansion control valve.
WATER SUPPLIES
16
-1.0
no warranty applies to a:
temperature pressure relief valve or a
water heater cylinder unless an
expansion control valve is fitted.
no warranty applies to a:
-copper sheathed heating unit
-direct (open circuit) solar collector
SATURATION INDEX (SI)
SOLAR WATER HEATERS WITH ELECTRIC HEATING UNIT
WITHIN WARRANTY
SPECIFICATION
SATURATION INDEX
(calculated @ 80°C water temperature)
no warranty applies to a:
-standard watts density heating unit
-direct (open circuit) solar collector
+0.4 +0.80
very corrosive very scaling
scaling
corrosive
SUMMARY OF WATER CHEMISTRY ADVICE AFFECTING WARRANTY
The water heater and its components are not suitable for certain water chemistries. Those chemistries are listed below. If the water heater is connected at any time to a water supply with the following water chemistry, the Everhot warranty will not cover any resultant faults on the components listed below:
Water Chemistry
Component
Total Dissolved Solids (TDS) > 2500 mg/L
water heater cylinder
Total Dissolved Solids (TDS) not suitable for anode type
water heater cylinder
Saturation Index (SI) < -1.0
solar collector copper sheathed heating unit
Saturation Index (SI) > +0.4 (if an expansion control valve is not fitted)
water heater cylinder temperature pressure relief valve
Saturation Index (SI) > +0.8
solar collector standard watts density heating unit
Loading...
+ 36 hidden pages