Everflo EDS90, EDS60, EDS150, EDS180, EDS210 Installation Manual

...
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
INSTALLATION AND MAINTENANCE INSTRUCTIONS
ISSUE 3 MAY 2015
01
EVERFLO STAINLESS UV
PAGE CONTENT
2 Introduction
3 Storage, Handling & Supply Requirements
3 Component Table
4 Sitting the unit
5 General Installation
7-8 Discharge Arrangement
9 Technical Specications: Slimline - Direct & Indirect
10 Technical Specications: Direct & Indirect
11 Technical Specications: Solar Direct
12 Technical Specications: Solar Indirect
13 Solar Coil Installation
4 Solar High Limit
15 S-Plan Wiring Schematics
16 Y-Plan Wiring Schematics
17 - 18 Pre-Plumbed Wiring Schematics
19 Pre-Plumbed Installation
20 Technical Specications: Pre-Plumbed
21 System Fit Installation
22 Technical Specications: System Fit
23 Commissioning & Servicing
24 Fault Finding & User Instructions
25 - 27 Guarantee - Terms & Conditions
28 Technical Specication
29 - 30 Specication & Performance
31 Benchmark
32 Commissioning Check Sheet
33 Service Record
INTRODUCTION
The EVERFLO STAINLESS UV Unvented cylinder is made from
Duplex Stainless Steel for excellent corrosion resistance.
EVERFLO STAINLESS UV has a strong rust-proofed steel case
and is highly insulated with environmentally friendly foam.
EVERFLO STAINLESS UV is supplied complete with all the
necessary safety and control devices needed to connect
to the cold water mains. All are pre-adjusted. High quality
controls have been selected to combine high ow rate
performance with minimum pressure drop to make EVERFLO
STAINLESS UV perform well in all areas, even those with poor
water pressure.
EVERFLO STAINLESS UV is KIWA approved to show
compliance with Building Regulations G3+L.
Benchmark p laces responsibilities on both manufacturers and installers . The purpose is to ensure that customers are p rovided with the correct equipment for their ne eds, that it is installed, commissioned and ser viced in accordance with the manufacturer’s instructions by competent persons and that it meets the require ments of the appropriate Building R egulations. The Benchmark Checklis t can be used to demonstrate compliance with Building Regulations and should b e provided to the custome r for future reference.
Installers are required to carr y out installation, com missioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot water Industry Council who mana ge and promote the Scheme. Visit ww w.centralheating.co.uk for more info rmation.
IMPORTANT NOTE TO THE INSTALLER
Read these instructions before commencing installation.
Unvented cylinders are a controlled service as dened in the
latest edition of the building regulations and should only be
tted by a competent person.
The relevant regulations are: England and Wales – Building
Regulation G3, Scotland – Technical Standard P3, N Ireland –
Building Regulation Part F
After installation the Benchmark check list must be
completed and left, with these instructions, with the
householder for future reference.
IMPORTANT NOTE TO THE INSTALLER
Read these instructions before commencing installation. Unvented cylinders are a controlled service
as dened in the latest edition of the building regulations and should only be tted by a competent
person.
The relevant regulations are: England and Wales – Building Regulation G3, Scotland – Technical Standard
P3, N Ireland – Building Regulation Part F
After installation the Benchmark check list must be completed and left, with these instructions, with
the householder for future reference.
02
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
STORAGE PRIOR TO INSTALLATION
EVERFLO STAINLESS UV should be stored in its original packaging
in an upright position in an area free from excessive damp.
Regulations G3+L.
HANDLING PRODUCT
The EVERFLO STAINLESS UV should be carried upright where
possible. Assessments of risks for carrying the cylinder should
be conducted. Use more than 1 person for carrying where
appropriate. Always follow latest guide lines for lifting techniques,
to avoid injury and damage to the product.
WATER SUPPLY
EVERFLO STAINLESS UV operates at 3 bar (controlled by the inlet
control set) and is capable of delivering over 50 litres per minute.
The high quality inlet control set has been designed to make the
most of the ow rates available, however the performance of any
unvented system is only as good as the mains water supply. The
maximum possible water demand should be assessed, taking
into consideration that both hot and cold services are supplied
simultaneously from the mains.
The water supply should be checked to ensure it can meet these
requirements. If necessary, consult the local water company
regarding the likely pressure and ow rate availability.
If measuring the water pressure, note that a high static (no ow)
mains pressure is no guarantee of good ow availability. In a
domestic installation 1.5 bar and 25 l/min. should be regarded as
the minimum. The maximum mains pressure that the inlet control
set can accept is 12 bar.
Consideration should be given to upgrading existing ½” (15mm)
cold mains pipework to a larger size if the recommended
minimum pressure/ow rate is not being achieved.
ELECTRIC SUPPLY
The EVERFLO STAINLESS UV requires 240 Volt electrical supply for
the standard Incoloy immersion elements. The electrical supply
to each immersion heater must be fused at 13A via a double
pole isolating switch to BS 3456. The cable must be at least
2.5mm2 heat resistant (85°C HOFR) sheathed ex complying to BS
6141:1981 Table 8.
UNPACKING THE UNIT
EVERFLO STAINLESS UV comes complete with the ttings required
to complete the installation. Please see over for component
content list.
High ow rate inlet control set
TS201-533
Temperature and pressure relief valve
TS202
Acetal tundish 15 x 22 mm
TS3
Incoloy long life
3 kW immersion heater
TS9 - DIRECT TS10 - INDIRECT
Two port valve
TS5
Dual thermostat
US201
High Limit thermostat
TS28
Installation &
Maintenance Instructions
Expansion Vessel
• 60, 90, 120 & 150 ltr units - 12 ltr vessel TS212
• 180, 210 & 250 ltr units - 18 ltr vessel TS219
• 300 ltr units - 25 ltr vessel
TS224
03
EVERFLO STAINLESS UV
COMPONENT CONTENT TABLE
Inlet Control set
Temp & Pressure relief valve
Tundish
Expansion vessel
Immersion Heater (Direct)
Immersion Heater (Indirect)
Two Port Valve
Dual Thermostat
Single High Limit Stat
Sensor pocket retaining bungs
Robo-Kit
TP9000
TP5000
Installation & Maintenance Instructions
Slimline Direct Models (Electric)
Slimline Indirect Models
Direct Models
Indirect Models
Solar Direct Models
Solar Indiect Models
Indirect pre-plumbed
models - 1 zone heating
Indirect pre-plumbed
models - 2 zone heating
Solar indirect pre-plumbed models - 1
zone heating
Solar indirect pre-plumbed models - 2
zone heating
Direct M odels (Elect ric) Direct S olar Models (Ele ctric + Coil) Indirec t Models (Single Co il) Indirec t Solar Models ( Twin Coil)
04
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
SITTING THE UNIT
EVERFLO STAINLESS UV can supply outlets above it or at some
distance from it. Site the unit to minimise “dead leg” distances,
especially to the point of most frequent use.
Outlets above the EVERFLO STAINLESS UV will reduce the outlet
pressure available by 0.1 bar for every 1m of height dierence. The
unit should be protected from frost. Particular care is needed if
sitting in a garage or outbuilding. All exposed pipework should be
insulated. EVERFLO STAINLESS UV must be installed VERTICALLY
on a at base capable of supporting the weight of the cylinder
when full. See technical specication section (page 27-28) for
weights. The minimum recommended cupboard size is 650mm
square.
NOTES: The pressure reducing valve, non-return valve and expansion relief valve are combined together in the inlet control set.
On 60 – 180 litre sizes there is no dedicated secondar y return boss and the secondary return circuit should be tee’d into the cold feed pipe just above the drain elbow.
SCHEMATIC DIAGRAM
Access for maintenance of the valves should be considered.
Consideration should be given to position of discharge pipes
(tundish), drain valves - shall be positioned away from electrical
components.
The immersion heaters are 375mm long and care should be taken
to ensure that they can be withdrawn for servicing if required.
The discharge pipework from the safety valves should fall
continuously and terminate safely.
IMMERSION
HEATER
COLD
MAIN ISOLATING VALVE
PRESSURE REDUCING VALVE
NON
RETURN
VALVE
EXPANSION RELIEF VALVE
TUNDISH
TEMPERATURE & PRESSURE RELIEF VALVE
BALANCED COLD CONNECTION
COLD INLET VIA DRAIN
NON RETURN VALVE
BRONZE PUMP
SECONDARY RETURN CIRCUIT ( 210, 250 & 300 L SIZES )
DUAL STAT
2 PORT VALVE
BOILER FLOW
BOILER RETURN
HOT OUTLET
EXPANSION VESSEL WITH WALL BRACKET
05
EVERFLO UNVENTED HOT WATER CYLINDERS
GENERAL INSTALLATION
COLD MAINS PIPEWORK
Run the cold main through the building to the place where the
EVERFLO STAINLESS UV is to be installed. Take care not to run the
cold pipe near hot water or heating pipework so that the heat
pick-up is minimized. Identify the cold water supply pipe and t
an isolating valve (not supplied).
A 22mm BS1010 stopcock can typically be used but a 22mm
quarter turn full bore valve would be better as it does not
restrict the ow as much. Do not use “screwdriver slot” or similar
valves. Make the connection to the cold feed of the cylinder
and incorporate a drain valve. Position the drain valve no higher
than the cold inlet to ensure sucient draining of cylinder when
required. Position the inlet control just ABOVE the Temperature &
Pressure Relief Valve (TPRV) mounted on the side of the cylinder.
This ensures that the cylinder does not have to be drained down
in order to service the inlet control set. Ensure that the arrow
points in the direction of the water ow. Select a suitable position
for the expansion vessel. Mount it to the wall using the bracket
attached to the vessel. Use suitable ttings capable of supporting
full vessel weight (and with appropriate consideration to wall
material). Ensure the pre-charge in the vessel is set at 3 Bar.
Connect the expansion vessel to the cold feed pipework between
the inlet control set and the cold inlet on the cylinder. Ensure that
the top of the vessel is accessible for servicing.
CONNECTING TO THE CYLINDER
All of the pipework connections on the cylinder are 22mm
compression and supplied complete with gland nuts and olives, in
the Accessory Kit box. Only connect 22mm Table X copper tube to
these connections.
Cut the tube with a pipe cutter and ensure no sharp edges or
burrs protrude. Slide both gland nut and olive onto the tube and
push tube fully home into the connection, ensuring the tube
end fully bottoms on the connection recess. Smear the outer
wall of the olive with plumbing paste and tighten gland nut
in the prescribed manner. Upon lling/commissioning, ensure
all connections are completely watertight. Note: No control or
isolation valve should be tted between the expansion relief valve
and the storage cylinder. The relief valve connections should not
be used for any other purpose.
(expansion vessel not to scale)
Turn to test
Cold
Mains In
Balanced Cold Connection
Outlet to Cylinder
Expansion Relief to Tundish
Expansion Relief Connection
06
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
BALANCED COLD CONNECTION
If there are to be showers, bidets or monobloc taps in the
installation then a balanced cold supply is necessary. There is a
22mm balanced connection on the inlet set.
HOT WATER PIPEWORK
Run the rst part of the hot water distribution pipework in 22mm.
This can be reduced to 15mm and 10mm as appropriate for the
type of tap etc. Your aim should be to reduce the volume of the
hot draw-o pipework to a practical minimum so that the time
taken for the hot water is as quick as possible. Where monobloc
mixing taps and showers are used, these should be installed to
comply with the Water Supply (Water Fittings) Regulations 1999.
If these devices are supplied with un-balanced supplies there
should be single check valves installed at both inlets, to stop over
pressurising of either supply.
PRIMARY COIL CONNECTIONS FOR INDIRECT UNITS
For Solar input models refer to pages 13-14 before making any
connections.
Connect the primary connections (Indirect only) using the
compression connections provided. The primary circuit must
be positively pumped. Gravity circulation is not suitable. Either
primary connection may be used as the primary ow, reheat times
are not eected. The primary circuit can be open vented or sealed,
with up to a maximum pressure of 3.5 bar. If you seal the primary
circuit an additional expansion vessel and safety valve is required.
The boiler may be Gas, Electric or Oil but must be under eective
thermostatic control. Uncontrolled heat sources such as some
AGA’s, back boilers, solid fuel stoves, etc. are NOT SUITABLE. Please
contact our Technical department for guidance. Connect the two
port zone valve ( indirect only ) into the primary ow pipework.
The direction of ow arrow should be towards the primary ow
connection.
SECONDARY CIRCULATION
EVERFLO STAINLESS UV can be used with secondary circulation.
An appropriate WRAS approved bronze circulator should be
used in conjunction with a non-return valve to prevent backow.
On large secondary circulation systems it may be necessary
to incorporate an extra expansion vessel into the circuit to
accommodate the increased system water volume. Secondary
circulation should be avoided on Direct electrically heated units
being used on o-peak electricity taris.
A secondary return boss is tted as standard on 210, 250 & 300 ltr
units. On smaller sizes, tee into the cold feed pipe above the drain.
IMMERSION HEATERS
Only immersion heaters with a thermal cut-out may be used. To
help ensure this, the immersion heaters have a special 1¾” thread.
They are rated at 3kW at 240V and are of a low noise Incoloy
construction.
They have both a thermostat and a high limit cutout. Please order
the correct replacement via ourselves; tting non-approved
immersions may aect your guarantee. When tting, ensure the
‘O’ ring is positioned correctly on the head of the immersion
heater and lubricate before tting. Fit it by hand until almost
home then tighten gently as the ‘O’ rings will seal easily. The
electrical supply to each immersion heater must be fused at 13A
via a double pole isolating switch to BS 3456. The cable must be
2.5mm
2
heat resistant (85°C HOFR) sheathed ex complying to BS
6141:1981 Table 8. Do not operate the immersion heater/s until the
unit is full of water. Do not operate the immersion heater/s if any
sterilisation liquid is in the cylinder as this will cause premature
failure.
ELECTRICAL CONNECTIONS
Complete the wiring – use the appropriate wiring diagrams on
page 15 - 18.
07
EVERFLO STAINLESS UV
DISCHARGE ARRANGEMENT
Position the inlet control group so that the discharge from both
safety valves can be joined together via a 15mm end feed Tee (see
diagram above). Connect the Tundish and route the discharge
pipe. The discharge pipework must be routed in accordance with
Part G3 of schedule 1 of the Building Regulations. The information
that follows is not exhaustive and if you are in doubt you should
seek advice. The two safety valves will only discharge water under
fault conditions. When operating normally water will not be
discharged. The tundish should be vertical, located in the same
space as the unvented hot water storage system and be tted
as close as possible to, and lower than, the safety device, with
no more than 600mm of pipe between the valve outlet and the
tundish. The tundish should be positioned away from electrical
devices.
Any Discharge should be visible at the tundish. The tundish should
be located such that any discharge is visible. In addition, where
discharges from safety devices may not be apparent, e.g. people
with impaired vision or mobility, consideration should be given to
the installation of a suitable safety device to warn when discharge
takes place, e.g. electronically operated.
Diagram of a typical discharge pipe arrangement (extract from Building Regulation G3)
Note: The discharge will consist of scalding water and steam. Asphalt, roong felt and non-metallic rainwater goods may be damaged by such discharges.
Note: D2 pipe from tundish is now allowed to be installed in soil stacks within premises. This activity is not recommended by Kingspan as discharge from T&P may continue for long periods of time. It is the installer’s responsibility to ensure the discharge pipework can support the discharge for prolonged periods. If used follow guidance on mechanical seal without water trap given in G3 Building Regulations. As discharge can be in excess of 90
o
C discharge into plastic pipework is also not recommended.
08
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
The discharge pipe (D2) from the tundish should:
A) Have a vertical section of pipe at least 300mm long, below the
tundish before any elbows or bends in the pipework.
B) Be installed with a continuous fall of at least 1 in 200 thereafter.
The discharge pipe (D2) from the tundish should be of metal or
other material that have been demonstrated to be capable of
withstanding temperatures of the water discharged.
The discharge pipe (D2) should be at least one pipe size larger
than the nominal outlet size of the safety device unless its total
equivalent hydraulic resistance exceeds that of a straight pipe
9m long i.e. discharge pipes between 9m and 18m equivalent
resistance length should be at least two sizes larger than the
nominal outlet size of the safety device, between 18 and 27m at
least 3 sizes larger, and so on. Bends must be taken into account
in calculating the ow resistance. Refer to diagram 1, Table 1 and
the worked example. An alternative approach for sizing discharge
pipes would be to follow BS6700 Specication for design
installation, testing and maintenance of services supplying water
for domestic use within buildings and their curtilages.
The discharge pipe (D2) should terminate in a safe place where
there is no risk to persons in the vicinity of the discharge.
Examples of acceptable discharge arrangements are:
a. To a trapped gully with the end of the pipe below the xed
grating and above the water seal.
b. Downward discharges at a low level; i.e. up to 100mm above
external surfaces such as car parks, hard standings, grassed
areas etc. are acceptable providing that where children play or
otherwise come into contact with discharges, a wire cage or
similar guard is positioned to prevent contact whilst maintaining
visibility.
c. Discharges at a high level; e.g. in to metal hopper and metal
down pipe with the end of the discharge pipe clearly visible or
onto a roof capable of withstanding high temperature discharges
of water and 3m from any plastic guttering systems that would
collect such discharges.
d. Device to warn when discharge takes place.
WORKED EXAMPLE
The example below is for G1/2 temperature relief valve with a
discharge pipe (D2) having 4 No. elbows and length of 7m from
the tundish to the point of discharge.
From Table 1:
Maximum resistance allowed for a straight length of 22mm
copper discharge pipe (D2) from a G1/2 temperature relief valve is:
9.0m. Subtract the resistance for 4 No. 22mm elbows at 0.8m each
= 3.2m. Therefore the maximum permitted length equates to:
5.8m. 5.8m is less than the actual length of 7m therefore calculate
the next largest size. Maximum resistance allowed for a straight
length of 28mm pipe (D2) from a G1/2 temperature relief valve
equates to: 14m. As the actual length is 7m, a 28mm (D2) copper
pipe will be satisfactory.
TABLE 1
Sizing of copper discharge pipe ‘D2’ for a temperature
relief valve with a G1/2 outlet size (as supplied).
Size of discharge pipework
Maximum length of straight pipe (no bends or elbows)
Deduct the gure below from the maximum length for each bend or elbow in the discharge pipe
22mm Up to 9m 0.8m
28mm Up to 18m 1m
35mm Up to 27m 1.4m
09
EVERFLO STAINLESS UV
EVERFLO STAINLESS UV  SLIMLINE DIRECT
EVERFLO STAINLESS UV  SLIMLINE INDIRECT
B
A
120.00
F PTRV BOSS
1 2
D A B
C G
F D A B C G
22mm HOT DRAW - OFF
22mm SECONDARY RETURN (not always tted. See table)
22mm COLD FEED WITH DIP PIPE TO DEFLECTOR IN BOTTOM OF CYLINDER
22mm HOT DRAW - OFF
22mm SECONDARY RETURN (not always tted. See table)
F PTRV BOSS
1 2
22mm COLD FEED WITH
DRY STAT POCKET
DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
120.00
SECOND IMMERSION HEATER (not always tted. See table)
25.0˚
40.0˚
45.0˚
35.0˚
15.0˚
40.0˚
45.0˚
15.0˚
B
A
120.00
F PTRV BOSS
1 2
D A B
C G F D A B C G
22mm HOT DRAW - OFF
22mm SECONDARY RETURN (not always tted. See table)
22mm COLD FEED WITH DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
22mm HOT DRAW - OFF
22mm SECONDARY RETURN (not always tted. See table)
F PTRV BOSS
1 2
22mm COLD FEED WITH
DRY STAT POCKET
DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
120.00
SECOND IMMERSION HEATER (not always tted. See table)
30.0˚
50.0˚
50.0˚
10.0˚
25.0˚
40.0˚
45.0˚
35.0˚
15.0˚
F PTRV BOSS
1 2
22mm COLD FEED WITH
DRY STAT POCKET
DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
120.00
50.0˚
10.0˚
CODE H EIGHT D IAMETER A B C D G
EDS60 673 478 175 210 N/F N/F 483
EDS90 1048 478 175 210 610 N/ F 858
EDS120 1236 478 175 210 710 N /F 1046
EDS150 1424 478 175 210 810 N /F 1234
EDS180 1674 478 175 210 910 N /F 1484
EDS210 1987 478 175 210 1100 1500 1797
F D A B C G
22mm HOT DRAW - OFF
22mm SECONDARY RETURN (not always tted. See table)
F PTRV BOSS
1
2
22mm COLD FEED WITH
DRY STAT POCKET
DIP PIPE TO DEFLECTOR IN BOTTOM OF CYLINDER
120.00
CODE HEI GHT DIAME TER A B C D F G
ENS60 673 478 3 40 38 0 44 0 395 N/F 483
ENS90 104 8 478 340 380 4 40 39 5 N /F 858
ENS120 1236 478 340 38 0 4 40 395 N/F 1046
ENS150 1424 478 380 420 520 520 N/F 1234
ENS180 1674 478 380 420 520 610 N/F 1484
ENS210 1987 478 380 420 520 710 1500 1797
TECHNICAL SPECIFICATIONS
10
EVERFLO STAINLESS UV
UNVENTED HOT WATER CYLINDERS
EVERFLO STAINLESS UV  DIRECT
EVERFLO STAINLESS UV  INDIRECT
25.0˚
40.0˚
45.0˚
35.0˚
15.0˚
F PTRV BOSS
1 2
22mm COLD FEED WITH
DRY STAT POCKET
DIP PIPE TO DEFLECTOR IN BOTTOM OF CYLINDER
120.00
50.0˚
10.0˚
15.0
0
25.0
0
30.0
0
45.0
0
160mm
195mm
FD
22mm HOT DRAW - OFF
F PTRV BOSS
22mm SECONDARY RETURN (not always tted. See table)
22mm COLD FEED WITH
DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
1
2
SECOND IMMERSION HEATER (not always tted. See table)
CODE HEI GHT DIAME TER D F
ED90 718 550 N /F N/ F
ED120 906 550 N /F 510
ED150 1093 550 N/F 610
ED180 1281 550 N/F 710
ED210 1469 550 1000 810
ED250 1719 550 1250 950
ED300 2032 550 1500 1100
22mm COLD FEED WITH
DIP PIPE TO DEFLECTOR
IN BOTTOM OF CYLINDER
22mm SECONDARY RETURN (not always tted. See table)
22mm HOT DRAW - OFF
F PTRV BOSS
1
2
DRY STAT POCKET
SECOND IMMERSION HEATER (not always tted. See table)
F E D C B A
CODE HEIGHT D IAMETER A B C D E F
EN90 718 550 290 330 390 3 45 N /F N/F
EN120 906 550 2 90 33 0 39 0 34 5 N /F N/F
EN150 1093 550 330 370 465 385 N /F N/F
EN180 1281 550 330 370 46 5 385 N/F N/ F
EN210 1469 550 365 4 05 4 65 46 5 N/ F 1150
EN250 1719 550 365 4 05 4 65 56 0 950 1400
EN300 2032 550 365 4 05 4 65 66 0 1100 160 0
All Dimensions are in mm and are of the cased unit. N/F = not tted.
TECHNICAL SPECIFICATIONS
11
EVERFLO STAINLESS UV
TECHNICAL SPECIFICATIONS
EVERFLO STAINLESS UV  SOLAR DIRECT
AB GCDEF
22mm HOT DRAW-OFF
22mm COLD FEED
WITH DIP PIPE
TO DEFLECTOR
IN BOTTOM
OF CYLINDER
F PTRV BOSS
1
2
DRY STAT POCKET
25.0015.0
0
40.0
0
45.0
0
35.0
0
22mm SECONDARY RETURN (not always fitted. See table)
25.0015.0
0
40.0
0
45.0
0
35.0
0
CODE HEI GHT DIA METER A B C D E F G
ESD150 1093 550 2 90 3 45 39 0 610 N/F 892 390
ESD180 1281 550 2 90 3 45 4 45 710 N/F 1080 39 0
ESD210 1469 550 3 65 420 500 810 1150 12 68 465
ESD250 1719 550 3 65 420 670 1045 1400 1519 465
ESD30 0 2032 550 36 5 420 670 1100 1600 1831 465
Loading...
+ 26 hidden pages