Ever POWERLINE 31 Instruction Manual

Page 1
Page 2
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
2
TABLE OF CONTENTS
TABLE OF CONTENTS ...................................................................................................................................... 2
INTRODUCTION ................................................................................................................................................. 3
GENERAL FEATURES OF THE UPS UNIT ................................................................................................... 4
SAFETY INSTRUCTIONS AND RECOMMENDATIONS ............................................................................ 5
TECHNICAL DESCRIPTION .......................................................................................................................... 11
ELEMENTS OF THE UPS .............................................................................................................................. 11
Front panel ...................................................................................................................................................11
Rear panel ....................................................................................................................................................13
INSTALLATION ................................................................................................................................................ 14
UNPACKING THE PRODUCT ...................................................................................................................... 14
INSTALLING THE UPS UNIT ....................................................................................................................... 15
CONNECTING THE UPS TO THE MAINS .................................................................................................. 15
Connecting elements .....................................................................................................................................16
DESCRIPTION OF THE OPERATION OF THE POWER SUPPLY UNIT ............................................... 17
MODES OF UPS OPERATION ...................................................................................................................... 18
STANDBY mode (mode "00") .......................................................................................................................18
BYPASS mode (mode "01") ..........................................................................................................................18
LINE mode (mode "02") ...............................................................................................................................19
BATTERY mode (mode "03")........................................................................................................................20
BATTERY TEST Mode (mode "04") .............................................................................................................20
SERVICE BYPASS Mode ..............................................................................................................................21
EMERGENCY Mode .....................................................................................................................................21
PROTECTIONS AND SAFEGUARDS .......................................................................................................... 22
Overload protection ......................................................................................................................................22
Short-circuit protection ................................................................................................................................22
EPO ..............................................................................................................................................................23
COMMUNICATION WITH EXTERNAL MANAGEMENT/CONTROL SYSTEMS ............................... 24
COMMUNICATION USING RS 232 ............................................................................................................. 24
SNMP/HTTP NETWORK MANAGEMENT CARD ..................................................................................... 24
Installing the management card ...................................................................................................................25
CONFIGURATION OF UPS UNIT PARAMETERS ................................ ..................................................... 26
OPERATING INSTRUCTIONS ....................................................................................................................... 27
UPS OPERATION WITH POWER GENERATORS ..................................................................................... 28
STORAGE, MAINTENANCE AND TRANSPORT ....................................................................................... 28
DISPOSAL ....................................................................................................................................................... 28
TECHNICAL PARAMETERS .......................................................................................................................... 29
LEGAL REGULATIONS AND WARRANTY ................................................................................................ 32
DECLARATION OF CONFORMITY ............................................................................................................ 32
WARRANTY ................................................................................................................................................... 32
Page 3
EVER POWERLINE 31 UPS Range Operating Manual
3
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
INTRODUCTION
Thank you for purchasing the EVER POWERLINE 31 UPS system. This UPS system has been designed and engineered to meet your expectations and provide the highest standard of protection against power failure.
This manual contains all relevant information to ensure correct and safe operation of the unit. Please read this manual carefully and thoroughly prior to using the EVER POWERLINE unit. This will help to operate the unit and correctly and safely.
The POWERLINE 31 units are ONLINE (VFI) class units designed to work with equipment supplied from ~ 230 VAC single-phase electric power mains. These units are designed to work with particularly sensitive equipment. It is a range of advanced power supply units designed mainly for computer servers, computer networks and data processing systems.
Page 4
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
4
GENERAL FEATURES OF THE UPS UNIT
The POWERLINE 31 UPS systems consist of the following functional blocks:
system of rectifiers with PFC (power factor correction) battery charger, battery set, frequency converter produced in high frequency IGBT technology, automated by-pass system (static BYPASS), manual (service) bypass system, microprocessor-based control system with measurement circuits,
Upon converting AC power (from the three-phase mains), the input rectifier supplies the unit's internal direct current bus. The applied power factor correction system allows to radically reduce the consumption of reactive power from the mains. The DC voltage bus is the basic source of power for the inverter system which in turns generates single-phase, sinusoidal AC voltage with model parameters to be used to power the loads. Batteries are charged with an independently operating charger. The charging power has a very low variable component, translating into extended battery life. The microprocessor-based control system ensures precision and reliability of the entire power supply system.
The automated bypass system helps to increase the overall operating security of the entire system. In case of the failure of the inverter, the power from mains is supplied directly to the receivers. In this way the automated by-pass system works as an additional passive protection of the load.
The additional manual bypass allows switching over completely to supplying power to the connected loads from the mains only. That way, maintenance and service works can be completed conveniently.
Page 5
EVER POWERLINE 31 UPS Range Operating Manual
5
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
SAFETY INSTRUCTIONS AND RECOMMENDATIONS
A) General information
CAUTION! Before starting the procedures described in this manual,
please read the general safety instructions (including the instructions found in this document), health & safety information, environmental protection information and legal regulations that may apply. Always observe the instructions and recommendations found in these documents.
CAUTION! It is strictly forbidden for the user to perform any repairs, as this would constitute a health hazard and may result in death. Any repairs and replacement of batteries should be carried out only by suitably qualified service technicians, with professional licenses required by law.
CAUTION! The unit should be operated and stored in conditions complying with the requirements set in the specification (technical documentation).
CAUTION! The UPS is disconnected from the mains only when the power lead is disconnected removed from the mains socket.
CAUTION! The unit is equipped with an internal power source (batteries) or it may operate in combination with a fixed, external source of power (battery packs). Dangerous voltage may be present at the output terminal(s), even if the unit has been disconnected from the mains.
CAUTION! The user should place warning labels on all remotely installed primary isolation switches in order to warn electrical service technicians that the circuit is powered by a UPS unit. The following (or equivalent) text should be used on such warning labels:
DISCONNECT THE UPS SYSTEM BEFORE STARTING WORK ON THIS CIRCUIT.
Page 6
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
6
CAUTION! Opening the unit’s casing may result in electric shock.
CAUTION! Do not touch any electrical connectors, terminals and internal
metal elements unless power supply has been properly disconnected.
CAUTION! All openings and spaces designed to provide access to the unit's electrical connections must remain covered (with applicable covers). Failure to observe this requirement may create hazard potentially resulting in injury or death for persons who touch such connectors. It may also cause damage to the unit.
CAUTION! In the event of a short circuit, the resulting high current may cause serious burns or scalds.
CAUTION! There are no user-serviceable parts inside the UPS unit.
CAUTION! The POWERLINE range of UPS units is not intended to work
directly with medical equipment, life-supporting equipment or any other equipment that may have effect on health.
B) Installation information and requirements
CAUTION! The POWERLINE range of UPS units may only be installed and maintained by suitably qualified service technicians.
CAUTION! Before installation of the UPS unit, the staff and users must
become familiar with the Health and Safety regulations when working and handling electrical equipment up to 1 kV voltage.
CAUTION! Before connecting any cables or making any connections within the UPS unit or in the electrical system, make sure there is no dangerous voltage on electrical terminals and cables in the system.
Page 7
EVER POWERLINE 31 UPS Range Operating Manual
7
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
CAUTION! The UPS may only be connected to a power system with indicated rated voltage, with a suitable grounding connection installed. The facility's electrical system to which the UPS unit is connected must be fitted with overload and short-circuit protection.
CAUTION! Only TN-S or TN-C-S configuration is allowed on the UPS unit's input side, and only TN-S configuration is allowed on the UPS unit's output side.
CAUTION! No extension cords should be used for connecting the UPS unit.
CAUTION! Installing a UPS unit in proximity of flammable materials or substances is strictly prohibited!
Technicians must not work alone in hazardous conditions that may be dangerous
to health and/or life.
Shortly after the UPS unit has been moved from a cold environment to a warm
environment, moisture condensation may appear. The UPS unit must be completely dry before installation and operation. The acclimatization time should be at least 2 hours.
UPS units and battery packs must not be installed in humid environment. UPS units and battery packs must not be installed in places where they would be
exposed to direct sunlight. They must not be installed near sources of heat.
Ventilation openings in the UPS unit casing must not be blocked. Always observe
distances to ventilation openings specified in the manual.
Before connecting the units, is necessary to check the condition of all leads,
cables, connectors, sockets and plugs, as well as that of the unit itself.
The unit must be connected to a power circuit with a PE grounding conductor.
Failure to observe this requirement may result in electric shock.
To reduce the risk of electric shock (in case the grounding cannot be checked),
the unit must be disconnected from the mains before installation or connecting to other equipment. The power lead may only be connected again after making all required connections.
Page 8
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
8
The electric system's grounding conductor leads the leakage current away from
the receivers. The leakage currents of all loads connected to the UPS unit's output are totalized in the UPS unit's power lead. The summary leakage current may trigger protective devices (RCD) and result in disconnecting power to the loads.
A UPS unit is a fixed connection device; consequently, a breaker should be used
in the fixed cabling.
When connecting and disconnecting signal cables, all actions should be
performed with one hand only (if feasible). This is to avoid electric shock when touching two surfaces with different electrical potentials.
Connecting leads should be placed so that people walking over them will not step
or trip on them.
An emergency power-off button (EPO), dedicated to the UPS system, should be
installed in the building's electrical system. This is to allow disconnecting, in emergency, the UPS unit from the connected loads regardless of the mode in which the UPS is operating.
To minimize the risk of fire, connections should only be made to circuits (electrical
systems) whose rating is adequate for the connected loads, with properly selected overcurrent protection. Additionally, the breaker should feature at least a 3 mm insulating air gap.
C) Operation of the UPS unit
Health and Safety regulations and guidelines specified in the UPS unit operating
manual must be observed when handling and operating the UPS unit.
All these instructions must be executed step by step. If any problems emerge
when executing the instructions given in this document, please contact EVER service support (www.ever.eu).
Never disconnect the grounding at the UPS unit or at the terminals of the
building's electrical system, as this will disable the UPS unit's protective grounding.
There may be voltage on the UPS unit's output terminals, even if the UPS is
disconnected from the building's electrical system (due to presence of power in the unit's internal batteries and/or battery packs).
Liquids and foreign bodies must not be allowed to penetrate the UPS casing.
Page 9
EVER POWERLINE 31 UPS Range Operating Manual
9
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
WARNING: This is a C3 category UPS. For commercial and industrial use in
secondary environment. Additional precautions or limitations in installation may be required to prevent the emission of interferences.
D) Maintenance, repair and breakdown information
Dangerously high voltages are present in the UPS unit. Only qualified service
technicians may perform maintenance works.
CAUTION - Risk of electric shock! Even if the unit has been disconnected from
the mains (from terminals of the electrical power supply), parts inside the UPS unit remain connected to the batteries, which may create hazards. Disconnect the battery and/or battery packs before carrying out any servicing and/or maintenance. Make sure there is no dangerous voltage on the DC circuit internal elements.
WARNING: Only properly authorized and qualified service technicians who have
legally required protection gear may replace batteries.
CAUTION - Risk of electric shock! Dangerous voltage may be present between
the battery circuit and the grounding point!
Batteries have high short-circuit current and pose a risk of electric shock. The
following precautions should be taken when working with batteries:
remove jewellery, watches, rings and other metal items, only use tools with insulated handles.
When replacing batteries, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
 Always dispose of used batteries according to relevant instructions.  WARNING: Disposing of batteries in a fire may result in explosion.  WARNING: Opening or damaging batteries may cause electrolyte to leak;
electrolyte is harmful to skin and eyes, and may also be toxic.
To avoid the danger of fire and damage to the mains or power supply system,
always replace broken or blown fuses with fuses of the same type and parameters.
Disconnect the device from the mains before cleaning. Do not use liquid or
sprayed cleaning agents.
UPS units may only be disassembled by suitably qualified service technicians.
Page 10
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
10
E) Transport and packaging requirements
Exercise particular care when transporting the equipment, due to its heavy weight. Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit is very heavy and has been fitted with a wheel set to facilitate moving. The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS unit if the deadline has passed and the batteries have not been recharged. In such cases always contact service support.
Page 11
EVER POWERLINE 31 UPS Range Operating Manual
11
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
TECHNICAL DESCRIPTION
ELEMENTS OF THE UPS Front panel
The user's interface is the unit's front panel (Fig. 1) made up from an LCD display and a 4-button keyboard.
These controls are used to monitor the UPS unit’s parameters and modes of operation. They also allow modification of some of those parameters. Correct use of the interface and the meaning of individual states and parameters are described below.
Figure 1: LCD display
Table 1 presents the description of the keys of the control panel and Table 2 presents the description of information icons of the LCD display.
Table 1. Functions of the control panel buttons
No.
Symbol
Name
Description
1 SELECT
If the UPS unit is in BYPASS or STANDBY mode, the keys can be used to configure the unit's parameters: output voltage, frequency and BYPASS mode options. Press ENTER to confirm the selection (2).
2
ENTER
If the UPS unit is in BYPASS mode, press ENTER to accept parameters selected with the SELECT button.
3 OFF
If power supply parameters are correct, press OFF to switch the PSU unit into BYPASS and switch off the inverter. If BYPASS mode is available, the output is powered from the BYPASS line.
4
ON
For switching the UPS unit on. Deactivates sound alarms.
5 - LCD
LCD display.
Page 12
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
12
Table 2. Description of LCD display icons
Display
Description
Input*
Input voltage value
Input voltage frequency
Indicates excessive input voltage; not displayed for correct voltage
Indicates insufficient input voltage; not displayed for correct voltage
Output
Output voltage value
Output voltage frequency
Load
Percentage level of load of the UPS unit in relation to power, in W or VA
UPS output short circuit indicator
UPS overload indicator
Batteries
Indicates battery voltage
Battery charge level
Indicates overcharging of batteries; the UPS unit switches to battery mode
Indicates discharged batteries; the UPS unit is about to switch off
Mode/Error/Warning
Indicator for modes, error codes and warnings
Inverter
Indicates inverter operation
Bypass
Indicates BYPASS system operation
Input voltage, frequency, BYPASS mode option
If the UPS unit is in STANDBY or BYPASS mode, one of the four values of output voltage can be selected
If the UPS unit is in STANDBY or BYPASS mode, one of the two values of output frequency can be selected
If the UPS unit is in STANDBY or BYPASS mode, one of the two options for the BYPASS mode can be selected: off / on
* For POWERLINE 10-31 PUS units the information apply to phase C, and for POWERLINE 15-31 and 20-31 PSU units the information apply to phase A
Page 13
EVER POWERLINE 31 UPS Range Operating Manual
13
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
Rear panel
a) b)
Fig. 2: View of the rear panel
a) POWERLINE 10-31, b) POWERLINE 15-31 / 20-31
1. Cable mounts.
2. Cover of input and output terminal blocks.
3. Input breaker.
4. Communication interface for parallel operation (optional).
5. Expansion card slot.
6. RS 232 communication interface.
7. Fans.
8. Maintenance bypass switch.
9. External battery.
10. EPO.
Page 14
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
14
INSTALLATION
CAUTION! Before installation of the UPS unit, the user must get familiar
with the safety instructions in the present chapter and with general health and safety (H&S) recommendations.
UNPACKING THE PRODUCT
The UPS unit must be properly examined upon delivery or handover. Although care has been taken to ensure proper and safe packaging, the product may have suffered damage due to incorrect conditions in transit. If any damage is determined, inform the carrier or seller.
The UPS unit is packaged to ensure safe transportation (also by fork lift trucks). To unpack the unit:
carefully cut the bands fixing the unit to the pallet, remove the cardboard box, remove foam pieces protecting it during transportation, following OHS rules pick the UPS unit up from the wooden pallet and place on
the floor (possibly with the help of several other coworkers),
using the castor wheels bring the UPS unit to its place of installation, lock the castor wheels.
Keep the packaging for future transportation operations. Check carefully the contents of the packaging. The packaging should contain:
The UPS, RS 232 communication cable, User manual, Warranty card, Installation guidelines.
Page 15
EVER POWERLINE 31 UPS Range Operating Manual
15
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
INSTALLING THE UPS UNIT
When selecting the place and method of installation, always take into consideration the considerable weight of the UPS unit. The UPS unit should only be used in premises where the dust, temperature, and humidity levels are within the specification. Appropriate cooling conditions must be provided to ensure correct
operation of the UPS unit. For this reason, the UPS unit’s vents and venting openings
must be uncovered and free of obstruction at all times and the distance between the UPS unit and other objects should be as recommended (see technical parameters
table).
CAUTION! Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
CONNECTING THE UPS TO THE MAINS
The electrical system on the premises must comply with the installation guidelines that are applicable to the installed UPS unit. The guidelines are included in a separate document supplied with the product.
CAUTION! Connecting of the UPS unit may be carried out only by suitably qualified and authorized service technicians.
CAUTION! The UPS is disconnected from the mains only when the power lead is disconnected removed from the mains socket.
It is recommended that the protection systems available in the building's electric
system are used as one of the UPS unit’s protection levels. Their parameters should
be selected to meet the requirements of the load connected to the wiring system and the type the load (according to the installation guidelines).
Page 16
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
16
Connecting elements UPS POWERLINE 10-31
Figure 3: Connecting elements – POWERLINE 10-31
1 – Input Ground
6 – Jumper (optional parallel operation)
2 – Input Neutral
7 – Jumper (optional parallel operation)
3 – Input Phase A
8 – Output line
4 – Input Phase B
9 – Output Neutral
5 – Input Phase C
10 – Output Ground
POWERLINE 15-31 and UPS POWERLINE 20-31
Figure 4: Connecting elements – POWERLINE 15-31 and POWERLINE 20-31
1 – Input Ground
7 – Negative terminal of the battery module
2 – Input Neutral
8 – Output Line
3 – Input Phase A
9 – Output Neutral
4 – Input Phase B
10 – Output Ground
5 – Input Phase C
JP1 – Jumper (optional parallel operation)
6 – Positive terminal of the battery module
JP2 – Jumper (optional parallel operation)
Page 17
EVER POWERLINE 31 UPS Range Operating Manual
17
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
FIRST START-UP
When the UPS unit is started for the first time, it may be necessary to leave it connected to the mains to charge the batteries. To do this simply connect the UPS unit's mains lines. The UPS unit will charge its batteries regardless of the mode of operation (ONLINE - the UPS is on and the inverter is operating, OFFLINE - the UPS is off, the inverter is not operating, the output is supplied by the bypass).
CAUTION! The batteries reach their full capacity after approximately a month of mains operation mode.
DESCRIPTION OF THE OPERATION OF THE POWER
SUPPLY UNIT
The POWERLINE UPS unit is a modern electronic device, an autonomous source of ~230 V sine voltage. This unit belongs to a series of uninterruptible ONLINE class UPS devices whose characteristic feature is constant transformation of power. This feature allows POWERLINE units to condition the power in the output line. Regardless of voltage fluctuations and distortions on the input, the POWERLINE units generate, throughout operation, sinusoidal waveform of ~230 V in the output. The UPS unit operates in the Line mode (without drawing any energy from the batteries) in a wide range of voltages ~304÷478 V (voltage between phases), supplying receivers with ~230 V. Another advantage of constant power transformation featured in ONLINE UPS units is that there is no interruption when switching to another source of power (mains - battery). Loads connected to the UPS output do not even detect switching between the mains and battery operation.
Page 18
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
18
MODES OF UPS OPERATION
Table 3. UPS operation modes, their codes and signaling
Code
Operation status
Signaling
00
STANDBY (zero) mode
None
01
BYPASS mode
Single sound signal every 2 minutes
02
NETWORK mode
None
03
BATTERY
mode
0~20% battery charge level
Single sound signal every second
21%~100% battery charge level
Single sound signal every 4 seconds
04
Battery test mode
None
STANDBY mode (mode "00")
Figure 5: STANDBY MODE (MODE "00")
In the STANDBY (zero) mode the UPS unit's LCD panel shows information on the battery charge level and the mains parameters (voltage and frequency). The UPS unit is not supplying power to the output.
BYPASS mode (mode "01")
Figure 6: BYPASS MODE (MODE "01")
Page 19
EVER POWERLINE 31 UPS Range Operating Manual
19
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
The UPS unit goes into BYPASS mode when the inverter is overloaded, the permissible temperature is exceeded or the inverter is damaged, and also when the unit is switched off with the OFF pushbutton in the control panel. In BYPASS mode the voltage is supplied to the output directly from the input line via a mechanical switch (relay). If the UPS unit has entered BYPASS mode due to overload or exceeded permissible temperature, the unit will cyclically check the load and the inverter's temperature. When these parameters are back to standard levels, the UPS unit will restart the inverter. In BYPASS mode the UPS unit does not protect its receivers from power losses. The voltage from the input line is directed to the unit's output through an internal filter.
LINE mode (mode "02")
Figure 7: LINE MODE (MODE "02")
Upon connecting the UPS unit to the mains, voltage is supplied to its output and batteries are being charged. In such cases the output receives power from the internal BYPASS line. Switch the UPS unit logically on to put it in the line mode (press the ON pushbutton in the control panel for about 1 second). Once the UPS unit's self-diagnostics is over, the device is ready to operate and supplies power to the output (after the power from the input lines is transformed) through the inverter system. The UPS unit switches to battery mode if the mains parameters are incorrect (voltage and/or frequency). When the UPS unit is in the Line mode, power is supplied to the output.
Page 20
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
20
CAUTION! Switching the UPS unit with the OFF pushbutton, located in the control panel, will not stop providing power to the device's output. The voltage present in the output disappears only when the input line is disconnected.
BATTERY mode (mode "03")
Figure 8: BATTERY MODE (MODE "03')
If the input supply lines do not meet the mains correctness criteria, the UPS unit will switch to the back-up mode (battery operation). In the battery mode, the inverter unit supplies the energy stored in the batteries (after it has been transformed) to the output. The duration of the time power is being supplied in this way depends on the power accumulated in the batteries (specifically the number of batteries and battery packs used).
If there is no power in the mains, the UPS unit is switched on just like in the Line mode, except that once the self-diagnostics is over, the LCD display shows the view as in Fig. 8.
BATTERY TEST Mode (mode "04")
In the BATTERY TEST mode, the LCD panel displays the same information as in the BATTERY mode. This mode's code is "04". When the UPS unit operates in this mode, the indicators of insufficient or excessive input voltage are not operating.
The BATTERY TEST mode is switched on for about 10 seconds, by pressing the "ON" button when the UPS unit is in the Line mode (mode "02").
Page 21
EVER POWERLINE 31 UPS Range Operating Manual
21
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
SERVICE BYPASS Mode
When in this mode, the UPS unit can be serviced, without having to disconnect receivers connected to its output.
CAUTION! When the UPS unit is in SERVICE BYPASS mode, the receivers powered from its output are not protected against power losses in the input line in any way. In this mode the UPS unit is completely disconnected from the output.
EMERGENCY Mode
or
Figure 9: EMERGENCY MODE
When EMERGENCY mode is on, the LCD panel displays an error code and emits sound signals. Table 4 presents the explanation of error codes and sound signals.
Page 22
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
22
Table 4. Description of UPS unit statuses and signalization.
Code
UPS unit status
Signaling
01
Overload in Line mode, UPS in BYPASS mode
Double sound signal every second
02
Overload in Line mode, inverter still operating
Double sound signal every second
03
Overload in BATTERY mode, early warning
Double sound signal every second
05
Incorrect DC bus voltage
Continuous sound signal
06
Faulty inverter operation
Continuous sound signal
07
Overload in BATTERY mode, output disconnected
Continuous sound signal
08
Maximal temperature exceeded
Continuous sound signal
09
Short circuit in output
Continuous sound signal
10
Faulty communication *
Continuous sound signal
11
Battery circuit open
Continuous sound signal
12
Inverter relay damaged
Continuous sound signal
14
Battery thyristor damaged
Continuous sound signal
15
Parallel operation error
Continuous sound signal
22
Faulty fan operation
Single sound signal every second
23
Battery and charger damaged
Single sound signal every second
* Only frame and error code are displayed for code 10. Other parameters are not displayed.
PROTECTIONS AND SAFEGUARDS Overload protection
Overload is indicated by a corresponding message on the LCD display and a sound signal (see Table 4).
If the overload is within 105% - 130% of the rated load, the UPS unit will switch to BYPASS mode after 10 minutes. If the load exceeds 130%, the UPS unit will switch to BYPASS mode after 1 second and disconnect the power in the output after 1 minute.
Short-circuit protection
A short circuit is indicated by the UPS unit with a corresponding code in the LCD display and a sound signal. The power to the UPS unit's output is disconnected if short circuit occurs. If the UPS unit is switched off with the OFF button while the signal is on and the short circuit is not corrected, the UPS unit will switch to BYPASS mode, which triggers automatic input fuses.
Page 23
EVER POWERLINE 31 UPS Range Operating Manual
23
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
EPO
The Remote Emergency Power Off (Remote EPO) mechanism cuts the power supply from the UPS output to loads in extreme situations or in emergency (e.g. fire).
The mechanism can be activated by the means of opening contacts of the external EPO connector (a trigger).
Figure 10: EPO triggering signaling
If EPO is triggered when the UPS unit operates in Line mode, the unit will switch to STANDBY mode. However, if EPO is triggered when the UPS unit is in BATTERY mode, the unit will switch off completely. The output is switch again only after the user's intervention (the EPO circuit is reset and the UPS unit is restarted).
If the UPS unit is in STANDBY mode, EPO signaling is switched off by pressing the OFF button. The UPS unit switches to BYPASS mode, which is a precondition to restart the unit.
When the UPS unit is OFF, once the EPO circuit is reset, the unit can be restarted following the standard procedure.
The EPO connection contacts show safe voltage levels isolated from the remaining UPS unit systems.
CAUTION! The EPO circuit must be a separate circuit and it is forbidden to connect it with other installations.
Page 24
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
24
COMMUNICATION WITH EXTERNAL
MANAGEMENT/CONTROL SYSTEMS
COMMUNICATION USING RS 232
POWERLINE UPS units have extensive management options. The user can use the RS 323 interface. In order to ensure proper communication, the UPS unit must be connected to a free port on your PC, with the supplied communication cable. After connecting the cable switch the UPS unit on, start the PC and install the software, as described in the instruction manual or following the prompts of WinPower installer.
The up-to-date software and the installation procedure is available at
www.ever.eu.
SNMP/HTTP NETWORK MANAGEMENT CARD
The network management card is optional and can be installed by the user in service. This card is an electronic circuit used to integrate the UPS unit with an Ethernet-type computer network. The network card is mounted in the special slot on the back wall of the UPS unit. By using a network card the user is able to control the UPS unit from any computer in the network. This arrangement is most typically used for a central power supply system, or whenever there is a requirement to provide remote control for the power supply system (for instance in cases where there is a considerable distance between the server room and the location of the UPS unit).
More information on the management card can be found in the manual supplied with the card.
Page 25
EVER POWERLINE 31 UPS Range Operating Manual
25
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
Installing the management card
1. Switch off the UPS with the push button on the control panel.
2. Switch off the UPS unit's input protections.
3. Wait around 30 sec. (the time needed to discharge the internal capacities of the UPS unit).
4. Undo the screws of the cover which protects the card slot and remove the cover (Fig. 11a).
5. Insert the card into its slot (Fig. 11b and 11c).
6. Install the card slot cover to the rear panel (Fig. 11d).
7. Switch on the UPS unit's input protection.
8. Switch on the UPS with the push button on the control panel.
Fig. 11: Installation of the management card.
Page 26
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
26
CONFIGURATION OF UPS UNIT PARAMETERS
The UPS unit's user may use WinPower to alter some of the unit's parameters. To do this, the UPS unit must be connected to the PC with a cable provided by the manufacturer and the user must be logged in as the administrator. The administrator's default password is "Administrator". After logging in the user may change the password.
Parameters that can be modified by the user in the software: the range of input frequencies for BYPASS mode, the range of voltages for BYPASS mode, control panel buttons and sound alarm settings, behavior of the unit when switching off.
Page 27
EVER POWERLINE 31 UPS Range Operating Manual
27
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
OPERATING INSTRUCTIONS
CAUTION! This is a product designed for commercial and industrial
applications, meeting the Second Environment levels. Additional precautions or restrictions to be observed during installation may be required to prevent the emission of interferences (PN-EN 62040-2 standard).
CAUTION! There are no user-serviceable parts inside the UPS unit.
Damaging the warranty seal will render any product warranty void. All repairs of electrical appliances should be carried out by qualified service
personnel only.
The UPS unit may operate below the expected performance parameters if the
connected load requires high pulsed power. In practice this means that even if
the average power of the load is within the permitted UPS unit’s range, the
load could still shut the UPS down. The reason for this is that such a high level of power drawn instantaneously by the load considerably exceeds the UPS unit’s power rating. This may happen in the case of:
CRT TVs and monitors (when they start up, the CRT undergoes
degaussing, a process that requires very high instantaneous power),
laser printers (the process of heating up the drum),  other products with similar operating characteristics.
Hence, when the UPS unit operates with loads other than loads typical for PCs, the compatibility of the USP unit and the receiver must be tested. To do this connect the receiver to the UPS units and test it in all operating modes (starting up, switching off, standby, etc.).
Page 28
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
28
UPS OPERATION WITH POWER GENERATORS
The POWERLINE UPS units are ONLINE class units. The unit has been designed to tolerate voltage fluctuations in the range of ~ 304 ÷ 478 V (voltage between phases)
and changes in the frequency of ±4 Hz in relation to the model frequency of 50 Hz.
When working with a power generator, frequency changes are variable over time and are directly dependent on the load changes. If the generator voltage frequency changes exceed this tolerance, the power supply unit will identify this value as incorrect and switch to battery operation mode.
STORAGE, MAINTENANCE AND TRANSPORT
The power supply unit should be stored in a cool and dry place, in its working position, with batteries fully charged up:
at a temperature between 0°C ÷ +30°C, the battery should be charged every 6
months;
at a temperature between +30°C ÷ +40°C, the battery should be charged every 3
months.
The device should be transported in its original packaging, under conditions concordant with those set in the product specification. EVER Sp. z o.o. shall not be liable for mechanical damages arising during the transport of the appliance without its packaging of if the packaging is not original or is incomplete.
DISPOSAL
The appropriate utilization of used electric and electronic equipment helps to protect human health and the natural environment against the negative effects caused by the presence of hazardous materials and components, and the improper storage and processing of such equipment.
Law dated 29.07.2005 on used electric and electronic equipment, Art. 22.1 Item 1,2.
The crossed out waste container symbol means that, in the European Union, a used product should be handed over to a special waste handling outlet. This requirement applies both to the UPS unit itself and to all other accessories marked with this symbol. Such products should not be disposed of together with unsorted
municipal waste. Method of safe removal of the batteries from the appliance:
The battery should be removed from the appliance by an authorized service outlet or by a duly authorized electrician.
Page 29
EVER POWERLINE 31 UPS Range Operating Manual
29
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
TECHNICAL PARAMETERS
Table 5. POWERLINE 31 technical parameters.
PARAMETERS \ TYPE
POWERLINE 31
POWERLINE 10-31
POWERLINE 15-31
POWERLINE 20-31
Part number
T/PWRLTO-3110K0/00
T/PWRLTO-3115K0/00
T/PWRLTO-3120K0/00
Output Power (Apparent / Active)1)
10 kVA
7 kW
15 kVA
10,5 kW
20 kVA
14 kW
GENERAL DATA AND ENVIRONMENTAL
Topology
VFI (on-line, VFI-SS-111)
Number of phases (in/out)
3 / 1
Housing Type
Tower
Max efficiency (double conversion mode)
> 90%
Operating temperature 2)
0 ÷ +40 °C
Storage temperature
0 ÷ +40 °C
Relative humidity during operation
< 95% (non-condensing)
Relative humidity during storage
< 95% (non-condensing)
Operating elevation 3)
< 1000 m
Protection level
IP20
Environment of installation
Separate rooms with low contamination level
Cooling
Forced, internal fans
Temperature of the cooling air
< 25°C
Quantity of heat released for nominal work conditions
< 2400 BTU / h
< 3600 BTU / h
< 3600 BTU / h
INPUT
Rated input voltage
3 x 400 V AC
Input voltage range and tolerance
304 ÷ 478 V AC ± 2%
Rated current
12 A
18 A
24 A
Input voltage rated frequency
50 / 60 Hz
Input voltage frequency range and tolerance
46 ÷ 54 / 56 ÷ 64 Hz ± 1 Hz
Input Power Factor
> 0,95
OUTPUT
Rated output voltage
230 V AC
Output voltage range and tolerance ­normal mode
208 V AC / 220 V AC / 230 V AC / 240 V AC ± 1 %
(Output voltage value set with LCD panel. Default 230 V AC)
Output voltage range and tolerance ­battery mode
208 V AC / 220 V AC / 230 V AC / 240 V AC ± 1 %
(Output voltage value set with LCD panel. Default 230 V AC)
Rated current
43 A
65 A
87 A
Shape of output voltage (battery mode / normal mode)
sine-wave / sine-wave
Output voltage rated frequency
50 / 60 Hz
Output frequency range and tolerance ­mains operation mode
Synchronously
Output frequency range and tolerance ­battery mode
50 Hz ± 0,2 Hz
Output voltage regulation
< 1%
Output voltage distortion THDu
1,2% for Pmax (line)
< 5% (non-line by PN-EN 62040-3)
Crest Factor CF
3:1
Transfer time to battery mode
0 ms
Transfer time to normal mode
0 ms
Overload capability
4)
105 % ÷ 130 % - 10 min
> 130% - 1 s
Page 30
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
30
PARAMETERS \ TYPE
POWERLINE 31
POWERLINE 10-31
POWERLINE 15-31
POWERLINE 20-31
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
None
External Batteries
1 x 20 VRLA 12V
External battery modules (EBM)
Yes
Maximum number of EBMs
2
Backup time
Depends on the type and number of batteries
Nominal voltage DC circuit
240 V DC
Maximum charging time - after discharging at 80 % Pmax
Depends on the type and number of batteries
Maximum charging current
4 A
MECHANICAL SPECIFICATIONS
Dimensions (H x W x D)
717 x 260 x 570 mm
Net Weight 39 kg
55 kg
Gross Weight 49 kg
65 kg
Transport Dimensions (H x W x D)
1000 x 450 x 725 mm
Position in which devices transported
Vertical
PROTECT
Input over current protection
Short-circuit / Overload –
Three-pole breaker
D50 A / 400 V AC
Short-circuit / Overload – Three-pole breaker
D100 A / 400 V AC
Surge Protector
Output over current protection
Inverter working – electronic short-circuit and overload protection
ACCESSORY AND EXTRA FUNCTIONS
Power supply connection
3P5W
screw terminals M8 (L, N, JP1, JP2)
screw terminals M6 (PE)
Output connection (number and type of sockets )
1P3W
screw terminals M8 (L, N, JP1, JP2)
screw terminals M6 (PE)
EPO
Yes (NC)
Signalling
Acoustic and optical; LCD display
Communications interfaces
RS232, network management card SNMP / HTTP (optional),
AS 400 card - optional
Software
WinPower
CERTIFICATION
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Notice: The manufacturer reserves the right to change the above listed parameters without notice.
ADDITIONAL NOTES:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load current.
2)
With internal batteries 5 ÷ 35 °C. Constant exposure of the device to environment temperature over +25°C results in reducing
battery life.
3)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.
4)
With prolonged operation with recommended load.
Page 31
EVER POWERLINE 31 UPS Range Operating Manual
31
www.ever.eu
Technical Support, tel.: +48 61 6500 400
2016-01-15 13:16
HOW TO SOLVE PROBLEMS
POWERLINE UPS units have been designed for long-term, automatic operation and will alarm the user about problems that may appear during operation. Usually, the alarms displayed on the LCD panel do not indicate changes in input voltage parameters. Most frequently, these are preventive alarms aiming to alert the user to the possible causes of faulty operation of the UPS unit. Active alarms are accompanied by sound signals. Table 6 presents the most typical statuses and alarms, their expected causes and proposed troubleshooting activities.
Table 6. Typical statuses and alarms, their causes and recommended activities.
Problems
Possible cause
Solution
Error code "08", continuous sound signal
The UPS unit is in error status due to exceeded permissible temperature
Make sure the UPS unit is not overloaded, the fans are not blocked and the ambient temperature is not to high. Wait about 10 minutes to let the UPS unit cool down before switching it on again. If the problem persists, contact the technical support.
Error code "09", continuous sound signal
Short circuit in the UPS unit's output
Disconnect all receivers. Switch the UPS unit off. Before reconnecting the receivers make sure they are not faulty and that there are no internal errors in the UPS unit. If there are problems with the UPS unit, contact the technical support.
Error code "05" or "06", continuous sound signal
The UPS unit is in error status due to internal error
Contact the technical support
UPS unit starts up in BATTERY mode (mode "03")
Input voltage or frequency exceeds permissible limits
Check power source
Error code "07", continuous sound signal
Receiver is overloaded or faulty
Check the receivers and disconnect non-critical ones. Recalculate the load power and reduce the number of receivers connected to the UPS unit. Make sure none of the receivers is faulty.
Warning - code "23", sound signal every second
Batteries or charger is faulty
Contact the technical support
Error code "11", continuous sound signal
Low level of batteries or batteries are disconnected
Check batteries level
UPS unit will not start despite correct parameters of the mains
Service bypass switch is faulty
Contact the technical support
Reduced back-up time Batteries have not been fully
charged yet
Leave the UPS unit connected to the mains for at least 10 hours, until the batteries are fully charged
UPS unit is overloaded
Check the receivers and disconnect non-critical ones
Battery capacity reduced due to long-term use
Replace the batteries
UPS unit will not start when the ON button is pressed
The "ON" button is pressed and released too quickly
Keep the "ON" button pressed longer than 1 second
Batteries are disconnected from the UPS unit or batteries voltage is too low
Make sure the batteries are connected properly or recharge them UPS unit fault
Contact the technical support
When contacting the technical support, please have the basic information at hand:
- UPS unit model and serial number
- when the problem occurred
- complete description of the problem, including error codes, sound signals, the status of mains and loads. If your UPS unit was designed for long back-up times, it may be
necessary to have information on the applied batteries.
Page 32
EVER POWERLINE 31 UPS Range Operating Manual
2016-01-15 13:16
Technical Support, tel.: +48 61 6500 400
32
LEGAL REGULATIONS AND WARRANTY
DECLARATION OF CONFORMITY
The UPS structure conforms to the appropriate subject matter standards. The declaration of conformity is published at www.ever.eu.
WARRANTY
A separate document attached to the product constitutes the warranty. The document must meet all formal requirements (e.g. the fields: serial number, model/type, date of sale, and dealer stamp must be filled out). The manufacturer has made every effort to ensure that the offered products are free of defects in materials and workmanship. The liability of the manufacturer under this warranty is limited to the repair or replacement of products containing such defects. The method to remove such defects shall be determined by the manufacturer. The guarantee shall not cover appliances with mechanical damages that were improperly maintained or used, or that were modified in any way by the user. EVER Sp. z o.o. does not provide any guarantees or warranties, including the guarantees of fitness for sale or for any specific purpose, other than the provisions set out in the warranty card. EVER Sp. z o.o. shall not be liable for any direct, indirect, extraordinary, coincidental, or consequential losses resulting from the use of the UPS unit, even if notified of the possibility of such losses being incurred. The company shall not be held liable for any costs, such as the loss of profits or earnings, loss of equipment or equipment usage, software, data, costs of replacement products, claims of third parties, or for any other costs whatsoever.
Loading...