EVAX 25, 50, 150, 200, 100 Installation Manual

Installation Manual: EVAX 25/50/100/150/200 Voice Evacuation System
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the EVAX 25/50/100/150/200 Voice Evacuation Interface System.
All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC), NFPA 101 (Life Safety Code) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.
1. Description
is designed to be used in conjunction with a UL listed Fire Alarm Control Panel (FACP) to provide a Listed Voice Evacuation Alarm System.
The FACP provides all initiating circuitry and a signaling circuit to the EVAX 25/50/100. The EVAX 25/50/100 provides its own internal supervision as well as supervision for its speaker lines. Any fault is reported back to the FACP. In normal standby the supervisory circuit from the panel is connected to a matching EOLR. Should the EVAX 25/50/100 suffer an internal failure or should there be any fault on the speaker line a contact would open and the FACP would report it as an open fault for that circuit.
The EVAX 25/50/100 is designed to be powered from 120 VAC at 60 Hz. The EVAX 25 will provide 25W to the speaker circuit. The EVAX 50 will provide 50W. The EVAX 100 will provide 100W. Speakers may be 25 or 70 Vrms (jumper selected, 25V is factory set).
Note: Models may be supplied with transformers wired for 240 VAC for those regions where this is required. Please refer to Ratings section for Primary Power differences.
MODELS: The EVX-25/50/100 are complete Voice Evacuation Modules, EVX-25E/50E/100E are complete modules with built-in tone generators capable of operating as a stand-alone Voice Evacuation Systems with only tone and microphone amplication. They are not equipped with power transformers or cabinets. The EVAX 25/25EM/50/50EM/100/100EM/150/150EM/200/200EM are complete Voice Evacuation Panels. The EVX-50E/100E are capable of operating as slave ampliers when connected to the EVX-100 which supplies
source audio to the slaves. Different Model numbers are derived from the amplier sizes used together: These multiple amplier congurations are factory setup and pre-wired. When using any EVX-25E/50E/100E refer to installation instructions 5403672.
EVAX 150 contains one (1) EVX-100, one (1) EVX-50E and two (2) speaker circuits EVAX 200 contains one (1) EVX-100, one (1) EVX-100E and two (2) speaker circuits EVAX 150E contains one (1) EVX-100E, one (1) EVX-50E and two (2) speaker circuits EVAX 200E contains two (2) EVX-100E and two (2) speaker circuits.
The EVAX 100 / 200 are tested compliant with UL 464 520 Hz Low Frequency Signal for Sleeping Areas with the following:
Potter Signal Series: FASPKR, SPKSTR Gentex Series: SSPKCLP, SSPK24WLP System Sensor Series: SPCW, SPCR, SPR and SPW
2. Installation and Wiring
Install equipment in a clean, dry environment, avoid installation where equipment could be subjected to vibration. Remove electronic assemblies from the enclosure prior to any drilling or punching of the enclosure. Where possible, make all cable entries from the rear or
sides. Before making any modications to the enclosure, be certain that they will not interfere with assemblies or batteries
Install equipment adjacent to FACP or FACP Annunciator to ensure proper reporting and display of system Fault conditions.
1. Connect speaker lines to TB1 - 5(+) & 6(-), observe polarity and ensure all speakers are connected likewise. For Class "A" (Style "Z")the returns are TB1 - 7(-) & 8(+).
2. Ensure that the microphone is attached to connector P2. If Microphone is not installed ensure that switch SN1 - 8 is in the OFF position.
3. Attach the appropriate EOLR for the FACP to TB3 - 3 & 4 and TB3 - 5 & 6. The TB3 term 5 & 6 value must be placed at the end of the speaker line as well. You must use EOLR value as specied in the FACP Manufacturer’s installation instructions for the
indicating appliance circuit. All accessory cards such as the EVX-ZM, EVX-SL8, EVX-IL8 or EVX-OL8 must be mounted within the same cabinet or if mounted in a separate cabinet, be in the same room with all wiring run in conduit within 20 feet.
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
5403670 Rev A 12/17
PAGE 1 OF 8
INSTALLATION MANUAL: EVAX 25/50/100/150/200
ON
4. Connect FACP signaling circuit to TB1 - 3(+) & 4(-), Alarm Polarity (alarm polarity is shown).
5. Connect 120 VAC, 60 Hz, power to the white Terminal Block on the left side of the cabinet. Terminals are Hot / Neutral / Ground, from left to right. Pre-wired to unit and chassis on opposite side of Terminal Block. Wire colors Black / White / Green from left to right. Max. 10 AWG
6. Once power is on to the unit, connect battery wiring harness, Red (+) / Black (-). Observe polarity. Minimum battery size is 24V 7Ah. Maximum size to house in cabinet is 12Ah, battery box required beyond 12Ah (use two (2) 12V batteries connected in series, see typical installation diagram). If the unit does not have its own batteries and relies on an external power supply
with battery back-up, ensure that switch SN1 - 7 is in the OFF position. NOTE: Wiring for batteries is Non Power-Limited. Care
must be taken to ensure that all Power-Limited wiring maintain a minimum spacing of ¼" from any Non Power-Limited wiring. If batteries must be located in separate enclosure, it must be in the same room with a separate conduit run for battery wiring
only.
Once all power and circuits are connected, the Green LED will remain on to indicate that the EVAX 25 / EVAX 50 / EVAX 100 is fully operational and all circuits are nominal.
7. Terminal Designations
TB1:
TER 1 & 2 - Power Input 24-32V AC/DC (Note 1, 4) TER 3 & 4 - FACP Signal Circuit Input - 10mA max. (Alarm Polarity shown) (Note 1, 4)
TER 5 & 6 - 25/70 Vrms Speaker Loop Style Y/Z (Class "A"/"B" start) (Note 2, 4) TER 7 & 8 - 25/70 Vrms Speaker Loop Style Z (Class "A" return) (Note 2, 4)
TB3:
TER 1 & 2 (Note 1, 4)
Optional FACP Supervisory Circuit (See nstallation instructions page X diagram 2 for
details (32V - 0.4A max)). Factory set for
None - J1 (Installed)
Contact Ratings: 1A @30VDC
Connect to Resistive Load, Class II Power Or Power Limited Sources Only. Interconnected Equipment Must be in the Same Room and
Mounted Within 20'.
TER 3 & 4
FACP Signal/Supervisory Circuit EOLR
TER 5 & 6
Matching EOLR
TB1
1 2 3
4 5 6 7 8
12 3
1
2
TB3
LED 1
YEL
LED2
GRN
LED 3
RED
J1
FAULT
NORMAL
ALARM
5678
4
J2
123
70V 25V
TER 7 (Note 1, 3, 5)
General purpose output (pulls to circuit neg
on fault condition 32V - 0.2A max). Not for
Fire Protective Signaling use.
TER 8 (Note 1, 3, 5)
Trouble input +24 VDC 5mA
NOTES
1 - Intended for connection to Listed Class
2 - Class 3 (Power Limited) sources only
2 - Power Limited
3 - Non-Supervised
4 - Supervised 5 - Terminating equipment must be installed
in same room as EVAX 25/50/100
MSG GAIN
Switch Network Detail
P3
P5
SN1
S1
MIC
GAIN
SN2
18
P9
OFF
J3
DR
LED 5
LED 4
P8
P4
J5
11 10
9 8 7 6 5 4 3 2 1
TB2
P2
Field wiring connections:
#6-32 wire clamp screw 14-18 AWG #8-32 wire clamp screw 12-18 AWG
Horizontal wire entry terminal 18-26 AWG
Wire gauge determined by circuit load
TB2:
TER 1 - Circuit Neg
TER 2 (NOTE 1, 3) Aux Audio Input (0.5V nominal) (1VRMS - 1mA max.)
TER 3 (NOTE 1, 3, 5)
PreAmp In/Out (600 Ohm 0dBm)
TER 4 (NOTE 1, 3, 5) Master - Programmable +24VDC Active Slave - +24VDC Input
TER 5 (NOTE 1, 3, 5) Signal Active Master - Out / Slave - In
TER 6 (NOTE 1, 3) Aux Audio Enable
(+24V)(32V - 5mA max.)
TER 7 (NOTE 1, 3) Aux Signal Activate
(+24V) (32V - 5mA max.)
TER 8 (NOTE 2, 3, 5) Common Alarm Voltage +24V condition (0.1A)
TER 9 (NOTE 2, 3) Common Int V+ (+24V) disconnected in alarm condition (0.1A)
TER 10 (NOTE 2, 3) V+ (+24V 0.1A) TER 11 (NOTE 5) Mic PTT (+24V 0.1A)
P3/4: 14 Pin Connector Connection to
Expander Modules
P5: 10 Pin Connector HMX Connection
P8: I2C 10 Pin Connector EVX-ZM/SL8/
IL8/OL8
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
5403670 Rev A 12/17
PAGE 2 OF 8
INSTALLATION MANUAL: EVAX 25/50/100/150/200
Factory Default Switch/Jumper Settings:
SN1 SN2
1 = OFF 25V 1 = OFF 2 = OFF 2 = ON
3 = OFF 3 = OFF Std. Evac Message
4 = OFF Normal Op 4 = OFF 5 = OFF Do Not Use 5 = OFF Do Not Use 6 = OFF No AC Fault Delay 6 = ON Message On 7 = ON Battery connected 7 = OFF 8 = ON Mic connected 8 = ON
OPTIONS:
AUX +24VDC OUTPUT - TB2-4, 8, 9 & 10 These terminals provide a max. 200 mA of regulated 24VDC power for auxiliary functions. Do not exceed 200 mA load combined on these terminals. For connection to Listed General Signal devices only (Non-Fire Protective Signaling applications). Terminal 4
activation is programmed in the system conguration. Standard conguration is programmed for TB2-4 to go active +24VDC under these conditions: Aux Signal Active, Aux Audio Enable and Bell Circuit Active.
CONNECTION OF AN AUX AUDIO SOURCE - TB2-1 & 2 An aux audio source from additional paging equipment may be connected to the EVAX 25 / 50 / 100 to augment an existing paging system. It is not intended for continuous signal input, but may be used for paging applications. For such an operation the Aux Audio Enable input, TB2-6, must be powered from Int V+, TB2-9. This is to ensure that in the event of an alarm, the aux audio will not override the evacuation signal. See Wiring Diagram 5 for connection detail.
Do Not Use
2 Cycles Temporal Tone
3 Message
Repeats
J1 A/B:
1 - 2 = SHORT
J2
25 VRMS 2 - 3 = SHORT
70 VRMS 1 - 2 = SHORT
To change output voltage Power unit down, move J2 to new position, change SN1-1 to match.
J3
2 - 3 = SHORT R
Shorting block must be in the R position
J5
1 - 2 SHORT = Ground Fault Enable
OPTIONAL SUPERVISORY CIRCUIT - TB3-1 & 2 In place of normal supervision via the signaling circuit, an alternate method may be employed using any supervisory circuit from the
FACP. Connection would be made to Terminal Block 3, Ter. 1 and 2. This would provide a normally closed connection to the EOLR on Ter. 3 and 4. The relay contact in the circuit will open upon any trouble condition and report an open circuit trouble to the FACP. NOTE: Jumper shorting blocks A and B must be removed from J1 if a circuit is to be connected in this manner. See Optional
Supervisory Circuit Application (Wiring Diagram 2) for connection detail.
OPERATION
In normal standby the Green LED will remain on. In alarm condition the Red LED will remain on as long as the unit is in alarm. Green LED will modulate with the audio level.
Default Factory Alarm Sequence settings: (Alarm Tone - 2 cycles Temporal Whoop, Message On - 3 Repeats)
Alarm Tone / Digital Message plays / Alarm Tone / Digital Message plays / Alarm Tone / Digital Message plays / unit reverts to Alarm Tone until alarm condition is cleared. If the Mic is keyed it will override both the tone and the message so a direct broadcast may be made. If this occurs during the initial sequence the digital message will be reset and will not repeat. When the Mic is keyed or when the message is played the Green LED will dim. The intensity of the Green LED will vary with the level of the broadcast
audio. Under a fault condition, the Yellow LED will remain on. The Green LED will ash. The number of ashes display a code depending on the specic type of fault. When there is a fault condition the contact connecting the FACP signal circuit to the
EOLR will open indicating the fault to the panel which will provide annunciation. During a ground fault condition, Yellow LED 4 will illuminate.
Electrical Ratings: EVAX 25/25E EVAX 50/50E EVAX 100/100E
Primary Input Voltage 120 Vac @ 60 Hz 120 Vac @ 60 Hz 120 Vac @ 60 Hz Primary Input Current 0.8 A @ 120 Vac 0.5 A @ 120 Vac 1.0 A @ 120 Vac
*Battery Input Current Standby 0.18 A / 1.1 A 0.15 A / 1.0 A 0.16 A / 1.1 A Battery Input Current Alarm 1.1 A / 2.5 A 0.8 A / 1.1A 0.6 A / 2.0 A Output power 25 Watt 50 Watt 100 Watt Freq. Response 800 - 2800 Hz 400 - 4000 Hz 400 - 4000 Hz Output Voltage 25/70 Vrms Selectable 25/70 Vrms Selectable 25/70 Vrms Selectable Battery Charging Current 800mA 800mA 800mA Minimum Battery Size 24V 7 AH 24V 7 AH 24V 7 AH Maximum Battery Size 24V 18 AH 24V 18 AH 24V 18 AH Battery Type is two (2) 12V Gel Cell (in Series) for all products.
For units wired with 240 VAC Transformers the following ratings apply:
Evax by Potter • Phone: (888) 382-9835 • www.evax.com
5403670 Rev A 12/17
PAGE 3 OF 8