Eurotherm WV478 Data Sheet

Page 1
WV478-2000
ULTRA SLIMPAK® II
WV478
DC Powered Frequency Input
Isolating Signal Conditioner
High Accuracy Signal Conditioner with an
Isolated DC Voltage or Current Output
Lower Power Requirements with SmartPower Improved Accuracy Bussed Power with Plug-in Power Clips Removable Terminals for Easy Service
Description
The Ultra SlimPak II is an exciting new line of isolating signal conditioners from Action Instruments with greater accuracy and better stability than virtually any other signal conditioners on the market today. The Ultra SlimPak II features Smart Power, which eliminates wasted power for low loop resistance loads in the current output mode.
The WV478 accepts a frequency of up to 10kHz, with a minimum input span of 2Hz. The input amplitude can range from 150mVp to 150Vrms.
Smart Power
RoHS Compliant Touch Cal for Best Stability and Accuracy DIP Switch Configuration
Enhanced LED Diagnostics
Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:
GREEN:
Flashes at 2Hz when the input is under range. Flashes at 8Hz when the input is over range.
RED:
Flashes at 2Hz when the output is under range. Flashes at8Hz when the output is over range.
An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.
A voltage output short circuit may cause an under range condition (RED blinking at 2Hz rate). A current output open circuit may cause an over range condition (RED blinking at an 8Hz rate).
There could be two or more LEDs blinking at the same time, which means the module has more than one error condition. Only when all error conditions have been removed, will the LEDs be back to normal (Green ON, Red and Yellow Off).
Page 2
Configuring Modules
Unless otherwise specified, the factory presets the Model WV478 as follows:
Input: Frequency
Range: 0-1000Hz
Sensitivity: Low (set at 1Vrms)
Output: DC Current
Range: 4-20mA
Remote Cal: Off
Calibration
See the calibration flowchart in Figure 3. The complete calibration procedure is contained in the Installation & Calibration Instruc­tions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (
Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:
1. For other ranges, refer to the SWITCH SETTINGS table. Reconfigure switches S1 and S2 for the desired input type and range.
2. Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
3. Set position 2 and 3 of S1 for the desired output type.
4. Set position 4 of S1 to ON for reverse output operation.
5. Set position 1 of S2 for the desired input sensitivity.
It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.
noitcnuF2S
ytivitisneStupnI
:yeK a/n=-;desolCroNO=1=
noitcnuF1S
123
laCetomeR
--
tuptuO

V01ot0-
Am02ot0-
:yeK a/n=-;desolCroNO=1=
Am02ot4-
a) Input Frequency Range (for example: 0 to 5000Hz).
b) Input Amplitude (for example: 2.5 Volts, Peak).
c) Output Type and Range (for example: 4 to 20mA).
1
)smrV051otpVm005(egnaRhgiH
)smrV05otpVm051(egnaRwoL
ON = Closed
1
Remote Cal On Remote Cal Off
2
Output Range: 4 to 20 mA
ON = Closed
3
On Off
1
Input Sensitivity: 150mVp to 50Vrms
(see Table)
(see Table)
Figure 1: Switch Settings
Default Switch Settings
Page 3
niPnoitpircseD
11 )+(rewoPCD
21 )-(rewoPCD
12 )+(rewoPCD
22 )-(rewoPCD
14 )+(tupnI
24 )-(tupnI
15 )+(tuptuO
25 )-(tuptuO
Figure 2: Wiring Connections
Figure 3: Calibration Flowchart
Page 4
Specifications
r
Input:
Frequency Input Range: 0 to 10kHz Minimum Input Span: 2Hz Amplitude (switch selectable):
Low Range: 150mVp to 50Vrms High Range: 500mVp to 150Vrms
Output:
Voltage: 0 to 10VDC;
Source Impedance: 10 ohms Drive: 10mA
Current: 0 to 20mA
Source Impedance: >100k ohms Compliance: 20V@20mA (1k ohms max)
Output Accuracy:
±0.05% of full scale local range
Response Time:
100mSec + 3 input cycles (10-90%) typical
Stability:
±100ppm of full scale/°C (±0.01%/°C)
Common Mode Rejection:
60Hz: >90dB DC: >120dB
Isolation:
Input to Output to Power: 1800VDC
ESD Susceptibility:
Capable of meeting IEC801-2 level 3 (8kV)
Power:
9 to 30VDC 1W typical, 2W maximum
Host Module Interface:
IR Link
Size:
DIN rail case – refer to Dimensions drawing
Temperature Range:
Operating: 0°C to 60°C (32°F to 140°F) Storage: -25°C to 85°C (-13°F to 185°F)
Humidity Range:
Operating: 15% to 95% RHNC @ 45°C Storage: 90% RHNC @60°C for 24 hrs
Agency Approvals (EMC & Safety):
UL recognized per standard UL508 (File No.E99775) CE Conformance per EMC directive 2004/108/EC and Low Voltage
directive 2006/95/EC (Input < 75VDC, only).
RoHS Compliant
Ordering Information
Specify:
1. Model:
WV478-2000
2. Optional Custom Factory Calibration (specify C620, see required
settings under "Calibration, page 2).
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35 (model MD03) DIN rail. In addition, the following accessories are available:
WVC16 Communications Interface
MD03 TS35 x 7.5 DIN Rail (2 meters)
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp) H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C650 Utility software for WVC16
Printed on recycled pape
Note that detailed installation instructions are available on our website.
Dimensions
Dimensions are in millimeters (inches)
Action Instruments
Chessell
721-0806-00-I 09/06 Copyright© Eurotherm, Inc 2006
Eurotherm