Eurotherm WV408 Data Sheet

Page 1
WV408-2000
ULTRA SLIMPAK® II
WV408
DC Powered DC Voltage/Current Input
Isolating Signal Conditioner
High Accuracy Signal Conditioner with an
Isolated DC Voltage or Current Output
Lower Power Requirements with SmartPower Improved Accuracy Bussed Power with Plug-in Power Clips Removable Terminals for Easy Service Approved for use in Class I Div 2 Group A, B, C, D areas
Description
The Ultra SlimPak II is an exciting new line of isolating signal conditioners from Action Instruments with greater accuracy and better stability than virtually any other signal conditioners on the market today. The Ultra SlimPak II features Smart Power, which eliminates wasted power for low loop resistance loads in the current output mode.
The WV408 has both voltage and current input ranges. Four voltage input ranges (±150mV, ±1.5V, ±15V and ±150V) are DIP switch selectable. Each of these ranges has at least 95% zero and span adjustment, which, for example, would allow you to set a 0­20mV user range on the ±150mV full scale range. Two current input ranges (±2.5mA and ±25mA) are also DIP switch selectable. "Sigma-Delta" conversion produces an effective resolution of 15 bits. Both voltage and current have input accuracies of 0.015% of full scale. Outputs include 0-10V, 0-20mA and 4-20mA. The WV408 also supports reverse output. The WV408 is recognized for use in Class 1, Division 2, Groups A, B, C, D hazardous locations.
Smart Power
The Ultra SlimPak II uses Smart Power to control its output supply. Smart Power automatically adjusts the the voltage to drive the output loop to the required current. A low impedance current loop will subsequently require less voltage than a loop with higher impedance. Previous designs provided only a single supply at the highest voltage required to drive the highest impedance load. Using Smart Power results in power savings and reduces the operating temperature of the signal conditioner.
Approved for use in Class I Div 2 Group A, B, C, D areas
Users can now enjoy significant labor savings over traditional protection methods since there is no need for explosion proof enclosures and conduits.
RoHS Compliant Touch Cal for Best Stability and Accuracy DIP Switch Configuration Optional E-mail Notification of Alarms
A Division 2 area is one in which the flammable gases or vapors are normally not present in an explosive concentration, but could accidentally exist.
Group A is acetylene; Group B includes hydrogen; Group C includes ether; and Group D includes hydrocarbons, fuels and solvents.
Enhanced LED Diagnostics
Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:
GREEN:
Flashes at 2Hz when the input is under range. Flashes at 8Hz when the input is over range.
RED: Flashes at 2Hz when the output is under range.
Flashes at 8Hz when the output is over range.
An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.
A voltage output short circuit may cause an under range condition (RED blinking at 2Hz rate). A current output open circuit may cause an over range condition (RED blinking at an 8Hz rate).
There could be two or more LEDs blinking at the same time, which means the module has more than one error condition. Only when all error conditions have been removed, will the LEDs be back to normal (Green ON, Red and Yellow Off).
A Class I hazardous location is one in which flammable gases or vapors may be present in the air to be ignitable or explosive (typical applications include petroleum refineries, spray finishing areas, utility gas plants and fuel servicing areas).
Page 2
Configuring Modules
Unless otherwise specified, the factory presets the Model WV408 as follows:
Input: Current
Range: 4-20mA
Output: Current
Range: 4-20mA
Reverse Out: Off
Remote Cal: Off
Calibration
See the calibration flowchart in Figure 3. The complete calibration procedure is contained in the Installation & Calibration Instruc­tions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (
Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:
1. For other ranges, refer to the SWITCH SETTINGS table. Reconfigure switches S1 and S2 for the desired input type and range.
2. Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
3. Set position 2 and 3 of S1 for the desired output type.
4. Set position 4 of S1 to ON for reverse output operation.
5. Set positions 5-7 of S1 and positions 1and 2 of S2 for the desired input range.
It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.
a) Input Type, Range & Units (mA, mV, V).
b) Output Type, Range & Units (ma, mV, V).
c) Reverse Output (ON/OFF)
noitcnuF1S
:yeK desolCroNO=1=
ON = Closed
Remote Cal Enable
Remote Cal DisableOnOff
Output Range: 4 to 20ma
(see Table)
14
elbanElaCetomeR
tuOesreveR
:yeK desolCroNO=1=
2
45
3
Reverse Output
Direct OutputOnOff
1
Default Settings
noitcnuF1S
segnaRtuptuO
V01ot0
Am02ot0
Am02ot4
ON = Closed
7
6
Input Range: +/-25ma
(see Table)
23

1
noitcnuF1S2S
segnaRtupnI
:yeK desolCroNO=1=
2
Figure 1: Switch Settings
567812
 
Vm051-/+

V5.1-/+

V51-/+
V051-/+

Am5.2-/+

Am52-/+
Page 3
Figure 2: Wiring Connections
niPnoitpircseD
11 )+(rewoPCD
21 )-(rewoPCD
12 )+(rewoPCD
22 )-(rewoPCD
14 )+(tupnI
24 nommoCtupnI
15 )+(tuptuO
25 nommoCtuptuO
Figure 3: Calibration Flowchart
Page 4
Specifications
r
Inputs: Voltage:
±150mV, ±1.5V, ±15V or ±150VDC Impedance: >100k Ohms Over voltage:
Current:
±2.5mA or ±25mA Impedance: <75 Ohms Over current: 170mA, protected by resetting fuse Over voltage: 60V
Zero & Span Adjustment: ±95% of Full Scale Input Accuracy: ±0.015% of Full Scale Outputs:
Voltage: 0 to 10VDC Source Impedance: <10 Ohms Drive: 10mA Current: 0 to 20mA Source Impedance: >100k Ohms Compliance: 20V@20mA (1k Ohms max)
180Vrms
Output Accuracy: ±0.05% of Full Scale Local Range Selection: By DIP switch Response Time: 100mSec (10 to 90%) Stability: ±100ppm of full scale/°C (±0.01%/°C) Common Mode Rejection: 120dB @ DC,
>90dB @ 60Hz, or better
Isolation: 1800VDC or peak AC between input, output & power ESD Susceptibility: Capable of IEC 801-2 level 3 (8kV) Power: 9-30VDC; 1.0W typ., 2.0W max. Host Module Interface: IR Link Size: DIN rail case – refer to Dimensions drawing Operating Temperature: 0 to +60°C (32 to 140°F) Storage Temperature: -25 to +85°C (-13 to 185°F) Operating Humidity: 15% to 95% RH,non-condensing @ 45°C Storage Humidity: 90% RH, non-condensing @ 60°C for 24 hours Agency Approvals (EMC & Safety):
UL recognized per standard UL508
(File No.E99775)
CE Conformance per EMC directive 2004/108/EC and Low Voltage
directive 2006/95/EC (Input < 75VDC, only).
RoHS Compliant
Ordering Information
Specify:
1. Model:
WV408-2000
2.
Optional Custom Factory Calibration (specify C620, see required settings under "Calibration, page 2).
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35 (model MD03) DIN rail. In addition, the following accessories are available:
WVC16 Communications Interface
MD03 TS35 x 7.5 DIN Rail (2 meters)
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp) H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C650 Utility software for WVC16
Printed on recycled pape
Note that detailed installation instructions are available on our website.
Dimensions
Dimensions are in millimeters (inches)
Action Instruments
Chessell
721-0804-00-J 02/09 Copyright© Eurotherm, Inc 2009