Eurotherm WV128 Data Sheet

Page 1
WV128-2000 (non-latching) WV128-2001 (latching)
ULTRA SLIMPAK® II
WV128
DC Powered T/C Input Limit Alarm
Provides Relay Contact Closures at a
Preset Temperature Input Level
Programmable HI or LO, Failsafe or Non-failsafe Improved Accuracy Adjustable Deadband Bussed Power with Plug-in Power Clips Removable Terminals for Easy Service
Description
The Ultra SlimPak II is an exciting new line of isolating signal conditioners from Action Instruments with greater accuracy and better stability than virtually any other signal conditioners on the market today.
The WV128 is a Thermocouple Input Limit Alarm with dual setpoints and two contact closure outputs. The input type and alarm functions are field configurable, offering maximum flexibil­ity. There are seven thermocouple types (B, E, J, K, R, S and T) from which to choose. Alarm setpoints are fully adjustable throughout the entire range.
The WV128-2000 contains two standard non-latching SPDT relays. When power is removed, the relays revert to their non-powered state. The WV128-2001 contains two latching relays. Whatever position the relays are in when power is removed is where they will remain when power is re-applied (a reset switch is provided to reset the relays after the alarm is no longer true). Both models are configurable as a single or dual setpoint alarm, with HI or LO trips. The WV128-2000 supports failsafe or non-failsafe operation. In failsafe operation the relay coil is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non­failsafe). In the failsafe mode, a power failure results in an alarm state output.
Touch Cal for Best Stability and Accuracy RoHS Compliant LED Trip and Input Indicators Optional E-mail Notification of Alarms
Enhanced LED Diagnostics
Other than when executing the pushbutton calibration routine, the LEDs blink under the following conditions:
RUN (Green):
On when unit is powered. Flashes at 2Hz when input is under range. Flashes at 8Hz when input is over range.
SETPOINT A (Red):
On when Setpoint A is tripped. On when setting Setpoint A. Flashes while calibrating the input level.
SETPOINT B (Red):
On when Setpoint B is tripped. On when setting Setpoint B. On while calibrating the input level.
Operation
Each of the alarm setpoints has a respective HI or LO deadband. Red LEDs will illuminate indicating an alarm condition. The trip will reset only when the process falls below the HI deadband or rises above the LO deadband. (The WV128-2001 requires pressing the reset switch in order to reset the relays after being tripped.) The deadband can be left at the minimum level (the factory default) or can be set to whatever level is desired.
Options
C620 Factory cal of input range, setpoints and output relays.
Figure 1: Limit alarm operation and effect of deadband.
An Under Range condition exists when the signal is lower than the operational low value minus 6.25% of the operational span. An Over Range condition exists when the signal is higher than the operational high value plus 6.25% of the operational span.
Page 2
Configuring Modules
Unless otherwise specified, the factory presets the Model WV128 as follows:
Input: Type J
Output: Dual, SPDT
Trip: A: HI, B: LO
Failsafe: No
Deadband: A, B: minimum
Remote Cal: No
Calibration
See calibration flwchart in Figure 6. The complete calibration procedure is contained in the Installation & Calibration Instruc­tions document, which is available on our website (www.actionio.com). You can also obtain it by telephoning Action technical support (
Note that Custom Calibration (option C620) is available from the factory (settings MUST be within the units specifications). For a C620, specify the following:
1. For other ranges, refer to the SWITCH SETTINGS table (see Figure 4). Reconfigure switches S1 and S2 for the desired input type and range.
2. Set position 1 of S1 to ON if a WVC16 will be utilized and remote calibration capability is desired.
3. Set position 2 and 3 of S1 to ON for a Hi trip setpoint or to OFF for a Low trip setpoint.
4. Set position 4 of S1 to ON for failsafe operation (e.g. alarm trips upon power failure) or OFF for non-failsafe operation (-2000 only).
It is also possible to remotely select the setpoints using an Ethernet connection and the optional WVC16 WebView Communications Interface module.
Relay Protection and EMI Suppression
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 & 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly­rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1mF pulse film capacitor (foil polypropylene recom­mended) of sufficient voltage, and a 47ohm, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
a) Input type.
b) Setpoint A trip point and reset point.
c) Setpoint B trip point and reset point.
d) Failsafe (ON/OFF).
Note that if a deadband entry is not specified, the default setting of 0.25% will be used.
noitcnuF1S
tupnI
123 45 67 8
Vm02-/Vm08+----
c/tB----
c/tE----
c/tJ----
c/tK----
c/tR----
c/tS----
c/tT----




Figure 2: DC Inductive Loads
Figure 3: AC Inductive Loads
:yeK a/n=-;desolCroNO=1=
Figure 4: Switch Settings
ON = Closed
Remote Cal Enable
Remote Cal DisableOnOff
"A" Hi Trip
"A" Low TripOnOff
Default Switch Settings
elbanElaCetomeR
)iH(woL/iHA-----
)iH(woL/iHB-----
efasliaF------
1
45
3
2
Non-FailsafeOnOff
"B" Hi Trip
"B" Low TripOnOff
------
7
6
Input: Type J T/C
(see Table)
Failsafe
Page 3
Figure 5: Wiring Connections
niPnoitpircseD
11 ByaleR.O.N
21 ByaleR.moC
31 ByaleR.C.N
12 )+(rewoPCD
22 )-(rewoPCD
32 noitcennoCoN
14 )+(tupnIC/T
24 )-(tupnIC/T
34 noitcennoCoN
15 AyaleR.O.N
25 AyaleR.moC
35 AyaleR.C.N
Figure 6: Calibration Flowchart
Page 4
Specifications
r
Inputs:
Thermocouples Supported: B, E, J, K, R, S, T
Ranges: T/C ° B +75 to 1820 +167 to 3308 E -265 to 1000 -445 to 1832 J -210 to 760 -346 to 1400 K -265 to 1372 -445 to 2502 R -25 to 1760 -13 to 3200 S -25 to 1760 -13 to 3200 T -265 to 390 -445 to 734 Overvoltage: ±10V differential Common Mode: 1800VDC (Input to Ground) Limit Differential (deadband): 0.2% to 100% of span. Set by
Pushbutton Adjustment.
Response Time:
Dynamic Deadband: Relay status will change when proper setpoint/ process condition exists for 100mSec.
Normal Mode: <250mSec (analog filtering)
Setpoint:
Effectivity: Setpoints are adjustable (by pushbutton) over 100% of the selected input span.
Repeatability: ±0.05% of FS, ±1°C (constant temp)
Relay Contacts:
2 SPDT (2 form C) Relays
Current rating (general use):
C °F
1 relay per setpoint
120VAC: 5A; 240VAC: 2A; 28VDC: 5A Material: Gold flash over silver alloy Electrical Life: 10
5
operations
Reset Switch:
For unlatching the relay once the process is no longer in the alarm state. (WV128-2001 only)
Local Range Selection: By DIP switch Stability: ±100ppm of FS/°C Common Mode Rejection: 120dB @ DC, >90dB @ 60Hz, or better Isolation: 1800VDC or peak AC between contacts, input & power. ESD Susceptibility: Capable of meeting IEC 801-2 level 3 (8kV) Power: 9 to 30VDC; 1.2W typ., (3.25W max both relays energized) Host Module Interface: IR link Wire Terminations: Screw terminations for 12-22 AWG Size: DIN rail case – refer to Dimensions drawing Environmental:
Operating Temperature: 0°C to +60°C (32 to 140°F) Storage Temperature: -25°C to +85°C (-13 to 185°F) Operating Humidity (non-condensing): 15% to 95% at 45°C Storge Humidity (non-condensing): 90% at 60°C for 24 hours
Agency Approvals (EMC & Safety):
UL recognized per standard UL508
(File No.E99775)
CE Conformance per EMC directive 2004/108/EC and Low Voltage
directive 2006/95/EC (Input < 75VDC, only).
RoHS Compliant
Ordering Information
Specify:
1. Model:
WV128-2000 (non-latching) or WV128-2001 (latching)
2. Optional Custom Factory Calibration (specify C620, see required
settings under "Calibration, page 2).
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35 (model MD03) DIN rail. In addition, the following accessories are available:
WVC16 Communications Interface
MD03 TS35 x 7.5 DIN Rail (2 meters)
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1 Amp) H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C650 Utility software for WVC16