Installation Manual and
User guide
PC300 Process control system
The PC300 process control system uses highly reliable and field tested PC3000 components. The unit includes an integral power supply, the Local Controller Module ’plus’ and two free module positions for installing other I/O modules. The PC300 has a steel case construction and is designed for backplane mounting.
Specification
General
Supply voltage range 85 to 132V ac rms
176 to 240V ac rms Selected by external wiring option
Supply frequency range 48 - 62 Hz VA requirements < 40VA for fully loaded rack Power Supply Output 50W total, 24V @ 1.6A, 5V @ 2.5A
Inrush Current 25A, single cycle, cold start, high
line Power supply hold up time
>20ms at minimum line voltage and
maximum load (> 100ms t ypical) Input protection RFI Input filter, transient protection Replaceable Fuse Rating 1.6A time lag
Mechanical
Height 193 mm, inc. mounting brackets Depth 203 mm, inc. mounting brackets Width 316 mm Mount i ng Bulkhe a d mou nting Casing Robust Metal case to IP20 Module capacity 2 single with I/O slots Ventilation Space 25mm free space above and below
Environmental
Operating Temperature 0 to 50o C Storage Temperature -20 to 70o C Relative Hu midity 5 to 95 % non-condensi ng Weight 5.25 Kg Weight support brackets 0.4 Kg each
EMC
Emissions EN50081-2: 1994 Immunity EN50082-2: 1992
Safety
EN61010-1: 1993/A2: 1995
Installatio n c at II, Pollutio n d egree 2
LCM-Plus
RAM 256K base RAM
Slot 1 512K standard Slot 2 128k for special FB (optional)
Communications Ports
Ports A & B User po rts
Port C PC3000 extension rack port
Standard
Ports A & B RS422
Port C RS485 / RS422 (jumper selectable)
Baud Rates
Ports A & B 300 to 38.4k
Port C 300 to 115k
Protocols Software selectable
(2 of ports A,B, C)
Available I/O modules
Analogue Input 0-100mV
0-10V 0-20mA Thermocouple (J,K,R,S,B,Pyro) PT100 Resistance Thermometer Frequency 0-10kHz Zirconia probe
Analogue Output 0-5V, 0-10V, -10 to +10V etc
4-20mA, 0-20mA etc
Digital Inputs 5Vdc
25Vdc 24Vac 85-264Vac Volt Free
Digital Out Logic
Relay (N/O)
Pulse Input 200kHz - 5v, 12v(selectable)
Page 2
PC300 User Guide
HA 026773 Page 2 of 4 Issue 1.3 June 2000
Installation
Dimensional Details (mm)
Location
The Power Supply Unit resides in the first ’slot’ in every rack. The second ’slot’ contains the Local Control Module.
I/O module addresses
Configuration is made simple - there is no requirement to configure jumpers or switches to set I/O module addresses . The module address is read directly from t he backplane.
Compatability
The PC300 is directly compatible with and a subset of the PC3000. The two products share I/0 cards, programming tools.and instruction manuals.
Manuals
PC3000 instruction manuals are used for the PC300.
219 316
4453
3042120
193
166
44
16
182
Alternate Bracket Position
94
203
Earth Connection
M8
338
Allow 15mm clearance above bracket for fitti n g
Note:
5 THK.
Page 3
PC300 User Guide
HA 026773 Page 3 of 4 Issue 1.3 June 2000
User Wiring Slot 1
Supply Voltage
Configuration of the supply voltage is selected by an external wiring option. A link is necessary between terminals 10 and 11 for 85 to 132 V ac operation.
Health Relay
The health relay is energised during normal operation, and is de-ene r g is e d if the system watch do g fail s . W atc hdog failure can be caused by the applications program failing to run correctly of a system hardware failure.
Slot 2
Commissioning is simplified by the provision of status indicators fitted to the front of the module. Indication of system status (run and fault), I/O processor status (run and fault), system diagnostic functions and communication channel activity are provided.
System and IOC status LED’s
F = Fault R = Run
Diagnostic LED’s
Consult ’PC3000 Hardware Reference Manual’ for details
Communication LED’s
A, B, C. Serial channel communication activity D Extension rack communication activity
3RZHU6XSSO\8QLW368
nc nc nc nc C Common N/O Normally Open Health N/C Normally Closed Re lay nc nc Lk Link for Lk 85 - 132v operation nc L Live N Neutral Earth
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Label Function
Terminal
Status Indication
24V
5V
System [Health Relay] Auxilary Supply
/RFDO&RQWURO0RGXOH3OXV
S yst em Status
IOC Status
F
R
Status Indication
Diagn ostic s Communications
R
F
1
24
3
AB D
C
Connections to serial p orts
A
Extension Rack O n ly
C
B
8 4 7 3 6 2 5 1
Pi n
1: Rx 2: Tx 3: Tx ­4: Tx + 5: Rx­6: Rx+ 7: 0V 8: 0V
232
422
Page 4
PC300 User Guide
HA 026773 Page 4 of 4 Issue 1.3 June 2000
Safety Notes
Warning!
The mains (supply) voltage must be isolated before the mains (supply) connector is handled.
Warning!
Any interruption of the protect ive conductor in sid e or outside the apparatus or disconnection of the protec tive earth term inal is likely to make the appara tus dangerous under some fault conditions. Intentional interruption is prohibited.
Note: In order to comply with the requirements of safety standard EN61010, the power supply module must have one of the following as a disconnection device, fitted within easy reach of the operator and labelled as a disconnection device.
i. A switch or circ ui t br eaker which complies with the requireme nts of IEC947-1 a n d IEC947-3 ii. A separable coupler which can be disconnected without the use of a tool iii. A separable plug, without a locking device, to mate with a socket outlet in the building.
1. Before any other connection is made, the protective earth terminal shall be connected to a protective
conductor.
2. The Mains (supply voltage) wiring must be terminated in such a way that the Earth wire would be
the last wire to become disconnected should excess tension be applied to the mains cable.
3. It is recommended that crimps be used to terminate the wires before they are inserted into the
terminal bl o cks .
4. The Mains supply fuse within the Power supply unit is replaceable and should only be replaced with
a fuse of the same type and rating. In no conditions should the fuse be replaced with one of a higher rating.
5. Whenever it is likely that protection has been impaired, the unit shall be made inoperative and
secured against unintended operat ion. The nearest manufacturers service c entre should be consulted for advice.
6. Any adjustment, maintenance or repair of the opened apparatus und er voltage, is proh ibited.
7. The unit is designed for use only in an enclosure.
8. Where conductive pollution (e.g. condensation, carbon dust) is likely, adequate air conditioning /
filtering / sealing etc. mu st be installed in the enclosure.
9. If the equipment is used in a manner not specified by the man uf acturer, the pro te ction prov ided by
the equipment might be im paired.
Symbols used on the unit labelling
One or more of the symbols may appear on the apparatus.
!
Refer to User Guide for instructions Protective Earth
L
Connect the ’line ’( switched) wire her e
N
Connect the neutral wire her e