Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, service, or maintain it. The following
special messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of either symbol to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal
injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages that follow this
symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert
symbol shall not be used with this signal word.
Note: Electrical equipment must be installed, operated, serviced and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric for
any consequences arising out of the use of this material.
Note: A qualified person is one who has skills and knowledge related to the
construction, installation, and operation of electrical equipment, and has received
safety training to recognize and avoid the hazards involved.
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Power down all equipment before starting the installation, removal, wiring,
maintenance or inspection of the product.
Always use a properly rated voltage sensing device to confirm power is off.
Power line and output circuits must be wired and fused in compliance with local and
national regulatory requirements for the rated current and voltage of the particular
equipment, i.e. UK, the latest IEE wiring regulations, (BS7671), and USA, NEC
class 1 wiring methods.
Failure to follow these instructions will result in death or serious injury.
Reasonable use and responsibility
The safety of any system incorporating this product is the responsibility of the
assembler/installer of the system.
The information contained in this manual is subject to change without notice.
While every effort has been made to improve the accuracy of the information, your
supplier shall not be held liable for errors contained herein.
This controller is intended for industrial temperature and process control applications,
which meet the requirements of the European Directives on Safety and EMC.
Use in other applications, or failure to observe the installation instructions of this
manual may compromise safety or EMC. The installer must ensure the safety and
EMC of any particular installation.
Failure to use approved software/hardware with our hardware products may result in
injury, harm, or improper operating results.
Electrical equipment must be installed, operated, serviced and maintained only by
qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out
of the use of this material.
A qualified person is one who has skills and knowledge related to the construction
and operation of electrical equipment and its installation, and has received safety
training to recognize and avoid the hazards involved.
QUALIFICATION OF PERSONNEL
Only appropriately trained persons who are familiar with and understand the contents
of this manual and all other pertinent product documentation are authorized to work
on and with this product.
The qualified person must be able to detect possible hazards that may arise from
parameterization, modifying parameter values and generally from mechanical,
electrical, or electronic equipment.
The qualified person must be familiar with the standards, provisions, and regulations
for the prevention of industrial accidents, which they must observe when designing
and implementing the system.
INTENDED USE
The product described or affected by this document, together with software and
options, is the nanodac™ Recorder / Controller (referred to herein as "programmable
controller", "controller" or "nanodac"), intended for industrial use according to the
instructions, directions, examples, and safety information contained in the present
document and other supporting documentation.
The product may only be used in compliance with all applicable safety regulations
and directives, the specified requirements, and the technical data.
Prior to using the product, a risk assessment must be performed in respect of the
planned application. Based on the results, the appropriate safety-related measures
must be implemented.
Since the product is used as a component within a machine or process, you must
ensure the safety of this overall system.
Operate the product only with the specified cables and accessories. Use only
genuine accessories and spare parts.
Any use other than the use explicitly permitted is prohibited and can result in
unanticipated hazards.
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See applicable national standards e.g. NFPA70E, CSA Z462, BS
7671, NFC 18-510.
Electrical equipment must be installed, operated and maintained by only suitably
qualified personnel.
Refer to manual for installation and servicing.
Turn off all power supplying this equipment before working on the loads of the
equipment.
Replace doors and plug-in terminals before turning on power to this equipment.
If on receipt, the unit or any part within is damaged, do not install but contact your
supplier.
Do not disassemble, repair or modify the equipment. Contact your supplier for
repair.
This product must be installed, connected and used in compliance with prevailing
standards and/or installation regulations.
Do not exceed the device's ratings.
The unit must be installed in an enclosure or cabinet connected to the protective
earth ground.
Electrically conductive pollution must be excluded from the cabinet in which the
product is mounted.
Do not allow anything to fall through the case apertures and ingress the product.
Before any other connection is made, the protective earth ground terminal must be
connected to a protective conductor.
Any interruption of the protective earth ground conductor inside or outside the
product, or disconnection of the protective earth ground terminal is likely to make
the product dangerous under some conditions. Intentional interruption is prohibited.
Whenever it is likely that protection has been impaired, the unit shall be made
inoperative, and secured against accidental operation. The manufacturers nearest
service centre must be contacted for advice.
Power line and output circuits must be wired and fused in compliance with local and
national regulatory requirements for the rated current and voltage of the particular
equipment, i.e. UK, the latest IEE wiring regulations, (BS7671), and USA, NEC
class 1 wiring methods.
Tighten all connections in conformance with the torque specifications. Periodic
inspections are required.
Ensure all cables and wiring harness are secured using a relevant strain relief
mechanism.
Use appropriate safety interlocks where personnel and/or equipment hazards exist.
Respect electrical installation requirements to ensure optimum IP rating.
Always use a properly rated voltage sensing device to confirm power is off.
Grounding the temperature sensor shield: Where it is common practice to replace
the temperature sensor whilst the instrument is live, it is recommended that the
shield of the temperature sensor be grounded to a protective earth ground, as an
additional protection against electric shock.
Failure to follow these instructions will result in death or serious injury.
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
The maximum continuous voltage applied between any of the following terminals
must not exceed 240Vac.
1) Relay output to logic, dc or sensor input connections
2) Any connection to ground.
The ac supply must not be connected to sensor input or low-level inputs or outputs.
Ensure the power supply capacitors discharge to a safe voltage, the power supply
must be disconnected for at least two minutes, before the instrument is removed
from its sleeve. The touching of the exposed electronics of an instrument which has
been removed from its sleeve should be avoided.
Failure to follow these instructions will result in death or serious injury.
DANGER
FIRE HAZARD
A maximum of two wires, when identical in type and cross sectional size can be
inserted per controller terminal or terminal harness connector (where utilized).
The conductor stripping length must be as stated in electrical installation.Ensure all
wires that connect to the controller terminals or to the controllers terminal harness
connector (without ferrules), do not exceed the maximum exposed conductor
length.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not use the product for critical control or protection applications where human
or equipment safety relies on the operation of the control circuit.
Signal and power voltage wiring must be kept separate from one another. Where
this is impractical, all wires must be rated to the power voltage and shielded
cables are recommended for signal wiring.When shielded cable is used, it must
be grounded at one end only.
This product has been designed for environment A (Industrial). Use of this product
in environment B (domestic, commercial and light industrial) may cause unwanted
electromagnetic disturbances in which cases the installer may be required to take
adequate mitigation measures.
For Electromagnetic Compatibility, the panel or DIN rail to which the product is
attached must be grounded.
Observe all electrostatic discharge precautions before handling the unit.
At commissioning, ensure cybersecurity robustness of the installation.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
CAUTION
UNINTENDED EQUIPMENT OPERATION
If being stored before use, store within the specified environmental conditions.
Failure to follow these instructions can result in injury or equipment
damage.
Various symbols may be used on the controller. They have the following meaning:
D Risk of electric shock.
O Take precautions against static.
P Regulatory compliance mark for Australia (ACA) and New Zealand (RSM).
* Complies with the 40 year Environment Friendly Usage Period.
Hazardous Substances
This product conforms to European Restriction of Hazardous Substances (RoHS)
(using exemptions) and R
Ch
emicals (REACH) Legislation.
RoHS Exemptions used in this product involve the use of lead. China RoHS
legislation does not include exemptions and so lead is declared as present in the
China RoHS Declaration.
Californian law requires the following notice:
egistration, Evaluation, Authorisation and Restriction of
WWARNING: This product can expose you to chemicals including lead and lead
compounds which are known to the State of California to cause cancer and birth
defects or other reproductive harm.
For more information go to: http://www.P65Warnings.ca.gov
USB Device Precautions
Note: The use of U3 USB Flash drives is not recommended.
1. Precautions against electrostatic discharge should be taken when the instrument
terminals are being accessed. The USB and Ethernet connections are
particularly vulnerable.
2. Ideally, the USB device should be plugged directly into the instrument, as the use
of extension leads may compromise the instrument’s ESD compliance. Where
the instrument is being used in an electrically noisy’ environment however, it is
recommended that the user brings the USB socket to the front of the panel using
a short extension lead. This is because the USB may lock up’ or reset in noisy
environments and the only means of recovery is to remove the device, then
re-insert it. For memory sticks, EMC-related failure during a write operation might
cause corruption of the data held on the stick. For this reason, the data on the
memory stick should be backed up before insertion and checked after removal.
3. When using a USB extension cable, a high quality screened cable must be used.
The total length of USB cable between the device and the USB port must not
exceed 3 metres (10 ft.).
.
4. Most barcode readers and keyboards are not designed for use in industrial EMC
environments, and their operation in such environments may result in impaired
performance of the recorder/controller.
32-BIT Resolution
Floating point values are stored in IEEE 32-bit single precision format. Values which
require greater resolution than is available in this format are rounded up or down.
This chapter outlines some good practice approaches to cybersecurity as they relate
to use of the nanodac instrument, and draws attention to several nanodac features
that could assist in implementing robust cybersecurity.
Introduction
When utilising the nanodac in an industrial environment, it is important to take
‘cybersecurity’ into consideration: in other words, the installation’s design should aim
to prevent unauthorised and malicious access. This includes both physical access
(for instance via the front panel or HMI screens), and electronic access (via network
connections and digital communications).
Secure Network Topologies and Good Practices
Overall design of a site network is outside the scope of this manual. The
Cybersecurity Good Practices Guide, Part Number HA032968 provides an overview
of principles to consider. This is available from www.eurotherm.com.
Security Features
Principle of Secure by Default
HMI Access Level / Comms Config Mode
Typically, an industrial controller such as the nanodac together with any associated
HMI screens and controlled devices should not be placed on a network with direct
access to the public Internet. Rather, good practice involves locating the devices on a
fire-walled network segment, separated from the public Internet by a so-called
demilitarized zone’ (DMZ).
The sections below draw attention to some of the cybersecurity features of the
nanodac.
Some of the digital communication features on the nanodac can provide greater
convenience and ease-of-use (particularly in regards to initial configuration), but also
can potentially make the controller more vulnerable. For this reason, some of these
features are turned off by default. In particular, ID061 (the BACnet port is closed
unless the BACnet option is enabled).
As described in Login (page 49), the nanodac device features tiered,
password-restricted user access levels, so that available functions and parameters
can be restricted to appropriate personnel.
Note: User accounts of any access level require a password, otherwise they will not
be available for selection.
Logged Out Access Level
Logged out mode allows the user to select viewing mode, to view history, to view
alarms, to toggle faceplate cycling on and off, to send notes, to suspend/resume USB
archiving and to access the login process.
In addition to the logged out features, Operator access level allows the user to
acknowledge alarms, to edit notes and to perform demand archive operations. By
default, a password is required to enter Operator level. Passwords can be configured
either at Supervisor level or at Engineer level.
If the Auditor feature is enabled, the Operator user is pre-configured as ‘User 1’. See
next section for details.
Customizable Users
Overview
A total of 25 customizable user accounts are available. With the exception of ‘User 1’
which is pre-configured to replace the ‘Operator’ user account, the remaining 24 are
disabled by default and require the ‘Login Disabled’ permission to be enabled and a
unique password provided.
Each user account can automatically inherit the ‘Logged Out’ access level, however
the user can further choose to inherit the permission sets from any of the following
base users:
•Operator (these permissions can be individually configured)
•Supervisor (inherits as a set)
•Engineer (inherits as a set)
The following example demonstrates the number of user account types that can be
configured.
The username for each user can be up to 20 characters in length. Typically, only the
first 12 characters are displayed in scroll lists (such as when logging on) due to
space. When logging in, the user account number (1 to 25) is prefixed to the
username so that each name is unique by default.
Password
The password for each user can be up to 20 characters in length, and should contain
a selection of numbers, letters, uppercase, lowercase, etc. to provide a strong
password for enhancing cybersecurity.
The following parameters are configurable for each user. Refer to "User Accounts
(Auditor)" on page 107 for further details:
PermissionDescription
Batch ControlYes = Control batches via batch control page
Ack AlarmsYes = Acknowledge alarms in the alarm summary screen
Demand ArchivingYes = Access to the demand archiving screen
Login DisabledYes = Disable this account
SigningYes = This user will appear in the list when required to sign
for an action
AuthorisingYes = This user will appear in the list when required to
authorise an action
Archive IntervalYes = Modify the archive interval rate
Loop ControlYes = Change the mode, manual OP in control loop
screens
Supervisor Access Level
Engineer Access Level
HMI Passwords
Program ModeYes = Change the mode of programs
Program EditYes = Edit programs
Program StoreYes = Store programs
SupervisorYes = Inherits Supervisor user access level (mutually
exclusive with Engineer)
EngineerYes = Inherits Engineer user access level (mutually
exclusive with Supervisor)
In addition to the logged out features, this access level allows the user to view the
recorder’s configuration, and to edit some values (such as alarm thresholds).
This allows full access to all areas of the recorder configuration.
When entering passwords via the HMI, the following features help protect against
unauthorised access:
•Each digit is obscured (replaced with an asterisk character) after entry, to help
protect against an unauthorized person seeing the password as it is typed in.
•Password entry is locked after a configurable number of invalid attempts (if
Auditor option is enabled). If this number of attempts is exceeded, the User
account is disabled. This helps protect against “brute force” attempts to guess
the password.
•The controller records the number of successful and unsuccessful login attempts
for each level of password. This is recorded in the History. Regular auditing of
this History is recommended, as a means to help detect unauthorized access to
the controller.
Ethernet security features
Ethernet connectivity is available on the nanodac. The following security features are
specific to Ethernet:
Ethernet rate protection
One form of cyberattack is to try to make a controller process so much Ethernet traffic
that this drains systems resources and useful control is compromised. For this
reason, the nanodac device includes an Ethernet rate protection algorithm, which will
detect excessive network activity and help to ensure the controller’s resources are
prioritized on the control strategy rather than the Ethernet. If this algorithm is
activated, a message will be entered into the History.
Broadcast Storm protection
Configuration backup and recovery
Memory Integrity
A ‘broadcast storm’ is a condition which may be created by cyberattack: spurious
network messages are sent to devices which cause them to respond with further
network messages, in a chain reaction that escalates until the network is unable to
transport normal traffic. The nanodac device includes a broadcast storm protection
algorithm, which will automatically detect this condition, stopping the controller from
responding to the spurious traffic. If this algorithm is activated, a message will be
entered into the History.
Using the iTools software, you can ‘clone’ a nanodac device, saving all its
configuration and parameter settings to a file. This can then be copied onto another
controller, or used to restore the original controller’s settings. Clone files are digitally
signed using an SHA-256 cryptographic algorithm, meaning that if the file contents is
tampered with, it will not load back into a controller.
When a nanodac device powers up, it automatically performs an integrity check on
the contents of its internal non-volatile memory devices. Additional periodic integrity
checks are performed during normal runtime and when non-volatile data is being
written. If any integrity check detects a difference from what is expected, the
controller enters Standby mode and a message is displayed on then screen.
Firmware
From time to time, to provide new functionality or address known issues, Eurotherm
may make new versions of the nanodac firmware available.
This firmware may be downloaded from the Eurotherm website, and transferred to a
nanodac instrument in the field, via a USB memory stick (or FTP server).
CAUTION
NON-SCHNEIDER ELECTRIC FIRMWARE
There is a potential risk that an attacker could upgrade a nanodac with non-genuine
firmware that contains malicious code. To mitigate this potential risk, genuine
nanodac firmware upgrade utility executables are always supplied digitally signed
with the publisher as Schneider Electric. Do not use a firmware upgrade utility if it
has not been signed by Schneider Electric.
Failure to follow these instructions can result in injury or equipment damage.
The nanodac supports the following protocols on Ethernet. For each protocol, a list of
mitigations are provided. As a general comment, the firewall is configured to block all
ports except those required for installed/enabled options.
FTP Client
An external FTP client can access the FTP server on the instrument. This FTP server
has a remote username and password for each of the users (that will need
configuring). Passwords can be modified and additional users can be added with
configurable remote usernames and passwords.
To mitigate threats:
1. Physically protect access to subnet(s) in use.
2. Firewall to block TCP port 21.
3. It is recommended that user’s should change their passwords regularly, this
could be done manually or by using the password expiry feature.
FTP Server
ICMP (ping)
DHCP
Up to two external FTP servers can be configured. The nanodac will then connect to
these servers as an FTP client and push archive files to the servers.
Threat mitigation as for FTP Client.
The nanodac will respond to a ping to aid network diagnostics.
To mitigate threats:
1. Physically protect access to subnet(s) in use.
2. Use a firewall to block ICMP / ping.
The nanodac can allocate its IP address using DHCP; however this is typically set to
fixed IP address allocation by configuration. The DHCP server could be spoofed
allocating an invalid IP address to the instrument.
To mitigate threats:
1. Use fixed IP address allocation.
2. Physically protect access to subnet(s) in use.
SNTP
The nanodac can support SNTP for network time synchronisation.
The nanodac supports ModBus, which can be configured to act as Master via TCP
and Slave via serial or TCP.
To mitigate threats:
1. Physically protect access to subnet (or serial cabling) in use.
2. Firewall to block TCP port 502 (or alternate non-standard port if so configured).
HTTP (Web Server)
To mitigate threats:
1. Physically protect access to subnet(s) in use.
2. Firewall to block TCP port 80.
UHH Navigator
To mitigate threats:
Ethernet IP
BACnet
Decommissioning
1. Physically protect access to subnet(s) in use.
2. Firewall to block TCP port 50010.
To mitigate threats:
1. Physically protect access to subnet in use.
2. Firewall to block TCP port 2222. This port is opened when Ethernet IP option is
enabled.
To mitigate threats:
1. Physically protect access to subnet in use.
2. Firewall to block UDP port 47808. This port is opened when BACnet option is
enabled.
When a nanodac instrument is at the end of its life and being decommissioned,
Eurotherm advises reverting all parameters to their default settings using the
Engineer Password ‘ResetConfig’ or via iTools (see "Security menu" on page 98 and
"iTOOLS" for instructions). This can help to protect against subsequent data and
intellectual property theft if the controller is then acquired by another party.
The information provided in this documentation contains general descriptions and/or
technical characteristics of the performance of the products contained herein. This
documentation is not intended as a substitute for and is not to be used for
determining suitability or reliability of these products for specific user applications. It
is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific
application or use thereof. Schneider Electric, Eurotherm Limited or any of its
affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein.
If you have any suggestions for improvements or amendments or have found errors
in this publication, please notify us.
You agree not to reproduce, other than for your own personal, non-commercial use,
all or part of this document on any medium whatsoever without permission of
Eurotherm Limited, given in writing. You also agree not to establish any hypertext
links to this document or its content. Eurotherm Limited does not grant any right or
license for the personal and noncommercial use of the document or its content,
except for a non-exclusive license to consult it on an "as-is" basis, at your own risk.
All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when
installing and using this product. For reasons of safety and to help ensure compliance
with documented system data, only the manufacturer should perform repairs to
components.
When devices are used for applications with technical safety requirements, the
relevant instructions must be followed.
Failure to use Eurotherm Limited software or approved software with our hardware
products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
Eurotherm, EurothermSuite, ECAT, EFit, EPack, EPower, Eycon, Eyris, Chessell,
Mini8, nanodac, optivis, piccolo and versadac are trademarks of Eurotherm Limited
SE, its subsidiaries and affiliated companies. All other trademarks are the property of
their respective owners.
This document describes the installation, operation and configuration of a paperless
graphic recorder/controller. The instrument comes, as standard, with four input
channels and is equipped for secure archiving via FTP transfer and/or to USB
memory stick.
Unpacking the Instrument
The instrument is despatched in a special pack, designed to give adequate protection
during transit. Should the outer box show signs of damage, it should be opened
immediately, and the contents examined. If there is evidence of damage, the
instrument should not be operated and the local representative contacted for
instructions. After the instrument has been removed from its packing, the packing
should be examined to ensure that all accessories and documentation have been
removed. The packing should then be stored against future transport requirements.
For the sake of clarity, the
panel is shown as though
transparent
Installation
DANGER
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Do not exceed the device's ratings.
Failure to follow these instructions will result in death or serious injury.
Before installation, ensure that the specified instrument supply voltage matches the
facility supply.
Mechanical Installation
Figure 1 gives installation details.
Installation Procedure
1. If it is not already in place, fit the IP65 sealing gasket behind the front bezel of the
instrument.
2. Insert the instrument through the panel cutout, from the front of the panel.
3. Spring the retaining clips into place, and secure the instrument by holding it firmly
in place whilst pushing both clips towards the rear face of the panel.
4. The protective membrane can now be removed from the display.
HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical
work practices. See applicable national standards e.g. NFPA70E, CSA Z462, BS
7671, NFC 18-510.
Turn off all power supplying this equipment before working on the loads of the
equipment.
Failure to follow these instructions will result in death or serious injury.
1. Isolate the mains supply and secure it against accidental operation. Remove all
wiring and the USB device and Ethernet cable (if any).
2. Remove the retaining springs by unhooking them from the sides using a small
flat-blade screwdriver.
3. Pull the instrument forwards out of the panel.
Removing the Instrument from its Sleeve
The instrument is designed to be removed from its sleeve from the front panel.
However, if a USB memory stick or the Ethernet cable is fitted then this must be
removed first.
When the instrument is shipped from the factory it is fitted with two small red clips,
one in the top side of the sleeve and the other below. These are intended as a
safeguard against removal of the instrument from its sleeve when an Ethernet cable
is fitted. These clips must also be removed, using a small screwdriver, before the
instrument can be taken out of its sleeve.
Ease the latching ears (Figure 2) outwards and pull the controller forward.
When plugging back in ensure that the latching ears click into place to maintain the
panel sealing.
Each wire connected
to LA, LB and LC must
be less than 30 metres
in length.
Relay output
Isolated DC o/p (mA/V)
Contact closure
Contact closure
Relay output
T/C, Volts, millivolts
Milliamps
RTD (three wire)
RTD (two wire)
Ohms inputs
Digital
Dual mV/TC
Dual mA
Dual input option ("Dual Input Option" on page 31, below)
(Primary and secondary inputs are not electrically isolated from one
another.)
For maximum accuracy, it is recommended that separate returns are
made to the negative terminal.
I/O1
O/P2
O/P3
Dig InA
Dig InB
O/P4; O/P5
An In1; An In2; An In3; An In4
An In1; An In2; An In3; An In4
R<200R = active
R>350R = inactive
Brown
Blue
R>500R = inactive
R<150R = active
R>600R = inactive
R<300R = active
Electrical Installation
Figure 4 shows the locations of the various user terminations along with signal and
Figure 4 Connector locations and pinouts (rear panel)
Page 30
nanodac™ Recorder / ControllerInstallation
Installation Requirements
NOTICE
Safety requirements for permanently connected equipment state:
1. A switch or circuit breaker shall be included in the building installation.
2. The switch/circuit breaker will be in close proximity to the equipment and
within easy reach of the operator.
3. It shall be marked as the disconnecting device for the equipment.
Note: Recommended external fuse ratings are: 2A Type T 250V.
Termination details
The screw terminals accept single wires in the range 0.21 to 2.08mm2 (24 to 14
AWG) inclusive, or two wires each in the range 0.21 to 1.31mm2 (24 to 16 AWG)
inclusive. Screw terminals should be tightened to a torque not exceeding 0.4Nm
(3.54lb in).
Low Voltage Option
This option allows the use of a low voltage ac or dc 24V supply. The specification in
Appendix A gives full details. The polarity of the dc supply connection is not important
-it may be connected either way round.
Dual Input Option
This is a cost option, enabled on a channel-by-channel basis by means of entering
the relevant password in the ‘Feature3 Pass’ field in Instrument.Security menu
described in Section 6.1.6.
For each enabled channel, a pair of thermocouple, mV or mA inputs can be
connected to the instrument. These inputs are called ‘primary’ and ‘secondary’, and
are terminated at the analogue input terminals (An In1 to An In 4) as shown in Figure
4, above. The primary inputs 1 to 4 are assigned to channels 1 to 4, as normal. Each
secondary input must be soft wired to a maths channel configured as Operation =
‘Copy’ if it is to be recorded/ displayed/alarmed etc.
Note: Due to the nature of the input circuit, a large offset may appear for secondary
thermocouple inputs. This offset can be removed only by using the input adjust
feature described in "Input adjust" on page 103. Because of this offset, the dual
thermocouple input option is not suitable for AMS2750D applications.
Soft wiring is described in "iTOOLS".
Maths channels are described in "Maths channel configuration" on page 133.
Channel configuration is described in "Channel Main" on page 123.
Input adjust is carried out as described in "Input adjust" on page 103.
Sample Rate
For dual input channels, both primary and secondary sample rate is reduced to 4Hz
(250ms) from thenormal 8Hz (125ms).
Input sensor break detection is not supported for secondary inputs. The internal
circuit acts as a ‘pull up’ on the secondary input which therefore saturates high in the
event of a sensor break.
Dual Milliamp Offset Correction
If ‘Dual mA’ is selected as input type, then an automatic offset correction will be
made, according to the shunt value entered in channel configuration. Refer to
"Channel Main" on page 123 for further information.
Input Range Limitation
There is no 10V range associated with the secondary input. Any input greater than
+2V or less than -2V is deemed to be ‘bad range’.
Modbus Master communications
EtherNet/IP
The master instrument can be connected directly to up to two slaves using standard
Ethernet network cable either directly (single slave only) or via a hub or switch (one
or two slaves). In either case, ‘straight through’ or ‘crossover’ cable may be used.
The cable is terminated at the RJ45 socket at the rear of the unit.
The Client and Server are connected in the same way as described above for
Modbus Master communications, except that there can be only one client and one
server.
On power up a default or custom splash screen appears and remains
visible whilst the unit is initialising. If during this process a network
broadcast storm is detected, the unit stops, displaying a network failure
icon until the broadcast storm has cleared, after which the initialisation
process resumes.
Introduction - Initial Setup
Figure 5 Engineer password configuration screen - at initial start.
At initial start, after installation the unit will display the Engineer password
configuration screen, see Figure 5.
The Engineer password must be configured to allow any further operation, see
Engineer Password - Configuration.
Note: The initial Engineer password screen only appears after a Clone file load or
firmware upgrade, if no engineer password was configured. All user accounts require
an associated password.
NOTICE
ENGINEER ACCESS DENIED
When configuring the Engineer password, ensure the password can be recalled
and entered correctly. An incorrect password will prevent Engineer access (lock
out) and any further configuration or use of the controller. Contact your local
Eurotherm support desk in the unlikely event of being locked out.
Note: Please read the following information regarding the units display screen and
navigation controls to familiarize yourself with all the controls and their associated
functions, see Operator Interface (page 34).
Engineer Password - Configuration
1. From the Engineer password configuration screen, press the scroll button.
The Engineer Pass panel appears.
2. Enter a password, using the raise and lower buttons () which in turn will
move the highlighted key, and pressing the scroll button to enter each character.
3. Press the Page button (), once you have completed typing the Engineer
password.
The Accept changes? panel will appear with the following options:
•Cancel - cancels the panel and returns to the keyboard
•No - cancels the panel and returns to the Engineer password configuration
screen
•Yes - enters the password
4. Select Yes to enter the password.
Use the raise button twice (or the lower button once) to highlight the word ‘Yes’
and press the scroll key to confirm.
The Engineer password is accepted and completed. The display mode screen
will appear, see Figure 6 Display mode screen (vertical trend).
The Engineer password is configured at initial start up, but can also be updated when
required. The Engineer password must only be associated with and used when
logging in at Engineer level access, for further details see:
•Login (page 49)
Operator Interface
Display Screen
•To Log in as Engineer (page 51)
•Security menu (page 98)
The operator interface consists of a display screen and four push buttons.
The display screen is used both to display channel information (in one of a number of
display modes), and to display the various configuration screens which allow the user
to setup the recorder to display the required channels, to set up alarms and so on.
Display modes are described in "Display Modes" on page 52 below; configuration is
described in "Configuration".
In display mode, the screen is split horizontally into three areas (Figure 6):
1. A faceplate giving channel details.
2. the main display screen showing channel traces etc.
3. the status area, displaying instrument name, the current time and date and any
system icons.
In configuration mode, the entire display screen is devoted to the selected
configuration menu.
Navigation Pushbuttons
Figure 7 Top level menu (Engineer level access)
There are four navigation buttons, called ‘Page’, ‘Scroll’, ‘Lower’ and ‘Raise’ located
below the screen. The general properties of these buttons are described in the
remainder of this section, but some have additional, context sensitive functions,
which, for the sake of clarity are not described here but in the relevant sections (e.g.
‘Message summary’) of the manual.
Page Button
From any non-configuration page, pressing this push button causes the top level
menu (Figure 7) to appear. The figure shows the menu for a user logged in with
‘Engineer’ level access. Other access levels may have fewer menu items.
Within configuration pages, the Scroll button can be used as an enter key to select
lower menu levels. In such cases the page button is used to reverse this action,
moving the user up one menu level per operation.
Scroll Button
From trending pages, operation of the scroll push-button scrolls through the channels
enabled in the group. The Faceplate cycling ‘Off’ selection can be used to keep a
particular channel permanently displayed, and the scroll pushbuttons can then be
used to select channels manually.
In configuration pages, the scroll key operates as an ‘enter’ key to enter the next
menu level associated with the highlighted item. Once the lowest menu level is
reached, operation of the scroll key allows the value of the selected item to be edited
by the relevant means (for example, the raise/lower keys, or a keyboard entry).
The ‘Page’ key is used to move the user back up the menu structure, until the top
level menu is reached, when the scroll key can be used again to return to the Home
page. The scroll button is also used to initiate user wiring as described in "iTOOLS".
Raise/Lower Buttons
Within trending displays, the Raise and Lower keys can be used to scroll through the
enabled display modes in the sequence: vertical trend, horizontal trend, vertical
bargraph, horizontal bargraph, numeric, vertical trend... and so on.
The timer function block
offers a universal timer
which may be
re-configured between
single pulse outputs and
re-triggering outputs.
Timer types are:
On pulse on-timer
On-screen help.
(Use the Page button with the
down arrow to access hidden
text at the bottom of the
screen)
+
Select configuration menu
Within configuration pages, these pushbuttons act as cursor keys, allowing, for
example, the user to highlight menu items for selection using the scroll button, and in
many cases allowing the user to select one from a number of alternative values
within menu items. These keys are also used to navigate through the virtual
keyboards ("Text Entry" on page 89) and number pads used to enter text or numeric
strings.
On Screen Help
The top level configuration menu includes contextual help text on the right-hand half
of the screen. Mostly this text fits within on screen height. Where this is not the case,
the text can be moved up or down the screen by holding the Page button operated
whilst using the up and down arrows to move the text.
The down arrow moves the text upwards on the screen; the up arrow moves it
downwards.
(Use the Page button with the down arrow to access hidden text at the bottom of the
screen)
Process Variable Display
As discussed above, the operator interface consists of a display screen and
associated push buttons. The display screen shows process variables in one of a
number of formats, or operational details (notes or alarm history for example), or
configuration details for use in setting up the recorder to produce the required
displays and history formats. The remainder of this section discusses the process
variable displays, alarm displays and so on; configuration details are to be found in
"Configuration".
Note: Some of the items below can be selected for use only by users with a suitable
permission level as set up in the ‘Instrument’ ‘Security’ menu described in "Security
menu" on page 98.
Figure 9 depicts a typical trend display and gives details of the various areas of the
Figure 9 shows a vertical trend page. Operating the Raise/Lower push-buttons allows
the user to scroll through the other display modes: Horizontal trend, Vertical
bargraph, horizontal bargraph, numeric, vertical trend... and so on. All these display
modes are described in "Display Modes" on page 52, below.
A display mode can also be selected from the Top level menu ‘Go To View’ item
which appears when the ‘Page’ key is operated.
Alarm Icons
The scroll button can be used to scroll through the points in the group, overriding the
‘Faceplate Cycling’ on or off selection
Note: A full discussion of alarms is given in the Channel Configuration section of
this manual, "Alarm 1 menu" on page 128.
Note: Trigger alarms do not display threshold marks or bars, or faceplate symbols.
The alarm icons shown below appear in some display modes. The icons on a
channel faceplate show the status of that channel’s alarm(s), as follows:
Icon is flashingalarm is active but unacknowledged or it is an Auto alarm
which is no longer active but which has not been acknowledged.
Icon steadily illuminated
the alarm is active and has been acknowledged.
Alarm thresholds and deviation alarm bars appear for horizontal and vertical trend
modes. For deviation bars, the bar stretches from (Reference - Deviation) to
(Reference + Deviation). Vertical and Horizontal bargraph modes display only
absolute alarm symbols.
The following items can appear in a dedicated window immediately to the left of the
time and date, at the bottom right-hand corner of the display. The width of this
window expands as the number of icons increases, and the instrument name is
truncated, as necessary, to make room.
System Alarms
This indicator appears, flashing, if any one or more of the alarms listed below is
active. The System Alarms summary page (accessed from ‘Go to View in the top
level menu) allows the user to view such system alarms as are active. It is not
possible to ‘acknowledge’ system alarms
Archive DisabledAn unattended archiving strategy has temporarily been
disabled.
Archiving FailedAn unattended archiving strategy has failed to complete.
Archiving TimeoutA configured archiving strategy has timed out.
Battery failureIndicates that the battery is approaching the end of its use-
ful life, or that it is missing or is completely exhausted. Im-
mediate battery replacement is recommended ("Appendix
C: Reference", "Battery" on page 431).
Broadcast Storm detected
Networking is limited until the storm has passed.
Clock failureThe internal clock was found to be corrupt at power up, or
that the time has never been set. Time is forced to 00:00
1/1/1900. Can be caused by battery failure, in which case
a battery failure message appears. The error is cleared by
setting the time and date.
Channel errorIndicates a hardware failure in the channel circuit or in the
internal cold junction temperature measurement.
Database failureCorrupted EEPROM or flash memory.
DHCP Server failure For units with ‘IP Type’ set to ‘DHCP’ (Network.Interface
configuration) this alarm occurs if the instrument is unable
to obtain an IP address from the server.
FTP Archiving file lost
A file has been deleted that had not yet been archived.
Possible causes: Communications with the server could
not be established,; archive is disabled; archive rate too
slow.
FTP Archiving to slow
The archive rate is too slow to prevent the internal memory
from overflowing. The recorder effectively switches to ‘Au-
tomatic’ ("Archiving" on page 111) to ensure that data is
not lost.
FTP Primary Server Failure
This error occurs if the recorder fails to establish connec-
tion with the primary server, after two attempts. After the
second attempt fails, the recorder attempts to establish
connection with the secondary server instead. Primary and
secondary server details are entered in the Network. Ar-
chiving area of configuration ("Archiving" on page 111).
FTP Secondary Server Failure
This error occurs if the recorder fails to establish connec-
tion with the secondary server, after two attempts. Primary
and secondary server details are entered in the Net-
work.Archiving area of configuration ("Archiving" on
Appears if, for example, the divisor of a divide function is
zero.
Media archiving file lost
A file has been deleted that had not yet been archived.
Possible causes: memory stick missing, full or write pro-
tected; archiving has been disabled; archiving rate too
slow.
Media archiving to slow
The archive rate is too slow to prevent the internal memory
from overflowing. The recorder effectively switches to ‘Au-
tomatic’ ("Archiving" on page 111) to ensure that data is
not lost.
Media fullArchive storage device is full. The alarm becomes active
only when an archive is in progress.
Media missingNo archive storage device present when archive attempt-
ed.
Non-volatile memory failure
RAM copy of non-volatile parameters is corrupted.
Non-volatile Write Frequency warning
One or more parameters are being written frequently to
non-volatile memory. If this continues, it may lead to ‘mem-
ory depletion’ (i.e. the memory will no longer be able to
store values correctly). A common cause of this problem is
frequent writes over Modbus comms.
Recording failure (message)
Message explains reason for failure.
SNTP failureInvalid data received from SNTP server, for example, the
year received from the server is <2001 or >2035, or the
server cannot be accessed.
Time synchronisation failure
Instrument time has failed to synchronise with SNTP serv-
er. If more than 5 ‘Time change events’ occur within 24
hours a ‘Time synchronisation failure’ alarm is set. The
alarm occurs 24 hours after the first event. Once synchro-
nisation is re-established, the alarm self- clears within 24
hours. A ‘Time change event’ occurs whenever the record-
er time is found to be more than two seconds different from
the server time. If the instrument time differs from the
SNTP time by less than two seconds, the instrument time
is updated gradually (1ms, eight times a second) to pre-
vent time changes being recorded. SNTP time is based on
elapsed seconds since 00:00 hours on 1st January 1900.
The time is not affected by time zones or daylight saving
adjustments.
USB overcurrentUSB power fault - too much current (i.e. >100mA) is being
drawn by a USB device.
Wiring failureThe user wiring has failed to verify, i.e. one or more wires
has been detected that does not have both a source and a
destination defined. This may be the result, for example, of
power loss during a download from iTools.
Channel Alarm
This indicator appears if any channel (including channels not in the display group) is
in an alarm state. The symbol is illuminated continuously if all alarms are
acknowledged or flashes if any one or more alarms is unacknowledged. Alarms are
acknowledged from the Root menu ‘Alarm summary’ item as described in "Go to
View" on page 43 or in the Channel configuration area ("Alarm 1 menu" on page 128)
if theuser’s access permissionis appropriate.
This icon appears whenever a memory stick (max. capacity 8GB) or other supported
USB device ("USB Devices")
is plugged into the USB port at the rear of the recorder. When data transfer is in
progress between the instrument and the memory stick, the icon changes to a ‘busy’
version.
NOTICE
LOSS OF DATA
The memory stick must not be removed whilst archiving (demand or automatic) is
in progress.
Removal of the memory stick during archiving may irreparably
damage the file system of the memory stick, rendering it
unusable. It is recommended that all archiving is suspended
before the memory stick is removed.
FTP Icon
The FTP icon appears whenever transfer activity is taking place.
Record Icon
One of four icons appears at the bottom left corner of the display to indicate recording
status.
Record
This indicates that the recorder is recording the items selected in the Group
Recording area of configuration ("Group Configuration" on page 117).
Stopped
This means that ‘Enable’ has been set to ‘no’ in the Group Recording area of
configuration ("Group Configuration" on page 117). Trending is not affected.
Paused (Suspended)
This means that recording has been paused by a wire to the Suspend parameter
(Group Recording area of configuration ("Group Configuration" on page 117) going
true (high). Trending is not affected.
In Configuration
The recorder has been placed in configuration mode either at the user interface, or
via iTools. Recording is stopped until the recorder is no longer in configuration mode.
For each non-recording state (Stopped, Paused or In Configuration). A new history
file is created when the unit comes out of configuration mode.
Note: For recording to be enabled, configuration status must be ‘logged out’ both at
the instrument and at iTools.
This ‘envelope’ icon appears when a message is generated and it remains on display
until the Message Summary (see "Message Summary" on page 44) is accessed,
whenit is removed fromthedisplay until the next new message is generated.
www.GlobalTestSupply.com
Page 40
nanodac™ Recorder / ControllerOperation
"Home" on page 41
"Configuration" on page 42
"Go to View" on page 43
"History" on page 46
"Faceplate Cycling on/off" on page 46
"Operator Notes" on page 46
"Demand Archiving" on page 46
"Login" on page 49
Home
Configuration/User
Go to View
History
Faceplate cycling (On)
Operator Notes
Demand Archiving
Log out
Page key
Scroll key
Autotune Icon
For instruments fitted with the Loop option, this symbol appears during the Autotune
process.
Breaks in recording
Breaks in recording can be caused by the unit being powered down, by the user
entering configuration mode or when the recorder time is changed manually. In
vertical and horizontal trend modes, a line is drawn across the width/height of the
chart to indicate that recording has been interrupted.
On power up, a red line is drawn across the chart. In ‘History’, if messages are
enabled the message:
Date Time System power up
is printed on the chart, together with the configuration and security revisions.
On exiting configuration mode, a blue line is drawn on the chart and in ‘History’, if
messages are enabled, the messages:
Date Time Logged out.
Date Time Config Revision: N was N-1
Date Time Logged in as: Engineer
appear on the chart.
assuming a configuration change was made)
Top Level Menu
When the instrument time is changed (manually - not through daylight saving action)
a green line is drawn on the chart and in ‘History’, if messages are enabled, the
message:
Date Time Time/Date changed
appears on the chart.
This menu appears when the page key is operated from any non-configuration page.
The menu items displayed depend on the access permission of the user. One of the
menu items is highlighted, and if the scroll key is operated, then it is the highlighted
item that is ‘entered’.
Home
Operating the scroll key whilst ‘Home’ is highlighted causes a return to the ‘Home’
page. By default, this is the vertical trend mode, but the mode can be changed in
‘Instrument.Display’ configuration ("Display configuration" on page 94).
Operating the down arrow key highlights the ‘Configuration’ item. Operating the Scroll
key enters the configuration submenu described in "Configuration".
Note: ‘Configuration’ appears only if the user has an appropriate access level.
Note: If the Auditor feature is enabled, additional user accounts are available. If one
of these users are logged in, the ‘Configuration’ menu option is replaced by the ‘User’
menu option instead (see "User menu" on page 42).
User menu
If the Auditor feature is enabled, up to 25 additional user accounts are available with
configurable access permissions and each requiring a configured password.
If one of these users are logged in, the ‘Configuration’ menu option is replaced by a
‘User’ menu option which provides the ability for the user to change their password
and set the Archive Interval (if the user has appropriate permissions).
Operating the scroll key whilst the ‘User’ item is highlighted, displays the individual
user account menu, as shown in the following figure. The menu title matches that of
the username used to log in.
Figure 12 User menu
PasswordAllows the user to change their password (up to a maxi-
mum of 20 characters). The minimum password length can
be configured using the Min Password Len parameter in
the Security menu (see "Security menu" on page 98).
Archive RateAllows the user to specify the frequency at which the con-
tents of the flash memory are archived to the USB port, or
via FTP, to a PC. Scrollable settings are:
None:Automatic archiving is disabled. Any archiving must be in-
itiated by the user using Demand Archiving.
Minute: Archive is initiated on the minute, every minute.
Hourly: Archive is initiated at 00:00 each day.
Weekly: Archive is initiated at midnight every Sunday.
Monthly: Archive is initiated at 00:00 on the 1st of every month.
Automatic. The recorder selects the least frequent of the above archive periods
This field is editable if the logged in user has appropriate permissions to adjust
the archive interval (see "User Accounts (Auditor)" on page 107). For further
information on archiving, refer to "Archiving" on page 111.
which is guaranteed not to lose data as a result of the in-
Operating the scroll key whilst the ‘Go to view’ item is highlighted, calls the Go to
view submenu (Figure 13). This allows the user to view channel alarms, system
alarms, messages or to select a different display mode.
Figure 13 Go to view submenu
Note: If an option (e.g. ‘Steriliser’) is not fitted, its display mode does not appear in
the list.
Note: Some display modes must be enabled in Instrument.View configuration
("Display configuration" on page 94) before they become available.
Alarm Summary
For each active alarm, this page displays the channel identifier with alarm number
(e.g. C1(2) = channel 1; alarm 2), the channel descriptor, the alarm threshold the
current process value and an alarm type symbol. To return to the top level menu,
operate the Page key.
Note: The background colour to the channel ID is the same as that chosen for the
channel.
Note: A prefix ‘C’ in the channel ID means that this is a measuring channel; A prefix
1. Use the up and down arrows to
highlight the required alarm.
2. Operate the scroll button. The
‘Acknowledge alarm’ window
appears.
3. Use the up arrow to highlight the
relevant field (C2(1) in this
example), or ‘All’ if all alarms are
to be acknowledged.
4. Operate the scroll key to
confirm. If the alarm fails to
respond, this may be due to the
fact that it has been configured
as a ‘Manual’ alarm, and the trigger has not yet returned to a ‘safe’ (non-alarm)
state, or it could be that the instrument is in a logged out state.
System Alarms
Operating the scroll button whilst the ‘System Alarms’ field is highlighted displays a
list of all currently active system alarms. "Status Bar Icons" on page 38 contains a list
of system alarms and their interpretations. To return to the top level menu, operate
the Page key.
A further operation of the scroll button displays a ‘Help Information’ page, giving the
reason for the highlighted alarm. Operate the scroll button again to return to the
system alarm display.
Message Summary
Operating the scroll key whilst the ‘Message summary’ field is highlighted displays
the ten most recent
messages. Operating the scroll key whilst a message is highlighted shows the
selected message in more detail (and using the up/down keys allows the other
messages to be scrolled through). Whilst in this mode, operating the scroll key again,
allows the user to choose to jump to the message’s location in trend history mode
("Trend History" on page 87) or to return to the summary page.
By default, the interface is set up such that:
1. all message types are included.
2. the up and down arrow keys cause the highlighted selection to move up or down
by one message at a time.
20/11/09 08:05:59 Active: Ch2(Al1)
20/11/09 08:05:22 Battery flat less than
All Messages
Refresh
Exit Messages
Alarm Summary
System Alarms
Message Summary
Vertical Trend
Horizontal Trend
Vertical Bargraph
Horizontal Bargraph
Numeric
Alarm Panel
Control
Control (Dual Loop)
Cascade
MESSAGE FILTERS
Display Mode Selection
Use the up/down arrow buttons to highlight the
required display mode. Once the required
display mode is highlighted, operation of the
scroll button causes the recorder to leave the
‘Go to View’ menu and to display channel
values in the selected mode. See "Display
Modes" on page 52 for a description of the
various display modes.
Alternatively the up and down arrow buttons can
be used from any of the display modes to cycle
through the available modes in the order listed
in the figure.
Note: If an option (e.g. ‘Steriliser’) is not fitted,
its display mode is not available for selection.
Note: Some display modes must be enabled
in Instrument. Display configuration ("Display configuration" on page 94) before they
become available.
Figure 15 Message summary features
All MessagesCauses all messages to be displayed on the screen.
SystemShows only system alarms.
AlarmShows only channel alarms.
Power upShows only power up messages.
Login/outLimits the display to Log in and Log out events.
This top level menu item allows the user to switch from real-time trending to review
mode, where channel values, messages, alarm triggers, etc. can be viewed back as
far as the last significant configuration change. History mode is fully discussed in
"Trend History" on page 87.
Faceplate Cycling on/off
For the purposes of this document the channel whose faceplate is currently displayed
and whose ‘pen’ symbol is visible is called the ‘Active’ channel. By default, the
recorder scrolls through all the channels in the display group, with each channel
becoming the active channel in turn. This top level menu ‘Faceplate Cycling’ item
allows the user to inhibit this scrolling action such that the currently active channel
remains active permanently, or until a manual scroll is performed using the scroll
button (or until Faceplate Cycling is re-enabled).
‘Faceplate Cycling’ is highlighted by using the up/down arrow buttons. Once
highlighted, the status can be changed from ‘On’ to ‘Off’ or vice-versa using the scroll
button. Operation of the ‘Page’ button returns to the trend display.
Operator Notes
This area allows up to 10 notes to be created when logged in as Engineer, using
either the text entry techniques described in "Text Entry" on page 89, or "iTOOLS"
described in "iTOOLS". Once logged out, operating the scroll button whilst a note is
highlighted calls a selection box allowing the user either to send that note to the
chart, or to write a Custom Note.
Custom Note
The Custom Note is written using the text entry techniques described in "Text Entry"
on page 89. Once the note is complete, operation of the page button calls a
confirmation display. The down arrow is used to highlight ‘Yes’, and when the scroll
key is then operated, the message is sent to the chart. The user name is added to the
start of the custom note when saved. This custom note is not retained for further use,
so if it is required on a regular basis, it is suggested that one of the Operator Notes 1
to 10 be configured (Engineer access level required) so that it may be used instead.
Note: Note: Each note can contain up to 100 characters.
Demand Archiving
This allows a user, with a high enough access level, to archive a selected portion of
the recorder history, either to a ‘memory stick’ plugged into the USB port at the rear of
the recorder (Local Archiving), or to a PC, by means of the FTP protocol (Remote
Archiving). The archived data remains in the flash memory of the instrument. When
the flash memory is full, new data causes the oldest file(s) to be discarded.
The up and down arrow keys are used to navigate to the required field.
Figure 16 Demand Archiving menu (Local Archiving on left; Remote Archiving on right)
Archive To With this item highlighted, the scroll button and the
up/down arrows can be used to select ‘USB’ or ‘FTP Server’. For ‘USB’, the archive will be made to the rear USB
memory stick. For ‘FTP Server’ the archive will be made to
the Primary or Secondary server (configured in the Network.Ar-chive area of configuration described in "Archiving" on page 111. For more details about remote archiving, see ‘Remote archiving’, below.
Archive In a similar way, select the archive period:
None: No archiving to take place. (Not editable when
logged out).
Last Hour: Archives all files created within the last 60 minutes.
Last Day: Archive all files created in the last 24 hours.
Last Week: Archives all files created in the past seven
days.
Last Month: Archives all files created in the past 31 days.
Archive All: Archives all the files in the recorder’s history.
Bring To Date: Archives all files created or updated since
the ‘Last Archive’ date and time.
Suspend Schedule When set to ‘Yes’, automatic (scheduled) archiving is
stopped, once the transfer of the current file is complete.
Suspend Schedule must be set to ‘No’ again, to restart the
suspended archive. Suspend can be used to allow the
memory stick to be removed and re-fitted safely.
Cancel AllWhen set to ‘Yes’, this cancels USB archiving activity im-
mediately, or cancels FTP archiving once transfer of the
current file (if any) is complete.
Last ArchiveShows the date and time at which the last archive (demand
or automatic) was attempted. If a demand archive is requested, or is in operation when an automatic archive is
triggered, the automatic archive takes precedence.
StatusFor Archive to USB only: ‘Complete’ means that no archiv-
PriStatusFor Archive to FTP Server only, this shows the transfer
SecStatusFor Archive to FTP Server only, this shows the transfer
ing is currently taking place. ‘Transferring’ indicates that an
archiving is in progress. Accompanied by an animated circular display. ‘Suspended’ means that archiving has been
suspended as requested.
status between the instrument and the primary host computer.
status between the instrument and the secondary host
computer.
This allows the archiving of recorder files to a remote computer via the RJ45 type
connector at the rear of the recorder, either directly or via a network. In order to carry
out a successful transfer:
1. Details of the remote host must be entered in the Network.Archive area of
configuration ("Archiving" on page 111).
2. The remote computer must be set up as an FTP server. Help from the user’s IT
department may be necessary in order to achieve this. Appendix C, "Setting Up
An FTP Server Using Filezilla" on page 431 to this manual suggests one way,
using Filezilla.
3. The remote computer must also be set up to respond to ‘pings’. This is because
the instrument pings the host whilst establishing connection, and if it does not
receive a response the archive attempt fails.
When accessing files using Microsoft® Internet Explorer, the address (URL) field can
be in one of two formats:
1. ftp://<instrument IP address>. This allows a user to log in as the anonymous user
(if the recorder has any account with the user name set to ‘anonymous’ with a
blank password.
2. ftp://<user name>:<password>@<instrument IP address> to log in as a specific
user.
Microsoft® Internet Explorer displays, by default, history files only. To quit the history
folder, either uncheck the Tools/Internet Options/Advanced/Browsing/’Enable folder
view for FTP sites’ option, or check the Tools/Internet
Options/Advanced/Browsing/’Use Web based FTP’ option.
Review Software
‘Review’ is a proprietary software package which allows the user to extract ‘archive’
data from one or more suitable instruments* and to present this data on a host
computer, as if on a chart, or as a spreadsheet. The host computer must be set up as
an FTP server (see Appendix C, "Setting Up An FTP Server Using Filezilla" on
page 431 for a description of one way of doing this).
As described in the Review help system, ‘Review’ allows the user to set up a regular
transfer of data (using FTP) from connected instruments into a database on the PC,
and then from this database to the chart or spreadsheet. The chart/spreadsheet can
be configured to include one or more ‘points’ from one or all connected instruments
(where a ‘point’ is an umbrella term for channel, totaliser, counter etc.).
It is also possible to archive instrument history files to a memory stick, Compact
Flash card etc. (depending on instrument type) and to use this to transfer the data to
the PC.
Each type of instrument has its own remote user name and password configuration.
*Suitable instruments are connected instruments, the archive files of which have the
suffix ‘.uhh’.
Login allows the user to enter a password in order to gain access to areas of the
unit’s configuration which are not available when the user is logged out.
Passwords are required for the additional 25 user accounts, when the Auditor feature
is enabled. Failed login attempts are recorded in the history. It is recommended that a
strong password, that is difficult to guess is used. Failed login attempts are recorded
in the history.
Note: User accounts of any access level require a password, otherwise they will not
be available for selection.
Logged Out Access Level
Logged out mode allows the user to select viewing mode, to view history, to view
alarms, to toggle faceplate cycling on and off, to send notes, to suspend/resume USB
archiving and to access the login process.
Operator Access Level
In addition to the logged out features, Operator access level allows the user to
acknowledge alarms, to edit notes and to perform demand archive operations.
By default, a password is required to enter Operator level. Passwords can be
configured either at Supervisor level or at Engineer level.
If the Auditor feature is enabled, the Operator user is disabled and instead replaced
by the 25 User accounts (see section User Access Level below).
Note: The User 1 account defaults to a user with a user name of “Operator” in this
instance (with no additional permissions), which can be kept, disabled, modified or
overridden if necessary or desired.
Supervisor Access Level
In addition to the logged out level function, this access level allows the user to view
the recorder’s configuration, and to edit some values (such as alarm thresholds). The
password for the Supervisor level must be configured, if the access level is to be
used (and can be changed) in the Instrument area of configuration, either at
Supervisor or Engineer access level, see Security menu (page 98). It is
recommended that a strong password be used.
When the Auditor feature is enabled, it is regarded as best practise that the
Supervisor level is not used at all. This can be enforced by disabling the Supervisor
level altogether (refer to the ‘Sup Log Disabled’ parameter in Security menu
(page 98). With the Supervisor access level disabled, only the Engineer level can
This allows full access to all areas of the recorder configuration. The Engineer
password must be configured at initial start see Introduction - Initial Setup (page 33)
and can be changed in the Instrument area of configuration by the existing Engineer
access level user, see Security menu (page 98). It is recommended that a strong
password be used.
Note: Recording is stopped for as long as the user is
logged in at Engineer level, even if the recorder is not
being configured. This is indicated by the Record icon at
the bottom left corner of the process value display screen
being replaced by the Configuration (wrench) icon.
If the Auditor feature is enabled, it is recommended to only use the Engineering level
within the context of a formal change control procedure.
User Access Level
If the Auditor feature is enabled, an additional 25 user accounts are available which
can be configured to provide customisable levels of permission on a per-account
basis. When this is done, the standard Operator Access Level is disabled, and the
Logged Out user has no permissions. When logging in as one of these 25 user
accounts, the account number (1 to 25) is prefixed to the user name. Refer to "User
Accounts (Auditor)" on page 107 for details on how to configure these user accounts
and the permissions available to be assigned to each. Failed login attempts are
written to the history, as is the user being disabled if a maximum number of failed
login attempts is exceeded.
* If the Auditor feature is enabled, the
Operator user is not displayed. If the
Auditor feature is not enabled, the
<User> user is not displayed.
Logged out
<User>
Operator
Supervisor
Engineer
Engineer
Access
Password
Accept changes
Cancel
No
Yes
Access
Access
Access
Access
Access
Password
Login Procedure
From the top level menu, use the up or down arrow keys as often as necessary in
order to highlight ‘Login’, and then operate the Scroll key to produce the ‘Access
Logged out’ display.
Note: This procedure describes how to login to an access level with a password - all
access levels (user accounts) require a password, otherwise they will not be
available for selection.
Figure 17 Log in Menu
To Log in as Engineer
Note: Use the Engineer password configured at initial set up, see Introduction -
Initial Setup (page 33) for further details.
1. From the Log in panel, press the up arrow key and select Engineer.
2. Press the scroll key twice.
The ‘alpha’ keyboard, with the letter ‘q’ highlighted appears.
3. Enter the Engineer password configured at Initial Setup, using the raise and
lower buttons which, in turn will move the highlighted key, press the scroll button
to enter each selected character.
4. Press the Page button, once you have completed typing the Engineer password.
The Accept changes? panel will appear with the following options:
•Cancel - cancels the panel and returns to the keyboard
•No - cancels the panel and returns to the Engineer password configuration
screen
•Yes - enters the password
5. Select Yes to enter the password.
Use the raise button twice (or the lower button once) to highlight the word ‘Yes’
and press the scroll key to confirm.
The configuration menu appears. (See Configuration (page 91) for further
details).
www.GlobalTestSupply.com
Page 51
Operationnanodac™ Recorder / Controller
Display Modes
The following subsections describe the various display modes available to the user.
By default, the ‘Home’ display mode is ‘Vertical Trend’, but this can be edited as a
part of ‘Instrument.Display’ configuration ("Display configuration" on page 94). This
configuration area also allows the user to disable one or more display modes should
they not be required.
The current display mode can be chosen either by using the top level menu ‘Go to
View’ item or, from any display mode, by scrolling through the enabled modes using
the up or down arrow buttons.
Details of the various display modes are to be found in the following subsections:
Vertical trend"Vertical Trend Mode" on page 52
Horizontal trend"Horizontal Trend Mode" on page 53
Vertical bargraph"Vertical Bargraph Mode" on page 54
Horizontal bargraph"Horizontal Bargraph Mode" on page 54
Numeric "Numeric Mode" on page 55
Alarm panel"Alarm Panel Mode" on page 56
Control loop 1/2"Control Loop1/Loop2" on page 57
Cascade "Cascade Display Mode" on page 58
Programmer (inc. future trend)"Programmer Display Mode" on page 59
Steriliser "Steriliser Display Mode" on page 70
Batch"Batch Summary" on page 75
Promote list"Promote list" on page 77
Modbus Master"Modbus Master display mode" on page 78
EtherNet/IP"EtherNet/IP display mode" on page 80
Vertical Trend Mode
In this mode, channel values are traced as though on a chart rolling downwards (i.e
with the latest data at the top). The chart speed, and the number of major divisions
are configured in the ‘Group.Trend’ area of configuration ("Group Trend
configuration" on page 117). By default, the chart background is black, but this can
be changed to white or grey in the ‘Instrument’ ‘Display’ area of configuration
("Display configuration" on page 94).
By default, after a few seconds, the ‘chart’
expands leftwards to hide the scale. This
feature can be disabled in the
Instrument.Display area of configuration
("Display configuration" on page 94,
H.Trend scaling) so that the scale is
permanently on display.
Inst name
Channel 16.23V
Figure 18 Vertical trend mode display elements
One of the channels is said to be the ‘current’ or ‘scale’ channel. This channel is
identified by its pen icon being displayed, and by the channel descriptor, dynamic
value and its scale being displayed on a ‘faceplate’ across the width of the display,
above the chart.
Horizontal Trend Mode
Each channel in the Group becomes the ‘current’ channel in turn, for approximately
five seconds -i.e. the channels are cycled through, starting with the lowest numbered
channel. Once the final channel in the Group has been displayed for five seconds,
the first channel is returned-to and the process repeats. This scrolling behaviour can
be enabled/disabled from the top level menu ‘Faceplate Cycling (Off)’ item described
in "Faceplate Cycling on/off" on page 46.
The scroll button can be used to cycle through the channels manually in both
Faceplate cycle on and off modes. Use of the up arrow button causes the next
enabled display mode to be entered (default = horizontal trend). The page key calls
the top level menu.
This view is similar to the vertical trend mode described in "Vertical Trend Mode" on
page 52 above, except that the traces are produced horizontally rather than vertically.
Initially, as each channel appears, its scale appears at the left edge of the display (as
shown below), but in order to show the maximum amount of trend data, the scale is
overwritten after a few seconds.
The scroll button toggles
the text between point
descriptor (as shown) and
point value.
Note: Timestamps appear to the right of the gridline to which they relate.
Use of the up arrow button causes the next enabled display mode to be entered
(default = vertical bargraph). Use of the page key calls the top level menu.
Vertical Bargraph Mode
This display mode shows the channel values as a histogram. Absolute alarm
threshold values appear as lines across the bars, grey if the alarm is not triggered;
red if the alarm is triggered. Alarm symbols appear for active alarms.
Bargraph widths for four to six channels divide the width of the display screen equally
between them. For one and two channels, the width is fixed, and the bars are centred
on the screen. Figure 19 shows some examples (not to the same scale).
Figure 20 Vertical bargraph display mode
Use of the up arrow button causes the next enabled display mode to be entered
(default = horizontal bargraph). Use of the page key calls the top level menu.
Horizontal Bargraph Mode
Similar to the Vertical bargraph mode described in "Vertical Bargraph Mode" on
page 54, above, but includes channel descriptors.
The scroll button toggles the text between point descriptor (as shown) and point
value.
Use of the up arrow button causes the next enabled display mode to be entered
This display appears only if enabled in the Instrument Display configuration ("Display
configuration" on page 94). Alarm panel mode shows current value and alarm status
for each channel enabled in the Trend Group. The status is shown in two ways, by
the colour of the relevant bar, and by the alarm status indicators.
Figure 24 Alarm panel display (six channels)
The figure above shows an example where the Trend group contains six channels.
Figure 25 shows how the display appears for trend groups with fewer than six
channels configured.
Figure 25 Alarm panel display layouts for trend groups with fewer than six channels
These displays appear only if the controller option is enabled ("Security menu" on
page 98).
The loop display modes are interactive, in that the setpoint, the Auto/Manual mode
and the Manual Output value can be edited from the user interface. Full configuration
is carried out in the Loop setup menus ("Loop Option Configuration" on page 142)
and a fuller description of control loops is to be found in "Appendix B: Control Loops"
to this manual.
Figure 26 depicts a single loop display and the dual loop display. The up and down
arrow keys are used as normal to scroll through Loop1, Loop2 and Dual loop pages.
Figure 26 Loop displays
Note: The colours associated with the loops are those of the channels to which they
are wired.
Editing Techniques
1. With the loop page on display, operate the Scroll
key. This highlights the first editable item (SP1).
The scroll order includes both loop1 and loop 2
parameters in the dual loop display.
2. Use the up and down arrow keys to select the
required field for editing. When the required field is
highlighted, operate the scroll key again, to enter
edit mode.
3. Use the up/down arrows to edit the current setting.
4. Operate the scroll key to confirm the edit.
5. Select a further parameter for editing, or operate
the page key to return to normal operation.
Note: Edit permissions for Setpoint, Auto/Manual
and Manual Output Access are set in the Loop Setup
configuration menu ("Setup menu parameters" on
page 144). If the Auditor feature is enabled, user account permissions are set using
the User accounts menu ("User Accounts (Auditor)" on page 107).
www.GlobalTestSupply.com
Page 57
Operationnanodac™ Recorder / Controller
PV
WSP
SP1
Mode
Mode
Inst name
SP1
PV
WSP
Cascade
Slave
Master
Cascade Display Mode
This display mode appears only if ‘Cascade’ has been enabled in the
Instrument.Display area of configuration "Display configuration" on page 94). See
also Advanced Loop configuration ("Advanced Loop Configuration" on page 152).
Figure 27 Single channel
Operating the scroll button highlights the Master ‘Mode’ field. Operating the scroll
button again, enters edit mode allowing the user to use the up/down arrow buttons to
scroll through the available modes. Once the required mode appears, a further
operation of the scroll button confirms the entry and quits edit mode.
Once out of edit mode, the down arrow key can be used to select Master ‘SP1’, Slave
‘SP’ and Slave ‘Man OP’. The Mode selected determines how many of these items
are editable by the operator.
Mode Cascade: The master loop is in auto mode and provides
SP1Setpoint 1 is the primary setpoint of the controller. If the
SP The slave setpoint, either local (Manual or Slave mode) in
Man.OP The percentage output power to be applied when in Man-
Figure 27 Cascade display mode
the slave setpoint. Changing modes causes the slave to
switch to the local slave setpoint.
Slave: A simple single loop controlling with a local setpoint.
Manual: Provides a single manual percentage power output.
controller is in automatic control mode, then the difference
between the setpoint and the process variable (PV) is continuously monitored by the control algorithm. The difference between the two is used to produce an output
calculated to bring the PV to the setpoint as quickly as possible without causing overshoot.
which case it can be edited, or supplied by the master loop
(Cascade mode), in which case it is not editable.
ual mode (100% = full on; 0% = off).
Note: Note: The default loop names (‘Master’ and ‘Slave’) can be replaced by
user-entered strings of up to 10 characters in Advanced Loop Setup configuration
("Advanced Loop Setup menu" on page 154).
www.GlobalTestSupply.com
Page 58
nanodac™ Recorder / ControllerOperation
Program status
PV
WSP
Mode
Program Name (Segment name)
PV
WSP
Mode
Program edit
Ramp
Events
Ch1 PSP
Ch1 TSP
Status: Running
Seg Time Left
Ch1 Rate
Run
123.2
140.0
00:00:30
00:02:12
00:00:44
1
Ch1 PSP
Ch1 TSP
Status: Running
00:01:30
00:03:12
00:01:06
12.7
13.0
Events
Run
PV
WSP
Ch1 PSP
Ch1 TSP
Seg Time Left
123.2
140.0
Program Name (Segment name)
Program
progress
Segment
progress
Program time
remaining
Figure 27 Double channel
Programmer Display Mode
Figure 28 Programmer displays (typical)
This display mode (if enabled - see "Display configuration" on page 94) allows the
user to monitor the progress of a single or dual-channel setpoint program, and if
logged-in as ‘Operator*’, to reset or run the program. The program itself is created in
the Program edit page (described below) and in Programmer configuration
("Programmer Configuration" on page 171 or "iTOOLS").
Note: *Operator is the default access level - to edit, see ‘Prog Mode Access’ in
"Programmer Setup menu" on page 175).
The displays contain the following features:
Program nameThis is the name of the loaded program. If the program has
been modified since being saved, an asterisk (*) appears
after the name. Default background colour shown. This
colour changes to that assigned to the input channel when
this is configured.
Segment nameThis is the name of the current segment. If not named in
Segment configuration, then the segment number appears
instead.
Program statusAt the top right hand corner of the display, this can be any
one of the following:
The program is running (or ran last time) without any
PV ‘Alarm’ events or user intervention.
The user has intervened in the running of the program,
by placing it in ‘hold’ or ‘reset’, or by advancing a segment,
Program editThis icon appears for users with appropriate access
or by adjusting a duration, target setpoint, ramp rate or
time-to-target value.
A PV ‘Alarm’ Event has activated. A PV ‘Alarm’ Event
is an absolute high/low or a deviation alarm on the PV input.
There is no program loaded, or if a program is loaded,
it has not yet run.
permissions, to indicate that setpoint programs can be
configured (as described in Program edit, below).
Segment typeFor single channel displays, this indicates the type of seg-
www.GlobalTestSupply.com
ment currently being run:
Dwell. The segment value remains constant for the du-
Page 59
Operationnanodac™ Recorder / Controller
ration of the dwell period.
End (dwell). Displayed on completion of the program.
The segment value remains at the final value until reset.
End (reset). Displayed on completion of the program.
The program resets.
Ramp. The segment value ramps at a fixed rate or over
a fixed period to the Target setpoint. Ramp up icon shown;
ramp down is similar but inverted.
Step. The segment value switches immediately to the
new Target setpoint. Step down shown; step up similar but
inverted.
Wait. The segment value remains constant until the
wait criteria are satisfied.
PVThe current process value of the signal wired to Ch1(2) PV
Input. C
h1(2)PSPThis is the output setpoint from the programmer for the
channel. In reset this value tracks the configured servo parameter.
Ch1(2)TSPThe channel target setpoint. The target setpoint may be
edited while the program is in hold (in such cases, for ramp
rate segments the time remaining is recalculated.
EventsUp to eight events can be configured in the Program Edit
page. Any one or more of these events may be deemed to
be active for the duration of each individual segment.
ModeShows the current run mode of the program. If the user has
the correct access level, the mode can be set to ‘hold’, reset’ etc. by using the scroll key twice (first to highlight the
run mode, then again to enter edit mode) and then using
the up/down arrow keys to select the required mode. Run,
reset, hold etc. can also be selected by inputs from other
parameters, switch inputs etc.
StatusShows the status of the current segment.
Ch1 RateThe channel 1 rate-of-change of segment value for ‘Rate’
ramp segments.
Ch1 TimeShows the channel 1 duration configured for the segment
to ramp, dwell etc. for ‘Time’ ramp segments. For
two-channel programs, see the note below.
Seg Time LeftShows the time that the segment has to run before com-
pletion.
Program progressThe numerals show program elapsed time, and the bar
gives an indication of progress so far. For two-channel programs, see the note below.
Segment progressFor each segment as it runs, this gives a visual indication
of the proportion of total segment time which has elapsed
so far. For two-channel programs, see the note below.
Program time remaining
Shows the time remaining until the program completes.
For two-channel programs, see the note below.
Note: Note: For two-channel programs, in ‘Hold’ mode, the ‘program progress’,
‘segment progress’ and ‘program time remaining’ areas of the display are replaced
by ‘Ch1 Time’ and ‘Ch2 Time’, as shown below.
Programs can be controlled by users with the correct access level (defined in
Programmer configuration - "User Values" on page 225). The display page is placed
in edit mode by operation of the scroll key (‘Mode’ highlights). A second operation of
the scroll key followed by operation of the up/down arrows allows the user to select
‘Run’, ‘Hold’ or ‘Reset’. A further operation of the scroll key initiates the selected
action.
Figure 30 Setting the Mode
NOTES:
1. These functions can also be carried out by wiring relevant inputs to the ‘Run’,
‘Hold’ or ‘Reset’ parameters in Programmer configuration ("User Values" on
page 225).
2. The user must have either ‘Logged off’, ‘Operator’ or ‘Supervisor’ level access as
defined in ‘Prog Mode Access’ in the Programmer. Setup menu described in
"Programmer Setup menu" on page 175. Alternatively, if the Auditor feature is
enabled, a user with Program Mode permissions can also access the
Programmer Mode. The program cannot run if the unit is logged into at ‘Engineer’
level.
Program Editing
The program edit page is accessed by operating the scroll button once to highlight
the Mode, then using the up arrow key to highlight the page symbol at the top right
hand corner of the display and then the scroll button again to enter the program
editor.
www.GlobalTestSupply.com
Page 61
Operationnanodac™ Recorder / Controller
Mode
Ch1 PSP
Events
Program Name (Segment name)
Status: Reset
Ramp
Reset
14.3
Mode
Ch1 PSP
Events
Program Name (Segment name)
Status: Reset
Ramp
Reset
14.3
By default, Program Edit is available only to users with
Supervisor or Engineer level access. The required
access level can be edited in Programmer. Set Up
configuration as described in "Programmer Setup
menu" on page 175.
Program Edit
Operation
Status
Program
Holdback Style
Ch1 Holdback
Ch1 Holdback Val
Ch2 Holdback
Ramp Style
Ch1 Ramp Units
Ch2 Ramp Units
Select ...
Success
Program Name
Program
High
0.0 V
Off
Time
Per Second
Per Minute
1
Heat Init
Segment Number
Segment Name
Figure 31 Access to the program editor
As can be seen from the figure above, the initial Program Edit page is divided into
two areas - the top part contains program details; the lower part (Figure 33) contains
individual segment details. The editable items that appear in the program details area
depend on the features enabled in the Programmer Features configuration menu
("Programmer Features menu" on page 172).
Note: Access to some program operations is restricted to users with the correct
access level, as defined in the ‘Prog Mode Access’, the ‘Prog Edit Access’ and the
‘Prog Store Access’ parameters in the Programmer. Set Up area of configuration
described in "Programmer Setup menu" on page 175. Alternatively, if the Auditor
feature is enabled, individual users can be assigned access to the Program Mode,
Program Edit and Program Store functions. Access to some items also depends on
whether or not the program is running.
Program Details
OperationThis allows the user to select one of the following (see also
‘Program Store’, below): Load. Opens the program store
and allows the user to select a program to be loaded. The
program must have the same number of channels as defined in Programmer.Set Up ("Programmer Setup menu"
on page 175).
Store. Allows the current program to be saved to the internal program drive. This is useful if you wish to snapshot the
current program and store this under a different program
name.
Delete. Allows the selectedprogram to be deleted.
Delete All. Deletes all programs.
Copy. Copies the selected program for ‘pasting’ either
from the internal drive to the USB device, or vice-versa.
This is useful if you need to transfer a program to other
nanodac instruments.
Copy All. As above, for ‘Copy’, but copies all the programs
in the selected directory.
Note: If a ‘Store’, ‘Copy’ or ‘Copy All’ operation would result in there being a total of
more than 100 program files in the internal drive, the operation fails and an error
message is displayed.
StatusSuccess. Previous operation was successful.
Failed. Previous operation failed.
Loading. The program is loading.
Copying. The program copy process is underway.
Deleting. The relevant program is being deleted.
ProgramThe name of the program currently loaded.
Holdback StyleAppears only if ‘Holdback’ is enabled in the Programmer
Features configuration ("Programmer Features menu" on
page 172). See also ‘Holdback’, below.
Program: Holdback applies to all appropriate segments.
Per Segment: Holdback enabled on a segment by seg-
ment basis as described in ‘Segment Configuration’ below.
Ch1 HoldbackAppears only if ‘Holdback Style’ (above) is set to ‘Pro-
gram’.
Off: Holdback is disabled.
Low: Holdback is entered when PV < (PSP - Holdback Val-
ue).
High: Holdback is entered when PV > (PSP + Holdback
Value).
Band: Holdback is entered when PV < (PSP - Holdback
Value) or PV > (PSP + Holdback Value).
Ch1 Holdback value The value to be used in triggering holdback.
Ch2 HoldbackAs for Ch1 Holdback, above but for channel 2. Appears
only if ‘Channels’ is set to ‘2’ in Programmer Set Up con-
figuration ("Programmer Setup menu" on page 175).
Ch2 Holdback value As for ‘Ch1 Holdback value’, above, but for channel 2. Ap-
pears only if ‘Channels’ is set to ‘2’ in Programmer Set Up
configuration ("Programmer Setup menu" on page 175).
Ramp StyleRamp style applies to all ramp segments in the program.
Ramp Style can be edited only when the program is in Re-
set mode. Setpoints, rates, times etc. are set in the individ-
ual segment configurations.
Rate. A Ramp Rate segment is specified by a target
set-point and the rate at which to ascend/descend to that
set-point.
Time. A Ramp Time segment is specified by a target
set-point and a time in which to achieve that set-point.
Ch1 Ramp UnitsSelect ‘Per Second’, ‘Per Minute’ or ‘Per Hour’ for ramp
timing units. Ramp Units can be edited only when the pro-
gram is in Reset mode.
Ch2 Ramp UnitsAs for ‘Ch1 Ramp Units’ above. Appears only for two chan-
nel programs and allows different ramp units to be select-
ed for the two channels, if required. Ramp Units can be
Holdback pauses the program (freezes the Programmer setpoint (PSP) and the time
remaining parameters) if the difference between the Process value (PV) and the PSP
exceeds a user-specified amount (Holdback value). The program remains paused
until the PV returns to within the specified deviation. In ramp or step segments,
holdback indicates that the PV is lagging the SP by more than the specified amount
and that the program is waiting for the process to catch up. In a dwell segment,
holdback is used to guarantee that a work piece stays at set-point within a specified
tolerance for the specified dwell duration.
Figure 32 Holdback
Segment Configuration
Segment NumberSelect the relevant segment for configuration.
Segment NameEnter a segment name of up to 20 characters. This name
will be truncated on the display page if it, together with the
program name, are too long to fit the width of the display
area.
Ramp. For any program, Ramp segments can be either
‘Ramp Rate’ segments or ‘Ramp Time’ segments accord-
ing to the ‘Ramp Style’ setting described above. See also
Page 64
nanodac™ Recorder / ControllerOperation
‘Ch1(2) Time’ or ‘Ch1(2) Rate’, below.
Dwell. The setpoint is maintained at its current value for
the period defined in ‘Duration’ (see below).
Step. A step segment allows a step change to be entered
for the target set-points Ch1 TSP and Ch2 TSP.
Wait. A wait segment causes the program to wait for a cer-
tain event to occur before continuing. See ‘Wait For’, be-
low.
Go Back. A Go Back segment allows a specifiable number
of iterations to be performed of a group of segments. This
could be used, for example, to cycle an entire program by
having a Go Back segment immediately before the end
segment and specifying segment 1 as the ‘Go Back To’
point. Setting ’Cycles’ to ‘Continuous’ causes the program
to loop indefinitely, until interrupted by the user. ‘Nested’
loops are not permitted i.e. ‘Go Back’ is not available as a
segment type for segments inside an existing GoBack
loop.
End. The final segment of a program allows the user to se-
lect ‘Dwell’ or ‘Reset’ as the action to be taken at the end
of the program (see ‘End Type’, below).
Ch1(2) TSPTarget setpoint. The value that Ramp or Step segments
seek to attain, for channel 1(2).
Ch1(2) RateFor Ramp Rate segments, this specifies the speed at
which the process value ramps towards the target, for
Channel 1(2). The ramp units (per second, per minute, per
hour) are set in Ch1(2) ramp units described above.
Ch1(2) TimeFor Ramp Time segments, this allows the user to specify
the time to be taken by the segment for the process value
to reach the target.
DurationFor Dwell segments, this allows the entry of the time for
which the segment dwells.
Go Back ToFor ‘Go Back’ segments, this defines the number of the
segment to which the program is to return.
CyclesThe number of times the ‘Go Back’ instruction is to be car-
ried out. If set to ‘Continuous’, the program continues until
the user intervenes to stop it.
End TypeAllows the user to select the action to be taken at the end
of the program:
Dwell: the set-point is maintained indefinitely and event
outputs remain at their configured state.
Reset: the set-point reverts to the value used by the control
loop before the program was started and the event outputs
return to their default states.
Wait ForDigital High: Wait segments can be configured to wait for
‘Wait Digital’ to go ‘high’ before allowing the program to
continue.
Analog 1(2): The segment waits for ‘Wait Analog1(2) to
meet an Absolute High or Low, or Deviation High or Low
condition before allowing the program to continue.
Analog Both: As Analog 1(2) above, but waits for both
Channels’ conditions to be true before continuing.
Note: ‘Wait Digital’, Wait Analog 1’ and ‘Wait Analog 2’ parameters are configured in
the Programmer.Set Up menu described in "Programmer Setup menu" on page 175.
Ch1 WaitSelect ‘Abs High’, ‘Abs Low’, ‘Dev High’ or ‘Dev Low’ as the
wait criterion for channel 1. Appears only if ‘Wait For’
(above) is set to ‘Analog 1’ or ‘Analog Both’.
Ch2 WaitSelect ‘Abs High’, ‘Abs Low’, ‘Dev High’ or ‘Dev Low’ as the
wait criterion for channel 2. Appears only if ‘Wait For’
Event 1 to 8The number of Events available (Max Events) is defined in
Programmer Set Up configuration ("Programmer Setup
menu" on page 175). Enabling an event causes the rele-
vant indicator on the display page to be illuminated for the
duration of the segment. As with ‘User Val’, above, Events
can be wired to the inputs of other parameters if required.
Figure 35 iTools example showing Ch1 UserVal being used to trigger custom mes-
sage 1.
Future Trend Display Mode
If enabled in Instrument.Display configuration ("Display configuration" on page 94),
this allows the user to view the actual value of the PSP alongside the expected value,
so the two can be compared to see how the process is performing. Future trend is an
enhancement of the horizontal trend mode, with the display being divided into two
parts, with the instantaneous current value located at the divide, with past trends to
the left and the next few program segments to come, to the right.
NOTES:
1. For the future trend mode to appear, the programmer must be wired to the loop
or advanced loop feature.
2. Both historic and future trends move from right to left with the present anchored
at the screen centre.
3. The amount of history and of future trending displayed on the screen depends on
the trend interval set in Group.Trend configuration ("Group Trend configuration"
on page 117).
Symbol appears only if a
suitable USB device is
inserted
Figure 36 Future trend display
Program Store
Note: The access levels required for the operations described below are configured
in the Programmer Set Up menu ‘Prog Edit Access’ and ‘Prog Store Access’
parameters, described in "Programmer Setup menu" on page 175.
The program store allows access to the instrument’s local program storage area and
to programs stored on a USB memory stick (if any) and to those stored in a PC (if
any), via FTP. Programs may be saved to (Stored) or retrieved from (Loaded) from
the program store, or they can be copied or deleted. Selecting any of the program
operations (except ‘Delete All’), from the Program Edit page (Engineer access level
required) opens the file explorer page. "Program store display" on page 68 depicts
this page, with just a couple of example entries after a ‘Load’ operation has been
requested. On entry, use the up/down arrow button to select ‘User’, ‘USB’ or ‘FTP’
(selection highlights yellow), then use the scroll button to confirm. Use the up/down
arrow buttons to select the required file, and then use the scroll button again to
confirm. Other operations are similar.
The file explorer supports 100 entries, which may be directories or files.
Note: A ‘busy’ icon (rotating green flash) appears whilst directory listings are being
From firmware version V5.00 and above a quick selection of an internally stored
program may be made directly from the Program Summary page. The programmer
must be in Reset. Press and hold the scroll key for two seconds. The page will go
immediately to the file explorer page with the ‘User’ drive selected and the
‘Operation’ parameter set to ‘Load’. The first program file will be selected (assuming
different programs have been configured). Use the Up/Down keys to select the
required program followed by the scroll key to load it.
If the selected file cannot be loaded (for example, the programmer file is for a
different number of channels) then an error message is shown on the file explorer.
The Quick Access to load mode adheres to the access security settings set in
configuration mode - Programmer set up ("Programmer Setup menu" on page 175).
Note: Quick load is disabled when in Edit mode. This is indicated by the highlighted
parameter showing the raise/lower symbol to the right of its value.
Figure 38 Program load display
Program Load via a Program Number
This feature has been added to firmware versions V5.00 and above. To allow a
program (stored as a file) to be loaded, either via a BCD switch, wired to a set of
digital inputs, or via a single comms transaction, it is necessary to prefix the program
name with a program number in the range 01 to 99. For example, 01kiln1.uipz,
01furnace.uipz, 02kiln2.uipz, 03kiln3.uipz etc. The program name can consist of up
to 18 characters. Note that program numbers 1 to 9 must be entered as 01 to 09
otherwise they will not be recognised by the switch or via comms. On value change of
the program number, the first program file with the prefixed number in the
instrument’s internal User drive (listed lexicographically) will be loaded. In the above
example if program 01 is selected, 01fur-nace.uipz will be loaded, 01kiln1.uipz will
not be loaded using the BCD switch or through comms. It can, of course, be loaded
manually.
If no program number is prefixed it is not possible to load the program via the BCD
switch or via comms. It is, however, still possible to load the program by selecting the
file as described in the previous section.
Note: When a BCD switch is turned from its current value to another value,
intermediate switch positions may be seen on the inputs of the BCD function block
and could potentially be used by subsequent blocks wired from the BCD input. A
Settle Time parameter has been introduced which will in effect filter out these
intermediate values by applying a time in which the inputs can settle before their
converted decimal value is seen on the output parameters of the block. The Settle
Time can be set from 0-10 seconds with a default of 0s i.e. no filtering as in previous
firmware versions. The BCD block is described in "BCD Input" on page 214.
Example BCD Switch Wiring
Figure 39 shows an example of digital input channels soft wired to the BCD function
block using iTools.
Figure 39 BCD Switch Wiring
Figure 40 shows the corresponding hard wiring of a BCD switch.
This display mode appears only if the Steriliser option is fitted and if the display mode
has been enabled in the Instrument Display configuration ("Display configuration" on
page 94). Steriliser configuration parameters are to be found in "Configuration
parameters" on page 204.
www.GlobalTestSupply.com
Figure 40 BCD Switch Physical Wiring
Page 70
nanodac™ Recorder / ControllerOperation
Cycle status
Input status beacons
If any input is configured
‘Off’ (in Steriliser
configuration parameters,
"Configuration parameters"
on page 204), it does not
appear in the display, and
the other inputs occupy the
screen width equally.
Input status beacons are
black for inputs configured
‘Off’.
A sterilising cycle cannot be initiated whilst the unit is in Configuration (Engineer)
mode. A steriliser cycle is started by setting its relevant ‘Start’ input to ‘Yes’ for the
duration of the cycle. The cycle waits (status ‘Waiting’) until input 1 reaches its
setpoint, at which point the cycle enters the equilibration period (status
‘Equilibration’), and remains there until all the configured inputs are valid. The cycle
then enters the sterilising period and stays in this mode until the sterilising period has
expired (status ‘Passed’) or until one of the inputs becomes invalid (status ‘Failed’)
for longer than its configured ‘Failure Dwell’ time.
Note: The cycle stops (status ‘Failed’) if the trigger source is removed.
Terminology
Holding timeMost operating cycles have a stage in which the load must
be exposed to sterilisation conditions for a specified length
of time, known as the ‘Holding time’.
Equilibration timeThe holding time (above) is preceded by a period during
which, although the sterilising condition is present in the
chamber, the load has not yet attained that temperature
due to its thermal inertia. ‘Equilibration time’ is defined as
the time between the attainment of sterilisation temperature in the chamber, and the attainment of that temperature in all parts of the load.
BandsFor steam and dry heat sterilisers, sterilisation conditions
are specified by a sterilisation temperature band, defined
by a minimum acceptable temperature (known as the sterilisation temperature) and a maximum allowable temperature. A sterilisation band is normally quoted for each
steriliser type.
There are four input status beacons near the top right hand corner of the display, one
for each input. During equilibration, the beacons are flashing red for inputs that have
not attained the Target setpoint, and go green when the target setpoint is reached,
remaining green even if the input value rises above the Band High value The
beacons revert to red if input falls below* the target setpoint. During sterilisation, the
beacons go red for any input whose value rises above Band High or falls below*
setpoint for a duration exceeding the configured ‘Failure Dwell’ period. Beacons are
black for inputs that are configured as ‘Off’.
* ‘rises above’ for input types ‘Falling Pressure’ or ‘Fall Air Detect’.
Displayed Information
CycleA five-digit counter to indicate the total number of cycles
started.
StatusWait start: The initial state at power up. This status re-
mains until the first cycle is initiated Waiting: Waiting for input 1 to reach its target setpoint. The cycle then enters
Equilibration. Equilibration: Currently in the equilibration
period, during which the cycle waits until all inputs have
reached sterilisation conditions.
Sterilising: Currently in the decontamination phase.
Passed: The cycle has completed successfully.
Failed: The cycle has failed either through one or more inputs becoming invalid, or because the ‘Start’ signal was removed. Test cycle: A test cycle is in progress.
RemainingThe sterilising time remaining for the current cycle. Display
field is replaced by ‘Target Time’ (below) when the cycle is
not running.
Target timeThe intended sterilisation time. This can be configured by
operating the scroll button twice (once to highlight the field,
and again to enter edit mode), and then using the up
and/or down arrows to edit the time. Use the Scroll button
again to quit edit mode, and the page key to ‘unhighlight’
the field.
Replaced by ‘Remaining’ (above) when the cycle is run-
ning.
EquilibrationThe equilibration time period for the current cycle.
SterilisingThe time for which the load has currently been at sterilisa-
tion conditions.
Total CycleThe elapsed time since the initiation of the current cycle.
This time increments from the time the cycle is triggered
until the time the trigger is removed.
Input valuesTemperature are required in °C; pressure inputs in mBar.
If necessary, maths channels and user values can be used
to convert from other units (see ‘Note’ overleaf).
Sterilisation starts when slowest
input reaches setpoint
Equilibration starts when
input 1 reaches setpoint
Sterilisation chamber
Temperature
transducers
Pressure
transducer
nanodac
PV1
PV2
PV3
PV4
Start
121°C/134°C
Controller
I/O terminals
User wiring
Steriliser configuration
parameters
Data Flow
Sterilising Cycle Diagram
Figure 42 shows a steriliser cycle in diagrammatic form.
Figure 42 Steriliser cycle
NOTES:
1. For temperature inputs in most applications, the Setpoint value is the same as
the Band Low value. For the sake of clarity, this is not as shown in the figure
above.
2. For the sake of clarity all four inputs in the figure above are shown with the same
Band High, Band Low and Setpoint value. This would not be unusual for
temperature units, but the pressure input would normally have a different set of
values from temperature inputs.
3. Band High and Band Low are effective only during Sterilisation phase.
Application Details
Figure 43 shows a typical steriliser application, with temperature and pressure
signals from the sterilisation chamber being applied directly to the rear terminals of
the controller/recorder, and control signals connected from the controller to both the
chamber and the controller/recorder.
Analogue inputs 1 to 3 receive signals from temperature transducers (typically
thermocouples) within the chamber. These inputs are internally connected to
channels 1 to 3 respectively, allowing transducer type, ranges, alarms, etc. to be
configured ("Input Channel Configuration" on page 123). Inputs are assumed to be
degrees Celsius (see Note).
The pressure transducer is connected to channel 4 and can be configured in the
same way. The input is assumed to be in milliBar. Other pressure inputs should be
converted using virtual channels (see Note).
PV1 to PV4 in the Steriliser configuration is software wired (Section 9) to Ch 1 to Ch4.
Start cycle input and the ‘Running Output’ and ‘Passed Output’ signals are software
wired to suitable DIO terminals, for connection to the Controller.
Note: For Fahrenheit inputs, use one virtual channel to subtract 32, and a second to
divide the result by 1.8 (where 32 and 1.8 can be configured as user values). Similar
techniques should be used to convert pressure input units if necessary.
Test Cycles
A ‘Test’ cycle is initiated by initiating a 121°C cycle and a 134°C cycle simultaneously.
A test cycle allows the user to check actual performance against expected
performance.
F0
F0 is a means of calculating ‘equivalent time at sterilising temperature’ for
temperatures below, at and above sterilizing temperature, using the equation below.
Where:
Sterilisation timeDepends on the application, typically 15 minutes at Ts =
121°C
TempThe value of the temperature measuring input.
TsDesired Sterilising temperature.
ZTemperature interval representing a factor-of-10 reduction
in killing efficiency. Z = 10 for steam sterilising (F0), or
Z=20 for dry heat sterilising (FH). Z = 10 for thermal disin-
fection (A0).
To ensure that steriliser loads which contain materials with different thermal inertias
are thoroughly sterilised, a number of sensors are located within the load. The F
value should be calculated using the sensor closest to that part of the load which has
the highest thermal inertia. For maximum accuracy, the temperature sensor should
be calibrated and the input adjust function used to compensate for any inaccuracy
found.
F0 calculation examples
For all the examples following, the following are assumed: Sterilisation time = 15
minutes; Sterilisation target temperature =121°C and Z = 10.
1. For an actual sterilising temperature of 111°C.
Which means that 15 minutes at 111°C is equivalent to 1.5 minutes at 121°C.
2. For a sterilising temperature of 121°C.
Which means that the sterilising temperature is ideal (by definition).
1. For a sterilising temperature of 124°C.
Which means that 15 minutes at 124°C is equivalent to nearly 30 minutes at 121°C.
Normally sterilising temperatures would not remain constant at temperatures below
or above the target value, so the above equations are illustrative only of the facts:
1. Temperatures below the target have some killing efficacy.
2. Temperatures above the target value have a greater killing efficiency, so
that the sterilising time can be reduced.
In order to calculate the value dynamically, the instrument uses the equation:
where
Batch Summary
This display page shows the user a summary of the current, or last run (if no batch is
currently running), batch. Access to the Batch Control page is available through this
page if the logged in user has sufficient permissions; otherwise the Batch Summary
page is display-only. The page shows basic information about the batch includ-ing
whether a batch is currently active, the customised Field 1 descriptor and value, start
date and time and the batch run duration.
Fvalt = F value this iteration
Fvalt-1 = F value last time
T = Iteration period (minutes)
mat = input temperature value this iteration
Target Temp = 121°C for F0, 170°C for FH, 80°C for A0
Z = 10°C for F0, 20C for FH, 10°C for A0
Page icon only visible if logged in user is the Supervisor or has Batch permissions.
If the logged in user is the Supervisor or has Batch permissions, the page icon
appears at the top-right of the display. This provides access to the Batch Control
page where a batch can be initiated, started or stopped. To access the Batch Control
page, press the scroll button twice (the first press highlights the page icon, and the
second press enters the page). An example Batch Control page is shown in Figure
45.
Figure 45 Batch control page
Batch ActiveRead-only parameter showing the current running state of
the batch -either ‘Yes’ (active) or ‘No’ (inactive).
Batch NewWhen set to ‘Yes’, initialises a new batch and resets all the
Batch Descriptor values to the default values (see "Batch
Configuration" on page 119). Any Batch Descriptor fields
which require user input are set blank and must be completed before a batch can be started using the Batch Start
pa-rameter. This field can only be changed if no batch is
Batch Descriptor {n} Up to six user-definable text values which are pre-config-
Batch StartSet to ‘Yes’ to start the batch. This field can only be set to
www.GlobalTestSupply.com
currently active.
ured (see "Batch Configuration" on page 119) and written
to the log on batch initialisation, batch start and batch stop
(according to configuration rules). Batch field 1 can be configured to automatically populate with the current PV value.
These fields are only editable if the Batch New field is set
to Yes and the batch hasn’t yet been started.
‘Yes’ if a batch has already been initialised and the required Batch Descriptor fields have content (if configured).
Page 76
nanodac™ Recorder / ControllerOperation
Batch StopSet to ‘Yes’ to stop the current active batch. This field can
only be set to ‘Yes’ if a batch is currently active.
Promote list
This display page allows the user to display up to 10 of the parameters that appear
anywhere in the operator interface. The parameters can be selected only by using
iTools, as described below.
NOTES:
1. ‘Promote List’ must be enabled (in ‘Instrument.Display’ configuration), before it
appears in the ‘Go to View’ list.
2. There are more parameters visible in iTools than appear at the operator interface.
If non-operator interface parameters are selected for inclusion in the promote list,
they do not appear.
3. If parameters which appear only in certain circumstances are selected, then they
appear in the promote list only when they appear in the Operator interface. For
example, a channel PV is not visible unless that channel is enabled (i.e. it is not
‘Off’).
Parameter Selection
1. Open iTools and scan for the instrument, (see "iTOOLS").
2. Once the instrument has been found, stop the scan. When the instrument has
synchronised, click on the ‘Access’ button near the top of the display to set the
unit into configuration mode (a password may be required).
3. Click on the ‘+’ sign to the left of the Instrument folder in the tree list (left-most
pane) to expand the folder. Double-click on ‘Promote List’, to display the Promote
list in the main pane. The list contains 20 entries, 1 to 10 being for parameters, 11
to 20 being available to the user to add descriptors for parameters 1 to 10
respectively.
4. Expand further folders, as necessary, to access the required parameters, and
click-drag these parameters into the promote list. Enter a descriptor for the
parameter if the default is not as required. As each parameter is dragged into the
list, it appears in the Promote list.
5. If the parameters are modified at the operator interface, the changes are
reflected in iTools, and vice-versa.
6. Once all the parameters have been added, it is recommended that the Access
button be used to quit configuration mode, as otherwise it will not subsequently
be possible to quit from the operator interface.
This display mode consists of two pages, as shown in Figure 47.
Page one opens by default and shows the first eight parameters being read
from (left pointing arrow) or written to (right pointing arrow) the relevant slave.
These items are configured in the Modbus Master configuration described in
Section 6.10. Hidden parameters may be viewed by operating the scroll key,
then using the arrow keys to scroll through the list. A green arrow means that
the item may be edited by the user when logged in. A pair of animated
indicators in the top left-hand corner of the screen show the connection status
of the two possible slaves. A green moving ‘streak’ indicates that successful
communications are being carried out. A red flashing circle indicates that there
is a break in the transmission line or that the slave is switched off. A grey,
non-animated display indicates that the slave has not yet been configured as a
part of the communications link (i.e it is ‘off line’).
A ‘traffic light’ indicator appears to the right of each parameter. Green indicates that
the parameter is being read from or written to successfully. Orange indicates that a
write of the value is pending. Red indicates that there is an error and that no value is
currently being read or written; the value displayed is the last good value read or
written depending on whether the data item is a read or write. If the indicator is black,
the parameter is ‘off’.
Operation of the scroll key highlights the page symbol in the top right-hand corner of
the screen, and a further operation of the scroll key calls page two to the screen.
Page two contains the IP address of the Modbus master and of any slaves connected
to it, together with some diagnostic information, as described in ‘Ping Details’, below.
The list of parameters can be scrolled through using the up/
down arrows. Values being read by the master are read
only, but the user may enter values for parameters being
written by the master, by highlighting the relevant item and
using the scroll key to enter edit mode. The use of the Page
key causes a return to be made to the initial Modbus
Master display.
Total number of successful
read and write transactions
Total number of failed read
and write transactions
Ping initiation field.
}
}
Ping Details
The ‘Ping...’ field of the first slave is highlighted by default. As shown above, the
down (or up) arrow can be used to highlight the ‘Ping...’ field of the other slave
instead.
Once the relevant ‘Ping...’ field is highlighted, the scroll key can be used to enter edit
mode and the up/down arrow key used to select ‘Start’. A further operation of the
scroll key initiates the ‘Ping’ and if this is successful, a green indicator appears
alongside the field (and the text returns to ‘Ping...’). If the Ping is unsuccessful, then
the indicator is coloured red.
The up or down arrow can now be used to return to slave 1, or the page key can be
used to return to the previous parameter display page.
As shown in the figure above, some diagnostic information is given. This includes the
total number of successful attempts that the master has made to communicate with
the relevant slave, and the total number of failed attempts. Fuller diagnostic details
are to be found in the Modbus Master Communications configuration description
("Modbus Master Configuration" on page 182).
This display mode appears only if enabled in Instrument.Display configuration
("Display configuration" on page 94) and is used to display the input and output
parameters assigned to the Client and Server input and output tables. Parameters
which have been configured with descriptors are identified by these descriptors
insteadof their ‘opc’names (shown inFigure 49).
The list of parameters can be scrolled through
using the up/down arrows.
Items with green arrows can be edited if the See
user is logged in with the correct access level.
Inputs
Outputs
Server IP
address,
Connection
type, RPI
IP address
and mode of
operation for
this unit
See
‘Explicit
data’ below
Data depends on the slave.
These items appear only for the Client
Virtual
Channel.1.Main.Input1
Loop.1.Setpoint.SP2
Loop.1.Setpoint.SP1
Loop.1.Setpoint.SP2
Loop.2.Setpoint.SP1
123.0
132.0
246.2
Figure 49 Typical EtherNet/IP display
If the EtherNet/IP option has been ordered and enabled, the nanodac can be
configured as either a client (master) or a server (slave) (see "Ethernet/IP
Configuration" on page 189). The client and server displays are identical except that
the configuration area of the client display is more extensive than that of the server
display.
Figure 49, above shows a typical set of display pages for an EtherNet/IP client.
www.GlobalTestSupply.com
Page 81
Operationnanodac™ Recorder / Controller
Client (nanodac) input table
Server output table
Virtual Channel.2.Main.Input1
Input Data Destination
The implicit data value
coming in from the
EtherNet/IP device will
be copied to this wired
parameter
Virtual Channel.1.Main.Input1
Output Data Source
The value coming in
from this wire will be
sent to the EtherNet/IP
device.
Wired parameters
Val ues
Wired parameters
Client (nanodac) output tableServer input table
Output Data Source
The value coming in from
this wire will be sent to the
EtherNet/IP device.
Input Data Destination
The implicit data value
coming in from the
EtherNet/IP device will be
copied to this wired
parameter
I/P1
I/P2
Virtual Channel.4.Main.Input1
Virtual Channel.3.Main.Input1
I/P4
etc.
Out Parameter 2
Out Parameter 1
Out Parameter 4
Out Parameter 3
I/P3
O/P1
etc.
O/P3
O/P4
O/P2
Channel.1.Alarm1
User Values.1.Value
O/P2
etc.
O/P1
In Parameter 1
In Parameter 2
I/P1
etc.
I/P2
Configuration of Implicit Input/Output Tables
Configuration of the input and output tables is carried out via iTools drag and drop
only by:
a. Entering the parameters to be read by the client into the server output table.
b. Entering the destination parameter into the equivalent location in the client
input table.
c. Entering the parameters to be written by the client into the client output table.
d. Entering the destination parameter into the equivalent location in the server
input table.
The example in Figure 50 shows this (using the nanodac as the client) in graphical
form, using just a few parameters (there can be up to 50 in each table).
Figure 50 Input/Output table entries
NOTES:
1. Channel values from the Server can be ‘wired’ into nanodac Virtual channel
inputs (as shown above) so that they can be traced and/or recorded. In such
cases the virtual channel ‘Operation’ must be set to ‘Copy’ (see "Maths channel
configuration" on page 133).
2. Inputs and outputs would normally be given suitable descriptors (e.g. ‘Reset
timer’ instead of ‘Channel.1.Alarm1’).
Connection Status Indicator
A circular status indicator appears in a number of the EtherNet/IP display pages. This
indicator can indicate the following states:
Green rotating ‘flash’: the instrument is on line and at least one CIP
connection is established.
Green flashing circle: the instrument is on line but no CIP connections have
been established.
Red flashing circle: there is a break in the physical connection between the
client and the server, or the remote unit is switched off or is initialising.
Adding parameters to the input and output tables can be achieved only through the
proprietary software package ‘iTools’, running on a PC. It cannot be configured
through the user interface. The following description assumes that the user is familiar
with ‘iTools’. "iTOOLS" of this manual shows how to set up an iTools link to the unit
and the iTools on-line help system and its PDF version (HA028838) should be
referred-to as necessary.
Note: The client/server and the PC must all be on the same network.
Once iTools has started up and the ‘Scan’ process
has ‘found’ the relevant instrument, the scan
process should be stopped and the instrument (s)
allowed to synchronise. (The scan may be left to run
its course, but the speed at which iTools operates is reduced for the duration of the
scan process.)
Example
To add Loop 2 Setpoint 2 to Output 4 of the Client
Output table. In the example shown below, the
instruments have both synchronised, and the
‘Access’ tool button clicked-on for both instruments
to set them into configuration mode. With the client
selected, expand the EtherNet/IP folder in the
Browse list, then double-click on the
‘ImplicitOutputs’ folder. Locate and expand the
Loop 2 SP folder in the Browse window, and
click-drag SP2 to ‘Output 4’ and release.
Figure 51 Dragging a parameter to the Output table
An alternative to the click-drag technique is to right click on the required output (five
in the example below), and select ‘Edit Wire...’ from the context menu that appears. A
browse window pops up, allowing the user to navigate to the required parameter.
This technique can be used both on previously empty inputs or outputs and on those
previously filled.
As shown in Figure 53, when configured as a server, there is only one explicit
application object, and that has the class ID= A2 (162 decimal). The instance ID is
the Modbus address of the parameter and the Attribute is always = 1. Explicit service
codes hex10 (decimal 16) and 0E (14) are both supported, for writing and reading
single attributes respectively.
Figure 53 Explicit data specification
When configured as a client, two separate connections are available allowing the
user to produce two independent explicit read or write messages to different server
devices.
Figure 54, shows an example of how to configure an explicit message request. The
instance ID and the data type are taken from the server manufacturer’s data. In this
example a read request is configured to determine the Group recording status of a
nanodac server, and it can be seen from the table in "Parameter List" on page 232
that the decimal Modbus address for this parameter is 4150 and the data type is
int16. It is this address which is used as the instance ID.
Once all the information has been entered, the read is requested by setting ‘Send’ to
‘Yes’. The Data field changes to ‘3’ for this example and from the table in "Parameter
List" on page 232 it can be seen that the recording status is ‘Recording enabled’.
Note: The nanodac supports only 16 bit data types for reading and writing of explicit
messages.
When wired to parameters which have
descriptors, the descriptor names appear
instead of the ‘opc’ names (e.g.
Loop.1.Setpoint.SP1) shown here.
Tags page appears if ‘Mode’ is set to ‘Client
(Tags)’ in EtherNet/IP configuration
("Ethernet/IP Configuration" on page 189).
Explicit messaging is not possible in tag IO
mode as tag mode needs to consume both
connections for communications with the PLC.
When acting as servers, many PLCs present their data in a tag format instead of
implicit data format. For this reason, when the client is configured as ‘Client (Tags)’,
(see "Ethernet/IP Configuration" on page 189) 30 input and 30 output tags become
available to the user via iTools (Figure 55).
This allows tag names to be typed in, input tags 1 to 30 being associated with implicit
inputs 1 to 30 respectively and output tags 1 to 30 being associated with implicit
outputs 1 to 30 respectively.
www.GlobalTestSupply.com
Page 86
nanodac™ Recorder / ControllerOperation
Trend History
Figure 55 iTools display showing input tags.
In the example above, the value of the parameter with the tag ‘Channel 1’ will be
written to implicit input 1.
NOTES:
1. Most PLCs have a data buffer limit of 500 Bytes. The total number of bytes being
used is given by the equation: Total number of data bytes = (tag length + 10) ×
the number of requested tags.
2. Input data direction is always to the nanodac: in server mode input data is written
to the nanodac from the client in client mode, input data is read by the nanodac
from the server device.
3. Output data direction is always from the nanodac: in server mode output data is
written to the client from the nanodac in client mode, output data is read by the
server from the nanodac.
Entered from the top level menu ("Introduction" on page 25), this allows vertical and
horizontal traces to be reviewed for Trend group channels. The amount of data
displayed in one screen depends on the ‘Zoom In/Out’ setting in the History menu
("History Options Menu" on page 89) and on the recording interval selected in Group
Recording configuration ("Group Recording configuration" on page 117). It is also
possible to enter a time and date to which the history then jumps.
The history display is identical in appearance with the trend display except:
1. History displays can include messages if so configured in the History menu.
2. For horizontal trends, the scale is displayed permanently at the left edge of the
display.
The down arrow button moves the display backwards in time by 1/3
screen-full per operation (assuming that the current display is not the
earliest). See also ‘SEARCH FOR’, below.
The up arrow button moves the display forwards in time by 1/3 screen-full
per operation (assuming that the current display is not the latest). See also
‘SEARCH FOR’, below.
The scroll key scrolls through the trend group channels, emphasizing each
channel (and displaying its faceplate) as it is selected.
The page key calls the History Menu, described in "History Options Menu"
on page 89, below.
Search For
In the history display, holding the up or down
arrow key operated for approximately two
seconds produces a ‘Search for’ display which
allows the user to enter a time and date. Once a
time and date have been entered, ‘Yes’ then
causes the history display to jump to that time
and date (if such history exists).
To enter a time and date:
1. Use the up/down arrows to highlight the item to be edited.
2. When highlighted (orange background), operate the scroll button. The
highlighted text turns black.
3. Use the up and down arrow keys to scroll to the required value for the field, then
operate the scroll button again. The text goes white.
4. Repeat the above editing process for all the remaining items which are to be
edited.
5. Use the up/down keys to select ‘Yes’. The ‘Search for’ window closes, and the
history display jumps to the selected time and date.
1. N If no history exists for the selected time and/or date ‘No History Available’ is
displayed.
www.GlobalTestSupply.com
Page 88
nanodac™ Recorder / ControllerOperation
All Points
0.125 sec
Off
No
Zoom In/Out
Trend
Show Messages
Exit History
History Menu
2. The time and date format and Daylight Savings Time (DST) effects are as set in
the ‘Locale’ area of Instrument configuration. See "Locale" on page 93 for further
details.
History Options Menu
Operating the page key from within a history display, causes the History Options
menu to appear.
Figure 57 History Options menu
Text Entry
Parameters
Zoom In/outAllows the user to select the amount of history displayed
on the screen.
TrendSelect either ‘All Points’ or ‘Each Point’.
‘All points’ displays all channels in the trend group, with the
first channel emphasized on the screen and its faceplate
displayed. The Scroll button is used to select the next
channel in the group.
‘Each Point’ initially displays only the first point in the trace
group. The scroll key is used to cycle through individual
group channels in turn.
Show Messages‘Off’ disable the inclusion of messages in history display.
‘On’ causes messages to appear, superimposed upon the
point traces (vertical trend mode only).
Exit History Selecting ‘Yes’ for this item causes a return to the top level
menu or to the message summary page.
Note: Operating the page key from the History menu causes a return to the history
display.
The user is often required to enter text characters or numbers (when editing operator
notes, for example). This is done using the pop-up keyboards which are displayed
when required. When only numerals are required a special keyboard is presented
which contains only numerals.
Figure 58 shows the three standard keyboards, along with a ‘scan’ direction for
operations of both up arrow and down arrow keys. To change keyboards, use the
arrow push buttons to highlight the keyboard name (‘Numeric’, ‘Symbols’ or ‘Alpha’),
and then operate the scroll button.
Generally, to enter text, the required character is highlighted using the up and down
arrows and the scroll button is used as an ‘Enter’ key. Once text entry is complete,
the Page button is used to confirm the edit (use the down arrow to select ‘Yes’ then
operate the scroll button).
Press and hold scroll
button for alternative
character set.
Pressing and holding the scroll button and then immediately operating the up or down
arrow, causes the character insertion point to move to the left (down arrow) or to the
right (up arrow). The user can press and hold the scroll key to display variations on
certain characters (the letter ‘e’ in the figure). Once displayed, the up and down
arrows can again be used to scroll through auxiliary list, allowing capital letters, and
characters with diacriticals (e.g. accents, umlauts, tildes, cedillas) to be selected and
entered using the scroll button.
The backarrow key is used as a back space key - i.e. it deletes the character to the
left of the cursor position. The ‘Del’ key deletes the character to the right of the
cursor.
Note: Leading and trailing space characters are automatically removed from text
strings.
Numeric keyboard
USB keyboard
Figure 58 Standard Keyboards
As mentioned previously, for functions which can take only numerals, a special
numeric keyboard appears, as depicted in Figure 59.
Figure 59 Numeric keyboard
Text and numeric entry can also be carried out using a USB keyboard as described in
"USB Keyboard" on page 388.
Entered from the top level menu ("Top Level Menu" on page 41) this allows the
instrument configuration to be accessed and edited (‘Engineer’ access level required
for full editing).
CAUTION
EQUIPMENT OPERATION HAZARD
When logged in at Engineer access level, recording is stopped and the
input/output circuits are switched off. Ensure the controlled process is in a suitable
control and recording state before entering the Engineer access level.
Failure to follow these instructions can result in injury or equipment
damage.
As shown in Figure 60, below, the instrument configuration is arranged in a number
of ‘areas’, each of which is allocated its own sub-section within this Section.
The factory default configuration can be returned to, if required, by entering a special
Engineer password, as described in "Security menu" on page 98.
cycling
Setpoint colour
Number format
USB auto scan
Info
("Info menu" on
page 96)
Name
Type
Version
Bootrom
Company ID
Config Rev
Security Rev
Nvol writes
Line Voltage
Wires Free
Upgrade
("Upgrade" on
page 97)
Type
IP Address
Username
Password
Source Path
Initiate
Security
("Security menu"
on page 98)
Engineer
Password
Supervisor
Password
Operator
Password
Feature
Passwords
Comms
Password
OEM Pass
OEM Entry
OEM Status
Input Adjust
("Input adjust"
on page 103)
Select channs
Start IP adjust
Abort
I/O Fitted
("I/O fitted" on
page 101)
Output Adjust
("Output adjust"
on page 106)
Output
Measured o/p
Confirm
Save/Restore
("Save/Restore"
on page 102)
Select Save or
Restore
User Accounts
(Auditor)
("User Accounts
(Auditor)" on
page 107)
User 1 to User
25
Instrument
Instrument Menu
Clock
The up and down arrows are used to highlight ‘Date’ (default) or ‘Time’.
To set the date, the scroll button is used to display the numeric keyboard described in
"Numeric keyboard" on page 90. The up and down arrows are used to highlight the
relevant numeral or separator (‘/’ or ‘:’) and the scroll key used to enter it into the
display window.
To set the time, the scroll button is operated to enter edit mode, then the up and
down buttons are used to scroll to display a time, say 15 seconds later than the
current time. Once the current time matches the display, the scroll button is pressed
to confirm the time and to start the clock.
The ‘DST’ field appears only If ‘DST Enable’ is selected ‘Yes’, in ‘Locale’ ("Locale" on
page 93). If the ‘box’ contains a cross (as shown) then Daylight Saving Time (DST) is
not currently active. A ‘tick’ means that the time shown has been advanced by an
hour because DST is active.
Locale
Figure 62 Typical Instrument configuration menu (expanded to show all fields)
LanguageSelect the language to be used for displays etc.
Date formatSelect either DD/MM/YY, MM/DD/YY, or YY/MM/DD as
the required format.
Time ZoneSelect the required offset from GMT (UTC). This setting af-
DST EnableDaylight Saving Time enable. Once the selection is ena-
Start TimeAppears only when ‘DST Enable’ (above) is set to ‘Yes’.
Start OnSelect ‘Last’, ‘First’, ‘Second’, ‘Third’ or ‘Fourth’ as the re-
Start DaySelect the day of the week on which DST is to commence.
Start MonthSelect the month in which DST is to commence.
End Time, End On, End Day, End Month
fects only the displayed time. Archiving, recording etc.
times remain in GMT.
bled, the following (previously hidden) fields appear, allowing the start and end dates for Daylight Saving Time (DST)
to be configured. DST affects only the displayed time. Archiving, recording etc. times remain in GMT.
Use the up/down keys to scroll to the required start time.
quired week. Used in conjunction with the ‘Start Day’ and
‘Start Month’ entries following.
As for ‘Start Time’ etc. above, but specifies the end time
and date for daylight savings.
Page 93
Configurationnanodac™ Recorder / Controller
70%
7 min
50%
Brightness
Save After
Saver Brightness
Horizontal Trend
V.Trend
Off
Hide
Home Page
HPage Timeout
Vertical Trend
Off
Red
Ver ti cal Bar
History Backgrnd
Rounded
No
Black
Horizontal Bar
Promote List
Trend Backgrnd
DarkGrey
Instrument.Display
Number Format
H.Trend Scaling
Faceplate Cycling
Setpoint Colour
USB Auto Scan
Home page (always
enabled)
Mode disabled
Mode enabled
Display configuration
This allows the user to set display brightnesses and screen saver details, to select a
display mode as the ‘Home’ page, and to enable/ disable the various display modes.
The normal ‘Select, Scroll, Enter’ editing technique is used as has been previously
described.
Figure 63 Display menu (expanded to show all fields)
BrightnessAllows the user to select a normal operating brightness for
the screen from 10% to 100%, in 10% steps.
Save AfterThe elapsed time (since last button press) before the
screen switches from ‘Brightness’ to ‘Saver Brightness’.
(Off = saver function disabled). Saver BrightnessThe
screen saver brightness. Valid entries are 10% to 100% in-
Home pageAllows any display mode to be chosen as the ‘Home’ page.
HPage TimeoutThe elapsed time (since last button press) before the dis-
Vertical TrendThis is the default home page, and its tick is greyed. If this
www.GlobalTestSupply.com
clusive, in 10% steps. Using a lower power when not ‘in
use’ not only saves power, but also increases display life.
Typical screen power consumption is 0.5W at 100%, falling in a linear fashion to 0.05W at 10%.
This is the page that the instrument displays at power up,
and also the page displayed when the ‘Home’ key is selected from the top level menu ("Top Level Menu" on
page 41). The selected display mode (vertical trend in Fig-
ure 63) is always enabled in the following display mode en-
able fields (its ‘tick’ is greyed out and cannot be edited).
See "Display Modes" on page 52 for a description of the
available modes.
play returns to the home screen. (Off = disabled).
is not the home page, the tick can be changed to a cross,
by highlighting it and operating the scroll button.
As for Vertical Trend, above. By default some display
modes are disabled (grey cross). In order to enable such
display modes the relevant cross is highlighted using the
up/down arrow buttons, and the scroll button then used to
change the grey cross to a white tick. The tick associated
with the selected home page is always grey.
Note: Some display modes are available only if the relevant option is fitted.
Future TrendThis and the associated colour selections appear only if
the Programmer option is fitted. See "Programmer Display
Mode" on page 59 for more details.
Trend BackgroundAllows the user to select black (default), white dark grey or
light grey as the ‘chart’ colour.
History Background As above for ‘Trend background’, but for history displays.
H.Trend ScalingAs described in "Horizontal Trend Mode" on page 53, by
default, the scale for horizontal trends appears at the left
edge of the chart for a few seconds before the chart ex-
pands leftwards to occupy the scale area. Setting ‘H.Trend
Scaling’ to ‘Permanent’, ensures that the scale remains
permanently on display.
Faceplate cyclingAllows the default faceplate cycling state to be defined as
‘On’ or ‘Off’ ("Faceplate Cycling on/off" on page 46)
Setpoint colourThe colour for the setpoint in Control Loop display pages
("Control Loop1/Loop2" on page 57).
Number FormatRounded
Truncated
USB Auto ScanIf set to ‘Yes’, bar code data messages are automatically
generated and appear on the display and in the Message
list without operator intervention. If set to ‘No’, the Mes-
sage appears on the screen for editing and/or confirma-
tion, before being displayed etc. "Barcode Reader" on
page 387 provides further details.
From firmware versions V3.01 and above there is an option to allow numbers to be
rounded. The reason for this is driven primarily from a control point-of-view. With
truncation, it is quite likely that the PV will look as though it never settles onto the
setpoint. The rounding/truncation affects the UI display and MODBUS scaled
integers, the underlying numbers are not affected, nor the values saved in the history
files. Over MODBUS communications, all floating point parameters that are read via
scaled integer communications will take note of the configured setting for rounding or
truncating and reflect this. On the UI, ALL floating point values rendered will adhere
to the configured setting of rounding or truncating.
Gives information about the instrument hardware and software, and allows the user
to enter a descriptor for the instrument. The normal ‘Select, Scroll, Enter’ editing
technique, previously described) is used to edit those fields that are not read only.
Figure 64 Info menu (expanded to show all fields)
NameAllows the user to enter a descriptor of up to 20 characters,
using the text entry techniques described in "Text Entry"
on page 89. The number of characters visible in the dis-
play mode pages varies according to the number of alarm
symbols on display.
TypeNano. Read only display of the instrument model (used by
‘iTools’).
VersionRead only. The software version of the instrument.
BootromRead only. Instrument software Boot ROM version
Company IDRead only. For CNOMO
1
purposes over Modbus (1280
decimal; 0500 hex).
Config RevRead only. This value is updated, and a message including
this value generated, every time configuration is exited, if
any one or more configuration parameter has been
changed.
Security RevRead only. This number is incremented every time config-
uration is exited, if any one or more passwords has been
changed, or if the FTP Server username has been
changed, or if the Comms Enable field has been edited.
Nvol writesNumber of non volatile write operations for diagnostic pur-
poses.
Line voltageThe instantaneous value of the supply voltage applied to
the instrument. Used in some control loop operations.
Wires FreeThis shows the number of wires free to be used. The value
takes into account all user wiring whether carried out at the
instrument or downloaded from the iTools graphical wiring
editor.
1.CNOMO = Comite denormalisation des moyens de production.
This item allows the user to update the instrument firmware, either from a memory
stick in the USB socket at the rear of the unit, or via FTP transfer from a host
computer. Firmware upgrade files are downloaded from the instrument manufacturer
and transferred to the instrument by memory stick or by FTP transfer. Splash screens
are prepared by the user and transferred using a memory stick. The unit restarts
automatically after an upgrade or splash screen replacement.
Note: After a firmware upgrade the Engineer password must be configured to allow
any further operation, see Engineer Password - Configuration (page 33). All user
accounts require an associated password.
CAUTION
INOPERABLE EQUIPMENT
Power must not be removed from the unit whilst upgrade is in progress.
The memory stick must not be removed whilst upgrade is in progress.
Removal of the either of the above whilst an upgrade is in progress, will cause
permanent damage to the unit.
Failure to follow these instructions can result in injury or equipment
damage.
Default Config. option
appears only if Engineer
Password = ResetConfig
Customising the Splash Screen
‘Splash (USB)’ allows the user to select a new image for the splash screen (i.e. the
screen that appears at power up or restart). When ‘Initiate’ is set to ‘Yes’, the
instrument searches the USB device for a file called ‘splash.bmp’ located in the
‘release’ folder. If such a file is found, it is loaded, and the instrument re-starts with
the new image as the ‘splash’ screen. If no file is found, the request is ignored. If the
image is not of the correct type or size, the instrument re-starts with the default
splash screen.
The original splash screen is included on the ‘tools’ DVD, so that it can be restored if
required. Rules:
1. This feature is available only with Bootrom versions 2.0 and above.
2. The file must be located in a folder called ‘release’ and the file name must be
‘splash.bmp’.
3. The image must be 320 x 240; 24-bit resolution.
4. The image must be in bitmap (suffix.bmp) format.
5. The image may not exceed 256kB.
Security menu
This allows the user to enter passwords for all security levels (except logged out),
and to enable/disable serial communications security.
Engineer PassGives access to configuration menus. The Engineer pass-
word must be configured to allow any access,
see Introduction - Initial Setup (page33). The password
Page 98
nanodac™ Recorder / ControllerConfiguration
can be edited here, if required, by entering an alternative
of up to 20 characters (Notes no.1).
If ‘ResetConfig’ (case sensitive) is entered as the Engineer
Password, the ‘Default Config.’ field appears allowing the
instrument default configuration to be restored (Notes no.
2).
Supervisor PassA password of up to 20 characters must be entered here to
protect Supervisor level access.
Operator PassA password of up to 20 characters must be entered here to
protect Operator level access.
If the Auditor (auditor) feature is enabled, this option is not
available as Operator level access is replaced by Users 1
to 25 - all configured user accounts must have an associated password, making them available for selection.
Note: User accounts, of any access level require a password, otherwise they will
not be available for selection.
Feature PassThis is a password supplied by the manufacturer to enable
the software options (e.g. Loop, Zirconia block, Toolkit
blocks, Batch, 21CF11, etc.). When applying for this password, the manufacturer will require the instrument’s MAC
address (Network.Interface menu "Interface" on page 110)
and the instrument’s firmware Version (Instrument.info
menu "Info menu" on page 96). The password is MAC address dependent so that it cannot be used on any other instrument.
Note: When the Auditor feature is enabled, entry of an invalid feature password will
result in the feature codes becoming read-only for a period of 30 minutes. This is to
discourage multiple attempts to guess a feature password. This period cannot be
shortened.
Feature2/3 PassSimilar to ‘Feature Pass’ above, but for additional features.
Comms PassEnables/disables password security for external communi-
cations (including via iTools). If set to ‘Enabled’, the Engineer level password will be required if an attempt is made
to enter the configuration menus from a remote PC. If set
to ‘Disabled’, then access to configuration can be gained
over a communications link, without a password. If enabled, then entry to configuration mode via the Instrument
Mode (IM) parameter must be completed within 5 seconds
of entering the password, or the attempt will fail.
NOTES:
1. It is recommended that only characters that appear on the user’s PC keyboard
be used in the Engineer password. The use of other characters makes it
necessary to use ‘Escape’ codes (e.g. Alt 0247 for the ‘÷’ sign) when trying to
enter configuration mode from iTools, for example.
2. Restoring factory default configuration can also be carried out in iTools, using the
Engineer password ‘ResetConfig’ and selecting Default Config to ‘Yes’.
OEM PassThe configured pass phrase used to enable / disable the
OEM security option. This field is editable whilst the OEM
Status is ‘Unlocked’ and the user has ‘Engineer’ access.
OEM EntryTo lock or unlock the OEM security feature, the user must
enter the pass phrase entered in ‘OEM Pass’ above. The
default passcode is ‘OEM’ (in capitals).
OEM StatusRead only ‘Locked’ or ‘Unlocked’ status display.
Audit TrailDetermines whether an audit trail is written to the history
file (when set to ‘Yes’). When enabled, all configuration pa-
rameter changes, operator alarm acknowledgements, and
cloningstatus changes are recorded in thehistory. Note
password, between 3 and 9 characters. This field appears
only if the Auditor feature is enabled.
(‘No’) or disabled (‘Yes’). It is recommended that this be
set to ‘Yes’ if the Auditor feature is used. This field only ap-
pears if the Auditor feature is enabled.
Page 100
nanodac™ Recorder / ControllerConfiguration
Passwords ExpireProvides the option to specify the number of days before a
password will expire. This can be set to ‘Off’ for no expiring
passwords, or between 1 and 999 days. The expiry coun-
ter is reset when the password is changed. When the
password expires, it will not work any more. The engi-
neer’s password never expires so as not to block all ac-
cess. This field appears only if the Auditor feature is
enabled.
{uuu} Pass Expires If the Passwords Expire parameter is set to any number
(other than ‘Off’), indicating that passwords will expire after
a set number of days, a list of all configured (and enabled)
users is displayed next to the Pass Expires parameter,
showing the number of days remaining before each ac-
count’s password will expire. These are read-only and can-
not be altered here. This field appears only if the Auditor
feature is enabled, and the Passwords Expire parameter is
set to anything other than ‘Off’.
Default ConfigThis field appears only if ‘ResetConfig’ has been entered
as the Engineer Password. Selecting ‘Yes’ Causes the in-
strument to restart with default configuration (i.e. the in-
strument ‘cold starts’). See Note 2 above.
Note: After a cold start (returned to default configuration) the Engineer password
must be configured to allow any further operation, see Engineer Password -
Configuration (page 33). (All user accounts require an associated password).
OEM Security
In products that incorporate user wiring, the value of an application may lie more in
the user wiring (connecting the function blocks together) than in the configuration of
the instrument's parameters. OEM Security allows the user to prevent the application
from being copied either via comms (by iTools or a third party comms package) or via
the instrument's user interface.
When OEM security is enabled, users are prevented from accessing wiring (for
reading or writing) from any source (comms or user interface), and it is not possible to
Load or Save the configuration of the instrument via iTools or by using the
Save/Restore facility ("Save/Restore" on page 102).
From firmware version V5.00 onwards OEM Security is enhanced by providing an
option, enabled by a new parameter ‘Instrument.Security.OEMParamLists. This
parameter is available only through iTools and allows the OEM to:
1. Make all parameters that are read/write in Engineer access level only, read only
when the instrument is OEM locked AND it is in Engineer access level. It is
possible for the OEM to select up to 100 parameters which are to remain
read/write in Engineer access level.
2. Make up to 100 parameters that are read/write in Supervisor access level, read
only when the instrument is OEM locked.
Examples of how to set up OEM security are given in the iTools ("To Set Up OEM
Security" on page 376).
I/O fitted
This provides a read only display showing what type of input or output circuit is
associated with each set of rear terminals.