HA028838 Printable version of iTools Help
HA025464 EMC installation guidelines
HA027962 Printable version of ‘Review’ Help
Application notes
HA030817U001 Archiving data from the nanodac recorder/controller
HA030817U002 Heat/Cool with carbon potential or oxygen level monitoring
HA030817U003 Heat only temperature control and carbon potential control
HA030817U004 Virtual channels using the nanodac recorder/controller.
Software effectivity
This manual refers to instruments fitted with software version 5.5.
Software versions 2.20 onwards are ‘backwards compatible’ so that it can be used on
all hardware versions of the unit.
Previous software versions are not compatible with instruments with hardware status
greater than 2.
The status level may be found on the instrument label and consists of a letter indicating
software status followed by a numeral indicating the hardware status (e.g. ‘B2’)
HA030554
Issue 9 Mar 15
Page i
Page 4
nanodac RECORDER/CONTROLLER: USER GUIDE
nanodac Recorder/Controller
User Guide
Contents List
Warning: Any interruption of the protective conductor inside or outside the apparatus, or dis-
Warning: Live sensors: The unit is design ed to operate if the temperature sensor is connected
Warning: Grounding the temperature sensor shield: Where it is common practice to replace
nanodac RECORDER/CONTROLLER: USER GUIDE
connection of the protective earth terminal is likely to make the apparatus dangerous
under some fault conditions. Intentional interruption is prohibited.
directly to an electrical heating element. It must be ensured that service personnel
do not touch connections to such inputs whilst the inputs are live. With live sensors,
all cables, connections and switches for connecting the sensor must be mains rated
for use in 240V Cat II.
the temperature sensor whilst the instrument is live, it is recommended that the
shield of the temperature sensor be grounded to safety earth, as an additional
protection against electric shock.
Warning: The instrument must not be wired to a three-phase supply with an unearthed star
connection, because, under fault conditions, such a supply could rise above 240V
RMS with respect to ground, thus rendering the instrument unsafe.
Note: Safety requirements for permanently connected equipment state:
a. A switch or circuit breaker shall be included in the building installation
b. It shall be in close proximity to the equipment and within easy reach of the operator.
c. It shall be marked as the disconnecting device for the equipment.
Note: Recommended external fuse ratings are: 2A Type T 250V.
Page 1
HA030554
Issue 9 Mar 15
Page 12
nanodac RECORDER/CONTROLLER: USER GUIDE
* A full definition of ‘Hazardous’ voltages appears under ‘Hazardous live’ in BS EN61010. Briefly, under normal operating conditions, hazardous voltages are defined as being > 30V RMS (42.2V peak) or > 60 V dc.
1.This instrument is intended for industrial temperature and process control applications within the requirements of the European directives on safety and EMC.
2.Installation may be carried out only by qualified personnel.
3.To prevent hands or metal tools coming into contact with parts that are electrically live the instrument
must be installed in an enclosure.
4.Where conductive pollution (e.g. condensation, carbon dust) is likely, adequate air conditioning/filtering/
sealing etc. must be installed in the enclosure.
5.The mains supply fuse within the power supply is not repl a ceable. If it is susp ected tha t the fuse is fa ulty,
the manufacturer’s local service centre should be contacted for advice.
6.Whenever it is likely that protection has been impaired, the unit shall be made inoperative, and secured
against accidental operation. The manufacturer’s nearest service centre should be contacted for advice.
7.If the equipment is used in a manner not specified by the manufacturer, the protection provided by the
equipment might be impaired.
8.The unit must be wired according to the instructions in this manual.
9.Before any other connection is made, the protective earth terminal shall be connected to a protective conductor. The mains (supply voltage) wiring must be terminated in such a way that, should it slip, the Earth
wire would be the last wire to become disconnected. The protective earth terminal must remain connected (even if the equipment is isolated from the mains supply) , if any of the I/O circuits are co nnected to
hazardous voltages*.
The protective earth connection must always be the first to be connected and the last to be disconnected.
Wiring must comply with all local wiring regulations, e.g. in the UK, the latest IEEE wiring regulations
(BS7671) and in the USA, NEC class 1 wiring methods.
10. Signal and supply voltage wiring should be kept separate from one another. Where this is impractical,
shielded cables should be used for the signal wiring.SAFETY NOTES (Cont.)
11.
The maximum continuous voltage applied between any of the following terminals must not exceed 240Vac.
1.Relay output to logic, dc or sensor input connections
2.Any connection to ground.
The ac supply must not be connected to sensor input or low-level inputs or outputs.
12. Over temperature protection: A separate over-temperature protection unit (with an independent temperature sensor) should be fitted to isolate the process heating circuit should a fault condition arise.
Alarm relays within the recorder/controller do not give protection under all fault conditions/
13. In order to allow the power supply capacitors to discharge to a safe voltage, the supply must be disconnected at least two minutes before the instrument is removed from its sleeve. The touching of the
exposed electronics of an instrument which has been removed from its sleeve should be avoided.
14. Instrument labels may be cleaned using iso-propyl alcohol, or water or water-based products. A mild
soap solution may be used to clean other exterior surfaces.
Page 2
Issue 9 Mar 15
HA030554
Page 13
nanodac RECORDER/CONTROLLER: USER GUIDE
Refer to manual for instructions
This unit is CE approved
C-Tick mark for Australia (ACA)
and New Zealand (RSM)
Underwriters laboratories listed mark for
Canada and the U.S.A.
For environmental reasons, this unit must
be recycled before its age exceeds the
number of years shown in the circle.
Risk of electric shock
Precautions against static electrical dis-
charge must be taken when handling this
unit
Ethernet connector
USB connector
Protective conductive terminal
(Safety Earth)
USB DEVICE PRECAUTIONS
Note: The use of U3 USB Flash drives is not recommended.
1.Precautions against electrostatic discharge should be taken when the instrument terminals are being
accessed. The USB and Ethernet connections are particularly vulnerable.
2.Ideally, the USB device should be plugged directly into the instrument, as the use of extension leads may
compromise the instrument’s ESD compliance. Where the instrument is being used in an electrically
‘noisy’ environment however, it is recommended that the user brings the USB socket to the front of the
panel using a short extension lead. This is because the USB may ‘lock up ’ or reset in noisy envir onments
and the only means of recovery is to remove the device, then re-insert it. For memory sticks, EMC-related
failure during a write operation might cause corruption of the data held on the stick. For this reason, the
data on the memory stick should be backed up before insertion and checked after removal.
3.When using a USB extension cable, a high quality scre ened cable must be used. The total length of USB
cable between the device and the USB port must not exceed 3 metres (10 ft.)
4.Most barcode readers and keyboards are not designed for use in industrial EMC environments, and their
operation in such environments may result in impaired performance of the recorder/controller.
32-BIT RESOLUTION
Floating point values are stored in IEEE 32-bit single precision format. Values which require gr eater resolution
than is available in this format are rounded up or down.
SYMBOLS USED ON THE RECORDER LABELLING
One or more of the symbols below may appear as a part of the recorder labelling.
Page 3
HA030554
Issue 9 Mar 15
Page 14
nanodac RECORDER/CONTROLLER: USER GUIDE
For the sake of clarity, the
panel is shown as though
transparent
Retaining spring (two places)
Push springs towards panel
Push springs towards panel
1 INTRODUCTION
This document describes the installation, operation and configuration of a paperless graphic recorder/controller. The instrument comes, as standard with four input channels and is equipped, for secure archiving via FTP
transfer and/or to USB memory stick.
1.1 UNPACKING THE INSTRUMENT
The instrument is despatched in a special pack, designed to give adequate protection during transit. Should
the outer box show signs of damage, it should be opened immediately, and the contents examined. If there is
evidence of damage, the instrument should not be operated and the local re presenta tive conta cted for in structions. After the instrument has been removed from its packing, the packing should be examined to ensure that
all accessories and documentation have been removed. The packing should then be stored against future
transport requirements.
2 INSTALLATION
Caution: Before installation, ensure that the specified instrument supply voltage matches the
facility supply
2.1 MECHANICAL INSTALLATION
Figure 2.1.1 gives installation details.
2.1.1 Installation Procedure
1.If it is not already in place, fit the IP65 sealing gasket behind the front bezel of the instrument.
2.Insert the instrument through the panel cutout, from the front of the panel.
3.Spring the retaining clips into place, and secure the instrument by holding it firmly in place whilst pushing
both clips towards the rear face of the panel.
4.The protective membrane can now be removed from the display.
Page 4
Figure 2.1.1 Securing the Instrument
HA030554
Issue 9 Mar 15
Page 15
nanodac RECORDER/CONTROLLER: USER GUIDE
2.1.2 Demounting
Warning: Before removing the supply voltage wiring, isolate the su pply voltage and secure it
against unintended operation.
1.Isolate the mains supply and secure it against accidental operation. Remove all wiring and the USB
device and Ethernet cable (if any).
2.Remove the retaining springs by unhooking them from the sides using a small flat-blade screwdriver.
3.Pull the instrument forwards out of the panel.
2.1.3 Removing the Instrument from its Sleeve
The instrument is designed to be removed from its sleeve from the front panel. However, if a USB memory stick
or the Ethernet cable is fitted then this must be remove d first.
When the instrument is shipped from the factory it is fitted with two small red clips, one in the top side of the
sleeve and the other below. These are intended as a safeguard against removal of the instrument from its
sleeve when an Ethernet cable is fitted. These clips must also be removed, using a small screwdriver, before
the instrument can be taken out of its sleeve.
Ease the latching ears (Figure 2.1) outwards and pull the controller forward.
When plugging back in ensure that the latching ears click into place to maintain the panel sealing.
Page 5
HA030554
Issue 9 Mar 15
Page 16
Mechanical Installation (Co n t.)
Panel cutout:
92mm x 92mm (both -0 + 0.8mm)
3.62in x 3.62in (both -0.00 + 0.03in)
Minimum inter-unit spacing:
Figure 2.2 shows the locations of the various user ter m inations along with signal and supply wiring pinouts.
Figure 2.1a Mechanical installation details (wash down case option)
2.2.1 Termination details
The screw terminals accept single wires in the range 0.21 to 2. 08 mm2 (24 to 14 AWG) inclusive, or two wires
each in the range 0.21 to 1.31 mm2 (24 to 16 AWG) inclusive.
Screw terminals should be tightened to a torque not exceeding 0.4Nm (3.54 lb in)
Page 7
HA030554
Issue 9 Mar 15
Page 18
nanodac RECORDER/CONTROLLER: USER GUIDE
1
8
mV
0 to 1V
0 to 10V
T/C
1R0≤R≤1k0
Supply
Voltage
Safety Earth
Brown
Blue
Each wire connected to
LA, LB and LC must be
less than 30 metres in
length.
I/O1
Contact closure
O/P2
O/P3
Dig InA
Dig InBO/P4; O/P5
Relay output
Contact closureRelay outputContact closure
An In1; An In2; An In3; An In4
T/C, Volts, millivolts
RTD (two wire)
RTD (three wire)
MilliampsDigital
R<200R = active
R>350R = inactive
100 to 230Vac±15%;
48/62 Hz
24Vac; -15%, +10%
48 to 62 Hz or
24V dc; -15%, +20%
(polarity irrelevant)
Isolated DC o/p (mA)
Ohms inputs
R>500R = inactive
R<150R = active
Relay output
Logic o/p (active high)
Isolated DC o/p (mA/ V)
Internal Link (0V)
R>600R = inactive
R<300R = active
Relay output
Logic o/p (active high)
Isolated DC o/p (mA)
An In1; An In2; An In3; An In4
Dual mV/TC
Dual mA
Dual input option (Section 2.2.3, below)
(Primary and secondary inputs are not electrically isolated from one another.)
For maximum accuracy, it is recommended that separate returns are made to
Mains (Line) supply voltage
Low voltage option wiring
ELECTRICAL INSTALLATION (Cont.)
Page 8
Figure 2.2 Connector locations and pinouts (rear panel)
HA030554
Issue 9 Mar 15
Page 19
nanodac RECORDER/CONTROLLER: USER GUIDE
2.2.2 Low Voltage Option
This option allows the use of a low voltage ac or dc 24 V supply. The specification in Appendix A gives full
details. The polarity of the dc supply connection is not important - it may be connected either way round.
2.2.3 Dual Input Option
This is a cost option, enabled on a channel-by-channel basis by means of entering the relevant password in the
‘Feature3 Pass’ field in Instrument.Security menu described in Section 4.1.6.
For each enabled channel, a pair of thermocouple, mV or mA inputs can be connected to the instrument. These
inputs are called ‘primary’ and ‘secondary’, and are terminated at the a nalogue inpu t terminals (An In1 to An In
4) as shown in ‘figure 2.2, above. The primary inputs 1 to 4 are assign ed to channels 1 to 4, as nor mal. Each
secondary input must be soft wired to a maths channel configured as Operation = ‘Copy’ if it is to b e recorded/
displayed/alarmed etc.
Note: Due to the nature of the input circuit, a large offset may appear for secondary thermocouple
inputs. This offset can be removed only by using the input adjust feature described in Section 4.1.9 Because of this offset, the dual thermocouple input option is not suitable for
AMS2750D applications
Soft wiring is described in Section 7
Maths channels are described in Section 4.5.1
Channel configuration is described in Section 4.4.1
Input adjust is carried out as described in Section 4.1.9
SAMPLE RATE
For dual input channels, both primary and secondary sample rate is reduced to 4 Hz (250ms) from the no rmal
8Hz (125ms).
SENSOR BREAK DETECTION
Input sensor break detection is not supported for secondary inputs. The internal circuit acts as a ‘pull up’ on the
secondary input which therefore saturates high in the event of a sensor break.
DUAL MILLIAMP OFFSET CORRECTION
If ‘Dual mA’ is selected as input type, then an automatic offset correction will be made, according to the shunt
value entered in channel configuration.
INPUT RANGE LIMITATION
There is no 10V range associated with the secondary input. Any input greater than +2V or less than -2V is
deemed to be ‘bad range’.
2.2.4 Modbus Master communications
The master instrument can be connected directly to up to two slaves using standard ethernet network cable
either directly (single slave only) or via a hub or switch (one or two slaves). In e ither ca se, ‘straigh t through’ or
‘crossover’ cable may be used. The cable is terminated at the RJ45 socket at the rear of the unit.
2.2.5 EtherNet/IP
The Client and Server are connected in the same way as described above for Modbus Master communications,
except that there can be only one client and one server.
Page 9
HA030554
Issue 9 Mar 15
Page 20
nanodac RECORDER/CONTROLLER: USER GUIDE
12:01:08
Channel 16.23V
Instrument name
Faceplate
Main display screen
Status area
Home
Configuration
Go to View
Faceplate cycling (On)
Operator Notes
Demand Archiving
Log out
History
3 OPERATION
On power up a default or custom splash screen appears and remains visible whilst the unit is initialising. If during this process a network broadcast storm is detected, the unit stops, displaying a
network failure icon until the broadcast storm has cleared, after which the initialisation process resumes.
3.1 INTRODUCTION
The operator interface consists of a displa y sc re e n and fo ur pus h bu tto n s.
3.1.1 Display Screen
The display screen is used both to display channel information (in one of a number of display modes), and to
display the various configuration screens which allow the user to setup the recorder to display the required
channels, to set up alarms and so on. Display modes are described in Section 3.4 below; configuration is described in Section 4.
In display mode, the screen is split horizontally into three areas (figure 3.1.1)
1.a faceplate giving channel details.
2.the main display screen showing channel traces etc.
3.the status area, displaying instrument name, the current tim e and date and any system icons.
Figure 3.1.1 Display mode screen (vertical trend)
In configuration mode, the entire display screen is devoted to the selected configuration menu.
3.1.2 Navigation Pushbuttons
Figure 3.1.2 Top level menu (Engineer level access)
There are four navigation buttons, called ‘Page’, ‘Scroll’, ‘Lower’ and ‘Raise’ located below the screen. The general properties of these buttons are descri bed in the remainder of this section, but some have additional, context
sensitive functions, which, for the sake of clarity are not described here but in the relevant sections (e.g. ‘Message summary’) of the manual.
Page 10
Issue 9 Mar 15
HA030554
Page 21
nanodac RECORDER/CONTROLLER: USER GUIDE
Select configuration menu
Logic (2 Input)
Logic (8 input)
Multiplexer
Math (2 input)
Timer
User values
Alarm Summary
The timer function
block offers a universal timer which may
be
re-configured between single pulse
outputs and re-triggering
outputs. Timer types
are:
On-screen help.
(Use the Page button with the
down arrow to access hidden
text at the bottom of the screen)
+
Navigation Pushbuttons (Cont.)
PAGE BUTTON
From any non-configuration page, pressing this push button causes the top level menu (figure 3.1.2) to appear.
The figure shows the menu for a user logged in with ‘Engineer’ level access. Other access levels may have
fewer menu items.
Within configuration pages, the Scroll button can be used as an enter key to select lower menu levels. In such
cases the page button is used to reverse this action, moving the user up one menu level per operation.
SCROLL BUTTON
From trending pages, operation of the scro ll push-button scrolls through the ch annels enabled in the group. The
Faceplate cycling ‘Off’ selection can be used to keep a particular channel permanently displaye d, and the scroll
pushbuttons can then be used to select channels manually.
In configuration pages, the scroll key operates as an ‘enter’ key to enter the next menu level associated with
the highlighted item. Once the lowest menu level is reached, operation of the scroll key allows the valu e of the
selected item to be edited by the relevant means (for example, the raise/lower keys, or a keyboard entry).
The ‘Page’ key is used to move the user back up the menu structure, until the top level menu is reached, wh en
the scroll key can be used again to return to the Home page.
The scroll button is also used to initiate user wiring as described in Section 7.
RAISE/LOWER BUTTONS
Within trending displays, the Raise and Lower keys ca n be used to scroll through the enabled display modes in
the sequence: vertical trend, horizontal trend, vertical bargraph, horizontal bargraph, numeric, vertical trend...
and so on.
Within configuration pages, these pushbuttons act as cursor keys, allowing, for example, the user to highlight
menu items for selection using the scroll button, and in many cases allowing the u ser to select one from a number of alternative values within menu items. These keys are also used to navigate through the virtual keyboards
(Section 3.6) and number pads used to enter text or numeric strings.
3.1.3 On Screen Help
The top level configuration menu includes contextual help te xt on the righ t-hand half of the screen. Mostly this
text fits within on screen height. Where this is not the case, the text can be moved up or down the screen by
holding the Page button operated whilst using the up and down arrows to move the text.
The down arrow moves the text upwards on the screen; the up arrow moves it downwards.
Page 11
Figure 3.1.3 On-screen help (typical)
HA030554
Issue 9 Mar 15
Page 22
nanodac RECORDER/CONTROLLER: USER GUIDE
12:01:08
Channel 16.23V
Inst name
Current time/date
Current point value and units
Current point ‘pen’
Current point scale
Time/date stamps
Current point name
Recording status
Instrument name
3.2 PROCESS VARIABLE DISPLAY
As discussed above, the operator interface consists of a display screen and associated push buttons. The
display screen shows process variables in one of a number of formats, or operational details (notes or alarm
history for example), or configuration details for use in settin g up the recorder to produce th e required displa ys
and history formats. The remainder of section three discusses the process variable displays, alarm displays
and so on; configuration details are to be found in Section 4.
Note: Some of the items below can be selected for use only by users with a suitable permission
level as set up in the ‘Instrument’ ‘Security’ menu described in Section 4.1.6.
Figure 3.2 below, depicts a typical trend display an d give s de ta ils of the var io us ar ea s of the dis pla y page .
Figure 3.2 shows a vertical trend page. Operating the Raise/Lower push-buttons allows the user to scroll
through the other display modes: Horizontal trend, Vertical bargraph, horizontal bargraph, numeric, vertical
trend... and so on. All these display modes are described in Section 3.4, below.
A display mode can also be selected from the Top leve l menu ‘Go To View’ item which appears when the ‘Pag e’
key is operated.
The scroll button can be used to scroll through the p oints in the gr oup, o verriding the ‘F aceplate Cyclin g’ on or
off selection
3.2.1 Alarm Icons
The alarm icons shown below appear in some display modes. The icons on a channel faceplate show the status
of that channel’s alarm(s), as follows:
Icon is flashingalarm is active but unacknowledged or it is an Auto alar m which is no longer a ctive
Icon steadily illuminatedthe alarm is active and has been acknowledged.
Alarm thresholds and deviation alarm bars app ear for hori zontal and ver tical tren d modes. For deviation bars,
the bar stretches from (Reference - Deviation) to (Reference + Deviation). Vertical and Horizontal bargraph
modes display only absolute alarm symbols.
Note 1: A full discussion of alarms is given in the Channel Configuration section of this manual,
Section 4.4.3.
Note 2: Trigger alarms do not display threshold marks or bars, or faceplate symbols.
but which has not been acknowledged
Page 12
HA030554
Issue 9 Mar 15
Page 23
nanodac RECORDER/CONTROLLER: USER GUIDE
Absolute High
Absolute Low
Deviation High
Deviation Low
Deviation Band
Rising Rate of change
Falling Rate of change
Digital High
Digital Low
Alarm Icons (Cont.)
Table 3.2.1 Alarm icons
3.2.2 Status Bar Icons
The following items can appear in a dedicated window immediately to the left of the time and date, at the bottom
right-hand corner of the display. The width of this wi n dow expands as the number of ico ns increase s, and the
instrument name is truncated, as necessary, to make room.
SYSTEM ALARMS
This indicator appears, flashing, if any one or more of the alarms listed below is active. The System Alarms
summary page (accessed from ‘Go to View in the top level menu) allows the user to view such system alarms
as are active. It is not possible to ‘acknowledge’ system alarms
Archive DisabledAn unattended archiving strategy has temporarily been disabled.
Archiving FailedAn unattended archiving strategy has failed to complete.
Archiving TimeoutA configured archiving strategy has timed out.
Battery failureIndicates that the battery is approaching the end of its useful life, or that
it is missing or is completely exhausted. Immediate battery replacement
is recommended (Appendix C; section C1).
Broadcast Storm detectedNetworking is limited until the storm has passed.
Clock failureThe internal clock was found to be corrupt at power up, or that the time
has never been set. Time is forced to 00:00 1/1/1900. Can be caused
by battery failure, in which case a battery failure message appears. The
error is cleared by setting the time and date.
Channel errorIndicates a hardware failure in the channel circuit or in the internal cold
junction temperature measurement.
Database failureCorrupted EEPROM or flash memory.
DHCP Server failureFor units with ‘IP Type’ set to ‘DHCP’ (Network.Interface configuration)
this alarm occurs if the instrument is unable to obtain an IP address from
the server.
FTP Archiving file lost A file has been deleted that had not yet been archived. Possible
FTP Archiving to slowThe archive rate is too slow to prevent the internal memory from
causes: Communications with the server could not be established,;
archive is disabled; archive rate too slow.
overflowing. The recorder effectively switches to ‘Automatic’ (Section
4.2.2) to ensure that data is not lost.
(Continued)
Page 13
HA030554
Issue 9 Mar 15
Page 24
nanodac RECORDER/CONTROLLER: USER GUIDE
Status Bar Icons (Cont.)
FTP Primary Server FailureThis error occurs if the recorder fails to establish connection with the
primary server, after two attempts. After the second attempt fails, the
recorder attempts to establish connection with the secondary server
instead. Primary and secondary server details are entered in the
Network. Archiving area of configuration (Section 4.2.2).
FTP Secondary Server FailureThis error occurs if the recorder fails to establish connection with the
secondary server, after two attempts. Primary and secondary server
details are entered in the Network.Archiving area of configuration
(Section 4.2.2).
Maths channel failureAppears if, for example, the divisor of a divide function is zero.
Media archiving file lostA file has been deleted that had not yet been archived. Possible
causes: Memory stick missing, full or write protected; archiving has
been disabled; archiving rate too slow.
Media archiving to slowThe archive rate is too slow to prevent the internal memory from
overflowing. The recorder effectively switches to ‘Automatic’ (Section
4.2.2) to ensure that data is not lost.
Media fullArchive storage device is full. The alarm becomes active only when a n
archive is in progress.
Media missingNo archive storage device present when archive attempted.
Non-volatile memory failureRAM copy of non-volatile parameters is corrupted.
Non-volatile Write Frequency warning
Recording failure (message)Message explains reason for failure.
SNTP failureInvalid data received from SNTP server, for example, the year received
Time synchronisation failureInstrument time has failed to synchronise with SNTP server.
USB overcurrentUSB power fault - too much current (i.e. >100mA) is being drawn by a
Wiring failureThe user wiring has failed to verify, i.e. one or more wires has been
One or more parameters are being written frequently to non-volatile
memory. If this continues, it may lead to ‘memory depletion’ (i.e. the
memory will no longer be able to store values correctly). A common
cause of this problem is frequent writes over Modbus comms.
from the server is <2001 or >2035, or the server cannot be accessed.
If more than 5 ‘Time change events’ occur within 24 hours a ‘Time
synchronisation failure’ alarm is set. The alarm occurs 24 hours after
the first event. Once synchronisation is re-established, the alarm self-
clears within 24 hours. A ‘Time change event’ occurs whenever the
recorder time is found to be more than 2 seconds different from the
server time. If the instrument time differs from the SNTP time by less
than 2 seconds, the instrument time is updated gradually (1 ms 8 times
a second) to prevent time changes being recorded.
SNTP time is based on elapsed seconds since 00 :0 0 ho u rs on 1st
January 1900. The time is not affected by time zones or daylight saving
adjustments.
USB device.
detected that does not have both a source and a destination defined.
This may be the result, for example, of power loss during a download
from iTools.
Page 14
HA030554
Issue 9 Mar 15
Page 25
nanodac RECORDER/CONTROLLER: USER GUIDE
Memory
stick fitted
Transfer in
CHANNEL ALARM
This indicator appears if any channel (including channels not in the display group) is in an alarm state. The
symbol is illuminated continuously if all alarms are acknowledged or flashes if any one or more alarms is
unacknowledged. Alarms are acknowledged from the Root menu ‘Alarm summary’ item as described in Section
3.3.3 or in the Channel configuration area (Section 4.4.3) if the user’s access permission is appropriate.
USB
This icon appears whenever a memory stick (max. capacity 8GB) or other supported USB device (Se ction 8) is
plugged into the USB port at the rear of the recorder.
When data transfer is in progress between the instrument and the memor y stick, the icon changes to a ‘busy’
version.
Caution: The Memory stick must not be removed while archiving
(demand or automatic) is in progress, as to do so may
irreparably damage the file system of the memory stick,
rendering it unusable. It is recommended that all archiving be
suspended before the memory stick is removed.
FTP ICON
The FTP icon appears whenever transfer activity is taking place.
RECORD ICON
One of four icons appears at the bottom left corner of the display to indicate recording status.
Record
This indicates that the recorder is recording the items selected in the Group Recording area of configuration
(Section 4.3).
Stopped
This means that ‘Enable’ has been set to ‘no’ in the Group Recording area of configuration (Section 4.3).
Trending is not affected.
Paused (Suspended)
This means that recording has been paused by a wire to the Suspend parameter (Group Recording area of
configuration (Section 4.3) going true (high). Trending is not affected.
In Configuration
The recorder has been placed in configuration mode either at the user interface, or via iTools. Recording is
stopped until the recorder is no longer in configur ation mode . For each n on-recor ding state (Stopp ed, Paused
or In Configuration). A new history file is created when the unit comes out of configuration mode.
MESSAGE ICON
This ‘envelope’ icon appears when a message is generated and it remains on display until the Message
Summary is accessed, when it is removed from the display until the next new message is generated.
AUTOTUNE ICON
For instruments fitted with the Loop optio n, th is symbol appears during the Autotune process.
Page 15
Note: For recording to be enabled, configuration status must be ‘logged out’ both at the instrument
Breaks in recording can be caused by the unit being powered down, by the user entering configuration mode
or when the recorder time is changed manually. In vertical and horizontal tren d modes, a lin e is drawn acr oss
the width/height of the chart to indicate that recording has been interrupted.
On power up, a red line is drawn across the chart. In ‘History’, if messages are enabled the message:
Date Time System power up
is printed on the chart, together with the configuration and security revisions.
On exiting configuration mode, a blue line is drawn on the chart and in ‘History’, if messages are enabled, the
messages:
Date Time Logged out.
Date Time Config Revision: N was N-1 (assuming a configuration change was made)
Date Time Logged in as: Engineer
appear on the chart.
When the instrument time is changed (manually - not through daylight saving action) a green line is drawn on
the chart and in ‘History’, if messages are enabled, the message:
Date Time Time/Date changed
appears on the chart.
3.3 TOP LEVEL MENU
This menu appears when the page key is operated fr om any non-configuration page. The menu items displaye d
depend on the access permission of the user. One of the menu items is highlighted, and if the scroll key is
operated, then it is the highlighted item that is ‘entered’.
Figure 3.3 shows the top level menu for Engineer level access.
Figure 3.3 Top level menu
3.3.1 Home
Operating the scroll key whilst ‘Home’ is highlighted causes a return to the ‘Home’ page. By default, this is the
vertical trend mode, but the mode can be changed in ‘Instrument. Display’ configuration (Section 4.1.3)
3.3.2 Configuration
Operating the down arrow key highlights the ‘Configuration’ item. Operating the Scroll key enters the configuration submenu described in Section 4of this manual.
Page 16
Note: ‘Configuration’ appears only if the user has an appropriate access level.
Issue 9 Mar 15
HA030554
Page 27
nanodac RECORDER/CONTROLLER: USER GUIDE
Alarm Summary
System Alarms
Message Summary
Vertical Trend
Horizontal Trend
Vertical Bargraph
Horizontal Bargraph
Numeric
Alarm Summary
System Alarms
Message Summary
Vertical Trend
Horizontal Trend
Vertical Bargraph
Horizontal Bargraph
Numeric
Alarm Panel
Control
Dual Loop
Cascade
Programmer
Steriliser
Promote List
Modbus Master
EtherNet/IP
Alarm Panel
Control
Control (Dual Loop)
Cascde
Programmer
Steriliser
Promote List
Modbus Master
EtherNet/IP
3.3.3 Go to View
Operating the scroll key whilst the ‘Go to view’ item is highlighted, calls the Go to view submenu (figure 3.3.3a).
This allows the user to view channel alarms, system alarms, messages or to select a different display mode.
Page 17
Figure 3.3.3a Go to view submenu
Note 1: If an option (e.g. ‘Steriliser’) is not fitted, its display mode does not appear in the list.
Note 2: Some display modes must be enabled in Instrument. View configuration (Section 4.1.3)
For each active alarm, this page displays the channel identifier with alarm number (e.g. C1(2) = channel 1;
alarm 2), the channel descriptor, the alarm threshold the current process value and an alarm type symbol.
To return to the top level menu, operate the Page key.
Note 1: The background colour to the channel ID is the same as that chosen for the channel
Note 2: A prefix ‘C’ in the channel ID means that this is a measuring channel; A prefix ‘V’ means
that this is a virtual channel (i.e. a totaliser, counter or maths channel
ALARM ACKNOWLEDGEMENT
To acknowledge an alarm from this view:
1.Use the up and down arrows to highlight the required
alarm
2.Operate the scroll button. The ‘Acknowledge alarm’ window appears.
3.Use the up arrow to highlight the relevant field (C2(1) in
this example), or ‘All’ if all alarms are to be acknowledged.
4.Operate the scroll key to confirm. If the alarm fails to
SYSTEM ALARMS
respond, this may be due to the fact that it has been configured as a ‘Manual’ alarm, and the trigger has
not yet returned to a ‘safe’ (non-alarm) state, or it could be that the instrument is in a logged out state.
Operating the scroll button whilst the ‘System Alarms’ field is highlighted displays a list of all currently active
system alarms. Section 3.2.2 contains a list of system alarms and their interpretations. To return to the top
level menu, operate the Page key.
A further operation of the scroll button displays a ‘Help Information’ page, giving the reaso n for the highlig hted
alarm.
Operate the scroll button again to return to the system alarm display.
Page 18
Figure 3.3.3b Alarm summary page with acknowledge confirmation display
Use scroll button to scroll through ‘All Messages’, ‘System’, ‘Alarm’ and ‘Power Up’. Use page
button to confirm selection.
Use scroll button to return to refreshed Message Summary page.
Use the scroll or page button to return to the top
level menu.
9/47
Go to?
SummaryHistory
To Trend History
display (Section 3.5)
Go To View (Cont.)
MESSAGE SUMMARY
Operating the scroll key whilst the ‘Message summary’ fi eld is highlighted displays the10 most recent messages.
Operating the scroll key whilst a message is highlighted shows the selected message in more detail (and using
the up/down keys allows the other messages to be scrolled through). Whilst in this mode, operating the scroll
key again, allows the user to choose to jump to the message’s location in trend history mode (Section 3.5) or
to return to the summary page.
By default, the interface is set up such that:
1.all message types are included
2.the up and down arrow keys cause the highlighted selection to move up or down by one message at a
time.
MESSAGE FILTERS
All Messages Causes all messages to be displayed on the screen.
SystemShows only system alarms
AlarmShows only channel alarms
Power upShows only power up messages
Login/outLimits the display to Log in and Log out events.
Figure 3.3.3c Message summary features
Page 19
HA030554
Issue 9 Mar 15
Page 30
Go To View (Cont.)
Alarm Summary
System Alarms
Message Summary
Vertical Trend
Horizontal Trend
Vertical Bargraph
Horizontal Bargraph
Numeric
Alarm Panel
Control
Control (Dual Loop)
Cascde
Programmer
Steriliser
Promote List
Modbus Master
EtherNet/IP
DISPLAY MODE SELECTION
Use the up/down arrow buttons to highlight the required display mode.
Once the required display mode is highlighted, operation of the scroll button causes the recorder to leave the ‘Go to View’ menu and to display
channel values in the selected mode. See Section 3.4 for a description of
the various display modes.
Alternatively the up and down arrow buttons can be used from any of the
display modes to cycle through the available modes in the order listed in
the figure.
Note 1: If an option (e.g. ‘Steriliser’) is not fitted, its display
mode is not available for selection.
Note 2: Some display modes must be enabled in Instrument.
Display configuration (Section 4.1.3) before they
become available.
3.3.4 History
This top level menu item allows the user to switch from real -time trending
to review mode, where channel values, messages, alarm trigge rs etc. can
be viewed back as far as the last significant con.figuration change. History
mode is fully discussed in Section 3.5.
3.3.5 Faceplate Cycling on/off
For the purposes of this document the channel whose fac eplate is currently displayed and whose ‘pen’ symbol is visible is called the ‘Active’ channel.
By default, the recorder scrolls through all the channels in the display group, with each channel becoming the
active channel in turn. This top level menu ‘Faceplate Cycling’ item allows the user to inhibit this scrolling action
such that the currently active channel remains active permanently, or until a manual scroll is performed using
the scroll button (or until Faceplate Cycling is re-enabled).
‘Faceplate Cycling’ is highlighted by using the up/down arrow buttons. Once highlighted, the status can be
changed from ‘On’ to ‘Off’ or vice-versa using the scroll button. Operation of the ‘Page’ button returns th e user
to the trend display.
3.3.6 Operator Notes
This area allows up to 10 notes to be created when logged in as Engineer, usin g either the text entry techniques
described in Section 3.6, or ‘iTools’ described in Section 6. Once logged out, operating the scroll button whilst
a note is highlighted calls a selection box allowing the user either to send that note to the chart, or to write a
Custom Note.
CUSTOM NOTE
The Custom Note is written using the text entry tech niques described in Section 3.6. Once the note is complete,
operation of the page button calls a confirmation display. The down ar row is used to h igh light ‘Yes’, and whe n
the scroll key is then operated, the message is sent to the chart. This custom message is not retained for further
use, so if it is required on a regular basis, it is suggested that one of the Operator Notes 1 to 10 be configured
(Engineer access level required) so that it may be used instead.
Note: Each note can contain up to 100 characters
nanodac RECORDER/CONTROLLER: USER GUIDE
Page 20
HA030554
Issue 9 Mar 15
Page 31
nanodac RECORDER/CONTROLLER: USER GUIDE
Demand Archiving
Archive To
Archive
Suspend Schedule
Cancel All
Status
Last Archive
USB
None
No
No
Complete
02/11/2011 11:37:09
Demand Archiving
Archive To
Archive
Cancel All
Pri Status
Sec Status
Last Archive
FTP Server
None
No
Complete
Connecting
02/11/2011 11:37:09
3.3.7 Demand Archiving
This allows a user, with a high enough access level, to archive a selected portion of the reco rder history, eith er
to a ‘memory stick’ plugged into the USB port at the rear of the recorder ( Local Archiving), or to a pc, by means
of the FTP protocol (Remote Archiving). The archived data remains in the flash memory of the instrument.
When the flash memory is full, new data causes the oldest file(s) to be discarded.
The up and down arrow keys are used to navigate to the required field.
ARCHIVE MENU
Figure 3.3.7 Demand Archiving menu (Local Archiving on left; Remote Archiving on right)
Archive ToWith this item highlighted, the scroll button and the up/down arrows can be used to select
‘USB’ or ‘FTP Server’.
For ‘USB’, the archive will be made to the rear USB memory stick. For ‘FTP Server’ the
archive will be made to the Primary or Secondary server (configured in the Network.Archive area of configuration described in Section 4.2.2. For mo re deta ils abo ut r emote ar chiving, see ‘Remote archiving’, below.
ArchiveIn a similar way, select the archive period:
None: No archiving to take place. (Not editable when logged out)
Last Hour: Archives all files created within the last 60 minutes.
Last Day: Archive all files created in the last 24 hours.
Last Week: Archives all files created in the past seven days.
Last Month: Archives all files created in the past 31 days.
Archive All: Archives all the files in the recorder’s history.
Bring To Date: Archives all files created or updated since the ‘Last Archive’ date and time.
Suspend Schedule When set to ‘Yes’, automatic (scheduled) archiving is stopped, once the transfer of the
current file is complete. Suspend Schedule must be set to ‘No’ again, to restart the suspended archive. Suspend can be used to allow the memory stick to be removed and refitted safely.
Cancel AllWhen set to ‘Yes’, this cancels USB archiving activity immediately, or cancels FTP archiv-
ing once transfer of the current file (if any) is complete.
Last ArchiveShows the date and time at which the last archive (demand or automatic) was attempted.
If a demand archive is requested, or is in operation when an a utomatic archive is triggered,
the automatic archive takes precedence.
StatusFor Archive to USB only
‘Complete’ means that no archiving is currently taking place.
PriStatusFor Archive to FTP Server only, this shows the transfer status betwe en the instrument and
SecStatusFor Archive to FTP Server only, this shows the transfer status between the instrument and
Page 21
‘Transferring’ indicates that an archiving is in prog ress. Accompanied by an animated circular display.
‘Suspended’ means that archiving has been suspended as requested.
the primary host computer.
the secondary host computer.
Issue 9 Mar 15
HA030554
Page 32
nanodac RECORDER/CONTROLLER: USER GUIDE
Demand Archiving (Cont.)
FTP SERVER ARCHIVING
This allows the archiving of recorder files to a remote computer via the RJ45 type connector at the rear of the
recorder, either directly or via a network.
In order to carry out a successful transfer:
1.Details of the remote host must be entered in the Network.Archive area of configuration (Section 4.2.2).
2.The remote computer must be set up as an FTP server. Help from the user’s IT department may be necessary in order to achieve this. Appendix C, Section C2 to this manual suggests one way, using Filezilla.
3.The remote computer must also be set up to respond to ‘pings’. This is because the instru ment pings the
host whilst establishing connection, and if it does not receive a response the archive attempt fails.
When accessing files using Microsoft® Internet Explorer, the address (URL) field can be in one of two formats:
1.ftp://<instrument IP address>. This allows a user to log in as the anonymous user (if the recorder has any
account with the user name set to ‘anonymous’ with a blank password.
2.ftp://<user name>:<password>@<instrument IP address> to log in as a specific user.
For IE5 users, Microsoft® Internet Explorer displays, by default, history files only. To quit the history folder,
either uncheck the Tools/Internet Options/Advanced/Browsing/’Enable folder view for FTP sites’ option, or
check the Tools/Internet Options/Advanced/Browsing/’Use Web based FTP’ option.
REVIEW SOFTWARE
‘Review’ is a proprietary software package which allows the user to extract ‘archive’ data from one or more suitable instruments* and to present this data on a host computer, a s if on a ch art, or as a spre adsheet. The ho st
computer must be set up as an ftp server (see Appendix C section C2 for a description of one way of doing this).
As described in the Review help system, ‘Review’ allows the user to set up a regular transfer of data (u sing ftp)
from connected instruments into a database on the pc, and then from this database to the chart or spreadsheet.
The chart/spreadsheet can be configured to includ e one or more ‘points’ from o ne or all connected instruments
(where a ‘point’ is an umbrella term for channel, totaliser, counter etc.).
It is also possible to archive instrument history files to a memory stick, Compact Flash card etc. (depending on
instrument type) and to use this to transfer the data to the pc.
Each type of instrument has its own remote user name and password configuration - for this instrument, the
user name and password are both ‘history.
*Suitable instruments are connected instruments, the archive files of which have the suffix ‘.uhh’.
Page 22
HA030554
Issue 9 Mar 15
Page 33
nanodac RECORDER/CONTROLLER: USER GUIDE
Record icon
Configuration
3.3.8 Login
Login allows the user to enter a password in or der to gain access to area s of the un it’s configuration which are
not available when the user is logged out.
LOGGED OUT ACCESS LEVEL
Logged out mode allows the user to select viewing mode, to view history, to view alarms, to toggle faceplate
cycling on and off, to send notes, to suspend/resume USB archiving and to access the login process.
OPERATOR ACCESS LEVEL
In addition to the logged out features, Ope ra to r ac ce ss level allows the user to acknowledge alarms, to edit
notes and to perform demand archive operations.
By default, no password is required in order to enter Operator level, but a password can be set either at Supervisor level or at Engineer level.
SUPERVISOR ACCESS LEVEL
In addition to the logged out level functio n, this access level allows the user to view the record er’s configuration,
and to edit some values (such as alarm thresholds). By default, there is no password required to enter Supervisor level, but a password can be set in the Instrument area of configuration, either at Supervisor level or at
Engineer level.
ENGINEER ACCESS LEVEL
This allows full access to all areas of the recorder configuration. The default password is 100, but this can be
edited in the Instrument area of configuration (Section 4.1.5).
Note: Recording is stopped for as long as the user is logged in at Engineer
level, even if the recorder is not being configured. This is indica te d by
the Record icon at the bottom left corner of the process value display
screen being replaced by the Configuration (wr e nch ) icon.
LOGIN PROCEDURE
From the top level menu, use the up or down arrow keys as often as necessary in order to highlight ‘L ogin’, and
then operate the Scroll key to produce the ‘Access Logged out’ display.
Note: This procedure describes how to login to an access level with a password associated with it.
For non-password protected logins, the user needs only to select the required access level,
and press the scroll key.
Page 23
HA030554
Issue 9 Mar 15
Page 34
nanodac RECORDER/CONTROLLER: USER GUIDE
Access
Access
Logged out
Operator
Access Supervisor
Access Engineer
Access Engineer
Password
Password
Password
Accept changes
No YesCancel
To log in as Engineer (password = 100):
1.Operate the up arrow key three times, to display ‘Engineer’.
2.Press the scroll key to call the ‘alpha’ keyboard, with the letter ‘q’ highlighted.
3.Use the down arrow key three times to highlight ‘Numeric’.
4.Operate the scroll key to display the numeric keyboard (numeral ‘1’ highlighted.)
5.Operate the scroll key to enter ‘1’, then use the up arrow key nine times to highlight numeral ‘0’ and use
the scroll key twice to enter ‘0’ 0’, completing the password of 100.
6.Use the Page key to call the confirmation display.
7.If the password entry is as required, use the up arrow twice (or the down ar row once) to highlight the word
‘Yes’ and operate the scroll key to confirm. The top level configuration menu appears. Otherwise, ‘Cancel’ can be used to clear the entry in order to start again, or ‘No’ can be used to quit login.
The following subsections describe the various display modes availab le to the user. By default, the ‘Home’ display mode is ‘Vertical Trend’, but this can be edited as a part of ‘Instrument.Display’ configuration. This configuration area also allows the user to disable one or more display modes should they not be required.
The current display mode can be chosen either by using the top level menu ‘Go to View’ item or, from any display mode, by scrolling through the enabled modes using the up or down arrow button.
Details of the various display modes are to be found in the following subsections:
3.4.1 Vertical Trend
In this mode, channel values are traced as though on a chart rolling downwards (i.e with the latest data at the
top). The chart speed, and the number of major divisions are configured in the ‘Group.Trend’ area of configuration (Section 4.3.1). By default, the chart background is black, but this can be changed to white or grey in the
‘Instrument’ ‘Display’ area of configuration (Section 4.1.3).
One of the channels is said to be the ‘current’ or ‘scale’ channel. This channel is identified by its pen icon being
displayed, and by the channel descriptor, dynamic value and its scale being displayed on a ‘faceplate’ across
the width of the display, above the chart.
Each channel in the Group becomes the ‘current’ channel in turn, for app roximately five seconds -i.e. the channels are cycled through, starting with the lowest numbered channel. Once the final channel in the Group has
ben displayed for five seconds, the first channel is returned-to and the process repeats. This scrolling behaviour
can be enabled/disabled from the top level menu ‘Faceplate Cycling (Off)’ item described in Section 3.3.5.
The scroll button can be used to cycle through th e channels manually in both Faceplate cycle on and off modes.
Use of the up arrow button causes the next ena bled display mode to be entered (default = horizontal trend).
The page key calls the top level menu.
Page 25
Figure 3.4 Vertical trend mode display elements
HA030554
Issue 9 Mar 15
Page 36
nanodac RECORDER/CONTROLLER: USER GUIDE
Inst name
Channel 1
6.23
V
By default, after a few seconds,
the ‘chart’ expands leftwards to
hide the scale. This feature can
be disabled in the Instru-
ment.Display area of configura-
tion (Section 4.1.3, H.Trend
scaling) so that the scale is per-
Channel 1
35.40
V
Inst name
Active alarm symbol
Alarm threshold (active)
Alarm threshold (non-active)
Full scale value
‘Zero’ value
2 channels
1 channel
3.4.2 Horizontal Trend mode
This view is similar to the vertical trend mode described in section 3.4.1 above, except that the traces are produced horizontally rather than vertically. Initially, as each channel appears, its scale appears at the left edge o f
the display (as shown below), but in order to show the maximum amount of trend data , the scale is overwritten
after a few seconds.
Figure 3.4.2 Horizontal trend display mode
Note: Timestamps appear to the right of the gridline to which they relate
Use of the up arrow button causes the next enabled display mode to be entered (default = vertical bargraph).
Use of the page key calls the top level menu.
3.4.3 Vertical Bargraph mode
This display mode shows the channel values as a histogram. Absolute alarm threshold va lues appear as lines
across the bars, grey if the alarm is not triggered; red if the alarm is triggere d. Alarm symbols appear for active
alarms.
Bargraph widths for four to six channels divide the width of the display screen e qually between them. For o ne
and two channels, the width is fixed, and the bars are centred on the screen. Figure 3.4.3 shows some examples (not to the same scale).
Use of the up arrow button causes the next enabled display mode to be entered (default = horizontal ba rgraph).
Use of the page key calls the top level menu.
Page 26
Figure 3.4.3 Vertical bargraph display mode
HA030554
Issue 9 Mar 15
Page 37
nanodac RECORDER/CONTROLLER: USER GUIDE
Furnace 1 temp 12
Channel 2
Channel 3
Channel 4
VirtualChan 1
VirtualChan 2
Inst name
Furnace 1 temp 12
Channel 2
Furnace 1 temp 12
2 channels
1 channel
The scroll button tog-
gles the text between
point descriptor (as
shown) and point value.
Furnace 1 temp 12
Channel 2
Channel 3
Channel 4
VirtualChan 1
VirtualChan 2
Alarm type indication
(table 3.2.1)
6 channels5 channels4 channels
3 channels2 channels1 channel2 channels1 channel
3.4.4 Horizontal Bargraph mode
Similar to the Vertical bargraph mode described in Section 3.4.3, above, but includes channel descriptors.
Figure 3.4.4 Horizontal bargraph mode
Use of the up arrow button causes the next enabled display mode to be entered (default = numeric).
Use of the page key calls the top level menu.
3.4.5 Numeric mode
Shows the enabled channels’ values along with their de scriptors and with indications of the type(s) of a larm configured for each channel.
The figure above shows an example whe re t he Tr en d group contains six channels. Figure 3.4.5b shows how
the display appears for trend groups with fewer than six channels configured.
The up arrow button returns to the vertical trend display mode; the page key calls the top level menu.
Page 27
Figure 3.4.5b Display layout for diff erent numbers of channels
HA030554
Issue 9 Mar 15
Page 38
nanodac RECORDER/CONTROLLER: USER GUIDE
Red bar
Alarm 2 is active, or alarm 1
and alarm 2 are both active.
Amber bar
Alarm 1 is active for this
channel, but not alarm 2.
Green bar
Neither alarm 1 nor alarm two
active for this channel.
Alarm type indication (table
Inst name
6 channels5 channels4 channels
3 channels2 channels1 channel
3.4.6 Alarm panel
This display appears only if enabled in the Instrument Display configuration (Section 4.1.3) Alarm panel mode
shows current value and alarm status for each channel enabled in the Trend Group. The status is shown in two
ways, by the colour of the relevant bar, and by the alarm status indicators.
Figure 3.4.6a Alarm panel display (six channels)
The figure above shows an example whe re t he Tr en d group contains six channels. Figure 3.4.6b shows how
the display appears for trend groups with fewer than six channels configured.
Figure 3.4.6b Alarm panel display layouts for trend groups with fewer than six channels
Page 28
HA030554
Issue 9 Mar 15
Page 39
nanodac RECORDER/CONTROLLER: USER GUIDE
Loop 1
°C
PVPVWSP
Working Output
WSP
SP1
Mode
Man Op
Loop 1
Loop 2
Manual
Manual
Manual
SP1
Mode
Man Op
SP1
Mode
Man Op
SP
PV
WSP
PV
WSP
Inst nameInst name
SP1
Mode
Man Op
SP1
Mode
Man Op
SP1
Mode
Man Op
SP1
Mode
Man Op
SP1
Mode
Man Op
Manual
Manual
Manual
Auto
Auto
3.4.7 Control Loop1/Loop2
These displays appear only if the controller opt ion is ena ble d (Section 4.1.6).
The loop display modes are interactive, in that the setpoint, the Auto/Manual mode and the Manual Output value
can be edited from the user interface. Full configuration is carried out in the Loop setup menus (Section 4.6)
and a fuller description of control loops is to be found as Appendix B to this manual.
Figure 3.4.7 depicts a single loop display and the dual loop display. The up and down arrow keys are used as
normal to scroll through Loop1, Loop2 and Dual loop pages.
EDITING TECHNIQUES
1.With the loop page on display, operate the Scroll key. This highlights the first editable item (SP1). The scroll order includes both loop1 and loop 2 parameters in the
dual loop display.
2.Use the up and down arrow keys to select the required field for editing. When the
required field is highlighted, operate the scroll key again, to enter edit mode.
3.Use the up/down arrows to edit the current setting.
Figure 3.4.7 Loop displays
Note: The colours associated with the loops are those of the channels to which they are wired.
4.Operate the scroll key to confirm the edit.
5.Select a further parameter for editing, or operate the page key to return to normal
operation.
Page 29
Note: Edit permissions for Setpoint, Auto/Manual and Manual Output Access are set in the Loop
Setup configuration menu (Section 4.6.2).
HA030554
Issue 9 Mar 15
Page 40
nanodac RECORDER/CONTROLLER: USER GUIDE
Master
Cascade
Slave
Mode
Sp1
SP
Man.OP
PV
WSP
PV
WSP
Inst name
3.4.8 Cascade Display Mode
This display mode appears only if ’Cascade’ has been enabled in the Instr ument.Displa y area of configura tion
Section 4.1.3). See also Advanced Loop configuration (Section 4.7).
Figure 3.4.8a Cascade display mode
Operating the scroll button highlights the Master ‘Mode’ field. Operating the scroll button again, enters edit
mode allowing the user to use the up/down arrow buttons to scroll through the available modes. Once the required mode appears, a further operation of the scroll button confirms the entry and quits edit mode.
Once out of edit mode, the down arrow key can be used to select Master ‘SP1’, Slave ‘SP’ and Slav e ‘Man OP’.
The Mode selected determines how many of these items are editable by the operator.
ModeCascade: The master loop is in auto mode and provides the slave setpoint. Changing
modes causes the slave to switch to the local slave setpoint.
Slave: A simple single loop controlling with a local setpoint.
Manual: Provides a single manual % power output.
SP1Setpoint 1 is the primary setpoint of the controller. If the controller is in automatic control
mode, then the difference between the setpoint and the process variable (PV) is continuously monitored by the control algorithm. The difference between the two is used to produce an output calculated to bring the PV to the setpoint as quickly as possible without
causing overshoot.
SPThe slave setpoint, either local (Manual or Slave mode) in which case it can be edited, or
supplied by the master loop (Cascade mode), in which case it is not editable.
Man.OPThe percentage output power to be applied when in Manual mode (100% = full on; 0% =
off).
Page 30
Note: The default loop names (‘Master’ and ‘Slave’) can be replaced by user-entered strings of up to
10 characters in Advanced Loop Setup configuration (Section 4.7.2).
Issue 9 Mar 15
HA030554
Page 41
nanodac RECORDER/CONTROLLER: USER GUIDE
Program Name (Segment name)
Ramp
Events
Status:
Seg Time Left
Ch1 Rate
PV
PSP
00:00:3000:02:12
Running
00:00:44
1
Program
progress
Segment
progress
Program time
remaining
Program status
Single channel
Double channel
Program edit
Seg Time Left
Ch2 PSP
CH2 TSP
Events
Mode
Ch1 PSP
Ch1 TSP
Run
123.2
140.0
00:01:05
12.7
13.0
Mode
Ch1 PSP
Ch1 TSP
Run
123.2
140.0
Status: Running
00:01:3000:03:12
PV
PSP
PV
PSP
Program Name (Segment name)
Program nameThis is the name of the loaded program. If the program has been modified since being
saved, an asterisk (*) appears after the name . Default background colour shown. This colour changes to that assigned to the input channel when this is configured.
Segment nameThis is the name of the current segment. If not named in Segment configuration, then the
segment number appears instead.
Program statusAt the top right hand corner of the display, this can be any one of the following:
The program is running (or ran last time) without any PV ‘Alarm’ events or user intervention.
The user has intervened in the running of the program, by placing it in ‘hold’ or ‘r eset’,
or by advancing a segment, or by adjusting a duration, target setpoint, ramp rate or timeto-target value.
A PV ‘Alarm’ Event has activated. A PV ‘Alarm’ Event is an absolute high/low or a
deviation alarm on the PV input.
There is no program loaded, or if a program is loaded, it has not yet run.
Program edit This icon appears for users with appropriate access perm issions, to in dicate that set-
point programs can be configured (as described in Program edit, below).
Segment typeFor single channel displays, this indicates the type of segment currently being run:
Dwell. The segment value remains constant for the duration of the dwell period.
End (dwell). Displayed on completion of the program. The segme nt value remain s
at the final value until reset
End (reset). Displayed on completion of the program. The program resets.
Ramp. The segment value ramps at a fixed rate or over a fixed period to the Target
setpoint. Ramp up icon shown; ramp down is similar but inverted.
Step. The segment value switches immediately to the new Target setpoint. Step
down shown; step up similar but inverted.
Wait. The segment value remains constant until the wait criteria are satisfied.
3.4.9 Programmer Display Mode
Figure 3.4.9a Programmer displays (typical)
This display mode (if enabled - see Section 4.1.3 allows the user to monitor the progress of a single or dualchannel setpoint program, and if logged- in as ‘Operator*’, to reset or run the program. The program itself is
created in the Program edit page (described below) and in Programmer configuration (Section 4.8 or ‘iTools’).
Note: *Operator is the default access level - to edit, see ‘ Prog Mode Access’ in Section 4.8.3)
The displays contain the following features:
Page 31
HA030554
Issue 9 Mar 15
Page 42
nanodac RECORDER/CONTROLLER: USER GUIDE
Seg Time Left
Ch2 PSP
CH2 TSP
Ch2 Time
Events
Hold
123.2
140.0
00:00:34
00:01:05
12.7
13.0
00:00:49
Status: Holding
PV
PSP
PV
PSP
Program Name (Segment name)
Mode
Ch1 PSP
Ch1 TSP
Ch1 Time
Programmer Display Mode (cont.)
PVThe current process value of the signal wired to Ch1(2) PV Input.
Ch1(2)PSPThis is the output setpoint from the programmer for the channel. In reset this value tracks
the configured servo parameter.
Ch1(2)TSPThe channel target setpoint. The target set-point may be edited while the program is in
hold (in such cases, for ramp rate segments the time remaining is recalculated.
EventsUp to eight events can be configured in the Program Edit page. Any one or more of these
events may be deemed to be active for the duration of each individual segment.
ModeShows the current run mode of the program. If the user has the corre ct access level, the
mode can be set to ‘hold’, reset’ etc. by using the scroll key twice (first to highlight the run
mode, then again to enter edit mode) and then using the up/down arro w keys to select the
required mode. Run, reset, hold etc. can also be selected by inputs from other parame-
ters, switch inputs etc.
StatusShows the status of the current segment.
Ch1 RateThe channel 1 rate-of-change of segment value for ‘Rate’ ramp segments.
Ch1 TimeShows the channel 1 duration configured for the segment to ramp, dwell etc. for ‘Time’
ramp segments. For two-channel programs, see the note below.
Seg Time LeftShows the time that the segment has to run before completion.
Program progressThe numerals show prog ram elapsed time, and th e bar gives an indication of progress so
far. For two-channel programs, see the note below.
Segment progressFor each segment as it runs, this gives a visual indication of the proportion of total seg-
ment time which has elapsed so far. For two-channel programs, see the note below.
Program time remaining
Shows the time remaining until the program completes. For two-channel programs, see
the note below.
Note: For two-channel programs, in ‘Hold’ mode, the ‘prog ra m progr es s ’, ‘s eg m en t pr og re ss ’ and
‘program time remaining’ areas of the display are replaced by ‘Ch1 Time’ and ‘Ch2 Time’, as
shown below.
Figure 3.4.9b two channel program in Hold mode
Page 32
HA030554
Issue 9 Mar 15
Page 43
nanodac RECORDER/CONTROLLER: USER GUIDE
Program Name
Ramp
Events
Status:
PV
PSP
Reset
Mode
Ch1 PSP
Reset
14.3
Reset
14.3
Reset
15.7
Run
17.3
Hold
18.9
‘Hold’ appears
only if the program
Programmer Display Mode (cont.)
PROGRAM RUN/RESET/HOLD
Programs can be controlled by users with the correct access level (defined in Pr ogrammer co nfiguration - Section 4.25). The display page is placed in edit mode by operation of the scroll key (‘Mode’ highlights). A second
operation of the scroll key followed by opera tion of the up/down arrows allows the user to select ‘Run’, ‘Ho ld’ or
‘Reset’. A further operation of the scroll key initiates the selected action.
Figure 3.4.9c Setting the Mode
Note: 1. These functions can also be carried out by wiring relevant inputs to the ‘Run’, ‘Hold’ or
‘Reset’ parameters in Programmer configuration (Section 4.8).
Note: 2. The user must have either ‘Logged off’, ‘Operator’ or ‘Supervisor’ level access as defined
in ‘Prog Mode Access’ in the Programmer. Setup menu described in Section 4.8.3 . The
program cannot run if the unit is logged into at ‘Engineer’ level.
Page 33
HA030554
Issue 9 Mar 15
Page 44
nanodac RECORDER/CONTROLLER: USER GUIDE
By default, Program Edit is available only to
users with Supervisor or Engineer level access. The required access level can be edited in Programmer. Set Up configuration as
described in Section 4.8.3.
Program Name (Segment name)
Ramp
Events
Status: ResetMode
Ch1 PSP
Reset
14.3
Program Name (Segment name)
Ramp
Events
Status: ResetMode
Ch1 PSP
Reset
14.3
Program Edit
Operation
Status
Program
Holdback Style
Ch1 Holdback
Ch1 Holdback Val
Ch2 Holdback
Ramp Style
Ch1 Ramp Units
Ch2 Ramp Units
Select ...
Success
Program Name
Program
High
0.0 V
Off
Time
Per Second
Per Minute
Segment Number
Segment Name1Heat Init
Programmer Display Mode (cont.)
PROGRAM EDITING
The program edit page is accessed by operating the scroll button once to highlight the Mode, th en using the up
arrow key to highlight the page symbol at the top right hand corner of the display and then the scroll button again
to enter the program editor.
As can be seen from the figure above, the initial Program Edit page is divided into two areas - the top part contains program details; the lower part (figure 3.4.9f) contains individual segment details. The editable items that
appear in the program details area depend on the fe atures e nabled in the Progr ammer Fe atures con figuration
menu (Section 4.8.1).
Note: Access to some program operations is restricted to users with the correct access level, as
defined in the ‘Prog Mode Access’, the ‘Prog Edit Access’ and the ‘Prog Store Access’ parameters in the Programmer. Set Up area of configuration described in Section 4.8.3. Access to
some items also depends on whether or not the program is running.
Figure 3.4.9d Access to the program editor
Page 34
HA030554
Issue 9 Mar 15
Page 45
nanodac RECORDER/CONTROLLER: USER GUIDE
Programmer Display Mode (cont.)
PROGRAM DETAILS
OperationThis allows the user to select one of the following (see also ‘Program Store):
Load. Opens the program store and allows th e user to select a program to be loaded. The
program must have the same number of channels a s defined in Programmer.Set Up (Sec-
tion 4.8.3).
Store. Allows the current program to be saved to the internal program drive. This is useful
if you wish to snapshot the current program and store this under a different progra m name.
Delete. Allows the selected program to be deleted.
Delete All. Deletes all programs.
Copy. Copies the selected program for ‘pasting’ either from the internal drive to the USB
device, or vice-versa. This is useful if you wish to transfer a program to other nanodac
instruments.
Copy All. As above, for ‘Copy’, but copies all the programs in the selected directory.
Note: If a ‘Store’, ‘Copy’ or ‘Copy All’ operation would result in there being a total of more than 100
program files in the internal drive, the operation fails and an error message is displayed.
StatusSuccess. Previous operation was successful.
Failed. Previous operation failed.
Loading. The program is loading.
Copying. The program copy process is underway.
Deleting. The relevant program is being deleted.
ProgramThe name of the program currently loaded.
Holdback StyleAppears only if ‘Holdback’ is enabled in the Programmer Features configuration (Section
4.8.1). See also ‘Holdback’, below.
Program: Holdback applies to all appropriate segments.
Per Segment: Holdback enabled on a segment by segment basis as described in ‘Seg-
ment configuration below.
Ch1 HoldbackAppears only if ‘Holdback Style’ (above) is set to ‘Program’.
Off: Holdback is disabled
Low: Holdback is entered when PV < (PSP - Holdback Value)
High: Holdback is entered when PV > (PSP + Holdback Value)
Band: Holdback is entered when PV < (PSP - Holdback Value) or PV > (PSP + Holdback
Value)
Ch1 Holdback value
Ch2 HoldbackAs for Ch1 Holdback, above but for channel 2. Appears only if ‘Channels’ is set to ‘2’ in
Ch2 Holdback value
Ramp StyleRamp style applies to all ramp segments in the program. Ramp Style can be edited only
Ch1 Ramp UnitsSelect ‘Per Second’, ‘Per Minute’ or ‘Per Hour’ for ramp timing units. Ramp Units can be
Ch2 Ramp UnitsAs for ‘Ch1 Ramp Units’ above. Appears only for two channel programs and allows dif-
The value to be used in triggering holdback.
Programmer Set Up configuration (Section 4.8.3).
As for ‘
‘2’ in Programmer Set Up configuration (Section 4.8.3).
when the program is in Reset mode. Setpoints, rates, times etc. are set in the individual
segment configurations
Rate. A Ramp Rate segment is specified by a target set-point and the rate at which to
ascend/descend to that set-point.
Time. A Ramp Time segment is specified by a target set-point and a time in which to
achieve that set-point.
edited only when the program is in Reset mode.
ferent ramp units to be selected for the two channels, if required . Ramp Units can be ed -
ited only when the program is in Reset mode.
Ch1 Holdback value
’, above, but for channel 2. Appears only if ‘Channels’ is set to
Page 35
HA030554
Issue 9 Mar 15
Page 46
nanodac RECORDER/CONTROLLER: USER GUIDE
PV
PSP
Holdback applied
Holdback re-
Holdback
applied
Holdback
Program Edit
Segment Number
Segment Name
Type
Ch1TSP
Ch1 Time
Ch1 Holdback
1
Heat init
Ramp
43.358 °C
00:10:30
High
Ch1 Holdback Val
Ch1 PVEvent
Ch1 PVEvent Val
Ch1 User Val
Ch2TSP
Ch2 Time
Ch2 User val
Event 1
Event 2
5.0 °C
Abs High
58 °C
40.0
19.5 °C
00:01:00
33.00
Programmer Display Mode (cont.)
PROGRAM DETAILS (Cont.)
HOLDBACK
Holdback pauses the program (freezes the Programmer setpoint (PSP) and the time remaining parameters) if
the difference between the Process value (PV) and the PSP exceeds a user-specified amount (Holdback
value). The program remains paused until the PV returns to within th e specified deviation.
In ramp or step segments, holdback indicates that the PV is laggi ng the SP by mor e than the specified amount
and that the program is waiting for the process to catch up. In a dwell segment, holdback is used to guaran tee
that a work piece stays at set-point within a specified tolerance for the specified dwell duration
.
SEGMENT CONFIGURATION
Figure 3.4.9e Holdback
Segment NumberSelect the relevant segment for configurat ion .
Segment NameEnter a segment name of up to 20 characters. This name will be truncated on the display
Page 36
Figure 3.4.9f Segment configuration
page if it, together with the program name, are too long to fit the width of the display ar ea.
Issue 9 Mar 15
HA030554
Page 47
nanodac RECORDER/CONTROLLER: USER GUIDE
Programmer Display Mode (cont.)
TypeSelect a segment type. Default is ‘End’.
Ramp. For any program, Ramp segments can be either ‘Ramp Rate’ segments or ‘Ramp
Time’ segments according to the ‘Ramp Style’ setting described above. See also ‘Ch1(2)
Time’ or ‘Ch1(2) Rate’, below.
Dwell. The setpoint is maintained at its current value for the period defi ne d in ‘Dur a tion’
(see below).
Step. A step segment allows a step change to be entered for the target set-points Ch1
TSP and Ch2 TSP.
Wait. A wait segment causes the program to wait for a certain event to occur befo re con-
tinuing. See ‘Wait For’, below.
Go Back. A Go Back segment allows a specifiable number of iterations to be performed
of a group of segments. This could be used, for example, to cycle an entire program by
having a Go Back segment immediately before the end segment an d specifying segment
1 as the ‘Go Back To’ point. Setting ’Cycles’ to ‘Continuous’ causes the program to loop
indefinitely, until interrupted by the user. ‘Nested’ loop s are not permitted i.e. ‘Go Back’ is
not available as a segment type for segments inside an existing GoBack loop.
End. The final segment of a program allows the user to select ‘Dwell’ or ‘Reset’ as the ac-
tion to be taken at the end of the program (see ‘End Type’, below)
Ch1(2) TSPTarget setpoint. The value that Ramp or Step segments seek to attain, for channel 1(2).
Ch1(2) RateFor Ramp Rate segments, this specifies the speed at which the process value ramps to-
wards the target, for Channel 1(2). The ramp units (per second, per minute, per hour) are
set in Ch1(2) ramp units described above.
Ch1(2) TimeFor Ramp Time segments, this allows the user to specify the time to be taken by the seg-
ment for the process value to reach the target.
DurationFor Dwell segments, this allows the entry of the time for which the segment dwells.
Go Back ToFor ‘Go Back’ segments, this defines the number of the segment to which the program is
to return.
CyclesThe number of times the ‘Go Back’ instruction is to be carried out. If set to ‘Continuous’,
the program continues until the user intervenes to stop it.
End TypeAllows the user to select the action to be taken at the end of the program:
Dwell: the set-point is maintained indefinitely and event outputs remain at their configured
state.
Reset: the set-point reverts to the value used by the control loop before the program was
started and the event outputs return to their default states.
Wait ForDigital High: Wait segments can be configured to wait for ‘Wait Digital’ to go ‘high’ before
allowing the program to continue.
Analog 1(2): The segment waits for ‘Wait Analog1(2) to meet an Absolute High or Low,
or Deviation High or Low condition before allowing the program to continue.
Analog Both: As Analog 1(2) above, but waits for both Channels’ conditions to be true
before continuing.
Note: ‘Wait Digital’, Wait Analog 1’ and ‘Wait Analog 2’ parameters are configured in the
Programmer.Set Up menu described in Section 4.8.3.
Ch1 WaitSelect ‘Abs High’, ‘Abs Low’, ‘Dev High’ or ‘Dev Low’ as the wait criterion for channel 1.
Appears only if ‘Wait For’ (above) is set to ‘Analog 1’ or ‘Analog Both’.
Ch2 WaitSelect ‘Abs High’, ‘Abs Low’, ‘Dev High’ or ‘Dev Low’ as the wait criterion for channel 2.
Appears only if ‘Wait For’ (above) is set to ‘Analog 2’ or ‘Analog Both’.
Ch1(2) Wait ValEnter the trigger value for ‘Ch1(2) Wait’
Ch1(2) HoldbackSelect ‘Off’, ‘Low’, High’, or ‘Band’ (see description in Program details above).
Ch1(2) Holdback Val
Ch1(2) PV EventAppear only if ‘PV Events’ have been enabled in the Programmer Features menu (Section
4.8.1). A PV Event (an analogue alarm on the channel PV) is av ailable for each channel
in every segment (excluding Wait and Go Back segment types). The following PV Events
are supported:
Off: The PV Event is disabled
Abs High: The event is triggered when the channel PV exceeds PVEvent Val for the rel-
evant channel.
Abs Low: Triggered when the channel PV becomes less than PVEvent Val for the relevant
channel.
Dev High: This event is triggered when the channel PV exceeds (PSP + PVEvent Val) for
the relevant channel
Dev Low: Triggered when the channel PV becomes less than (PSP - PVEven t Val) for the
relevant channel.
Dev Band - This event is triggered when the channel PV differs from the PSP by more than
the configured deviation value (either above or below)
In the following example, in segment 1 Ch1 PV Event has been configured as Dev Band
and in segment 2 it has been configured as an Abs low:
Figure 3.4.9g PV Events
Ch1 PVEvent ValAppears only if ‘Ch1 PVEvent’ is not ‘Off’. Sets the level at which Ch1 PV Event becomes
active.
Ch2 PVEvent ValAppears only if ‘Ch2 PVEvent’ is not ‘Off’ and if ‘Channels’ is set to ‘2’ in Programmer Set
Up configuration (Section 4.8.3). Sets the level at which Ch2 PV Event becomes active.
Ch1 (2) Event UseWhen PV events become active, they can be used either to Trigger a secondary process
or as a simple analogue alarm on the PV inpu t. Appear s only if the relevant PV Event pa-
rameter is not set to ‘Off’.
Ch1 (2) User ValSpecifies the User Value for this segment, for channel 1(2). Appears only if ‘User Value’
has been enabled in the Programmer Features menu (Section 4.8.1).
The example below (from iTools) shows this parameter wired to the trigger 1 inp ut of the
Custom Messages block, so that, if a User value >0 is entere d, then every time the seg-
Event 1 to 8The number of Events available (Max Events) is defined in Programmer Set Up configu-
ment runs, Custom message 1 is generated.
ration (Section 4.8.3). Enabling an event causes the relevant indicator on the display page
to be illuminated for the duration of the segment. As with ‘User Val’, above, Events can
be wired to the inputs of other parameters if required.
Figure 3.4.9h iTools example showing Ch1 UserVal being used to trigger custom message 1.
FUTURE TREND DISPLAY MODE
If enabled in Instrument.Display configuration (Section 4.1.3), this allows the user to view the actual value of the
PSP alongside the expected value, so the two can be compared to see how the process is performing.
Future trend is an enhancement of the horizontal trend mode , with the display being divided into two parts, with
the instantaneous current value located at the divide, with past trends to the left and the next few program segments to come, to the right.
Note: For the future trend mode to appear, the programmer must be wired to the loop or advanced
loop feature.
Note: Both historic and future trends move from right to left with the present anchored at the screen
centre
Note: The amount of history and of future trending displayed on the screen depends on the trend
interval set in Group.Trend configuration (Section 4.3.1)
Figure 3.4.9i shows a typical future trend display
Page 39
Figure 3.4.9i Future trend display
HA030554
Issue 9 Mar 15
Page 50
nanodac RECORDER/CONTROLLER: USER GUIDE
User
Kiln1.UIPZ
Kiln1 type 2.uipz
kiln2.uipz
furnace1 purge.uipz
Symbol appears
only if a suitable
USB
Selected file
highlighted
Programmer Display Mode (cont.)
PROGRAM STORE
Note: The access levels required for th e ope rations de scr ibe d b elow ar e configur ed in the Pro gram-
mer Set Up menu ‘Prog Edit Access’ and ‘Prog Store Access’ parameters, described in Section 4.8.3.
The program store allows access to the instrument’s local program storage area and to programs stored on a
USB memory stick (if any) and to those stored in a pc (if any), via FTP. Programs may b e saved to (Stored) or
retrieved from (Loaded) from the program store, or they can be copied or deleted.
Selecting any of the program operations (except ‘Delete All’), from the Program Edit page (Engineer access
level required) opens the file explorer page. Figure 3.4.9j depicts this page, with just a couple of example entries after a ‘Load’ operation has been requested.
On entry, use the up/down arrow button to select ‘User’, ‘USB’ or ‘FTP’ (selection highlights yellow), then use
the scroll button to confirm. Use the up/down arrow buttons to select the required file, and then use the scroll
button again to confirm. Other operations are similar.
The file explorer supports 100 entries, which may be directories or files.
Figure 3.4.9j Program store display
Note: A ‘busy’ icon (rotating green flash) appears whilst directory listings are being accessed.
Page 40
HA030554
Issue 9 Mar 15
Page 51
nanodac RECORDER/CONTROLLER: USER GUIDE
Kiln1.uipz
Kiln1 type 2.uipz
kiln2.uipz
furnace1 purge.uipz
User
Ramp
PV
PSP
Status:
Seg Time Left
Ch1 Rate
Reset
00:00:44
01
Mode
Ch1 PSP
Ch1 TSP
Reset
14.3
140.0
Events
Press and hold
the Scroll key for
2 seconds
PROGRAM LOAD - QUICK ACCESS
From firmware version V5.00 and above a quick selection of an internally stored program may be made directly
from the Program Summary page. The programmer must be in Reset. Press and hold the scroll key for 2 seconds. The page will go immediately to the file explorer page with the ‘User’ drive selected and the ‘Operation’
parameter set to ‘Load’. The first program file will be selected (assuming different programs have been configured). Use the Up/Down keys to select the required program followed by the scroll key to load it.
If the selected file cannot be loaded (for example, the pr ogrammer file is for a different number of channels) then
an error message is shown on the file explorer.
The Quick Access to load mode adheres to the access security settings set in configuration mode - Programmer set up (Figure 4.8.3).
Note: Quick load is disabled when in Edit mode. This is indicated by the highlighted parameter
showing the raise/lower symbol to the right of its value.
Page 41
Figure 3.4.9k Program load display
HA030554
Issue 9 Mar 15
Page 52
nanodac RECORDER/CONTROLLER: USER GUIDE
1A
1B
2A
2B
LA
LC
3A
3B
L
N
LB
LC
5A
E
4A
C
1I
1+
12I
2+
23I
3+
4+
4-
34I
USB
1
8
1
2
4
8
C
BCD Switch
PROGRAM LOAD VIA A PROGRAM NUMBER
This feature has been added to firmware versions V5.00 and above.
To allow a program (stored as a file) to be loaded, either via a BCD switch, wir ed to a set of digital inputs, or via
a single comms transaction, it is necessary to prefix the progam name with a program number in the range 01
to 99. For example, 01kiln1.uipz, 01furnace.uipz, 02kiln2.uipz, 03kiln3.uipz etc. The program name can consist of up to 18 characters. Note that program numbers 1 to 9 must be entered as 01 to 09 otherwise they will
not be recognised by the switch or via comms.
On value change of the program number, the first program file with the prefixed number in the instrument’s internal User drive (listed lexographically) will be loaded. In the above example if program 01 is selected, 01furnace.uipz will be loaded, 01kiln1.uipz will not be loaded using the BCD switch or through comms. It can, of
course, be loaded manually.
If no program number is prefixed it is not po ssible to load the progra m via the BCD switch or via comms. It is,
however, still possible to load the program by selecting the file as described in the previous section.
Note: When a BCD switch is turned from its current value to another value, intermediate switch
positions may be seen on the inputs of the BCD function block and could potentially be used
by subsequent blocks wired from the BCD input. A Settle Time parameter has been introduced which will in effect filter out these intermediate values by applying a time in which the
inputs can settle before their converted decimal value is seen on the output parameters of the
block. The Settle Time can be set from 0-10seconds with a default of 0s i.e. no filtering as in
previous firmware versions. The BCD block is described in Section 4.19.
EXAMPLE BCD SWITCH WIRING
Figure 3.4.9l below shows an example of digital input channels soft wired to the BCD function block using
iTools.
Figure 3.4.9l BCD Switch Wiring
Figure 3.4.9m below shows the correspond in g hard wirin g of a BCD switc h.
Page 42
Figure 3.4.9m BCD Switch Physical Wiring
HA030554
Issue 9 Mar 15
Page 53
nanodac RECORDER/CONTROLLER: USER GUIDE
Cycle: 123
Equilibration
120.8°C121.6°C122.4°C
2885mB
Equilibration
Total Cycle
Remaining
Sterilising
00.05.00
00.00.00
00.03.00
00.03.00
Band High
Band Low (red)
Cycle number
Cycle status
Input status beacons
Current input values
If any input is configured ‘Off’
(in Steriliser configuration), it
does not appear in the display,
and the other inputs occupy the
screen width equally.
Input status beacons are black
for inputs configured ‘Off’
Input 1Input 2Input 3Input 4
3.4.10 Steriliser display mode
This display mode appears only if the Steriliser option is fitted and if the display mode has been enabled in the
Instrument Display configuration (Section 4.1.3). Steriliser configuration parameters are to be found in Section
A sterilising cycle cannot be initiated whilst the unit is in Configuration (Engineer) mode.
A steriliser cycle is started by setting its relevant ‘Start’ input to ‘Yes’ for the duration of the cycle. The cycle
waits (status ‘Waiting’) until input 1 reaches its setpoint, at which point the cycle enters the equilibration period
(status ‘Equilibration’), and remains there until all the configured inputs are valid. The cycle then enters the sterilising period and stays in this mode until the sterilising period has expired (status ‘Passed’) or until one of the
inputs becomes invalid (status ’Failed’) for longer than its configured ‘Failure Dwell’ time.
TERMINOLOGY
Holding timeMost operating cycles have a stage in which the load must be exposed to sterilisation con-
Equilibration timeThe holding time (above) is preceded by a period during which, although the sterilising
BandsFor steam and dry heat sterilisers, sterilisation conditions are specified by a sterilisation
BEACONS
There are four input status beacons near the top right hand corner of the display, one for each input.
During equilibration, the beacons are flashing red for inputs that have not attained the Target setpoint, and go
green when the target setpoint is reached, remaining green even if the input value rises above the Band High
value The beacons revert to red if input falls below* the target setpoint.
During sterilisation, the beacons go red for any input whose value rises above Band High or falls below* setpoint
for a duration exceeding the configured ‘Failure Dwell’ period.
Beacons are black for inputs that are configured as ‘Off’.
* ‘rises above’ for input types ‘Falling Pressure’ or ‘Fall Air Detect’
Page 43
Note: The cycle stops (status ‘Failed’) if the trigger source is removed.
ditions for a specified length of time, known as the ‘Holding time’.
condition is present in the chamber, the load has not yet attained that temperature due to
its thermal inertia. ‘Equilibration time’ is defined as the time between the attainment of
sterilisation temperature in the chamber, and the attainment of that temperature in all parts
of the load.
temperature band, defined by a minimum acceptable temperature (known as the sterilisation temperature) and a maximum allowable temperature. A sterilisation band is normally
quoted for each steriliser type.
Issue 9 Mar 15
HA030554
Page 54
nanodac RECORDER/CONTROLLER: USER GUIDE
Cycle start
EquilibrationSterilisation
Overheat
Band High
(Note 3)
Target setpoint
Band Low
(Note 3)
Sterilisation starts when
slowest input reaches setpoint
Equilibration starts when
input 1 reaches setpoint
WaitingWait Start
Steriliser Display Mode (Cont.)
DISPLAYED INFORMATION
CycleA five-digit counter to indicate the total number of cycles started.
StatusWait start: The initial state at power up. This status remains until the first cycle is initiated
Waiting: Waiting for input 1 to reach its target setpoint. The cycle then enters Equilibration.
Equilibration: Currently in the equilibration period, during which the cycle waits until all inputs have reached sterilisation conditions.
Sterilising: Currently in the decontamination phase
Passed: The cycle has completed successfully
Failed: The cycle has failed either through one or more inputs becoming invalid, or be-
cause the ‘Start’ signal was removed.
Test cycle: A test cycle is in progress
RemainingThe sterilising time remaining for the current cycle. Display field is replaced by ‘Target
Time’ (below) when the cycle is not running.
Target timeThe intended sterilisation time. This can be configured by operating the scroll button twice
(once to highlight the field, and again to enter edit mode), and then using the up and/or
down arrows to edit the time. Use the Scroll button again to quit edit mode, and the page
key to ‘unhighlight’ the field.
Replaced by ‘Remaining’ (above) when the cycle is running.
EquilibrationThe equilibration time period for the current cycle
SterilisingThe time for which the load has currently been at sterilisation conditions
Total CycleThe elapsed time since the initiation of the current cycle. This time increments from the
time the cycle is triggered until the time the trigger is removed.
Input valuesTemperature are required in °C; pressure inputs in mBar. If necessary, maths channels
and user values can be used to convert from othe r un its (see ‘Note’ overleaf).
STERILISING CYCLE DIAGRAM
Page 44
Figure 3.4.10b, below, shows a steriliser cycle in diagrammatic form.
Figure 3.4.10b Steriliser cycle
Note: 1. For temperature inputs in most applications, the Setpoint value is the same as the Band
Low value For the sake of clarity, this is not as shown in the figure above.
Note: 2. For the sake of clarity all four inputs in the figure above are shown with the same Band
High, Band Low and Setpoint value. This would not be unusual for temperature units,
but the pressure input would normally have a different set of values from temperature
inputs.
Note: 3. Band High and Band Low are effective only during Sterilisation phase.
Figure 3.4.10c shows a typical steriliser application, with temperature and pressure signals from the sterilisation
chamber being applied directly to the rear terminals of the controller/recorder, and control signals connected
from the controller to both the chamber and the controller/recorder.
Analogue inputs 1 to 3 receive signals from temperature transducers ( typically thermocouples) within the chamber. These inputs are internally connected to channels 1 to 3 respectively, allowing transducer type, ranges,
alarms etc. to be configured (Section 4.4). Inputs are assumed to be degrees Celsius*.
The pressure transducer is connected to channel 4 and can be configured in the same way. The input is assumed to be in milliBar. Other pressure inputs should be converted using virtual channels*.
PV1 to PV4 in the Steriliser configuration is software wired (Section 7) to Ch 1 to Ch4.
Start cycle input and the ‘Running Output’ and ‘Passed Output’ signals are software wired to suitable DIO terminals, for connection to the Controller.
TEST CYCLES
A ‘Test’ cycle is initiated by initiating a 121°C cycle and a 134°C cycle simultaneously. A test cycle allows the
user to check actual performance against expected performance.
Figure 3.4.10c Typical steriliser application
Note: For Fahrenheit inputs, use one virtual channel to subtract 32, and a second to divide the
result by 1.8 (where 32 and 1.8 can be configured as user values). Sim ilar techniques should
be used to convert pressure input units if necessary.
Page 45
HA030554
Issue 9 Mar 15
Page 56
nanodac RECORDER/CONTROLLER: USER GUIDE
Z
TsTemp−
×=10 ion timeSterilisatF0
minutes .10 10 Fval
10
10 -
10
121 - 111
511515=×=×=
minutes 10 10 Fval
10
0
10
121 - 121
151515=×=×=
minutes ..10 10 Fval
10
3
10
121 - 124
925299951151515=×=×=×=
Z
tempTarget-tma
10T Fval Fval
1-tt
×+=
Steriliser Display Mode (Cont.)
F
0
F0 is a means of calculating ‘equivalent time at sterilising temperature’ for temperatures below, at and above
sterilizing temperature, using the equation below.
Where:
Sterilisation timeDepends on the application, typically 15 minutes at Ts = 121°C
TempThe value of the temperature measuring input.
TsDesired Sterilising temperature
ZTemperature interval representing a factor-of-10 reduction in killing efficiency. Z = 10 for
steam sterilising (F
), or Z=20 for dry heat sterilising (FH). Z = 10 for thermal disinfection
0
(A0).
To ensure that steriliser loads which contain materials with different thermal inertias are thoroughly sterilised, a
number of sensors are located withing the load. The F va lue sh ould be calculated using the sen sor clo sest to
that part of the load which has the highest thermal inertia. For maximum accuracy, the temperature sensor
should be calibrated and the input adjust function used to compensate for any inaccuracy found.
F0 calculation examples
For all the examples following, the following are assumed: Sterilisation time = 15 minutes; Sterilisation target
temperature =121°C and Z = 10.
1.For an actual sterilising temperature of 111°C
Which means that 15 minutes at 111°C is equivalent to 1.5 minutes at 121°C
2.For a sterilising temperature of 121°C
Which means that the sterilising temperature is ideal (by definition)
3.For a sterilising temperature of 124°C
Which means that 15 minutes at 124°C is equivalent to nearly 30 minutes at 121°C.
Normally sterilising temperatures would not remain constant at temperatures below or above the target value,
so the above equations are illustrative only of the facts:
1Temperatures below the target have some killing efficacy
2Temperatures above the target value have a greater killing efficiency, so that the sterilising time can be
reduced.
In order to calculate the value dynamically, the instrument uses the equation:
This display page allows the user to display up to 10 of the parameters that appear anywhere in the operator
interface. The parameters can be selected only by using iTools, as described below.
Note: 1. ‘Promote List’ must be enabled (in ‘Instrument.Display’ configuration), be fo re it appears in
the ‘Go to View’ list.
Note: 2. There are more parameters visible in iTools than appear at the operator interface. If non-
operator interface parameters are selected for inclusion in the promote list, they do not
appear.
Note: 3. If parameters which appear only in certain circumstances are selected, then the y appear in
the promote list only when they appear in the Operator interface. For example, a channel
PV is not visible unless that channel is enabled (i.e. it is not ‘Off’).
PARAMETER SELECTION
1.Open iTools and scan for the instrument, (see Section 6).
2.Once the instrument has been found, stop the scan. When th e in strume nt has synchronise d, click on the
‘Access’ button near the top of the display to set the unit into configuration mode (a password may be
required).
3.Click on the ‘+’ sign to the left of the Instrument folder in the tree list (left-most pane) to expand the folder.
Double-click on ‘Promote List’, to display the Promote list in the main pane. The list contains 20 entries, 1
to 10 being for parameters, 11 to 20 being available to the user to add descriptors for parameters 1 to 10
respectively.
4.Expand further folders, as necessary, to access the required parameters, and click-drag these parameters into the promote list. Enter a descriptor for the parameter if the default is not as required. As each
parameter is dragged into the list, it appears in the Promote list.
5.If the parameters are modified at the operator interface, the changes are reflected in iTools, and vice-versa.
6.Once all the parameters have been added, it is re commen ded that the Access bu tton be used to quit configuration mode, as otherwise it will not subsequently be possible to quit from the operator interface.
Figure 3.4.11 shows typical displays.
Page 47
Figure 3.4.11 Promote list displays.
HA030554
Issue 9 Mar 15
Page 58
nanodac RECORDER/CONTROLLER: USER GUIDE
Page sym-
Modbus Master
Chan 1 Tmp
Chan 2 Tmp
VChannel 1 PV
VChanne 2 PV
VChannel 3 Input
Any Channel alarm
Dig In 1
198.3
200.3
2.0
-20.0
122
Active
Off
Connection
status
Parameter status
Read/Write
Parameters
and values
Modbus Master
nanodac
123.123.123.123
26684
1
Ping...
nanodac
123.123.123.120
3rd Party
123.123.123.124
0
0
Ping...
Modbus Master
Chan 1 Tmp
Chan 2 Tmp
VChannel 1 PV
VChanne 2 PV
VChannel 3 Input
Any Channel alarm
Dig In 1
195.6
199.7
4.1
-23.9
13
Active
Off
The list of parameters can be scrolled through
using the up/down arrows. Values being read by
the master are read only, but the user may enter
values for parameters being written by the master, by highlighting the relevant item and using
the scroll key to enter edit mode.
The use of the Page key causes a return to be
3.4.12 Modbus Master display mode
This display mode consists of two pages, as shown below.
Page one opens by default and shows the first eight paramete rs being read from (left pointing arro w) or written
to (right pointing arrow) the relevant slave. These items are configured in the Mod bus Master configuration described in Section 4.9. Hidden parameters may be viewed by operating the scroll key, then using the arrow
keys to scroll through the list. A green arrow means that the item may be edited by the user when logged in.
A pair of animated indicators in the top left-hand corner of the screen show the conne ction status of the
two possible slaves. A green moving ‘streak’ indicates that successful communications are bein g carried
out. A red flashing circle indicates that there is a break in the transmission line or that the slave is switched
off. A grey, non-animated display indicates that that slave has not yet been configured as a part of the
communications link (i.e it is ‘off line’).
A ‘traffic light’ indicator appears to the right of each p arameter. Green indicates that the parameter is being read
from or written to successfully. Orange indicates that a write of the value is pending. Red indicates that there
is an error and that no value is currently being read or written; the value displayed is the last good value read
or written depending on whether the data item is a read or write. If the indicator is black, the parameter is ‘off’.
Operation of the scroll key highlights the page symbol in the top right-hand corner of the screen, and a further
operation of the scroll key calls page two to the screen.
Page two contains the IP address of the Modbus master and of an y slaves connected to it, together with some
diagnostic information, as described in ‘PING DETAILS’ below.
Page 48
Figure 3.4.12a Modbus Master display pages
HA030554
Issue 9 Mar 15
Page 59
nanodac RECORDER/CONTROLLER: USER GUIDE
nanodac
123.123.123.123
26684
1
Ping...
3rd Party
123.123.123.124
0
0
Ping...
3rd Party
123.123.123.124
0
0
Start
3rd Party
123.123.123.124
2
0
Ping...
Slave Name
Slave address
and write transactions
Total no of failed read
and write transactions
Ping initiation field.
Slave 1
Slave 2
}
}
Green: Ping successful
Red: Ping failed
Modbus Master Display Mode (Cont.)
PING DETAILS
The ‘Ping...’ field of the first slave is highlighted by default. As shown above, the down (or up) arrow can be
used to highlight the ‘Ping...’ field of the other slave instead.
Once the relevant ‘Ping...’ field is highlighted, the scroll key can be used to enter edit mode and the up/down
arrow key used to select ‘Start’. A further operation of the scroll key initiates the ‘Ping’ and if this is successful,
a green indicator appears alongside the field (and the text re turns to ‘Ping...’). If the Ping is unsuccessful, then
the indicator is coloured red.
The up or down arrow can now be used to retu rn to slave 1, or the page key can be used to re turn to the previous
parameter display page.
As shown in the figure above, some diagnostic information is given. This includes the total number of successful attempts that the master has made to communicate with the relevant slave, and the total number of failed
attempts. Fuller diagnostic details are to be found in the Modbus Master Communications configuration description (Section 4.9)
The list of parameters can be scrolled
through using the up/down arrows.
Items with green arrows can be edited if the
user is logged in with the correct access level.
See
‘Explicit data’
below
IO Server Identity
Vendor Number
Device Type
Product Code
Revision
Status Word
Serial number
Product Name
45
0
E780
n.nn
0
8D01904C
Nano
Data depends on the slave.
EtherNet/IP Client
3.4.13 EtherNet/IP display mode
This display mode appears only if enabled in Instrument.Display configuration ( Section 4.1.3) and is used to
display the input and output parameters assigned to the Client and Server input and output tables. Paramete rs
which have been configured with descriptors are identified by these descriptors instead of their ‘opc’ names
(shown below).
Page 50
Figure 3.4.13a Typical EtherNet/IP display
HA030554
Issue 9 Mar 15
Page 61
nanodac RECORDER/CONTROLLER: USER GUIDE
Client (nanodac) input table
Server output table
Client (nanodac) output table
Server input table
User Values.1.Value
Channel.1.Alarm1
I/P1
I/P2
I/P3
I/P4
etc.
O/P1
O/P2
O/P3
O/P4
etc.
Out Parameter 1
Out Parameter 2
Out Parameter 3
Out Parameter 4
O/P1
O/P2
etc.
I/P1
I/P2
etc.
In Parameter 1
In Parameter 2
Input Data
Destination
The implicit data
value coming in
from the EtherNet/
IP device will be
copied to this wired
parameter
Output Data
Source
The value coming in
from this wire will be
sent to the EtherNet/
IP device.
The value coming in
from this wire will be
sent to the EtherNet/
IP device.
Values Wired parametersWired parameters
Input Data
Destination
The implicit data
value coming in
from the EtherNet/
IP device will be
copied to this wired
parameter
Ethernet/IP Display Mode (Cont.)
If the EtherNet/IP option has been ordered and enabled, the nanodac can be con figured as either a client (m aster) or a server (slave) (see Section 4.10). The client and se rver displa ys are iden tical exce pt that the configuration area of the client display is more extensive than that of the server display.
Figure 3.4.13a, above shows a typical set of display pages for an EtherNet/IP client.
CONFIGURATION OF IMPLICIT INPUT/OUTPUT TABLES
Configuration of the input and output tables is carried out via iTools drag and drop only by:
a.Entering the parameters to be read by the clie nt into th e se rve r outp ut table.
bEntering the destination parameter into the equivalent location in the client input table.
c.Entering the parameters to be written by the client into the client output table.
dEntering the destination parameter into the equivalent location in the server input tab le.
The example in figure 3.4.13b attempts to show this (using the nanodac as the client) in graphical form, using
just a few parameters (there can be up to 50 in each table)
Note: 1.Channel values from the Server can be ‘wired’ into nanodac Virtual channel inputs (as
shown above) so that they can be traced and/or recorded. In such cases the virtual
channel ‘Operation’ must be set to ‘Copy’ (see Section 4.5.1).
CONNECTION STATUS INDICATOR
A circular status indicator appears in a number of the EtherNet/IP display pages. This indicator can indicate the
following states:
Note: 2.Inputs and outputs would normally be given suitable descriptors (e.g. ‘Reset timer’ instead
of ‘Channel.1.Alarm1’).
Green rotating ‘flash’: the instrument is on line and at least one CIP connection is established.
Green flashing circle: the instrument is on line but no CIP connections have been established.
Red flashing circle: there is a break in the physical conne ctio n be tween the client a nd the server, or the
remote unit is switched off or is initialising.
Page 51
Figure 3.4.13b Input/Output table entries
Issue 9 Mar 15
HA030554
Page 62
nanodac RECORDER/CONTROLLER: USER GUIDE
Synchronised
Not synchronised
Ethernet/IP Display Mode (Cont.)
Adding parameters to the input and output tables can be achieved only through the proprietary software package ‘iTools’, running on a pc. It cannot be configured through the user interface. The following descrip tion assumes that the user is familiar with ‘iTools’. Section 6 of this manual shows how to set up an iTools link to the
unit and the iTools on-line help system and its pdf version (HA028838) should be referred-to as necessary.
Note: the client/server and the pc must all be on the same network.
Once iTools has started up and the ‘Scan’ process has ‘found’ the relevant instru ment,
the scan process should be stopped and the instrument (s) allowed to synchronise.
(The scan may be left to run its course, but the speed at which iTools operates is reduced for the duration of the scan process.)
EXAMPLE
To add Loop 2 Setpoint 2 to Output 4 of the Client Output table.
In the example shown below, the instruments have both synchronised, and the
‘Access’ tool button clicked-on for both instruments to set them into configuration
mode.
With the client selected, expand the EtherNet/IP folder in the Browse list, then
double-click on the ‘ImplicitOutputs’ folder.
Locate and expand the Loop 2 SP folder in the Browse window, and click-drag
SP2 to ‘Output 4’ and release.
Page 52
Figure 3.14.3c Dragging a parameter to the Output table
HA030554
Issue 9 Mar 15
Page 63
nanodac RECORDER/CONTROLLER: USER GUIDE
Service codeClass IDInstance ID
Attribute
HexDecHexDecDecimal
001016A21621-655351
000E14A21621-655351
Ethernet/IP Display Mode (Cont.)
An alternative to the click-drag technique is to r ight click on the require d output (five in the example below), and
select ‘Edit Wire...’ from the context menu that appears. A browse window pops up, allowing the user to navigate to the required parameter. This technique can be used both on p reviously empty inputs or outputs and o n
those previously filled.
Figure 3.4.13d Context menu details
EXPLICIT DATA
As shown in table 3.4.13, when configured as a server, there is only one explicit ap plication object, and that has
the class ID= A2 (162 decimal). The instance ID is the Modbus address of the parameter and the Attribute is
always = 1. Explicit service codes hex10 (decimal 16) and 0E (14) are both supported, for writing and reading
single attributes respectively.
Table 3.4.13 Explicit data specification
When configured as a client, two separate connections are available allowing the user to produ ce two independent explicit read or write messages to different server devices.
Figure 3.4.13e below, shows an example of how to configure an explicit message request. The instance ID and
the data type are taken from the server manufacturer’s data. In this example a read request is configured to
determine the Group recording status of a nanodac server, and it can be seen from table 5.3 that the decimal
modbus address for this parameter is 4150 and the data type is int16. It is this address which is used as the
instance ID.
Once all the information has been entered, the read is requested by setting ‘Send’ to ‘Yes’. The Data field
changes to ‘3’ for this example and from table 5.3 it can be se en that the recording status is ‘Recording enabled’.
Note: The nanodac supports only 16 bit data types for reading and writing of explicit messages.
Tags page appears if ‘Mode’ is set to ‘Client
(Tags)’ in EtherNet/IP configuration (Sect i on
4.10).
Explicit messaging is not possible in tag IO
mode as tag mode needs to consume both
connections for communications with the PLC.
When wired to parameters which have descriptors, the descriptor names appear instead of
the ‘opc’ names (e.g. Loop.1.Setpoint.SP1)
shown here.
nanodac RECORDER/CONTROLLER: USER GUIDE
Page 54
Figure 3.4.13e explicit messaging example
HA030554
Issue 9 Mar 15
Page 65
nanodac RECORDER/CONTROLLER: USER GUIDE
Ethernet/IP Display Mode (Cont.)
USING TAGS
When acting as servers, many PLCs present their data in a tag format instead of implicit data format. For this
reason, when the client is configured as ‘Client (Tags)’, (Section 4.10) 30 input and 30 output tags become available to the user via iTools (figure 3.4.13f).
This allows tag names to be typed in, input tags 1 to 30 being associated with implicit inputs 1to 30 respectively
and output tags 1 to 30 being associated with implicit outputs 1to 30 respectively.
Figure 3.4.13f iTools display showing input tags.
In the example above, the value of the parameter with the tag ‘Channel 1’ will be written to implicit input 1.
Note: 1. Most PLCs have a data buffer limit of 500 Bytes. The total number of bytes being used is
given by the equation: Total number of data bytes = (tag length + 10) × the number of
requested tags.
Note: 2. Input data direction is always to the nanodac:
in server mode input data is written to the nanodac from the client
in client mode, input data is read by the nanodac from the server device.
Note: 3. Output data direction is always from the nanodac:
in server mode output data is written to the client from the nanodac
in client mode, output data is read by the server from the nanodac.
Page 55
HA030554
Issue 9 Mar 15
Page 66
nanodac RECORDER/CONTROLLER: USER GUIDE
Home
Configuration
Go to view
Faceplate cycling (Off)
Operator Notes
Demand Archiving
Log out
History
Enter trend history mode
The down arrow button moves the display backwards in time by
1
/
3
screen-full per operation (assuming that the
current display is not the earliest). See also ‘SEARCH FOR’, below.
The up arrow button moves the display forwards in time by
1
/
3
screen-full per operation (assuming that the cur-
rent display is not the latest). See also ‘SEARCH FOR’, below
The scroll key scrolls through the trend group channels, emphasizing each channel (and displaying its face-
plate) as it is selected.
The page key calls the History Menu, described in Section 3.5.2, below.
Search for
10:31:58 21/09/10
CancelYes
3.5 TREND HISTORY
Entered from the top level menu (Section 3.1), this allows vertical and horizontal traces to be reviewed for Trend
group channels. The amount of data displayed in one screen depends on the ‘Zoom In/Out’ setting in the History
menu (Section 3.5.2) and on the recording interval selected in Group Recording configuration (Section 4.3.2).
It is also possible to enter a time and date to which the history then jumps.
The history display is identical in appearance with the trend display except:
1.History displays can include messages if so configured in the History menu.
2.For horizontal trends, the scale is displayed permanently at the left edge of the display.
Figure 3.5a Top level menu
3.5.1 Navigation
SEARCH FOR
In the history display, holding the up or down arrow key operated for approximately two seconds produces a ‘Search for’ display which allows the user
to enter a time and date. Once a time and date have been entered, ‘Yes’
then causes the history display to jump to that time and date (if such history
exists).
To enter a time and date:
1.Use the up/down arrows to highlight the item to be edited.
2.When highlighted (orange background), operate the scroll button. The highlighted text turns black.
3.Use the up and down arrow keys to scroll to the required va lue for th e fie ld, then oper ate th e scro ll butto n
again. The text goes white.
4.Repeat the above editing process for all the remaining items which are to be edited.
5.Use the up/down keys to select ‘Yes’. The ‘Search for’ window closes, and the history display jumps to
the selected time and date.
Note: 1. If no history exists for the selected time and/or date ‘No History Available’ is displayed.
Note: 2. The time and date format and Daylight Savings Time (DST) effects are as set in the
‘Locale’ area of Instrument configuration. See Section 4.1.2 for further details.
Page 56
Issue 9 Mar 15
HA030554
Page 67
nanodac RECORDER/CONTROLLER: USER GUIDE
Zoom In/Out
Trend
Show Messages
Exit History
0.125 sec
All Points
Off
No
History Menu
3.5.2 History Options Menu
Operating the page key from within a history display, causes the History Options menu to appear.
Figure 3.5.2 History Options menu
PARAMETERS
Zoom In/outAllows the user to select the amount of history displayed on the screen.
TrendSelect either ‘All Points’ or ‘Each Point’.
‘All points’ displays all channels in the trend group, with the first channel emphasized on
the screen and its faceplate displayed. The Scroll button is us ed to select the next channel
in the group.
‘Each Point’ initially displays only the first point in the trace group. The scroll key is used
to cycle through individual group channels in turn.
Show Messages‘Off’ disable the inclu sion of messages in history display. ‘On’ causes messages to ap-
pear, superimposed upon the point traces (vertical trend mode only).
Exit HistorySelecting ‘Yes’ for this item causes a return to the top level menu or to the message sum-
mary page.
Note: Operating the page key from the History menu causes a return to th e history display.
Page 57
HA030554
Issue 9 Mar 15
Page 68
nanodac RECORDER/CONTROLLER: USER GUIDE
ΩΓΕΘΠΣΤ
Press and hold scroll
button for alternative
character set.
3.6 TEXT ENTRY
The user is often required to enter text characters or num bers (when editing operator notes, for exa mple). This
is done using the pop-up keyboards which are displayed when required. When only numerals are required a
special keyboard is presented which contains only numerals.
Figure 3.6 shows the three standard keyboards, along with a ‘scan’ direction for operations of both up arrow
and down arrow keys. To change keyboards, u se the ar row pushb utto ns to high ligh t th e keybo ar d name ( ‘Nu meric’, ‘Symbols’ or ‘Alpha’), and then operate the scroll button.
Generally, to enter text, the required character is highlighted usin g the up and down arrows and the scroll button
is used as an ‘Enter’ key. Once text entry is complete, the Page button is used to confirm the edit (use the down
arrow to select ‘Yes’ then operate the scroll button).
Pressing and holding the scroll button and then immediately operating the up or down arrow, causes the character insertion point to move to the left (down arrow) or to the right (up ar ro w) .
The user can press and hold the scroll key to display variations on certain characters (the letter ‘e’ in the figure).
Once displayed, the up and down arrows can again be used to scroll through auxiliary list, allowing capital letters, and characters with diacriticals (e.g. accents, umlauts, tildes, cedillas) to be selected and entered using
the scroll button.
The backarrow key is used as a back space key - i.e. it deletes the character to the left of the cursor position.
The ‘Del’ key deletes the character to the right of the cursor.
Note: Leading and trailing space characters are automatically removed from text strings
.
3.6.1 Numeric keyboard
As mentioned previously, for functions which can take only numerals, a special numeric
keyboard appears, as depicted in figure 3.6.1.
Figure 3.6 Standard Keyboards
3.6.2 USB keyboard
Text and numeric entry can also be carried out using a USB keyboard as described in Section 8.3.
Entered from the top level menu ( Section 3.1) this allows the recorder configuration to be accessed and ed ited
(‘Engineer’ access level required fo r full ed itin g) .
Caution: Recording is stopped for as long as the recorder login is at Engineer level. This
means that Input/output circuits are switched off during configuration.
As shown in figure 4, below, the recorder configuration is arranged in a number of ‘areas’, each of which is allocated its own sub-section within section 4.
Figure 4 Top level configuration menu
The factory default configuration can be returned-to, if required, by entering a special Engineer password, as
described in Section 4.1.6.
Page 59
Issue 9 Mar 15
HA030554
Page 70
4.1 INSTRUMENT MENU
Instrument
Clock
(section
4.1.1)
Date
Time
Locale
(Section
4.1.2)
Language
Date format
Time zone
DST enable
Display
(Section
4.1.3)
Brightness
Save after
Saver Brightness
Home page
HPage timeout
Vertical trend
Horizontal trend
Future trend
Vertical bar
Horizontal bar
Numeric
Alarm panel
Loop control
Dual loop
Cascade
Programmer
Steriliser
Promote list
Modbus Master
EtherNet/IP
Trend
background
History
background
H.Trend
scaling
Faceplate
cycling
Setpoint colour
Number format
USB auto scan
Info
(Section
4.1.4)
Name
Type
Version
Bootrom
Company ID
Config Rev
Security Rev
Nvol writes
Line Voltage
Wires Free
Upgrade
(Section
4.1.5)
Type
IP Address
Username
Password
Source Path
Initiate
Security
(Section
4.1.6
Engineer
Password
Supervisor
Password
Operator
Password
Feature
Passwords
Comms
Password
OEM Pass
OEM Entry
OEM Status
Input Adjust
(Section
4.1.9)
Select channs
Start IP adjust
Abort
I/O Fitted
(Section
4.1.7
Output Adjus
t
(Section
4.1.10)
Output
Measured o/p
Confirm
Save/Re-
store
(Section
4.1.8)
Select Save or
Restore
nanodac RECORDER/CONTROLLER: USER GUIDE
* CNOMO = Comité de normalisation des moyens de production.
Page 60
HA030554
Issue 9 Mar 15
Page 71
nanodac RECORDER/CONTROLLER: USER GUIDE
Date
Time
DST
Instrument.Clock
4.1.1 Clock
The up and down arrows are used to highlight ‘Date’ (default) or ‘Time’.
To set the date, the scroll button is used to display the numeric keyboard described in Section 3.6.1. The up
and down arrows are used to highlight the relevant numeral or separator (‘/’ or ‘:’) and the scroll key used to
enter it into the display window.
To set the time, the scroll button is operated to enter edit mode, then the up and down buttons are used to scroll
to display a time, say 15 seconds later than the current time. Once the current time matches the display, the
scroll button is pressed to confirm the time and to start the clock.
Figure 4.1.1 Clock menu
The ‘DST’ field appears only If ‘DST Enable’ is selected ‘Yes’, in ‘Locale’ (Section 4.1.2). If the ‘box’ contains
a cross (as shown) then Daylight Saving Time (DST) is not currently active. A ‘tick’ means that the time sho wn
has been advanced by an hour because DST is active.
Page 61
HA030554
Issue 9 Mar 15
Page 72
4.1.2 Locale
English
DD/MM/YY
GMT
Yes
01:00
Last
Sunday
March
02:00
Last
Sunday
October
Language
Date Format
Time Zone
DST Enable
Start Time
Start On
Start Day
Start Month
End Time
End On
End day
End Month
Instrument.Locale
nanodac RECORDER/CONTROLLER: USER GUIDE
Figure 4.1.2 Typical Instrument configuration menu (expanded to show all fields)
LanguageSelect the language to be used for displays etc.
Date formatSelect MM/DD/YY, YY/MM/DD as the required format.
Time ZoneSelect the required offset from GMT (UTC). This setting affects only the displayed time.
Archiving, recording etc. times remain in GMT.
DST EnableDaylight Saving Time enable. Once the selection is enabled, the following (previously hid-
den) fields appear, allowing the start and end dates for Daylig ht Saving Time ( DST) to be
configured. DST affects only the displayed time. Archiving, recording etc. times remain in
GMT.
Start TimeAppears only when ‘DST Enable’ (above) is set to ‘Yes’. Use the up/down keys to scroll
to the required start time.
Start OnSelect ‘Last’, ‘First’, ‘Second’, ‘Third’ or ‘Fourth’ as the required week. Used in conjunction
with the ‘Start Day’ and ‘Start Month’ entries following.
Start DaySelect the day of the week on which DST is to commence.
Start MonthSelect the month in which DST is to commence.
End Time, End On, End Day, End Month
As for ‘Start Time’ etc. above, but specifies the end time and date for daylight savings.
Page 62
HA030554
Issue 9 Mar 15
Page 73
nanodac RECORDER/CONTROLLER: USER GUIDE
70%
7 min
50%
V.Trend
Off
Black
DarkGrey
Hide
Off
Red
Rounded
No
Brightness
Save After
Saver Brightness
Home Page
HPage Timeout
Vertical Trend
Horizontal Trend
Vertical Bar
Horizontal Bar
Promote List
Trend Backgrnd
History Backgrnd
H.Trend Scaling
Faceplate Cycling
Setpoint Colour
Number Format
USB Auto Scan
Instrument.Display
Home page
(always enabled)
Mode disabled
Mode enabled
4.1.3 Display configuration
This allows the user to set display brightnesses and screen saver details, to select a display mode as the ‘Hom e’
page, and to enable/ disable the various display modes. The normal ‘Select, Scroll, Enter’ editing technique is
used as has been previously described.
BrightnessAllows the user to select a normal operating brightness for the screen from 10% to 100%,
Save AfterThe elapsed time (since last button press) before the screen switches from ‘Brightness’ to
Saver BrightnessT he screen saver brightness. Valid entries are 10% to 100% inclusive, in 10% steps. Us-
Home pageAllows any display mode to be chosen as the ‘Home’ page. This is the page that the re-
HPage TimeoutThe elapsed time (since last button press) before the display returns to the home screen.
Vertical TrendThis is the default home page, and its tick is greyed. If this is not th e home page, the tick
Page 63
Figure 4.1.3 Display menu (expanded to show all fields)
in 10% steps.
‘Saver Brightness’. (Off = saver function disabled)
ing a lower power when not ‘in use’ not only saves power, but also increases display life.
Typical screen power consumption is 0.5W at 100%, falling in a linear fashion to 0.05W at
10%.
corder displays at power up, and also the page displayed when the ‘Home’ key is selected
from the top level menu (Section 3.3. The selected display mode (vertical trend in figure
4.1.3) is always enabled in the following display mode enable fiel ds (its ‘tick’ is greyed out
and cannot be edited). See Section 3.4 for a description of the available modes.
(Off = disabled)
can be changed to a cross, by highlighting it and operating the scroll button.
As for Vertical Trend, above. By default some display modes are disabled (grey cross).
In order to enable such display modes the relevant cross is highlighted using the up/d own
arrow buttons, and the scroll button then used to change the grey cross to a white tick.
The tick associated with the selected home page is always grey.
Note: Some display modes are available only if the relevant option is fitted.
Future TrendThis and the a ssocia ted co lour selectio ns ap pear on ly if the Progra mmer o ption is fitted.
See Section 3.4.9 for more details.
Trend BackgroundAllows the user to select black (default), white dark grey or light gray as the ‘chart’ colour.
History Background
H.Trend ScalingAs described in Section 3.4.2, by default, the scale for horizontal trends ap pears at the left
Faceplate cyclingAllows the default faceplate cycling state to be defined as ‘On’ or ‘Off’ (Section 3.3.5)
Setpoint colourThe colour for the setpoint in Control Loop display pages (Section 3.4.7).
Number FormatRounded:
USB Auto ScanIf set to ‘Yes’, bar code data messages are automatically generated and appear on the
There is a new paramter been added to the Instrument. Display list - Number format.
The options are to "Round" or "Truncate" values. On the previous firmware releases of the nanodac, numbers
As above for ‘Trend background’, but for history displays.
edge of the chart for a few seconds before the chart expands leftwards to occupy the scale
area. Setting ‘H.Trend Scaling’ to ‘Permanent’, ensures that the scale remains perma-
nently on display.
Truncated:
display and in the Message list without operator intervention. If set to ‘No’, the Message
appears on the screen for editing and/or confirmation, before being displayed etc. Section
8.2 provides further details.
were truncated (in the same way as the 6000).
From firmware versions V3.01 and above there is an option to allow numbers to be rounded. The reason for
this is driven primarily from a control point-of-view. With truncation, it is quite likely that the PV will look as
though it never settles onto setpoint. The rounding/truncation affects the UI display and MODBUS scaled integers, the underlying numbers are not affected, nor the values saved in the history files. Over MODBUS
comms, all floating point parameters that are read via scaled integer comms will take note of the configured
setting for rounding or truncating and reflect this. On the UI, ALL floating point values rendered will adhere to
the configured setting of rounding or truncating.
Page 64
Issue 9 Mar 15
HA030554
Page 75
nanodac RECORDER/CONTROLLER: USER GUIDE
nanodac
nanodac
2.0
1.8
1280
10
2
Name
Type
Version
Bootrom
Company ID
Config Rev
Security Rev
Instrument.Info
Nvol writes
Line Voltage
Wires Free
339
239.2 v
240
4.1.4 Info menu
Gives information about the recorder hardware and software, and allows the user to enter a descriptor fo r the
instrument. The normal ‘Select, Scroll, Enter’ editing technique, previously described) is used to edit those
fields that are not read only.
Figure 4.1.4 Info menu (expanded to show all fields)
NameAllows the user to enter a desc riptor of up to 20 characters, using the text entry techniques
described in Section 3.6. The number of character s visible in the display mode pages var -
ies according to the number of alarm symbols on display.
TypeNano. Read only display of the instrument model (used by ‘iTools’).
VersionRead only. The software version of the instrument.
BootromRead only. Instrument software Boot ROM version
Company IDRead only. For CNOMO* purposes over Modbus (1280 decimal; 0500 hex).
Config RevRead only. This value is updated, and a message including this value generate d, every
time configuration is quit, if any one or more configuration parameter ha s been ch anged .
Security RevRead only. This number is incremented ev ery time configuration is quit, if any one or more
passwords has been changed, or if the FTP Ser ver username has been changed, o r if the
Comms Enable field has been edited.
Nvol writesNumber of non volatile write operations for diagnostic purposes.
Line voltageThe instantaneous value of the supply voltage applied to the instrument. Used in some
control loop operations.
Wires FreeThis shows the number of wires free to be used. The value takes into account all user wir-
ing whether carried out at the instrument or downloaded from the iTools graphical wiring
editor.
Page 65
HA030554
Issue 9 Mar 15
Page 76
nanodac RECORDER/CONTROLLER: USER GUIDE
Firmware (FTP)
123.123.123.123
anonymous
****
release
No
Upgrade
Server IP Address
Account Username
Account Password
Source Path
Initiate
Firmware (USB)
release
No
Upgrade
Source Path
Initiate
Instrument.Upgrade
Instrument.Upgrade
4.1.5 Upgrade
Caution: 1. Power must not be remove d from the unit whilst upgrade is in progress, as to do
so will cause permanent damage to the unit.
2. For USB upgrades, the memory stick must not be removed whilst upgrade is in
progress or the instrument will be permanently damaged.
This item allows the user to update the instrument firmware, either from a memory stick in the USB socket at
the rear of the unit, or via FTP transfer from a host computer. Firmware up grade files are downloaded from the
recorder manufacturer and transferred to the instrument by memory stick or by FTP transfer. Splash screens
are prepared by the user and transferred using a memory stick. The unit re starts automatically after an upgrade
or splash screen replacement.
UpgradeSelect ‘Firmware (USB)’, ‘Firmware (FTP)’, ‘Bootrom (USB)’ or ‘Splash (USB)’ as the
source of the upgrade.
Server IP AddressFor ‘Upgrade’ = ‘Firmware (FTP)’ only, this field must contain the IP address of the pc
which is to supply the upgrade file.
Account Username For ‘Type’ = ‘Firmware (FTP)’ only, the username set up in the host ftp server
Account PasswordFor ‘Type’ = ‘Firmware (FTP)’ only, the password set up in the host ftp server
Source PathThe name of the directory from which the upgrade file is to be read. This is only the name
of the directory without any path elements (e.g. ’/’) included unless the path is ‘release/
upgrade/files’.
InitiateSelect ‘Yes’ to initiate the upgrade.
CUSTOMISING THE SPLASH SCREEN
‘Splash (USB)’ allows the user to select a new image for the splash screen (i.e. the screen that appears at power
up or restart). When ‘Initiate’ is set to ‘Yes’, the instrument searches the USB device for a file called
‘splash.bmp’ located in the ‘release’ folder. If such a file is found, it is loaded, and the instrument re-starts with
the new image as the ‘splash’ screen. If no file is found , the request is ignored. If the image is not of the correct
type or size, the instrument re-starts with the default splash screen.
The original splash screen is included on the ‘tools’ DVD, so that it can be restored if required.
Rules:
1.This feature is available only with Bootrom versions 2.0 and above.
2.The file must be located in a folder called ‘release’ and the file name must be ‘splash.bmp’.
3.The image must be 320 x 240; 24-bit resolution.
4.The image must be in bitmap (suffix.bmp) format.
5.The image may not exceed 256kB.
Page 66
Figure 4.1.5 Typical Upgrade menus
HA030554
Issue 9 Mar 15
Page 77
nanodac RECORDER/CONTROLLER: USER GUIDE
**********
12345
1232
54321
Enabled
Engineer Pass
Supervisor Pass
Operator Pass
Feature Pass
Feature2 Pass
Feature3 Pass
Comms Pass
Instrument.Security
Appears only if Engineer
Password = reset
**********
Unlocked
No
OEM Pass
OEM Entry
OEM Status
Default Config.
4.1.6 Security menu
This allows the user to enter passwords for all security levels (except logged out), and to enable/disable serial
communications security.
Figure 4.1.6 Security menu
Engineer PassGives access to configuration menus. Set to 100 when despatched, but can be edited
here, if required, by entering an alternative of up to 20 characters (note 1).
If ‘reset’ (case sensitive) is entered as the Engineer Password, the ‘Default Config.’ field
appears allowing the instrument default configuration to be restored (note 2).
Supervisor PassA password (none by default) of up to 20 characters can be entered here to protect Su-
pervisor level access.
Operator PassA password (none by default) of up to 20 characters can be entere d here to protect Op er-
ator level access.
Feature PassThis is a password supplied by the manufacturer to enable the software options (e.g.
Loop, Zirconia block, Toolkit blocks etc.). When applying for this code, the manufacturer
will require the instrument’s MAC address (Network.Interface menu Section 4.2.1) and the
instrument’s firmware Version (Instrument.info menu -Section 4.1.4). The password is
MAC address dependent so that it cannot be used on any other instrument.
Feature2/3 PassSimilar to ‘Feature Pass’ above, but for additional features.
Comms PassEnables/disables password security for external communications (including via iTools). If
set to ‘Enabled’, the Engineer level password will be required if an attempt is made to enter
the configuration menus from a remote pc. If set to ‘Disabled’, then access to configura-
tion can be gained over a communications link, without a password.
If enabled, then entry to configuration mode via the Instrument Mode (IM) para meter must
be completed within 5 seconds of entering the password, or the attempt will fail.
Note: 1. It is recommended that only such char acters as appe ar on the user’s p c keyboard be used
Note: 2. Restoring factory default configuration can also be carr ied out in iTools, using the Engineer
in the Engineer password. The use of other ch ar ac ter s ma ke s it nec ess ar y t o us e
‘Escape’ codes (e.g. Alt 0247 for the ‘÷’ sign) when trying to enter configuration mode from
iTools, for example.
password ‘reset’ and selecting Default Config to ‘Yes’.
Page 67
HA030554
Issue 9 Mar 15
Page 78
nanodac RECORDER/CONTROLLER: USER GUIDE
Security Menu (Cont.)
OEM PassThe configured pass phrase used to enable / disable the OEM security option. This field
is editable whilst the OEM Status is ‘Unlocked’ and the user has ‘Engineer’ access.
OEM entryTo lock or unlock the OEM security feature, the user must enter the pass phrase entered
in ‘OEM Pass’ above. The default passcode is OEM (in capitals).
OEM StatusRead only ‘Locked’ or ‘Unlocked’ status display.
Default ConfigThis field appears only if ‘reset’ has been entered as the Engineer Password. Selecting
‘Yes’ Causes the instrument to restart with default configuration (i.e. the instrument ‘cold
starts’). See note 2 above.
OEM SECURITY
In products that incorporate user wiring, the value of an application may lie more in the user wiring (conne cting
the function blocks together) than in the configuration of the instrument's parameters.
OEM Security allows the user to prevent the application from being cop ied either via comms (by iTools or a third
party comms package) or via the instrument's user interface.
When OEM security is enabled, users are prevented from accessing wiring (for reading or writing) from any
source (comms or user interface), and it is not possible to Load or Save the configuration of th e instrument via
iTools or by using the Save/Restore facility (Section 4.1.8).
From firmware version V5.00 onwards OEM Security is enhanced by providing an option, enabled by a new
parameter ‘Instrument.Security.OEMParamLists. This parameter is available only through iTools and allows
the OEM to:-
1. Make all parameters that are read/write in Engineer access level only, read only when the instrument is
OEM locked AND it is in Engineer access level. It is possible for the OEM to select up to 100 parameters
which are to remain read/write in Engineer access level.
2. Make up to 100 parameters that are read/write in Su pervisor acce ss level, read o nly when the instrument
is OEM locked.
Examples of how to set up OEM security are given in the iTools Section 6.6.10.
Note: The I/O types fitted in locations LALC, LBLC, 4AC and 5AC are always as shown above. The
Page 69
types of I/O fitted in locations 1A1B, 2A2B and 3A3B depends on the options specified at time
of order.
HA030554
Issue 9 Mar 15
Page 80
nanodac RECORDER/CONTROLLER: USER GUIDE
Instrument.Save/Restore
Restore
Complete
Operation
Status
RELEASE
history
FileName.UIC
4.1.8 Save/Restore
This allows the user to save and/or restore instrument clone configurations to a memory stick inserted into the
USB connector at the rear of the unit. The format of the saved/restored files is iTools clone files (*.uic)
Selecting ‘Restore’ presents a list of clone files in the configured directory on the USB device. (In the example
below, the file is located in the basic usb0 directory - it has not been saved to a particular configuration directory.)
When ‘Save’ is selected, the virtual keyboard must be used to enter the filename. If the file already exists on
the USB device, a warning appears offering ‘Cancel’ or ‘Overwrite’ alternatives.
Note: 1. The ability to save and restore is disabled if OEM security is enabled.
Note: 2. Configuration save/restore is available only when the unit is logged into at ‘Engineer’
access level.
Note: 3. During USB cloning (USB save/restore), the priority of modbus slave comms is lowered.
This allows the save/restore process to complete in a minimal time (around 60 seconds).
During this period, modbus slave comms response times will be extended and may result
in the master device timing-out.
Figure 4.1.8 Save/Restore display
OperationSelect ‘Save’ or ‘Restore’. Use the up/down arrow keys to highlight the required .UIC file,
then use the scroll key to initiate the operation.
StatusShows the status of the operation, as fo llow s:
Inactive: Neither saving or restoring a clone file has occurred since the last time the instrument was power cycled.
Complete: Indicates that the cloning process has completed.
Restoring: Restore operation is currently in progress.
Saving: A clone file is currently being saved.
Cold started: A power-cycle of the product occurred whilst a Restore operation was
in progress. The product configuration is unr eliable and has been rese t to factory default.
The ‘Restoring’ and ‘Saving’ status text is accompanied by an animated d isplay (circling green ‘flash’) to indicate
that the operation is in progress.
Page 70
Issue 9 Mar 15
HA030554
Page 81
nanodac RECORDER/CONTROLLER: USER GUIDE
Channel 1
Channel 2
Channel 3
Channel 4
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Unadjusted
Unadjusted
Adjusted
Unadjusted
No
No
Channel 1
Channel 2
Channel 3
Channel 4
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Unadjusted
Unadjusted
Adjusted
Unadjusted
Yes
No
Channel 1
Channel 2
Channel 3
Channel 4
Start IP Adjust
Abort
Instrument.Input Adjust
No
No
4.1.9 Input adjust
Note: 1. Input adjust cannot be applied to input channels with input type of ‘Digital’, ‘Test’ or ‘Off’.
Note: 2. Input adjustments can be carried out only by users logged in as ‘Engineer’ (see Section
3.3.8).
Note: 3. The instrument must be powered for a sufficient time (e.g. 30 minutes) for it to reach ther-
mal equilibrium before an input adjust is performed.
This facility allows the user to compensate for tolerance errors etc. The technique used is to select those channels to which adjust is to be applied, then for each channel to:
aapply a known low level signal (at or close to the low input range value) to the relevant input. When the
recorder reading is steady, press ‘Apply’.
b.apply a known high level signal (at, or close to, th e high inpu t range valu e) to the relevant inp ut. When the
recorder reading is steady, press ‘Apply’.
Figure 4.1.9a shows a typical display when ‘Input adjust’ is selected from the Instrument menu, and Apply adjust
has been selected. As can be seen, channel 3 has previously been adjusted.
Channel 1 to 4Shows the adjust status of each channel
Apply AdjustSelecting ‘Yes’ initiates the adjustment procedure described below.
Remove AdjustSelecting ‘Yes’ initiates the adjustment removal procedure described below.
AbortAllows the user to abandon input adjustment at any point in the procedure.
ADJUSTMENT PROCEDURE
1.As shown in figure 4.1.9b, highlight the ‘Apply Adjust’ field, and operate the scroll key to enter edit mode.
Use the up or down arrow key to select ‘Yes’. Use the scroll button to change Channel 1 ‘cross’ to a ‘tick’
(check mark). Similarly select any other channels which require adjustment.
Page 71
Figure 4.1.9a Input adjust top level display
Figure 4.1.9b Channel adjustment procedure (1)
HA030554
Issue 9 Mar 15
Page 82
nanodac RECORDER/CONTROLLER: USER GUIDE
Channel 1
Channel 2
Channel 3
Channel 4
Start IP Adjust
Abort
Instrument.Input Adjust
Yes
No
Low Target Value
Confirm Low
Channel 1 Value
Abort
Instrument.Input Adjust
0.00
Yes
0.21
No
High Target Value
Confirm High
Channel 1 Value
Abort
Instrument.Input Adjust
10.00
Yes
9.79
No
Channel 1
Channel 2
Channel 3
Channel 4
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Adjusted
Unadjusted
Adjusted
Unadjusted
Yes
No
Channel 1
Channel 2
Channel 3
Channel 4
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Adjusted
Unadjusted
Unadjusted
Unadjusted
Yes
No
Channel 1
Channel 2
Channel 3
Channel 4
Remove IP Adjust
Abort
Instrument.Input Adjust
Yes
No
Input Adjust (Cont.)
ADJUSTMENT PROCEDURE (Cont.)
2.Highlight the ‘Start IP ‘Adjust’ field and use the scroll and up/down arrow to select ‘Yes’. Use the scroll
key again to enter the low value adjust page.
3.Apply the known low value and wait for the value to stabilise. Enter the ‘Low Target Value’ (the value that
the recorder is to read for the applied input). When all is steady, use the scroll and up/down arrow to set
the ‘Confirm Low’ field to ‘Yes’, then operate the scroll button again.
Figure 4.1.9c Channel adjustment procedure (2)
4.The display changes to the high value adjust page.
5.Apply the known high value and wait for the value to stabilise. Enter the High Target Value (the value that
the recorder is to read for the applied input). When all is steady, set ‘Confirm High’ to ‘Yes’.
Figure 4.1.9d Channel adjustment procedure (3)
REMOVAL PROCEDURE
1.Set ‘Remove Adjust’ to ‘Yes’ and operate the scroll button.
2.Use the scroll and up/down arrow buttons to change the required channel icons from crosses to ticks.
3.Select Remove IP Adjust to ‘Yes’ and operate the scroll key. The adjustment is removed from all selected
channels without further confirmation.
Page 72
Figure 4.1.9e Channel adjustment removal
HA030554
Issue 9 Mar 15
Page 83
nanodac RECORDER/CONTROLLER: USER GUIDE
Input on Channel
Channel 1
Channel 2
Channel 3
Channel 4
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Primary
Unadjusted
Unadjusted
Unadjusted
Unadjusted
No
No
Input on Channel
Channel 1
Channel 3
Apply Adjust
Remove Adjust
Instrument.Input Adjust
Secondary
Unadjusted
Unadjusted
No
No
Only those channels with ‘Type’ set to ‘Dual mA’,
‘Dual mV’ or ‘Dual T/C’ appear in the list of secondary channels. In this example, only channels 1 and
3 are configured as dual input. (See section 4.4.1
for channel Type configuration.)
Input Adjust (Cont.)
DUAL INPUT CHANNELS
For the dual input channel option, input adjust is carried out as described above, except that for any channel
where dual inputs are configured, the user must initiate adjustment to prima ry and secondary inputs separately.
As shown in figure 4.1.9f, a new field ‘Input on Channel’ is introduced for this purpose.
Figure 4.1.9f Input adjust top level display (dual input channels)
For primary inputs, all four channels are included in the list and can therefore be selected for adjustment. For
secondary inputs, only those channels which have been configured as dual input are included.
Page 73
HA030554
Issue 9 Mar 15
Page 84
nanodac RECORDER/CONTROLLER: USER GUIDE
DC Output 3A3B
DC Output 2A2B
Apply Adjust
Remove Adjust
Instrument.Output Adjust
Unadjusted
Unadjusted
No
No
1A1B and 2A2B can be configured only as
mA outputs.
3A3B can be configured as mA or Volts.
See Section 4.13 for configuration details.
Output
Measured Output
Confirm Low
Abort
Instrument.Output Adjust
2V
2.000
No
No
Output
Measured Output
Confirm High
Abort
Instrument.Output Adjust
10V
10.000
No
No
DC Output 3A3B
DC Output 2A2B
Apply Adjust
Remove Adjust
Instrument.Output Adjust
Adjusted
Unadjusted
No
No
4.1.10 Output adjust
This item appears only if one or more of I/O type DC Output is fitted and allows the user to compensate for
tolerance errors etc. in connected equipment.
Figure 4.1.10a Output adjust initial display
ADJUST PROCEDURE
1.Highlight the ‘Apply Adjust’ field, and operate the scroll key to enter edit mode. Use the up or down arr ow
key to select the required output and confirm with the scroll key. The output adjust page appears for the
low point.
2.Measure the output at the required point, and enter this value in the ‘Measured Output’ field using the text
entry techniques described in Section 3.6. To skip this stage go to step 3.
3.Set ‘Confirm Low’ to ‘Yes’. The output adjust page appears for the high point.
4.Measure the output at the required point, and enter this value in the ‘Mea su re d Output ’ field as descr ibed
for the low point. To skip this stage go to step 5.
5.Set ‘Confirm High’ to ‘Yes’. The output adjust initial display reappears, with the word ‘Adjusted’ in the relevant DC Output field.
Note: 1 The figures above show the displays when the DC output is set to ‘Volts’ (Section 4.13) (3A3B
Note: 2. ‘Abort’ cancels operations so far and returns to the output adjust initial display (figure 4.1.10a).
ADJUST REMOVAL
In the output adjust initial display (figure 4.1.10c) highlight the ‘Remove Adjust’ field, and operate the scroll key
to enter edit mode. Use the up or down arrow key to select the required output and confirm with the scroll key.
The output adjustment is removed, without confirmation. The initial display returns to ‘Unadjusted’ as in figure
4.1.10a.
Page 74
Figure 4.1.10b Low and High adjust point displays
only). The mA displays are similar, but the fixed low and high values are 4mA and 20mA
respectively
Figure 4.1.10c Adjusted display
HA030554
Issue 9 Mar 15
Page 85
nanodac RECORDER/CONTROLLER: USER GUIDE
Interface
(Section 4.2.1)
MAC address
Client Identifier
IP type
IP address
Subnet mask
Gateway
SNTP Enable
SNTP Server
Archiving
(Section 4.2.2)
Media size
Media free
Media duration
Rate
Destination
File format
On media full
Remote path
Primary server
Primary user
Primary password
Secondary server
Secondary user
Secondary password
Trigger
Period
FTP Server
(Section 4.2.3)
User name
Password
Modbus
(Section 4.2.4)
Prefmaster IP
Address
Input timeout
Unit ID Enable
Serial Mode
Time Format
Pref Master Conn
Response time
Master Conn 2
Response time
Master Conn 3
Response time
Master Conn 4
Response time
Network
00:0A:8D:01:90:00
01000A8D019000
DHCP
123.123.123.123
255.255.248.0
234.234.234.234
Yes
192.168.111.123
MAC
Client identifier
IP Type
IP Address
Subnet Mask
Gateway
SNTP Enable
SNTP Server
Network.Interface
4.2 NETWORK MENU
4.2.1 Interface
This area of configuration allows the user to set up an IP address for the instrument, either by typing one in
(Fixed), or automatically (DHCP), assuming a DHCP server is running.
Page 75
Figure 4.2.1 Network Interface menu
MACRead only. Media Access Control. A unique address for each instrument, entered at the
factory.
Client IdentifierThe client identifier is a unique id used by DHCP servers th at implement optio n 61. Each
nano product will have a unique ID built up from its MAC address. If the DHCP server is
configured to use option 61, then it will use this id instead of the MAC address to assign a
dynamic IP address.
IP TypeIf ‘Fixed’, the user needs to enter an IP address and Subnet Mask in the following fields,
IP AddressRead only if ‘IP Type’ = ‘DHCP’.
Subnet MaskRead only if ‘IP Type’ = ‘DHCP’.
and a Gateway address if required.
If ‘DHCP’ the subsequent fields become read only, with the entries automatically generated by the DHCP server. When set to DHCP, it takes several seconds before the IP address is obtained from the DHCP server.
If ‘IP Type’ = ‘Fixed’, the user may enter an IP address (IPV4 dot notation). This would
normally be supplied by the user’s IT department, or from the Network supervisor.
If ‘IP Type’ = ‘Fixed’, this sets a range of IP addresses that can be accessed. Normally
supplied by the user’s IT department, or from the Network supervisor.
HA030554
Issue 9 Mar 15
Page 86
nanodac RECORDER/CONTROLLER: USER GUIDE
GatewayRead only if ‘IP Type’ = ‘DHCP’.
If ‘IP Type’ = ‘Fixed’ this allows the user to enter a gateway address for use when the unit
is to communicate outside the local network. Normally supplied by the user’s IT department, or from the Network supervisor.
SNTP EnableSelect ‘Yes’ to allow time synchronisation from a Simple Network Time Protocol (SNTP)
server to be enabled. When enabled the instrument time is updated every 15 minutes.
SNTP always works using UTC/GMT. Time zones are handled separa te ly.
SNTP is a protocol that allows clients on a TCP/IP network to synchronise the instrument
clock with that of a server - port number 123. nanodac can act only as a client.
Servers such as Microsoft ‘TimeServ’ cannot be used with the nanodac beca use they are
not SNTP servers.
SNTP ServerThe IP address of the SNTP Server. This only appears if the SNTP server is enabled.
If ‘IP Type’ is set to ‘DHCP’, the SNTP Server address is automatically assigned. Although
this address can be altered it will be overwritte n once the instrument is power cycle d. The
SNTP address should only be entered manually if ‘IP Type’ is set to ‘Fixed’.
For a description of SNTP alarms see Section 3.2.2.
Page 76
HA030554
Issue 9 Mar 15
Page 87
nanodac RECORDER/CONTROLLER: USER GUIDE
1907.46 MB
1902.90 MB
763.77 Days
Automatic
FTP server
Binary (UHH)
Overwrite
Media Size
Media Free
Media Duration
Rate
Destination
File Format
On Media Full
Network.Archiving
/archive
123.123.123.123
history
******
234.234.234.234
anonymous
****
No
None
Remote Path
Primary Server
Primary User
Primary Password
Sec. Server
Sec. User
Sec. Password
Trigger
Period
CSV Date Format
CSV Tab Del
On Media Full
Remote Path
Primary Server
Primary User
Primary Password
Sec. Server
Sec. User
Sec. Password
Trigger
Period
Text
No
Overwrite
/archive
123.123.123.123
history
******
234.234.234.234
anonymous
****
No
None
Monthly
USB
Both
Yes
No
No
Yes
Rate
Destination
File Format
CSV Values
CSV Messages
CSV Headers
CSV Headings
Network.Archiving
Remote with Binary file format
Local with CSV files included
4.2.2 Archiving
This area of configuration is used to set up the parameters for use during unattended archiving. Some of the
fields appear only if other fields are set to a particular value. For example, the CSV fields appear only if ‘File
Format’ is set to ‘CSV’ or to ‘Both’.
The archived data is not removed from the flash memory of the instrument. When the flash memory is full, new
data causes the oldest file(s) to be discarded.
Note: For remote archiving, the host computer must be se t up to respond to ‘pings’. This is because
the nano pings the host whilst establishing connection, and if it does not receive a response
the archive attempt fails.
Media SizeAppears only for File Format = ‘Binary (UHH)’. A read only value showing the capacity of
Media FreeAppears only for File Format = ‘Binary (UHH)’. A read only value showing the space re-
Media DurationAppears only for File Format = ‘Binary (UHH)’. A read only value showing the time it will
the memory stick inserted in the USB port at the rear of the unit. Shows zero if no memory
stick is present.
maining in the memory stick inserted in the USB port at the rear of the unit. Shows zero
if no memory stick is present.
take to fill the Memory stick if the recorder configuration remains unchanged.
HA030554
Issue 9 Mar 15
Page 88
nanodac RECORDER/CONTROLLER: USER GUIDE
RateAllows the user to specify the frequency at which the contents of the Flash memory are
archived to the USB port or, via FTP, to a pc. Scrollable settings are:
None: Automatic archiving is disabled. Any archiving must be initiated by the user
using Demand Archiving, as described in Section 3.3.7.
Hourly: Archive occurs on the hour, every hour.
Daily: Archive initiated at 00:00* each day
Weekly: Archive is initiated at midnight* every Sunday
Monthly: Archive is initiated at 00:00* on the 1st of every month.
Automatic: The recorder selects the least frequent of the above archive periods which is
guaranteed not to lose data as a result of the in ternal flash memory’s ru nning
out of space.
Note: * Archive times are not adjusted for daylight saving time (DST). Thus, if the archive is set to
‘Daily’, ‘Weekly’ or ‘Monthly’, then during summer time, the archive will be triggered an hour
late (i.e at 01:00 hours instead of midnight).
DestinationSelect ‘FTP Server’ for archive to a remote pc, or ‘USB’ to archive to the USB port device.
File formatSelect ‘Binary (UHH)’ ‘CSV’ or ‘Both’.
Binary (UHH):
A proprietary format used by the instrument that needs other software (e.g. Review’, to interpret the data before it can be presen ted in spreadsh eets etc. Bina ry
files have the extension ‘.uhh’.
CSV: This format is a standard open-file format for numeric data. A simple ASCII-based
format, it is readable by a wide range of pc applications as well as being suitable for
direct import into many commercial databases. CSV files have the extension ‘.csv’.
Both: Archiving includes both .uhh and .csv files.
Note: .CSV is ASCII based and cannot interpret Unicode characte rs. For this reason, some charac-
ters available to the user will not be displayed correctly in .csv files.
CSV ValuesAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’. If ‘Yes’ is selected, then process
values are included in the file (see figure 4.2.2b for details).
CSV MessagesAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’. If ‘Yes’ is selected, then messages
are included in the file (see figure 4.2.2b for details).
CSV HeadersAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’. If ‘Yes’ is selected, then Header
details are included in the file (see figure 4.2.2b for details).
CSV HeadingsAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’. If ‘Yes’ is selected, then column
headers are included in the file (see figure 4.2.2b for details).
CSV Date FormatAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’. Allows ‘Text’ or ‘Spreadsheet’ to be
selected. Text causes a time/date to appear in the spreadsheet. ‘Spreadsheet Nu’
displays the number of days since December 30th 1899. The decimal part of the number
represents the latest six hours. For example: DDD--- --DD.25 represents 06:00 hours and
DDD--- --DD.5 represents 12:00 hours. Spreadsheet Numeric format is more easily
interpreted than ‘Text’ by some spreadsheet applications.
CSV Tab DelAppears only if ‘File Format’ is set to ‘CSV’ or ‘Both’.
CSV (Comma Separated Variables) does not always use commas as separators. For
example, in some countries the decimal point is represented by a full stop (period), whilst
in others a comma is used. In order to avoid confusion between a comma as a decimal
point and a comma as a separator, a different separator can be used. This field allows
the ‘tab’ character (^t) to be used instead of a comma.
On Media FullFor ‘Destination’ = ‘USB’ only, this allows the user to select ‘Overwrite’ or ‘Stop’ as the
action to be taken when the memory stick is full. ‘Overwrite’ causes the oldest data to be
discarded from the memory stick to make room for newer data. ‘Stop’ inhibits archiving
activity.
Page 78
HA030554
Issue 9 Mar 15
Page 89
nanodac RECORDER/CONTROLLER: USER GUIDE
Click/drag separator
to edit field width
Right click, then:
Format cells...
select ‘time’ as number category
Select time/date ‘type’ as required.
Include messages
Include values
Include column
headings
Include header
details
Remote PathLeft blank if the archive destination is the home folder. If the destination is to a subfolder
within the home folder, then the name of the subfolder is entered here, preceded by a ‘/’
character (e.g. ‘/history’).
Primary ServerAllows the user to enter the IP address for the pc to be used as the primary FTP server.
Primary User/Password
These are the Login name and password of the remote host a ccount, assigned either by
the Network administrator, or set up in the ‘Guest’ account of the remote host’s ‘FTP
server’ or ‘User Manager’ configuration.
Sec. Server/user/password
As Primary server details above, but for the seco ndary FTP server used when the primary
is not available for any reason.
TriggerThis parameter can be ‘wired’ to, say, an alarm going active, or a digital input, to allow an
archive to be triggered remotely. Can also be set to ‘yes’ manually.
PeriodAppears only if ‘Trigger’ is wired (Section 7). Allows a period of history to be selected for
archiving when ‘Trigger’ goes ‘true. Selections are: None, Last Hour, Last Day, La st
Week, Last Month, All, Bring to Date. (‘Last Month’ archives the last 31 days of history.)
4.2.3 FTP Server
This area of configuration allows the user to enter the Username and Passwor d used to acce ss the in strument
from a remote FTP client.
Page 79
Figure 4.2.2b CSV data example
HA030554
Issue 9 Mar 15
Page 90
nanodac RECORDER/CONTROLLER: USER GUIDE
123.123.123.123
1
0 sec
Instrument
Modbus Slave
Seconds
123.123.123.123
PrefMaster IP
Address
Input Timeout
Unit ID Enable
Serial Mode
Time Format
PrefMaster Conn
Network.Modbus
0
0.0.0.0
0
0.0.0.0
0
0.0.0.0
0
0.0.0.0
0
Response Time
Master Conn 1
Response Time
Master Conn 2
Response Time
Master Conn 3
Response Time
Master Conn 4
Response Time
4.2.4 Modbus TCP
This allows the user to configure the recorder so as to allow it to communicate using Modbus Tran smission Control Protocol.
PrefMaster IPThe IP address of the relevant Modbus master. The Preferred master is guaranteed to
AddressThe Modbus address for this slave. This address must be unique for the network to which
Input TimeoutAllows a value of between 0 and 3600 seconds to be entered to set the timeout period for
Unit ID EnableEnables/Disables the checking of the Modbus TCP unit identity field.
Serial ModeSlave communications via the side mounted configuration port interface (CPI) clip (for
Time FormatAllows the user to choose milliseconds, seconds, minutes or hours as the time format.
PrefMaster ConnRead on ly. Shows the IP address of the preferred master, when connected.
Response TimeRead only. Shows the response time for a single communications request to the relevant
Master Conn 1 to 4 Read only. Shows the IP addresses of any other masters connected to this recorder.
Page 80
be able to connect, even if all slave connections (max. = 4 for TCP) are in use.
it is attached. The recorder will respond to this address and to Address 255.
modbus input channels. If a modbus input is not written to within this period the value of
the channel is set to -9999.0 with a 'No Data' status. A value of 0 disables the comms
inactivity timeout feature.
StrictThe Modbus TCP Unit Identity Field (UIF) does not have to match the instrument ad-
LooseThe Modbus TCP Unit Identity Field (UIF) does not have to match the instrument
InstrumentThe Modbus TCP Unit Identity Field (UIF) must match the instrument address
iTools use.) Parameters: Baud rate 19,200; Parity = none; Number of data bits = 8; Number of stop bits = 1; no flow control. Can be set to ‘Modbus Slave’ or ‘Off’. The unit must
be restarted before any change takes effect.
Sets the resolution for the reading and writing of time format parameters.
master.
Figure 4.2.4 Modbus TCP configuration menu
dress. The instrument responds only to Hex value FF in the UIF. iTools finds
this instrument only at location 255, and then stops scanning.
address. The instrument responds to any value in the UIF
or no response will be made to messages.
HA030554
Issue 9 Mar 15
Page 91
nanodac RECORDER/CONTROLLER: USER GUIDE
Group 1
0.25 sec
10
Channel1
Channel2
Channel3
Channel4
Descriptor
Interval
Major Divisions
Point1
Point2
Point3
Point4
Group.Trend
Point5
Point6
No Trend
VirtualChan1
4.3 GROUP CONFIGURATION
Group configuration is separated into two areas, one which defines trending characteristics (for display channels) the other defining the recording characteristics for saving data to the Flash memory ready for archiving.
4.3.1 Group Trend configuration
This allows the user to define which points are to be trace d on the disp lay and at what interval , and also allows
the number of chart divisions to be set up. Figure 4.3.1 shows a typical configuration page.
Note: The background chart colour is set up as a part of Instrument Display configuration (Section
4.1.3)
Figure 4.3.1 Group Trend Configuration
DescriptorAllows the user to enter a descriptor (20 characters max.) for the group.
IntervalThe trending interval which defines how much data appears on one screen height or width.
A number of discrete intervals can be chosen between 0.125 seconds to 1 hour. The selection should be made according to how much detail is required, and how much data is
to be visible on the screen.
Major DivisionsAllows the user to select the number of divisions into which the scale is divided and how
many gridlines are displayed. Setting the value to 1 results in just the zero and full scale
values appearing. Setting the value to 10 (the maximum) results in a scale with zero, full
scale and nine intermediate values appearing, with associated grid lines.
Point1 to Point6Allows the user to select which channels and virtual channels are to be traced. The max-
imum number of traces is six.
Page 81
Issue 9 Mar 15
HA030554
Page 92
nanodac RECORDER/CONTROLLER: USER GUIDE
50.00 MB
17.06 Days
Yes
1 sec
Normal
Yes
Yes
Flash Size
Flash Duration
Enable
Interval
UHH Compression
Channel 1
Channel 2
Group.Recording
Channel 3
Channel 4
VirtualChan 1
VirtualChan 2
VirtualChan 30
Suspend
Yes
Yes
Yes
No
No
No
4.3.2 Group Recording configuration
Similar to Trend configuration, above, but for saving the data to Flash memory history files. Each point can
individually be enabled or disabled for recording, or recording can be disabled for the whole group.
Figure 4.3.2 shows a typical page.
Flash SizeRead only. Shows the size of the Flash memory fitted in MB.
Flash DurationRead only. Shows the time it will take to fill the Flash memory if the recorder configuration
Enable‘Yes’ enables group recording so that all points set to ‘Yes’ are stored in the recorder’s
IntervalDefines the rate at which data is saved to the recorder’s Flash memory. The value affects
UHH CompressionSelect ‘Normal’ or ‘High’. ‘Normal’ compresses the data, but still provides an exact copy.
Channel 1 to VirtualChan 30 (see note 2, below)
SuspendIgnored unless the user has wired to this field. If wired then when set to 'No' recording is
Note: 1. Where very high values are involved, su ch as in some totaliser values, ‘High’ compression
Note: 2. Virtual channels 1 to 15 are included in the standard build. Chan nels 16 to 30 are included
Figure 4.3.2 Group trend recording configuration
remains unchanged.
flash memory. ‘No’ disables group recording.
how much trace history appears on the screen in trend history mode.
‘High’ compresses more, but values are saved only to 1 part in 10
8
resolution. See also
note 1, below.
Read only (greyed ‘yes’) for points being trended, (these are automatically reco rded). For
non-trending points the user may enable or disable each point individually.
active, when set to 'Yes' recording is paused.
may cause the value displayed at the recorder, and held in the history file , to be incorrect.
The problem may be resolved by changing to ‘Normal’ compression, or, in the case of a
totaliser, by re-scaling it (for example from MegaWatt hours to TeraWatt hours).
only if the Modbus Master and / or EtherNet/IP option is fitted.
Page 82
HA030554
Issue 9 Mar 15
Page 93
nanodac RECORDER/CONTROLLER: USER GUIDE
Main
(Section 4.4.1)
Descriptor
Type
PV
Status
IP adjust state
Resolution
Units
Test signal
Input low/high
Shunt value
Linearisation type
Range low/high
Scale low/high
Offset
CJ type
Filter
Sensor break type
Fault Response
Sensor break value
Measured value
Internal CJ Temp
Trend
Section 4.4.2)
Colour
Span low
Span high
Alarm 1/2
Section 4.4.3)
Type
Status
Threshold
Hysteresis
Latch
Block
Dwell
Acknowledge
Active
Inactive
Not acknowledged
Acknowledgement
Channel
N
Select channel number
4.4 INPUT CHANNEL CONFIGURATION
Page 83
Figure 4.4 Channel configuration menu
HA030554
Issue 9 Mar 15
Page 94
nanodac RECORDER/CONTROLLER: USER GUIDE
Channel 1
Thermocouple
197.35
Good
Adjusted
2
°C
Descriptor
Type
PV
Status
IP Adjust State
Resolution
Units
Channel.1.Main
Triangle 5 Hr
0
10
2.49
Type K
0.00
100.00
°C
0.00
100.00
0.000
External
0.00
1.0 sec
Break High
Drive Low
1%
0.2
35.1
Test Signal
Input Low
Input High
Shunt
Lin Type
Range Low
Range High
Range Units
Scale Low
Scale High
Offset
CJ Type
Ext CJ Temp
Filter
Sensor Break Type
Fault Response
Sensor Break Val
Measured Value
Internal CJ Temp
4.4.1 Channel Main
This section describes all possible menu items, but it should be noted that some items are context dependent
(e.g. Cold Junction settings appear only for Type = ‘Thermocouple’).
Channels one to four in the configuration relate to An In 1 (terminals 1I, 1+ and 1-) to An In 4 ( terminals 4I, 4+
and 4-) respectively - see figure 2.2.
Page 84
Note: For the sake of completeness, the figure above shows all possible fields, even though
many are mutually exclusive. For example, ‘Test signal’ appears only when ‘Test’ is
selected as Type. It would never appear when Type = thermocouple (as shown). Similarly, ‘Shunt’ would appear only for Type = mA.
Figure 4.4.1a Channel main menu (expanded)
HA030554
Issue 9 Mar 15
Page 95
nanodac RECORDER/CONTROLLER: USER GUIDE
Channel Main (Cont.)
DescriptorAllows a (20 character max.) descriptor to be entered for the channel. Some thought
should be given to ensure that the descriptor is mea nin gf ul be ca us e in som e disp lay
screens it is truncated. For example, ‘Furnace 1 area 1’ and ‘Furnace 1 area 2’ might both
appear as ‘Furnace 1 a’ and thus be indistinguishable from one another, except in
background colour.
PVRead only. Displays the current value of the channel.
StatusRead only. Shows the channel status as one of: ‘Good’, ‘Channel Off’, ‘Over range’,
‘Under range’, ‘HW error’, ‘Ranging’, ‘HW (capability) exceeded’.
PV2Read only. For dual inputs only, displays the current value of the secondary input.
Status2Read only. For dual inputs only, shows the secondary input status (as ‘Status’ above).
IP Adjust StateAppears only for channels which have been included in the ‘Adjust Input’ procedure
described in Section 4.1.9.
IP Adjust State2As ‘IP Adjust State’, above but for secondary channels.
ResolutionAllows the number of decimal places to be defined for the channel. Valid entries a re zero
to six.
UnitsAllows a units string of up to five characters to be entered.
TypeAllows the user to select an input type for the channel. Available selections are: ‘Off’,
‘Thermocouple’, ‘mV’, ‘V’, ‘mA’, ‘RTD’, ‘Digital’, ‘Test’ or ‘Ohms’. If the Dual Input option
is fitted, Dual mV, Dual mA, Dual T/C (if enabled) are also available.
Note: If Dual T/C is selected then it is essential that the secondary T/C input is field calibrated
using the Input Adjust procedure (Section 4.1.9)
Test signalAppears only if ‘Test’ is selected as ‘Type’. Allows either a sinusoidal or a triangular
waveform to be selected at one of a number o f cycle time s between 40 seconds a nd five
hours.
Input Low*For Type = mV, Dual mV, V, mA, Dual mA or Ohms, the lowest value of the applied signal
in electrical units.
Input High*As ‘Input Low’, but the highest value of the applied signal in electrical units.
Shunt valueFor mA and Dual mA input types only, this allows the value of the shunt resistor (in Ohms)
to be entered. The recorder does not validate this value - it is up to the user to ensure that
the value entered here matches that of the shunt resistor(s) fitted. For Dual mA input type,
both primary and secondary inputs must have independent shunts each of the same
value.
Lin typeLinear, Square root, x3/2, x5/2, User Lin.
Thermocouple types (alphabetical order): B, C, D, E, G2, J, K, L, N, R, S, T, U, NiMo/NiCo,
See Appendix A for input ranges, accuracies etc. asso ciated with the above thermoco uple
and RTD types. See Section 4.14 for details of user linearisations.
Range Low*For thermocouples, RTDs, User linearisations and retransmitted signals only, the lowest
value of the required linearisation range.
Range High*For thermocouples, RTDs, User li ne arisa tio ns and re tr ansmitted sig nals only, the
value of the required linearisation range.
Range UnitsFor thermocouples only and RTDs, Select °C, °F or K.
Scale Low/HighMaps the process value to (Scale High - Scale Low). For example, an input of 4 to 20mA
may be scaled as 0 to 100% by setting Scale low to 0 and Scale High to 100.
Scale Low2/High2As ‘Scale Low/High but for the secondary input (PV2).
OffsetAllows a fixed value to be added to or subtracted from the process variable.
highest
Page 85
HA030554
Issue 9 Mar 15
Page 96
nanodac RECORDER/CONTROLLER: USER GUIDE
Input
3x
Input filter
Instrument
Response
Note: * See Section 4.14 for details of the configuration of Range High/ Lo w an d In put High /L o w
when ‘Type’ = User 1 to User 4
Offset2The nature of the secondary input results in an offset being introduced into the process
variable value.
For mA inputs this offset is removed automatically, without user intervention.
For mV inputs the offset depends on the value of the voltage source impedance and is
equal to 199.9μV/Ω. This offset can be compensated for either by using this Offset2 pa-
rameter, or by carrying out the ‘Input Adjust’ procedure (Section 4.1.9).
For Dual T/C inputs, it is recommended that the ‘Input Adjust’ procedure be used instead
of Offset2 as the use of Offset2 results in an offset which is non-linear over the thermo-
couple range.
Input filterDamping can be used to filter out noise from slowly
changing signals so that the underlying trend can be
seen more clearly. Valid input values are between 0
and 60 seconds.
Note: Applying a filter to an input channel can affect the operation of any Rate-of-change alarms
configured to act on that channel.
CJC TypeFor thermocouple input types only, this allows the user to select ‘None’, ‘Internal’, ‘Exter-
nal’ or ‘Remote 1’ to ‘Remote 4’. For Dual T/C inputs, both primary and secondary inputs
use the same cold junction.
None: No Cold junction compensation applied.
‘Internal’ uses the recorder’s internal cold junction temperature measurement.
‘External’ means that the cold junction is to be maintained by the user, at a fixed, known
temperature. This temperature is entered in the ‘External CJ Temp’ field which appears
when ‘External’ is selected.
Remote 1 (2) (3) (4) means that the cold junctio n temperature is being measur ed by input
channel 1 (2) (3) (4) respectively. (This must be a different channel from that currently
being configured).
Ext. CJ TempAppears only if CJC type is set to ‘External’, and allows the user to enter the temperature
at which the external cold junction is being maintained.
Sensor Break Type Defines whether the sensor break becomes active for circuit impedances greater than
expected.
‘Off’ disables Sensor Break detection.
Break Low: Sensor break active if measured impedance is greater than the ‘Break Low
impedance’ value given in table 4.4.1.
Break High: Sensor break active if measured impedance is greater tha n the ‘Break High
Impedance’ value given in table 4.4.1.
For mA inputs, limits are applied, such that if the process value lies outside these limits, a
sensor break is assumed to have occurred. These limits are (Input lo - 4% Span) and
(Input high + 6% Span). For example, for a 4 to 20mA signal, an input below 3.36mA or
above 20.96mA will trigger a sensor break event
Page 86
HA030554
Issue 9 Mar 15
Page 97
nanodac RECORDER/CONTROLLER: USER GUIDE
Range
Break Low
impedance
Break High
Impedance
40mV
80mV
2V
10V
~5kΩ
~5kΩ
~12.5kΩ
~12.5kΩ
~20kΩ
~20kΩ
~70kΩ
~120kΩ
Table 4.4.1 Minimum impedances for sensor break detection
Note: Break High impedance values would be used typically for sensors which have a h igh nom inal
impedance when working normally
Sensor Break type (Cont.)
Input sensor break detection is not supported for secondary inputs. The internal circuit
acts as a ‘pull up’ on the secondary in put wh ich there fore saturates high in the event of a
sensor break.
Fault ResponseSpecifies the behaviour of the recorder if a sensor break is detected or if the input is over
driven (saturated high or low).
‘None’ means that the input drifts, with the wiring acting as an aerial.
‘Drive High’ means that the trace moves to (Scale High +10%). ‘Drive Low’ means that
the trace moves to (Scale Low -10%), where the 10% values represent 10% of (Scale High
- Scale Low).
Sensor Break ValA diagnostic representation of how close the sensor break detection circuitry is to tripping.
Measured ValueThe (read only) input channel measured value before any scaling or lin-
earisation is applied.
Measured Value2As ‘Measured Value’, above but for the secondary input.
Internal CJ tempThe (read only) temperature of the internal cold junction associated with this channel.
Page 87
HA030554
Issue 9 Mar 15
Page 98
nanodac RECORDER/CONTROLLER: USER GUIDE
Wheatgerm
0.00
200.00
Colour
Span Low
Span High
Channel.1.Trend
Channel.1.Colour
Wheatgerm
4.4.2 Channel Trend configuration
This area allows the configuration of channel colour and span.
Figure 4.4.2a Channel Trend menu Figure 4.4.2b Colour selection
ColourAllows a colour to be specified for the channel. The Scroll key is used to enter the colour
swatch page. The up and down arrows are used to scroll through the available colours,
with each colour being enlarged for as long as it is ‘selected’. Once the required colour, is
reached, the scroll key is used again to return to the Trend Configuration.
Span Low/HighSpan low and high values.
Note: Trend colours and alarm settings for secondary inputs are configured in the maths channels
to which they are wired.
SPAN EXAMPLE
In an input range of 0 to 600 degrees C, the temperatur e ra nge betwee n 500 an d 600 degr ees is of most inter est. In such a case, Span Low is set to 500 and Span High to 600 so that the recorder trends only the required
part of the temperature range, effectively magnifying the area of interest.
Note: Trending is restricted to th e PV range (Span High - Span Low) , but the instrument ca n display
values outside this range
CHANNEL CONFIGURATION EXAMPLE
A type J thermocouple is used to measure a temperature range of 100 to 200 degrees Celsius. This thermocouple output is transmitted to the recorder by a 4 to 20mA transmitter, for display as a value between 0 and
100%.
In Channel.Main, set the following for the relevant channel:
Type= mA
Units= %
Input Low= 4.00
Input high= 20.00
Shunt= 250 Ohms
Lin Type= Type J
Range Low= 100.00
Range High= 200.00
Range Units= °C
Scale Low= 0
Scale High= 100
Other items may be left at their defaults.
Page 88
Issue 9 Mar 15
HA030554
Page 99
nanodac RECORDER/CONTROLLER: USER GUIDE
Abs High
Active Not ackd
35.00°C
5.00°C
Manual
Off
00:00:00
Type
Status
Threshold
Hysteresis
Latch
Block
Dwell
Channel.1.Alarm1
No
Yes
No
Yes
No
Acknowledge
Active
Inactive
N.acknowledged
Acknowledgement
Inhibit
4.4.3 Alarm 1 menu
Allows the alarm characteristics for Alarm 1 to be configured. The figure below shows a typical configuration
page (expanded for clarity). Actual configuration parameters are context sensitive.
Figure 4.4.3 Typical alarm 1 configuration menu
TypeSelect an alarm type from: ‘Off’, ‘Abs. High’ (absolute high). ‘Abs. Low’ (absolute low),
Low’. See ‘Alarm types’, below, for definitions.
StatusRead only. This shows that the alarm is Off, Active, SafeNotAcked or ActiveNotAcked.
For ‘Auto’ and ‘Manual’ alarms only, ‘SafeNotAcked’ means that the alarm trigger source
has returned to a non-alarm state, but the alarm is still active because it has not been ac-
knowledged. Similarly, ‘ActiveNotAcked’ means that the source is still active and the
alarm has not been acknowledged. Always shows ‘Off’ when the alarm is inhibited (see
below).
ThresholdFor absolute alarms only, this is the trip po int for th e ala rm. Fo r ab so lu te hig h alar ms , if
the threshold value is exceeded by the proces s value (PV) of this channel, th en the alarm
becomes active, and remains active until the PV falls below the value (threshold - hyster-
esis). For absolute low alarms, if the PV of this channel falls below the threshold value,
then the alarm becomes active and remains active until the PV rises above (T hre shold +
Hysteresis).
ReferenceFor deviation alarms only, this provides a ‘centre point’ for the deviation band.
DeviationFor deviation alarms only, ’Deviation’ defines the width of the deviation band, each side of
Page 89
For ‘deviation high’ alarms, the alarm becomes active if the process value (PV) rises
above the value (Reference + Deviation) and re mains active u ntil the PV falls below (Ref-
erence + Deviation - Hysteresis).
For ‘deviation low’ alarms, the alarm become s active if the process value (PV) falls below
the value (Reference - Deviation) and remains active until the PV rises above (Reference
- Deviation + Hysteresis).
For ‘deviation band’ alarms, the alarm is active whenever the process value (PV) lies out-
side the value (Reference ± Deviation) and remains active until the PV returns to within
the band, minus or plus Hysteresis as appropriate.
the Reference value, as described immediately above.
Issue 9 Mar 15
HA030554
Page 100
nanodac RECORDER/CONTROLLER: USER GUIDE
Alarm 1 Menu (Cont.)
HysteresisFor absolute and deviation alarms, this provides a means of preventing multiple alarm trig-
gering, if the process value is drifting close to the trigger value.
AmountFor rate-of-change alarms only. The alarm becomes active if the process value rises
(Rise ROC) or falls (Fall ROC) by more than the specified ‘Amount’ within the time period
defined in ‘Change Time’, below. The alarm remains active until the rate of change falls
below the value (Amount/Change Time) in the relevant sense.
Change TimeSettable to 1 second, 1 minute or 1 hour. See ‘Amount’ (above).
Average TimeFor rate-of-change alarms only. This allows an averaging period (for the process value) to
be entered to reduce nuisance trips due to signal noise, or if the rate of change is hovering
around the trip value.
LatchNone: the alarm remains active until the monitored value has returned to a non alarm
state, when it becomes inactive.
Auto: The alarm remains active until the monitored value has r eturned to a non alarm state
and the alarm has been acknowledged. Acknowledgement can take place either before
or after the value has returned a non alarm state.
Manual: The alarm remains active until the monitor ed value has retu rned to a n on alar m
state and the alarm has been acknowledged. Acknowledgement is permitted only after
the value has returned a non alarm state.
Trigger: Not enunciated, this mode is used only to initiate an action de fined by user wiring
either using iTools or using the user interface.
BlockAlarms with ‘Block’ set to ‘On’ are inhibited until the monitored value has entered the 'safe'
condition after a start-up. This prevents such alarms from becoming active whilst the pro-
cess is brought into control. If a latching alarm is not acknowledged then the alarm is re-
asserted (not blocked), unless the alarm’s threshold or reference value is changed, in
which case the alarm is blocked again.
DwellInitiates a delay between the trigger source becoming active, and the alarm becoming ac-
tive. If the trigger source returns to a non alarm state before the dwell time has elapsed,
then the alarm is not triggered and the dwell timer is reset.
AcknowledgeSelect ‘yes’ to acknowledge the alarm. Display returns to ‘No’.
ActiveRead only. Shows the status of the alarm as ‘Yes’ if it is active , or No, if inactiv e. The ac-
tive/inactive state depends on the Latch type (above) and acknowledgment status of the
alarm. Always shows ‘No’ if the alarm is inbited (below).
InactiveAs for ‘Active’ above, but shows ‘Yes’ if the alar m in inactive and ‘No’ if the alarm is active.
Always shows ‘Yes’ if the alarm is inbited (below).
N.acknowledgedAs for ‘Active’ above but shows ‘Yes’ for as long as the alarm is unacknowledged, and ‘No’
as soon as it is acknowledged. Always shows ‘No’ if the alarm is inbited (below).
AcknowledgementFleetingly goes ‘Yes’ on alarm acknowledgement, and then returns to ‘No’.
InhibitWhen ‘Inhibit’ is enabled, (tick symbol), the alarm is inhibited. Status is set to ‘Off’; ‘Active’
and ‘N.acknowledged’ are set to ‘No’, and ‘Inactive’ is set to ‘Yes’. If the alarm is active
when inhibit is enabled, then it becomes inactive until inhibit is disabled, when its status
depends on its configuration. Similarly if the alarm tr igger becomes active when the alarm
is inhibited, the alarm remains ‘off’ until inhibit is disab led, when its status dep ends on its
configuration.
4.4.4 Alarm 2 menu
As above for Alarm 1 menu.
Note: The parameters ‘Acknowledge’, ‘Active’, ‘Inactive’, ‘N(ot) Acknowledged’ and, ‘Acknowledge-
ment’ can all be ‘wired’ to other parameters, so, for example, a relay can be made to operate
whilst the alarm is inactive or whilst it is active or on acknowledgement etc. by wiring the relevant parameter to the relay’s ‘PV’ input. See Section 7 for details of user wiring.
Page 90
HA030554
Issue 9 Mar 15
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.