Eurotherm Invensys 2408, Invensys 2404 Installation And Operating Handbook

Page 1
Installation and operation handbook
2404
2408
CONTROL SETPOINT PROGRAMMER
ENG
Page 2
Page 3
Contents Installation and Operation Handbook
ii Issue 10.0 Nov-04 Appli es to 2408 and 2404 controller software version 4.0
Enhancements to Software Version 4
The following enhancements have been added to software versions 4.
Isolated Single Logic Output Module
Transducer Power Supply Module to provide 5 or 10Vdc to an external transducer. (Not
intended for melt pressure control)
DeviceNet communication s
Linear over range limits are +5% of high instrument range and –5% of low instrument
range for all process input ranges (i.e. 0-20mA, 4-20mA, 0-10V)
Sensor break or input open circuit faults are detected on all analogue inputs (PV1.PV2
and remote input channels)
PV2 alarm, full scale high and low limits default to maximum and minimum display
limits
Deviation alarms are not inverted when direct acting control is selected. Alarm
behaviour when using reverse acting control is unchanged
The PD track valve positioning parameter (Pd.tr) has been removed
Controllers Affected:-
Standard controllers – which include programmers with up to 4 programs
Version 4.11 or later
Setpoint programming controllers with up to 20 programs
Version 4.61 or later
Profibus controllers – which include programmers with up to 4 programs
Version 4.32 or later
The 10Amp output relay in module 4 is not available on controllers supplied after Jan 04
Related Information
DeviceNet Communications Handbook part no. HA027506 which includes the
parameter address map.
Profibus Communications Handbook part no. HA026290
EMC (Electromagnetic Compatibility) Installation Guide, part no. HA025464
These are available on www. eu rotherm.co. uk.
Page 4
Page 5
Installation Installation and Operat i on Handbook
1-2
2
408 and 2404 Controller
Outline dimensions Model 2408
Outline dimensions Model 2404
The electronic assembly of the controller plugs into a rigid plastic sleeve, which in turn fits into the standard DIN size panel cut-out shown in Figures 1-3 and 1-4.
2408
OP 1 OP2
SP2 REM
AUTO
MAN
RUN
HOLD
Figure 1-3
Outline dimensi ons of Model 2408 controller
150mm
5.91in
48mm
1.89in
96mm
3.78in
150mm
5.91in
96mm
3.78in
96mm
3.78in
2404
OP 1
OP2
SP2
REM
AUTO
MAN
RUN
HOLD
Panel cut-out
92 x 92 mm
3.62 x 3.62 in
-0
+0.8
-0
+0.03
Panel
cut-out
92 x 45mm
3.62x1.77in
-0
+0.8
-0
+0.6
-0
+0.03
-0
+0.02
38mm (1.5in)
10mm (0.4in)
(Not to scale
)
Recommended
m
inimum s pacing
of controllers
R
ecommended minimum spacing of controllers
38mm (1.5in)
10mm (0.4in)
(Not to scale
)
Figure 1-4 Outline dimens i ons Model 2404 controller
Page 6
Page 7
Installation Installation and Operat i on Handbook
1-4
2
408 and 2404 Controller
NEW SLEEVE DESIGN MKIII
From Jan-03 an improved design of 1/8 DIN long sleeve is shipped with all new 2408 controllers and indicators. (The month and year of manufacture are shown in the last two pairs of digits of the instrument serial number).
Details
A new sealing gasket will be fitted onto the instrument bezel !. This gasket replaces the gasket which was moulded into the front of the sleeve of all previous instruments. The gasket previously moulded into the sleeve where it fits behind the panel is now supplied as a separate item ".
Reasons for the Change
This change is to ensure that IP65 sealing is reliably achieved and less physical effort is required to insert the instrument into the new sleeve.
Recommendations
1. An instrument delivered after Jan 03 should be used with the sleeve supplied
2. If the instrument i s required to replace one already in use, the existing sleeve should also be replaced
3. A new instrument can be fitted into an existing sleeve by carefully removing gasket ! but IP65 sealing will not be maintained
4. An existing instrument can be fitted into a new sleeve but IP65 sealing will not be maintained
It is, however, possible to achieve IP65 sealing for 3 and 4 above. A gasket kit is available by quoting Part No SUB24/GAS2408. Then:-
5. To fit a new instrument in an older sleeve carefully remove gasket !. Replace it with the thinner (1.25mm) gasket from the kit
6. To fit an existing instrument into a new sleeve fit the thicker (1.6mm) gasket from the kit between th e i nstrument and the sleeve
The seal " supplied as a separate item with a new instrument, should be placed over the sleeve prior to mounting it through the panel cut out as shown below:-
Panel
New
Instrument
Sleeve seal " (supplied as a separate item)
Instrument
sleeve
New gasket ! fitted onto bezel
Page 8
N
L
V+
VI
V-
G
*
2
2
2
3
3
3
3
1
1
1
1
M
O D U L E
M O D U L E
3
M
O D U L E
2
J
J
JE
C
O M M S
L
LA
LB
AC
A
AB
A
H
H
H
C
O M M S
H
HA
H
JB
JC
PV
R
T/C
p
*
Page 9
Installation Installation and Operat i on Handbook
1-6
2
408 and 2404 Controller
All electrical connections are made to the screw terminals at the rear of the controller. If you wish to use crimp connectors, the correct size is AMP part number 349262-1. They accept wire sizes from 0.5 to 1.5 mm
2
(16 to 22 AWG). The terminals are protected by a clear
plastic hinged cover to prevent han ds, or metal, making accidental contact with live wires.
Rear terminal layouts
The rear terminal layouts are shown in Figures 1-5 and 1-6. The right-hand column carries the connections to the power supply, digital inputs 1 and 2, alarm relay and sensor input. The second and third columns from the right carry the connections to the plug-in modules. The connections depend upon the type of module installed, if any. To determine which plug-in modules are fitted, refer to the ordering code and wiring data on the controller side labels.
Model 2404 rear terminal layout
Figure 1-6 Rear terminal layout Model 2404
RTD/Pt100
N
L
V+
VI
V-
L
ine
N
eutral
G
round*
2D
2B
2A
2C
3D
3B
3A
3C
1D
1B
1A
1C
M
O D U L E 1 M O D U L E 3 M O D U L E 2
HF
HD
HE
C
O M M S 1
JF
JD
JE
C
O M M S 2
C
ommon
Input 1
Input 2
85 to 264Vac
LC
LA
LB
AC
AA
AB
A
larm
relay
+
PV
T/C
HB
HA
HC
JB
JA
JC
+
5B
5A
4D
4B
4A
4C
20 29Vac/dc
Ground
*
24
24
Low voltage supply
6D
6C
6B
5D
5C
6A
Page 10
+
-
Page 11
Installation Installation and Operat i on Handbook
1-8
2
408 and 2404 Controller
Two terminal modules
Note: Module 1 is connected to terminals 1A and 1B Module 2 is connected to terminals 2A and 2B Module 3 is connected to terminals 3A and 3B.
Terminal identit y Module type A B C D P ossible functions Relay: 2-pin
(2A, 264 Vac max.)
Unused Heating, cooling, al arm,
program event, valve
raise, or valve lower
Logic - non-isolated
(18Vdc at 20mA)
++++ −−−−
Unused Heating, cooling, P DS IO
mode 1, PDSIO mode 2,
program event
Triac
(1A, 30 to 264Vac)
Unused Heating, cooling,
program event, valve
raise, or valve lower
DC output:
- non-isolated
(10Vdc, 20mA max.)
++++
Unused Heating, or cooling, or
retransmission of PV,
setpoint, or cont rol output
Table 1-1 Two terminal module c onnections
Snubbers
The relay and triac modules have an internal 15nF/100 ‘snubber’ connected across their output, which is used to prolong contact life and to suppress interference when switching inductive loads, such as mechanical contactors and solenoid valves.
WARNING
When the relay contact is open, or the tri a c is off, the snubber cir c uit passes 0.6mA at 110Vac and 1.2mA at 240Vac. You must ensure that this current, passing through the snubber, will not hold on low power electrical loads. It is your responsibility as the installer to ensure that this does not happen. If the snubber circuit is not required, it can be removed from the relay module (BUT NOT THE TRIAC) by breaking the PCB track that runs crosswise, adjacent to the edge connectors of the module. This can be done by inserting the blade of a small screwdriver into one of the two slots that bound it, and twisting.
Line Load
Page 12
Page 13
Installation Installation and Operat i on Handbook
1-10
2
408 and 2404 Controller
Module type Terminal identit y Possible func t i ons
A B C D
Isolated Logic
Output
+ -
This is a fully is ol ated module which can be fitted in all t hree module slots. It may be used for heating, cool i ng or events outputs up to 18Vdc at 20mA.
Transducer
Power Supply
+ -
This provides fully isolated 5 or 10Vdc to power external transmitters up t o 20mA. It can be fitted in module slots 1 and 2.
Table 1-2 Four terminal module connections
Connections for Process Value 2 in module posi tion 3
The diagrams below show the connections for the various types of input. The input will have been configured in accordance with the ordering code.
Triple Logic Input and output ratings
1. Triple logic input (current sinking) OFF state: 3 to 5Vdc ON state: 10.8 to 30Vdc(max), at 2 to 8mA
2. Triple contact closure or open collector transistor input Internally generated switching Vdc & mA: 15 to 19Vdc at 10 to 14mA
OFF state >28KΩ input resistance OFF state voltage >14Vdc ON state <100Ω resistance ON state voltage <1.0Vdc
3. Triple logic output (current sourcing) OFF state output 0 to 0.7Vdc. ON state output 12 to 13Vdc, at up to 8mA.
Thermocouple
3B
3C
3D
3A
+
C
urrent
sense
r
esistor
2.49
mA input
3B
3C
3D
3A
+
Resistance thermometer
3B
3C
3D
3A
Volts or mV inputs
+
0-1.6Vdc
High Impedance
or
mVdc
3B
3C
3D
3A
10V inputs
+
0-10Vdc
3B 3C
3D
3A
Page 14
Page 15
Installation Installation and Operat i on Handbook
1-12
2
408 and 2404 Controller
Wiring of 2-wire EIA-485 serial communications link
Com
Note:
All resistors are 220 ohm 1/4W carbon composition. Local grounds are at equipotential. Where equipotential is not available wire into separate zones using a galvanic isolator. Use a repeater (KD845) for more than 32 units.
A B
PC
Eurotherm Universal
Communications Interface
KD485
RXTX
Com
Com
TXRX
Up to 32 S2000 controllers or Interface Units may be included on the network
232
Com B
A
Com
A B
Com
A B
Com
A B
Local Earth
Local Ground Zone 1
Local Ground Zone 2
Area 1
Com
A B
E
F
D
Local Earth
HE HF
HD
Series 2000 Controller
HE HF
HD
Series 2000 Controller
For reasons of safety do not connect to local earth here.
Local Earth
Local Earth
Local Earth
Local Earth
Local Earth
HE HF
HD
Series 2000 Controller
Galvanic Isolation
Barrier
Local Ground Zone 1
Local Ground Zone 1
Local Ground Zone 1
Figure 1-9 EIA-485 wiring
2-wire EIA-485 is a connect i on which al l ows up t o 32 controllers to be multi-
d
ropped from a single c ommunications link over a distance of up to 1.2Km. To ensure reliabl e operation of the com munications link, (without data corruption due to noise or li ne reflections) the connecti ons
b
etween the controller should be made using a twisted pair of
w
ires inside a screened cable with the connections terminated with resi stors in the manner shown in this diagram. This diagram also shows the use of a KD485 converter to connect t he EIA-485 link into a standard E I A-
2
32
computer port.
Page 16
Page 17
Installation Installation and Operat i on Handbook
1-14
2
408 and 2404 Controller
Example of Devicenet Wiring
To configure DeviceNet Communications see Chapter 6.
HA HB
HC HD HE HF
2400 Controller
(SLAVE)
A
ddress 11
V+ CAN-H
CAN-L
Drain
V-
V+ 5
CAN-H 4
CAN-L 2
Drain 3
V- 1
Red
Wht
Blu Blk
* Fit 121!
resistor to
last instrument in
t
he
chain
Network
Supply
24Vdc ( +
1%)
250mV p-p
Ripple
HA HB
HC HD HE HF
2400 Controller
(SLAVE)
A
ddress N+1
V+
V-
V-
V+
Typical Interfac e
Card (MASTER)
Daisy chain to
further
instruments
121! terminating
r
esistor required if not
fitted internally
L N E
L N E
*
Page 18
B
A
BAB
A
Page 19
Installation Installation and Operat i on Handbook
1-16
2
408 and 2404 Controller
TYPICAL WIRING DIAGRAM
Fig 1-10 Typical wiring diagram, Model 2408 Cont rol l er
For logic drive capability see following chart:-
N
L
V+
VI
V-
2D
2B
2A
2C
3D
3B
3A
3C
1D
1B
1A
1C
M
O D U L E
3
HF
HD
HE
C
O M M S
1
JF
JD
JE
LC
LA
LB
AC
AA
AB
Cooling
Power Fuse
1A(T)
Heating power fuse
(load dependent)
Cooling
Solenoid
Heater
T/C
+
-
+
PV
-
Logic
h
eating
output
Triac
c
ooling
output
L
ine
N
eutral
C
ontroller
Fuse 2A(T)
Solid State
Relay *
+
C
O M M S
2
H
B
HA
H
C
Page 20
Page 21
Installation Installation and Operat i on Handbook
1-18
2
408 and 2404 Controller
MOTORISED VALVE CONNECTIONS
Motorised valves will normally be wired either to dual relay, or dual triac, output modules installed in the Module 1 position, or to single channel relay and triac outputs installed in Module positions 1 and 2. In the latter case, the convention is to configure output 1 as the raise output and output 2 as the lower output. Depending on the configuration, control of the valve is achieved in one of three ways:
1. With no position feedback potentiometer.
2. With a feedback potentiometer used to monitor the valve’s position. It does not influence the control.
3. With a feedback potentiometer, where the valve’s position is controlled in response to the signal from it.
Fig 1-11 Motorised valve connections
N
L
V+
VI V-
Line
N
eutral
G
round
++++
−−−−
++++
PV
−−−−
2D
2B
2A
2C
3D
3B
3A
3C
1D
1B
1A
1C
M
O D U L E
2
HF
HD
HE
C
O M M S
1
JF
JD JE
C
O M M S
2
Common
Input 1
Input 2
8
5 to 264Vac
LC
LA
LB
AC
AA
AB
A
larm
relay
Motor supply
M
otorised
valve
R
A
I S E
L
O W E
R
Dual
relay, or
triac,
output
module
RTD/Pt100
H
B
HA
H
C
Motor
F
eedback
Potentiometer
(Optional)
++++
−−−−
Pot
Input
Module
Page 22
Page 23
Operation Installation and Operat i on Handbook
2-2
2
408 and 2404 Controller
FRONT PANEL LAYOUTS
2408
OP 1 OP2
SP2 REM
AUTO
MAN
RUN
HOLD
Figure 2-1 Model 2408 front panel layout
2404
OP 1
OP2
SP2
REM
AUTO
MAN
RUN
HOLD
Figure 2-2 Model 2404 front panel layout
O
utput 1
S
etpoint 2
Auto/Man button
Auto mode
Manual mode
Page
Button
Scroll
Button
Down
Button
Remote setpoint / comms (flashing)
Output 2
U
pper
Lower readout
Program running
Program in Hold
Up
Button
Remote setpoint/ comms(flashing)
Output 2
Upper readout
Lower readout
Program running
Run/Hold button
Program in Hold
Up
Button
Output 1
Setpoint 2 Auto/Man
button
Auto mode
Manual mode
Page
Button
Scroll
Button
Down
Button
2408
2
404
OP 1 OP 2
OP 1 OP 2
SP2 REM
SP2 REM
Run/Hold
Page 24
Page 25
Operation Installation and Operat i on Handbook
2-4
2
408 and 2404 Controller
BASIC OP ERATION
Switch on the power to the controller. It runs through a self-test sequence for about three seconds and then shows the measured temperature, or process value, in the upper readout and the target value, called the setpoint, in the lower readout. This is called the Home display.
2404
OP1
OP2
SP2
REM
AUTO
MAN
RUN
HOLD
Figure 2-4 Hom e di splay
You can adjust the setpoint by pressing the
or buttons. Two seconds after releasing
either button, the display blinks t o show that the contro l ler has accepted the new value.
OP1 will light whenever output 1 is ON. This is normally the heating output when used as a temperature controller. OP2 will light whenever output 2 is ON. This is normally the cooling output when used as a temperature controller.
Note: You can get back to this display at any time by pressing
and together. Alternatively, you will always be returned to this display if no button is pressed for 45 seconds, or whenever the power is turned on.
Alarms
If the controller det ects an alarm condition, it flash es an alarm message in the Home display. For a list of all the alarm messages, their meaning and what to do about them, see Alarms at the end of this chapter.
Measured temperature or process value
Setpoint
SP2 REM
OP2
OP1
2
404
Page 26
Page 27
Operation Installation and Operat i on Handbook
2-6
2
408 and 2404 Controller
A UTOMATIC MODE
You will normally work with the controller in automatic mode. If the MAN light is on, press the AUTO/MAN button to select automatic mode. The AUTO light comes on.
Power on
x 2
The Home display
Check that the AUTO light is on. The upper readout shows the measured temperature. The lower readout shows the setpoint. To adjust the setpoint up or down, press
or .
(Note: If Setpoint Rate Limit has been enabled, then the lower readout will show the active setpoint. If
or is pressed, it will change to show and allow adjustment of, the target setpoint.)
Press once.
Display units
A single press of
will flash the display units for 0.5
seconds, after which you will be returned to the Home display. Flashing of the display units may have been disabled in configuration in which case a single press will take you straight to the display shown below.
Press
twice
% Output power demand
The % output power demand is displayed in the lower readout. This is a read-only value. You cannot adjust it. Press
and together to return to the Home display.
Press
Pressing
from the Output Power display may access further parameters. These may be in
this scroll list if the ‘Promote’ feature has been used (see Chapter 3, Edit Level). When you reach the end of th i s scroll list, pressing
will return you to the Home display.
Page 28
Page 29
Operation Installation and Operat i on Handbook
2-8
2
408 and 2404 Controller
PARAMETERS AND HOW TO ACCESS THEM
Parameters are settings, within the controller, that determine how the controller will operate. For example, alarm setpoints are parameters that set the points at which alarms will occur. For ease of access, the parameters are arranged i n lists as shown in the n avi gation diagram on Pages 2-10 and 2-11. The lists are:
Home list Run list Programming list Alarm list Autotune list
PID list Motor list Setpoint list Input list Output list
Communications list Information list Access list.
Each list has a ‘List Header’ display.
List header displays
Figure 2-5 Typical list header di splay
A list header can be reco gnised by the fact that it always shows LiSt in the lower readout. The upper readout is the name of the list. In the above example, ‘ALindicates that it is the Alarm list header. List header displays are read-only.
To step through the list headers, press
. Depending upon how your controller has been configured, a single press may momentarily flash the display units. If this is the case, a double press will be necessary to take you to the first list header. Keep pressing
to step
through the list headers, eventually returning you to the Home display. To step through the parameters within a particular list, press
.
When you reach the end of the list, you will return to the list header. From within a list you can return to the current list header at any time can by pressing
.
To step to the next list header, press once again.
List name
A
lways displays ‘LiSt’
Page 30
Page 31
Operation Installation and Operat i on Handbook
2-10
2
408 and 2404 Controller
NAVIGATION DIAGRAM (PART A) (The parameters that appear depend upon how
the controller has been c onfigured)
Figure 2-7a Navigation diagram (P art A)
Home
List
P
rogrammer
List
(1)
Alarm
L
ist
A
utotune
List
Motor
List
(3)
Atun
LiSt
ProG
LiSt
Hb
OFF
PrG.n
1
Hb V
20
dwL.U
Hour
rmP.U
Hour
CYC.n
1
tYPE
rmP.r
SEG.n
1
tGt
200
SEG.n
2
rAtE
5.0
tYPE
dwEl
Pid
LiSt
PID List
PrG.t
35.0
out.n
OFF
20.0
20.0
OP
100.0
m-A
Auto
AmPS
5
rAtE
5.0
run
LiSt
dur
1.0
StAt
run
PrG
1
PSP
20
CYC
1
SEG
1
SEG.t
1.0
StyP
rmP.r
Run List
(1)
tGt
200
tYPE
End
SEG.n
3
AL
LiSt
2---
2
0
1---
2
100
3---
2
5
HY 2
1
HY 1
1
HY 3
1
Lb t
OFF
HY 4
1
diAG
no
4---
2
5
drA
OFF
tunE
OFF
drA.t
0.8
Adc
mAn
FF.tr
0
FF.dv
100.0
rEL.2
1.00
FF.Pb
0.0
Lcb2
Auto
Hcb2
Auto
mtr
LiSt
tm
30.0
In.t
OFF
bAc.t
OFF
mp.t
Auto
V.br
dwn
20.0
o
C
FASt
no
tYPE
dwEl
rES.2
0.0
Pb
5
SEt
Pid.1
ti
300
rES
0.0
td
60.0
Hcb
Auto
rEL.C
1.00
Lcb
Auto
Pb2
10
td.2
50.0
ti.2
300
G.SP
500
SYnc
no
SEG.d
YES
C.id
1
Page 32
T
4
I
Page 33
Operation Installation and Operat i on Handbook
2-12
2
408 and 2404 Controller
PARAMETER TABLES
Name Description
Home list
Home Measured value and Setpoi nt
OP
OPOP
OP
% Output level
SP
SPSP
SP
Target setpoint (if i n Manual mode )
mmmm----AAAA
Auto-man select
AmPS
AmPSAmPS
AmPS
Heater current (With PDSIO mode 2)
C.id
C.idC.id
C.id
Customer defined i dent i fication number
+ Extra parameters, if the ‘Promote’ feature has been used (see Chapter 3, Edit Level).
run
runrun
run
Program run list Present only in s etpoint programming controllers
PrG
PrGPrG
PrG Active program number (Only on 4, or 20, program versions) StAt
StAtStAt
StAt Program status (OFF, run, hoLd, HbAc, End) PSP
PSPPSP
PSP
Programmer s et poi nt
CYC
CYCCYC
CYC
Number of cycles remaining in the program
SEG
SEGSEG
SEG
Active segment number
StyP
StyPStyP
StyP
Active segment type
SEG.t
SEG.tSEG.t
SEG.t
Segment time remaining in the segm ent uni ts
tGt
tGttGt
tGt
Target setpoint
rAtE
rAtErAtE
rAtE
Ramp rate (if a rate segment)
PrG.t
PrG.tPrG.t
PrG.t
Program tim e remaining in hours
FASt
FAStFASt
FASt Fast run through program (no / YES) out.n
out.nout.n
out.n Event output st at es (OFF / on) (not 8-segment programmer) SYnc
SYncSYnc
SYnc Segment synchroni sation (no / YES) (not 8-segment programmer) SEG.d
SEG.dSEG.d
SEG.d Flash active s egment type in the lower readout of the home di splay (no / YES)
Page 34
Page 35
Operation Installation and Operat i on Handbook
2-14
2
408 and 2404 Controller
Name Description
AL
ALAL
AL
Alarm list
1111 ---- ---- ----
Alarm 1 setpoi nt value
2222 ---- ---- ----
Alarm 2 setpoi nt value
3333 ---- ---- ----
Alarm 3 setpoi nt value
4444 ---- ---- ----
Alarm 4 setpoi nt value
In place of dashes, the last three characters indicate the alarm type. See alarm types table:
HY
HYHY
HY 1111
Alarm 1 Hysteresis (display units)
HY
HYHY
HY 2222
Alarm 2 Hysteresis (display units)
HY
HYHY
HY 3333
Alarm 3 Hysteresis (display units)
HY
HYHY
HY 4444
Alarm 4 Hysteresis (display units)
Lb
LbLb
Lb tttt
Loop Break Time in minutes
diAG
diAGdiAG
diAG Enable Diagnostic alarms ‘no’ /
YES
Alarm types table
----FSL
FSLFSL
FSL
PV Full scale low alarm
----FSH
FSHFSH
FSH
PV Full scale high al arm
----dEv
dEvdEv
dEv
PV Deviation band alarm
----dHi
dHidHi
dHi
PV Deviation high alarm
----dLo
dLodLo
dLo
PV Deviation low alarm
----LCr
LCrLCr
LCr
Load Current low alarm
----HCr
HCrHCr
HCr
Load Current high alarm
----FL2
FL2FL2
FL2
Input 2 Full Scale low alarm
----FH2
FH2FH2
FH2
Input 2 Full Scale high al arm
----LOP
LOPLOP
LOP
Working Output low alarm
----HOP
HOPHOP
HOP
Working Output high alarm
----LSP
LSPLSP
LSP
Worki ng S etpoint low alarm
----HSP
HSPHSP
HSP
Working Setpoint high alarm
4rAt
4rAt4rAt
4rAt
Rate of change alarm (A L 4 onl y)
Atun
AtunAtun
Atun
Autotune list
tunE
tunEtunE
tunE
One-shot autotune enable
drA
drAdrA
drA
Adaptive tune enable
drA.t
drA.tdrA.t
drA.t
Adaptive tune trigger level i n display units. Range = 1 to 9999
Adc
AdcAdc
Adc
Automatic Droop Compensation (PD control only)
Name Description
Pid
PidPid
Pid
PID list
G.SP
G.SPG.SP
G.SP
If Gain Scheduling has been enabled (see Chapter 4), this parameter sets t he PV below whic h ‘Pid.1’ is active and above whic h ‘Pid.2’ is active.
SEt
SEtSEt
SEt Pid.1’ or ‘Pid.2’ selected
Pb
PbPb
Pb Proportional B and (SEt 1)
(in display units)
ti
titi
ti Integral Time in secs (SEt 1)
td
tdtd
td Derivative Time in secs (SEt 1)
rES
rESrES
rES Manual Reset (%) (SEt 1)
Hcb
HcbHcb
Hcb Cutback High (SEt 1)
Lcb
LcbLcb
Lcb Cutback Low (SEt 1)
rEL.C
rEL.CrEL.C
rEL.C Relative Cool Gain (SEt 1)
Pb2
Pb2Pb2
Pb2 Proportional Band (SEt 2)
ti2
ti2ti2
ti2 Integral Time in secs (SEt 2)
td2
td2td2
td2 Derivative Time in secs (SEt 2)
rES.2
rES.2rES.2
rES.2 Manual Reset (%) (SEt 2)
Hcb2
Hcb2Hcb2
Hcb2 Cutback High (SEt 2)
Lcb2
Lcb2Lcb2
Lcb2 Cutback Low (SEt 2)
rEL.2
rEL.2rEL.2
rEL.2 Relative Cool Gain (SEt 2)
The following three parameters are used for cascade control. If t his f acility is not being used, then they can be i gnored.
FF.Pb
FF.PbFF.Pb
FF.Pb
SP, or PV, f eedf orward propband
FF.tr
FF.trFF.tr
FF.tr
Feedforward trim %
FF.dv
FF.dvFF.dv
FF.dv PID feedf orward limits ± %
mtr
mtrmtr
mtr
Motor list - see Tabl e 4-3
tm
Valve travel tim e i n seconds
In.t
Valve inertia time in secs
bAc.t
Valve backlash ti me in secs
mp.t
Minimum ON time of output pulse
U.br
Valve sensor break strategy
Page 36
Page 37
Operation Installation and Operat i on Handbook
2-16
2
408 and 2404 Controller
Name Description
oP
oPoP
oP
Output list
Does not appear if Motorised Valve control configured.
OP.Lo
Low power limit (%)
OP.Hi
High power limit (%)
OPrr
Output Rate Limit (% per sec)
FOP
Forced output level (%)
CYC.H
Heat cycle time (0.2S to 999.9S)
hYS.H
Heat hysteresis (display units)
ont.H
Heat output min. on-time (secs) Auto (0.05S), or 0.1 - 999. 9S
CYC.C
Cool cycle time (0.2S to 999.9S)
hYS.C
Cool hysteresis (di splay units)
ont.C
Cool output min. on-time (secs) Auto (0.05S), or 0.1 - 999. 9S
HC.db
Heat/cool deadband (display units)
Sb.OP
Sensor Break Output P ower (%)
cmS
cmScmS
cmS
Comms list
Addr
Communications Address
cmS
cmScmS
cmS
DeviceNet (additional parameters)
Nw.St
Indicates network s t atus
run
Network connected and operational
rdy
Network connected but not operational
oFF.L
Network not connected
inFo
inFoinFo
inFo
Information list
diSP
Configure lower readout of Home display to show:
VPoS Valve position Std Standard - display set poi nt AmPS Load current in amps OP Output Stat Program status PrG.t Program tim e remaining in
hours
Li 2 Proces s value 2 rAt Ratio setpoint PrG Selected program number rSP Remote setpoint
LoG.L
PV minimum
LoG.H
PV maximum
LoG.A
PV mean value
Log.t
Time PV above Threshold l evel
Log.v
PV Threshold for Tim er Log
Continued in next column
Name Description
inFo
inFoinFo
inFo
Information list - continued
rES.L
Logging Reset - ‘YES/no’
The following set of parameters is for diagnostic purposes .
w.OP
Working output
FF.OP
Feedforward component of output
VO
PID output to motorised valve
ACCS
ACCSACCS
ACCS
Access List
codE
Access password
Goto Goto level - OPEr, FuLL, Edit or
conF
ConF
Configuration password
Page 38
Page 39
Operation Installation and Operat i on Handbook
2-18
2
408 and 2404 Controller
Diagnostic alarms
These indicate th at a fau l t exists in either the controller or the con nected devices.
Display
shows
What it means What to do about it
EE.Er
EE.ErEE.Er
EE.Er
Electricall y Erasable Memory Error:
The value of an operator, or configuration, parameter has been corrupted.
This fault will automatically take you into Configuration level. Chec k all of the configuration param et ers before returning to Operator level. Once in Operator l evel , check all of the operator parameters before resuming normal operation. I f the fault persists, or occurs frequently, contac t your supplier
S.br
S.brS.br
S.br
Sensor Break:
Input sensor is unrel i abl e or the input signal is out of range.
Check that the s ensor is correctly connected.
L.br
L.brL.br
L.br
Loop Break
The feedback loop is open circuit.
Check that the heati ng and cooling circuits are working properly.
Ld.F
Ld.FLd.F
Ld.F
Load failure Indication that there is a fault in the heating c i rcuit or the solid state relay.
This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDSIO mode 1 - see Chapt er 1, Electrical Installation. It indicates either an open or short circuit SS R, bl own fus e, missing supply or open circuit heater.
SSr.F
SSr.FSSr.F
SSr.F
Solid state relay failure Indication that there is a fault in the solid state relay.
This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDSIO mode 2 - see Chapt er 1, Electrical Installation. It indicates either an open or short circuit condition in the SSR.
Htr.F
Htr.FHtr.F
Htr.F
Heater failure Indication that there is a fault in heating ci rcuit.
This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDSIO mode 2 - see Chapt er 1, Electrical Installation. It indicates either a blown fuse, missing supply, or open circuit heater.
Ct.OP
Ct.OPCt.OP
Ct.OP
C
urrent Transformer Open
C
ircuit
Indicates that the PDS input is open circuit. Mode 5 only
Ct.Sh
Ct.ShCt.Sh
Ct.Sh
C
urrent Transformer S hort
C
ircuit
Indicates that the PDS input is short ci rcuit Mode 5 only
Hw.Er
Hw.ErHw.Er
Hw.Er
Hardware error
Indication that a module is of the wrong type, missing, or faulty.
Check that the c orrect modules are fitted.
Page 40
Page 41
Operation Installation and Operat i on Handbook
2-20
2
408 and 2404 Controller
Page 42
Page 43
A
ccess Levels Installation and Operat i on Handbook
3-2
2
408 and 2404 Controller
SELECTING AN ACCESS LEVEL
Access to Full, Edit or Configuration levels is protected by a password to prevent unauthorised access. If you need to change the password, see Chapter 6, Configuration.
Access list header
Press
until you reach the access list header ACCS’.
Press
Password entry
The password is entered from the codE display. Enter the password using or . Once the correct p assword has been entered, there is a two second delay after which the lower readout will change to show PASS indicating t hat access is now unlocked. The pass number is set to 1 when the controller is shipped from the factory.
Note; A special case exists if the password has been set to 0. In this case access will be permanently unlocked and the lower readout will always show PASS’.
Press
to proceed t o the Goto page.
(If an incorrect password has been entered and the controller is still ‘locked’ then pressing
returns you to the ACCS list
header.)
Access to Read-only Configuration
From this display, pressing
and together will take you into Read-Only Configuration without entering a password. This will allow you to view all of the configuration parameters, but not adjust them. If no button is pressed for ten seconds, you will be returned to the Home display. Alternatively, pressing
and
together takes you immediately back to the Home display.
Page 44
A
Page 45
A
ccess Levels Installation and Operat i on Handbook
3-4
2
408 and 2404 Controller
EDIT LEVEL
Edit level is used to set which parameters you can view and adjust in Operator level. It also gives access to the ‘Promote’ feature, which allows you to select and add (‘Promote’) up to twelve parameters into the Ho me display list, thereby giving simple access to commonly used parameters.
Setting operator access to a parameter
First you must select Edit level, as shown on the previous page. Once in Edit level, you select a list, or a parameter within a list, in the same way as you would in Operator, or Full, level that is to say, you move from list header to list header by pressing
, and from parameter to parameter within each list using .
However, in Edit level what is displayed i s not the value of a selected parameter, but a code representing that param eter’s availability in Operator level.
When you have selected the required parameter, use and buttons to set its availability in Operator level.
There are four codes:
ALtr
ALtrALtr
ALtr Makes a parameter alterable in Operator level. PrO
PrOPrO
PrO Promotes a parameter into the Home display list. rEAd
rEAdrEAd
rEAd Makes a parameter, or list header, read-only (it can be viewed but not altered). HIdE
HIdEHIdE
HIdE Hides a parameter, or list header.
For example:
Hiding or revealing a complete list
To hide a complete list of parameters, all you have to do is hide the list header. If a list header is selected, only two selections are available: rEAd and HIdE. (It is not possible to hide the ACCS list, which always displays the code: LiSt’.)
Promoting a parameter
Scroll through the lists to the required parameter and choose the PrO code. The parameter is then automatically added (promoted) into the Home display list. (The parameter will also be accessible, as no r mal, from the standard lists.) A maximum of twelve parameters can be promoted. Promoted parameters are automatically ‘alterable’.
Please note, in the ‘PrOG List’, the parameters from segment number (SEG.n) onwards cannot be promoted.
The parameter select ed i s Alarm 2, Full Scale Low
It will be alterable in Operator level
Page 46
Page 47
Tuning Installation and Operat ion Handbook
4-2 2408 and 2404 Controller
AUTOMATIC TUNING
Two automatic tuning methods are provided in the 2408 and 2404:
A one-shot tuner, which automatically sets up the initial values of the parameters listed
in Table 4-1 on the previous page.
Adaptive tuning, which continuously monitors the error from setpoint and modifies the
PID values, if necessary.
One-shot Tuning
The ‘one-shot’ tuner works by switching the output on and off to induce an oscillation in the measured value. From the amplitude and period of the oscillation, it calculates the tuning parameter values. If the process cannot tolerate full heating or cooling being applied during tuning, then the level of heating or cooling can be restricted by setting the heating and cooling power limits in the oP list. However, the measured value must oscillate to some degree for the tuner to be able to calculate values. A One-shot Tune can be performed at any time, but normally it is performed only once during the initial commissioning of the process. However, if the process under control subsequently becomes unstable (because its characteristics have changed), you can re-tune again for the new conditions. It is best to start tuning with the process at ambient temperature. This allows the tuner to calculate more accurately the low cutback and high cutback values which restrict the amount of overshoot, or undershoot.
How to tune
1. Set the setpoint to the value at which you will normally operate the process.
2. In the Atun’ list, select ‘tunE’ and set it to ‘on’.
3. Press the Page and Scroll buttons together to return to the Home display. The display will
flash tunE to indicate that tuning is in progress.
4. The controller induces an oscillation in the temperature by first turning the heating on, and then off. The first cycle is not complete until the measured value has reached th e required setpoint.
5. After two cycles of oscillation the tuning is completed and the tuner switches itself off.
6. The controller then calculates the tuning parameters listed in Table 4-1 and resumes normal control action.
If you want ‘Proportional only’, ‘PD’, or ‘PI’ control, you should set the ti or td parameters to OFF before commencing the tuning cycle. The tuner will leave them off and will not calculate a value for them.
Page 48
Page 49
Tuning Installation and Operat ion Handbook
4-4 2408 and 2404 Controller
MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results, you can tune the controller manually. There are a number of standard methods for manual tuning. The one described here is the Ziegler-Nichols method.
With the process at its normal running temperature:
1. Set the Integral Time ti and the Derivative Time td to OFF.
2. Set High Cutback and Low Cutback, Hcb and Lcb, to Auto’.
3. Ignore the fact that the temperature may not settle precisely at the setpoint.
4. If the temperature is stable, reduce the proportional band Pb so that the temperature just
starts to oscillate. If the temperature is already oscillating, increase the proportional band until it just stops oscillating. Allow enough time between each adjustment for the loop to stabilise. Make a note of the proportional band value ‘B’ and the period of oscillation ‘T’.
5. Set the Pb, ti, td parameter values according to the calcu l ations given in Table 4 - 2.
Type of control
Proportional
band ‘Pb’
Integral time ‘ti’
Derivative time
‘td’
Proportional only
2xB
OFF
OFF
P + I control
2.2xB
0.8xT
OFF
P + I + D control
1.7xB
0.5xT
0.12xT
Table 4-2 Tuning values
Page 50
S
U
S
O
Page 51
Tuning
Installation and Operat i on Handbook
4-6 2408 and 2404 Controller
Integral action and manual reset
In a full three-term controller (that is, a PID controller), the integral term ‘ti’ automatically removes steady state errors from the setpoint. If the controller is set up to work in two-term mode (that is, PD mode), the integral term will be set to ‘OFF’. Under these conditions the measured value may not settle precisely at setpoint. When the integral term is set to ‘OFF’ the parameter manual reset (code rES) appears in the Pid LiSt in FuLL level. This parameter represents the value of the power output that will be delivered when the error is zero. You must set this value manually in order to remove the steady state error.
Automatic droop compensation (Adc)
The steady state error from the setpoin t , which occurs when the integral term is set to ‘OFF’ is sometimes referred to as ‘droop’. Adc automatically calculates the manual reset value in order to remove this droop. To use this facility, you must first allow the temperature to stabilise. Then, in the autotune parameter list, you must set Adc to cALc. The controller will then calculate a new value for manual reset, and switch Adc to mAn’.
Adc can be repeated as often as you require, but b et ween each adjustment you must allow time for the temperature to stabilise.
Tune Error
If any one stage of the automatic tuning process is not completed within two hours a diagnostic alarm will occur. The display shows tU.Er - Tune Error. This alarm could occur if:
1. The process to be tuned has a very slow response time
2. The sensor has failed or is incorrectly aligned
3. The loop is broken or not responding correctly
Page 52
Page 53
Tuning
Installation and Operat i on Handbook
4-8 2408 and 2404 Controller
COMMISS I ONING THE MOTORISED VALVE CONTROLLER
The commissioning procedure is the same for both bounded and boundless control modes, except in bounded mode you must first calibrate the position feedback potentiometer, as described in the section below. Proceed as foll ows:
1. Measure the time taken for the valve to be raised from its fully closed to its fully open
position and enter this as the value in seconds into the tm parameter.
2. Set all the other parameters to the default values shown in Table 4-3. The controller can then be tuned using any of the automatic, or manual, tuning procedures
described earlier in this chapter. As before, the tuning process, either automatic or manual, involves setting the values of the parameters in Table 4-1. The only difference with boundless control is that the derivative term td’, although present, will have no effect.
Adjusting the minimum on-time ‘mp.t
mp.tmp. t
mp.t
The default value of 0.2 seconds is satisfactory for most processes. If, however, after tuning the process, the valve activity is excessively high, with constant oscillation between raise and lower pulses, the minimum on-t ime can be increased. The minimum on-time determines how accurately the valve can be positioned and therefore the control accuracy. The shorter the time, the more precise the control. However, if the time is set too short, process noise will cause an excessively busy valve.
Inertia and backlash settings
The default values are satisfactor y for most processes, i.e. ‘OFF’. Inertia is the time taken for the valve to stop after the output pulse is turned off. If this causes a control problem, the inertia time needs to be determined and then entered into the parameter, ‘In.t’. The inertia time is subtracted from the raise and lower output pulse times, so that the valve moves the correct distance for each pu l se. Backlash is the output pulse time required to reverse the direction of the valve, i.e. the time taken to overcome the mechan ical backlash of the linkages. If the backlash is sufficient to cause a control problem, then the backlash time needs to be determined and then entered into the parameter, ‘bac.t’. The above two values are not part of the automatic tuning procedure and must be entered manually.
CALIBRATING THE POSITION FEEDBACK POTENTIOMETER
Before proceeding with the feedback potentio meter calibration, you should ensure, in configuration level, that module position 2 (2a), or 3 (3a), has its ‘id’ indicating ‘Pot.i’, (meaning Potentiometer Input). Continue to scroll down the module configuration list. ‘func’ should be set to ‘Vpos’, ‘VAL.L’ must be set to ‘0’ and ‘VAL.H’ to ‘100’. Exit from configuration and you are now ready to calibrate the position feedback potentiometer. Proceed as follows.
1. In Operator level , press the AUTO/MAN button to put the controller in Manual mode.
2. Drive the valve to its fully open position using
.
3. Press
until you get to ‘ip-List’.
4. Press
to get to ‘PCAL-OFF’.
Page 54
Page 55
Tuning
Installation and Operat i on Handbook
4-10 2408 and 2404 Controller
GAIN SCHEDULING
Gain scheduling is the automatic transfer of control between one set of PID values and another. In the case of the 2408 and 2404 controllers, this is done at a presettable process value. It is used for the more difficult to control processes which exhibit large changes in their response time or sensitivity at, for example, high and low temperatures, or when heating or cooling.
The 2408 and 2404 has two sets of PID values. You can select the active set from either a digital input, or from a parameter in the PID list, or you can transfer automatically in gain scheduling mode. The transfer is bumpless and will not disturb the process being controlled.
To use gain scheduling, follow the steps below:
Step1: Enable in configuration level
Gain scheduling must first be enabled in Configuration level. Goto the Inst Conf list, select the parameter Gsch, and set it to YES.
Step 2: Set the transfer point
Once gain schedu l ing has been enabled, the parameter G.SP will appear at the top of the Pid list in FuLL access level. This sets the value at which transfer occurs. PID1 will be active when the process value is below this setting and PID2 when the process value is above it. The best point of transfer depends o n the characteristics of the process. Set a value between the co ntrol regions that exhibit the greatest change.
Step 3: Tuning
You must now set up the two sets of PID values. The values can be manually set, or automatically tuned as described earlier in this chapter. When tuning automatically you must tune twice, once above the switching point G.SP and again below the switching point. When tuning, if the process value is below the transfer point G.SP the calculated values will automatically be inserted into PID1 set and if the process value is above G.SP, the calculated values will automatically be inserted into PID2 set.
GSch
YES
G.Sp
350
Page 56
Page 57
Programmer Operati on Installation and Operat i on Handbook
5-2 2408 and 2404 Controller
WHAT IS SETPOINT PROGRAMMING?
Many applications need to vary temperature, or pr ocess value, with time. Such ap plications need a controller which varies a setpoint as a function of time; all 2408 and 2404 models can do this.
The setpoint is varied by using a setpoint program. Within each 2408 and 2404 controller, there is a software module called the programmer, which stores one, or more, such programs and drives the setpoint according to the selected program. The program is stor ed as a series of ‘ramp’ and ‘dwell’ segments, as shown below.
(If the 8-segment programmer is being used, then the information in the next paragraph does not apply.)
In each segment you can define t he state of up to eight (8 ) digital outputs, each of which can be used to tr i gger external events. These are called event outputs and can drive either relay, logic, or triac outputs, depending on the modules installed.
A program is executed either, once, repeated a set number of times, or repeated continuously. If repeated a set number of times, then t he number of cycles must be specified as part of the program.
Fig 5-1 Setpoint profile
T
ime
Setpoint
Page 58
Page 59
Programmer Operati on Installation and Operat i on Handbook
5-4 2408 and 2404 Controller
PROGRAMMER STATES
The programs have five states: Reset, Run, Hold, Holdback and End.
State Description Indication
Reset
In Reset, the programmer is inactive and the controller behaves as a standard controller, with the setpoint determined by the value set in the lower readout.
Both the RUN and HOLD lights are OFF
Run
In Run, the programmer varies the setpoint according to the active program.
RUN light on
Hold
In Hold, the program i s frozen at its current point. In this state you can make temporary changes to any program parameter (f or exampl e, a target setpoint, a dwell time, or the ti me remaining in the current segment). Such changes will only remain
effective until the program is reset and run again, when they will be overwritten by the stored program values.
Note: When a program is running, you cannot
alter
a cALL
cALLcALL
cALLed program until it becomes active within
that program.
HOLD light on
Holdback
Holdback indicates that the measured value is lagging the setpoint by more than a preset amount and that the program is in Hold, waiting for the process to cat ch up. See Holdback in the section on Automatic behaviour later this chapter.
HOLD light flashes
A master c ont roller can re-transmit a s et poi nt value to a number of slave uni t s using PDSIO setpoint retransmission. Any of the slave units can generate a holdback signal which will also flash the HOLD light. Holdback will also occur if the PDSIO output is open circuit. This can be disabled in configuration by selecting the PdS out put as SP.nH - ‘setpoint retransmission without holdback’
HOLD light flashes
End
The program is complete.
RUN light flashes
Table 5-2 Program States
Page 60
Page 61
Programmer Operati on Installation and Operat i on Handbook
5-6 2408 and 2404 Controller
RUNNING A PROGRAM USING THE RUN/HOLD BUTTON
If you are using a 4, or 20, program version of the controller, you must first select the number of the program that you want to run. Do this in the run list see the previous topic,
Running a program from the Run list.
Then:
RUN
HOLD
RUN / HOLD
button
Press once to run a program (RUN light on) Press again to hold a program (HOLD light on) Press again to cancel hold and continue running (HOLD light off, RUN light on) Press and hold in for two seconds to reset a program (RUN and HOLD lights off).
Note: The RUN/HOLD button can be disabled, either when ordering the controller, or subsequently in configuration. This will force you to operate the programmer from the run list all the time. The main advantage of this method is that it will reduce the chance of accidentally changi ng the state of a program.
AUTOMATIC BEHAVIOUR
The preceding to pics explain how to operate the programmer manually. The following topics cover aspects of its automatic behaviour: Servo, Holdback and Power Failure.
Servo
When a program is RUN, the setpoint can start either from the initial controller setpoint, or from the process value. Whichever it is, the starting point is called the ‘servo’ point and you set it up in configuration. When the program starts, the transition of the setpoint to its starting point is called ‘servoing’.
The normal method is to servo to the process value, because this will produce a smooth and bumpless start to the process. However, if you want to guarantee the time period of the first segment, you should set the controller to servo to its setpoint.
Holdback
As the setpoint ramps up, or down (or dwells), the measured value may lag behind, or deviate from, the setpoint by an undesirable amount. ‘Holdback’ is available to freeze the program at its current state, should this occur. The action of Holdback is the same as a deviation alarm. It can be enabled, or disabled. Holdback has two parameters - a value and a type. If the error from the setpoin t exceeds the set ‘holdback’ value, then the Holdback feature, if enabled, will automatically freeze the program at its current point and flash the HOLD light. When the error comes within the holdback value, the program will resume normal running.
There are four different Holdback types. The choice of type is made by setting a parameter when creating a program, and may be one of the following:OFF Disables Holdback therefore no action is taken.
Page 62
t2
Page 63
Programmer Operati on Installation and Operat i on Handbook
5-8 2408 and 2404 Controller
CONFIGURING THE PROGRAMMER
When first installing a programmer you should check that the configuration conforms to your requirement. Configuration defines:
the number of stored programs (multi-programmer only)
the holdback strategy
the power fail strategy
the servo type
if event out puts are available (not 8-segment programmer)
if program synchronisation is available. (not 8-segment programmer)
selection of program number using digital inputs (multi-programmer only)
To check, or change, the configuration, select Configuration level. See Chapter 6.
Programmer list header
After selecting Configuration mode, press
until the PROG
ConF header is displayed.
Press
Number of programs
Use or to select:
•••• nonE: Disable built-in 8-segment programmer
•••• 1: Enable built-in 8-segment programmer
For 16-segment programmers:
•••• nonE
nonEnonE
nonE: no programs
•••• 1: One stored program
•••• 4: Four stored programs
20: Twenty stored programs
Press
Holdback Strategy
Use
or to select:
SEG: Holdback type to be set in each segment
ProG: Holdback type to be set for the whole program
Press
Continued on the next page.
Page 64
Page 65
Programmer Operati on Installation and Operat i on Handbook
5-10 2408 and 2404 Controller
CONFIGURING DIGITAL INPUTS TO SELECT PROGRAM NUMBER
The program number can be selected by external BCD inputs from, for example, a thumbwheel switch. The appropriate number of digital inputs must be installed in the controller and be configured for this function - see Chapter 6, Configuration. To invoke this mode of operation, the parameter ‘bcd’ in ‘inst-Conf’ must be set to ‘PrOg’.
bcd
PrOG
P
ress until you reach bcd.
Use the
or buttons, to select PrOG’.
Page 66
Page 67
Programmer Operati on Installation and Operat i on Handbook
5-12 2408 and 2404 Controller
Ramp units
Use
or to select:
Sec
min
Hour
Press
Dwell units
Use
or to select:
Sec
min
Hour
Press
Number of program cycles
Use
or to set the number of program cycles required from
1 to 999, or ‘cont’ for continuous cycling.
Press
Segment number
Use
or to select the number, from 1 to 16.
(1 to 8 in 8-segment programmers) The parameters that follow SEG.n set up the characterist i cs of the individually-selected segment number. By defining the characteristics of each segment of the program, you define the whole program.
Press
Continued on the next page.
Page 68
!
Page 69
Programmer Operati on Installation and Operat i on Handbook
5-14 2408 and 2404 Controller
Ramp rate
Ramp rate for rmP.r segments Using
or , set a value for the ramp rate, ranging from 0.0 to
999.9. The units are the ramp units (rmP.U) set earlier in this sequence.
Press
Duration time
Time for a dwEl segment, or time to target for a rmP.t segment. Set the time using
or . You have set the units earlier in
this sequence. [dwL.U defines the units for dwEl segments: rmP.U defines the units for rmP.t segments.]
Press
Called program number
Only appears for cALL segments.
(multi-program controllers only)
Set a called program number from 1 to 4, or from 1 to 20, using
or .
Press
Number of cycles of the cALLed program
Only appears for cALL segments.
(multi-program controllers only)
Sets the number of cycles of the cALLed program from 1 to 999, using
or .
Press
Continued on the next page.
Page 70
Page 71
Programmer Operati on Installation and Operat i on Handbook
5-16 2408 and 2404 Controller
Power Value [End Segment]
Use
or to set the power value in the range ±100.0%. This power level is clipped by the parameters ‘OP.Hi and ‘OP.Lo before being applied to the process.
Note: In programmer/controller softw are versions 3.56 onwards this parameter has been replaced by a parameter
End.P
End.PEnd.P
End.P whic h appe ar s at the end of the Output Li st, see
Chapter 2
P
ress to return to the ProG-LiSt header.
Page 72
Page 73
Configuration Installation and Operation Handbook
6-2
2
408 and 2404 Controller
SELECTING CONFIGURATION LEVEL
There are two alternative methods of selecting Configuration level:
If you have already powered up, then follow the access instructi ons given in Chapter 3,
Access levels.
Alternatively, press
and together when powering up the controller. This will
take you directly to the ConF password display.
Password entry
When the ConF display appears, you must enter the
Configuration password (which is a number) in order to
gain access to Configu r ation level.
Enter the password using the
or buttons.
The configuration password is set to 2 when the
controller is shipped from the factory.
Once the correct password has been entered, there is a two
second delay, after which the lower readout will change to
PASS indicati ng that access is now unlocked.
Note: A special case exists if the password has been set to
0. In this situ ation, access is permanently unlocked and
the lower readout will always show PASS’.
Press to enter configuration.
(If an incorrect password has been entered and the
controller is still ‘locked’ then pressing
at this point
will take you to the Exit display with no’ in the lower
readout. Simply press to return to the ConF
display.)
You will obtain the first display of configuration.
Page 74
Page 75
Configuration Installation and Operation Handbook
6-4
2
408 and 2404 Controller
NAVIGATION DIAGRAM (PART A)
Instrument Process Value Input Setpoi nt Alarms Programmer Logic inputs Config
Config Config Config Config Config Config
Fig 6.1a Navigation Diagram (P art A)
m-A
diSA
ti.td
SEc
CooL
Lin
Act
rEv
CtrL
Pid
inSt
ConF
rmt
nonE
rmP.U
PSEc
Pr.tr
OFF
m.tr
OFF
rm.tr
OFF
nSP
2
SP
ConF
AL
ConF
AL1
FSH
Ltch
no
bLoc
no
AL2
FSL
Ltch
no
bLoc
no
AL3
OFF
Ltch
no
bLoc
no
AL4
OFF
Ltch
no
bLoc
no
PROG
ConF
PtyP
20
Pwr.F
cont
Srvo
to.PV
out
no
SYnc
no
iP
ConF
id
LoG.i
Func
mAn
LA/b
ConF
inPt
k.tc
CJC
Auto
inp.L
0.0
VaL.H
100.0
VaL.L
0.0
inp.H
50.0
imp
Auto
HbAc
SEG
unit
o
C
dEc.P
nnnn
PV
ConF
rnG.H
1200
rnG.L
0
FOP
no
Sbr.t
b.
Pd.tr
no
Fwd.t
nonE
PwrF
YES
r-h
diSA
GSch
no
bcd
nonE
dtYP
PV
Page 76
M
c
t
t
Page 77
Configuration Installation and Operation Handbook
6-6
2
408 and 2404 Controller
NAVIGATION DIAGRAM (PART C)
Calibration Password Config
Config
Fig 6.1c Navigation Diagram (Part C)
ACC.P
1
cnF.P
2
Exit
no
PASS
ConF
cAL
nonE
UCAL
no
pt1.L
0
pt1.H
0
OF1.L
0.0
CAL
ConF
OF1.H
0.0
pt2.L
0
pt2.H
0
OF2.L
0.0
OF2.H
0.0
Page 78
Page 79
Configuration Installation and Operation Handbook
6-8
2
408 and 2404 Controller
Name Description Values Meaning
pV
pVpV
pV
Process value config
unit
Instrument uni ts
0
C
Celsius
0
F
Fahrenheit
0
k
none
Kelvin Display units blanked
dec.p
Decimal plac es in the
nnnn
None
displayed value
nnn.n nn.nn
One Two
rng.L
Range low
Low range limit. Also setpoint limit for alarms and programmers
rng.h
Range high
High range limit. Also setpoint lim i t for alarms and programmers
Notes:
1. Pyrometer Emmisivity
Controllers which are specifically supplied for pyrometer inputs (not Exergen K80), have the
curve downloaded in the Custom Input. The parameter, EmiS, Pyrometer Emmis ivity, appears in the Input List on page 2-15. This parameter is also now correctly adjusted.
2. Range
If a decimal point was configured, negative display and setpoint ranges were limited to -99.9
in previous software versions. The range has been increased to -199.9 by combining the negative sign with the figure one. This allows Setpoints, Process Variables, Alarm Setpoints and Programmers to be set to -199.9.
Page 80
Page 81
Configuration Installation and Operation Handbook
6-10
2
408 and 2404 Controller
Name Description Values Meaning
SP
SPSP
SP
Setpoint configuration
nSP
Number of setpoints
2, 4, 16
Select number of setpoints available
rm.tr
Remote Tracking
OFF
Disable
trAc
Local setpoint tracks remote setpoint
m.tr
Manual Track
OFF
Disable
trAc
Local setpoint tracks PV when in manual
Pr.tr
Programmer Track
OFF
Disable
trAc
Local setpoint tracks programmer SP
rmP.U
Setpoint rate limit units
PSEc
Per second
Pmin
Per minute
PHr
Per hour
rmt
Remote setpoint configuration
nonE
Disable
SP
Remote setpoint
Loc.t
Remote setpoint + local trim
rmt.t
Remote trim + local setpoint
Page 82
Page 83
Configuration Installation and Operation Handbook
6-12
2
408 and 2404 Controller
The following parameters apply if the standard 8-segment programmer is to be configured.
PROG
PROGPROG
PROG
Programmer configuration Values Meaning
PtyP
Programmer type
nonE
Programmer disabled (
factory setting)
1
8-segment program mer enabled
HbAc
Holdback
SEG
ProG
Holdback is indivi dual l y selectable in each segment. Holdback is applied across the whole Program.
Pwr.F
Power fail recovery
cont
Continue from las t setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo
Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
The following parameters apply if a 16-segment programmer is to be configured.
PROG
PROGPROG
PROG
Programmer configuration Values Meaning
PtyP
Programmer type
nonE
Programmer disabled
1
Single program
4
Four programs
20
Twenty programs
HbAc
Holdback
SEG
ProG
Holdback is indivi dual l y selectable in each segment. Holdback is applied across the whole Program.
Pwr.F
Power fail recovery
cont
Continue from las t setpoint (SP)
rmP.b
Ramp from PV to SP at last ramp rate
rSEt
Reset the program
Srvo
Starting setpoint of a
to.PV
From the Process Value (PV)
program (Servo point)
to.SP
From the setpoint
out
Programmable event outputs
no YES
Disabled Enabled
SYNC
Synchronisation of programs of several programmers
no YES
Disabled Enabled
Page 84
Page 85
Configuration Installation and Operation Handbook
6-14
2
408 and 2404 Controller
Name Description Values Meaning
AA
AAAA
AA
Alarm relay configuration
id
Identity
rELy
Relay output
Func
Function
nonE
No function
dIG
Digital output
SEnS
Digital output sense
nor
Normal (output energi ses when TRUE, e.g. program events)
inv
Inverted (output de-energis es when
TRUE, e.g. alarms)
The following digital events appear after SEnS. Any one, or more, of the events can be combined on to the output (see Fig. 6-2) by selecting YESin the lower readout.
1 - - -
Alarm 1 acti ve
YES / no (- - -) = alarm type (e.g. FSL).
2 - - -
Alarm 2 acti ve
YES / no
If an alarm has not been confi gured
3 - - -
Alarm 3 acti ve
YES / no in ‘AL ConF’ l i st, then display will
4 - - -
Alarm 4 acti ve
YES / no differ:- e.g. Alarm 1 = ‘AL 1’.
mAn
Controller in manual mode
YES / no
Sbr
Sensor break
YES / no
SPAn
PV out of range
YES / no
Lbr
Loop break
YES / no
Ld.F
Load failure alarm
YES / no
tunE
Tuning in progress
YES / no
dc.F
Voltage output open circuit, or mA output open circuit
YES / no
rmt.F
PDS module m easurement connection or remote input open circuit
YES / no
iP1.F
Input 1 failure
YES / no
nw.AL
New Alarm has occurred
YES / no
End
End of setpoint rat e l i mit, or end of program
YES / no
SYnc
Program Synchronis ation active
YES / no
PrG.n
Programmer event out put active, where ‘n’ = event number from 1 to 8. (Not available with 8-segment programmer.)
YES / no
Figure 6-2 Combining several digital events on to one output
dIG
S
EnS
nor
inv
Output
Module
Digital Events
OR
Page 86
Page 87
Configuration Installation and Operation Handbook
6-16
2
408 and 2404 Controller
Name Description Values Meaning
For ‘id
idid
id’ = ‘Pdsi’ (PDS setpoint input) use this parameter table:
Func
Function
SP.iP
PDS setpoint input
VAL.L
Setpoint Displayed Value - Low
VAL.H
Setpoint Di splayed Value - High
Note: Having configured the module function as remote setpoint you must then specify the type of
remote setpoint in the SP-conf list
JA
JAJA
JA
Comms 2 module config
As per Comm s 1 module configuration
VAL.L
100%
0%
VAL.H
Displayed Value
Electrical Input
Page 88
Page 89
Configuration Installation and Operation Handbook
6-18
2
408 and 2404 Controller
Name Description Values Meaning
For ‘id
idid
id’ = ‘dC.OP’, ‘dc.rE’, or ‘dc.OP’ use this parameter table:
Func
Function
nonE
Function disabled
HEAt
Heating output
COOL
Cooling output
PV
Retransmission of PV
wSP
Retransmission of setpoint
Err
Retransmission of error signal
OP
Retransmission of OP power
VAL.L
% PID, or Retrans ’ n Value,
giving minimum output
VAL.H
% PID, or Retrans ’ n Value,
giving maximum output
unit
voLt = Volts, mA = milliamps
Out.L
Minimum elec trical output
Out.H
Maximum electrical output
For ‘id
idid
id’ = ‘LoG.i’ (i.e logic input) use the
LA
LALA
LA Conf’ list on Page 6-13.
2A
2A2A
2A/bbbb/CCCC
Module 2 configuration As per module 1 conf i guration, but excluding the ‘SSr.1’, ‘SSr.2’ functions. id
Identity of m odul e installed. As per module 2 plus :
tPSU
Transmitter power supply
Pot.i
Potentiomet er i nput
For ‘id
idid
id’ = ‘Pot.i (i.e. potentiometer input module) use this parameter table:
Func
Function
nonE
Function disabled
rSP
Remote Setpoint
Fwd.i
Feedforward input
rOP.h
Remote OP power max.
rOP.L
Remote OP power min.
VPoS
Motorised valve position
VAL.L
Displayed value low equivalent to 0% potentiometer pos i tion
VAL.H
Displayed value high equivalent to 100% potentiometer pos i tion
V
AL.L
Out.H
O
ut.L
VAL.H
Electrical Output
%PID, or Retransmission Value
V
AL.L
100%
0
%
VAL.H
Displayed value
Potentiometer position
Page 90
Page 91
Configuration Installation and Operation Handbook
6-20
2
408 and 2404 Controller
Name Description Values Meaning
4A
4A4A
4A
Module 4 configuration
Note: This option is not available on controllers from 01 Jan-04
id
Identity of m odul e installed
HCS
High Current Switch
Func
Function
nonE
Function disabled
dIG
Digital output func tion
HEAt
Heating output
COOL
Cooling output
VAL.L
% PID demand signal giving
minimum output − ‘Out.L
VAL.H
% PID demand signal giving
maximum output − ‘Out.H
Out.L
Minimum electrical output
Out.H
Maximum electrical output
SEnS
Sense of output
(Only if ‘Func’ = ‘dIG’)
nor
Normal (output energi ses when TRUE, e.g. program events)
inv
Inverted (output de-energis es
when TRUE, e.g. alarms) When SEnS appears, then further parameters are available. These are identical to t hose in the AA ConF list on Page 6-14.
Cust
8-point Custom Linearisation
(1)
in 1
Custom input 1
VAL.1
Linearisation Value repres enting in 1
in 8
Custom input 8
VAL.8
Linearisation Value repres enting in 8
VAL.L
Out.H
Out.L
VAL.H
PID Demand Signal
Electrical Output
Note:
1.
Custom Linearisation is only available when ‘3a-Conf’or iP- ConF list has ‘inpt’ set to ‘mV.C’, or ‘mA.C’, or ‘V.C’.
2. The values and inputs must be continuously increasing or decreasing
VAL.1
VAL.3
in 8
in 1 in 3
VAL.8
Displayed Value
Electrical Input
Page 92
Page 93
Configuration Installation and Operation Handbook
6-22
2
408 and 2404 Controller
DC Output Calibration
The following parameters apply to DC output modules ie for
rcAL = 1A.Hi to 3A.Lo
cAL.H
Output Calibration High
0 0 = Factory set calibration.
Trim value until out put = 9V, or 18mA
cAL.L
Output Calibration Low
0 0 = Factory set calibration.
Trim value until out put = 1V, or 2mA
User calibration
UCAL User calibration enable Yes/no pt1.L
Low calibration point for Input 1 The factory calibration point at which the l ow
point offset was performed.
pt1.H
High calibration point for Input 1 The factory calibration point at which the high
point offset was performed.
OF1.L
Offset Low for Input 1 Calculated offset, in display uni t s.
OF1.H
Offset High for I nput 1 Calculated offset, in display units.
pt2.L
Low calibration point for Input 2 The factory calibration point at which the l ow
point offset was performed.
pt2.H
High calibration point for Input 2 The factory calibration point at which the high
point offset was performed.
OF2.L
Offset Low for Input 2 Calculated offset, in display uni t s.
OF2.H
Offset High for I nput 2 Calculated offset, in display units.
Name Description Values Meaning
PASS
PASSPASS
PASS
Password configuration
ACC.P
FuLL or Edit level password
cnF.P
Configuration level password
Note:- When passwords are changed pl ease make a note of the new numbers
Exit
ExitExit
Exit
Exit configuration
no/YES
Page 94
Page 95
Configuration Installation and Operation Handbook
6-24
2
408 and 2404 Controller
DeviceNet
To configure Function, Baud Rate, Resolution and Node Address:-
Do This The Display You Should
See
Additional Notes
1. Press as many times as necessary to select ‘HA’
This is the position in which
the DeviceNet modul e is fitted
2. Press to read ‘id’
If the module is present
id = ‘cms’ (digital communications) or ‘none’ if the module is not present
3. Press to read ‘Func
If the DeviceNet module is
fitted ‘Func’ = ‘dnEt’ and will be read only
4. Press to read ‘bAud
5. Press
and to
select the baud rate
Baud rate can be set to
125(K), 250(K) or 500(K)
6. Press to read ‘rES
7. Press
and to
select ‘FuLL’ or ‘int
FuLL - the decimal point
position is implied, eg 100.1 is transmi t ted as 1001.
int’ - rounded to the nearest integer value
HA
ConF
id
cms
Func
dnEt
bAud
500
res
FuLL
Page 96
Page 97
Configuration Installation and Operation Handbook
6-26
2
408 and 2404 Controller
Page 98
1
Page 99
User Calibration Installation and Operation Handbook
7-2 2408 and 2404 Controller
USER CALIBRATION ENABLE
The User calibration facility must first be enabled in configuration level by setting the parameter ‘UCAL' in the input conf list to 'YES'. This will make the User calibration parameters visible in Operator ‘FuLL’ level. Select configuration level as shown in Chapter 6, Configuration.
+
The Calibration Configuration List
Press
until you reach the ‘CAL-Conf’ list.
Press until you reachUCAL’.
User Calibration Enable
Use or to select:
YES: Calibration enable
no: Calibration disabled
Press
and together to go to the Exit display.
Exit configuration
Use
or to select ‘YES’ to return to Operator level.
CAL
UCAL
no
Page 100
3
Loading...