G168-0001
ULTRA SLIMPAK
®
G168-0001
DC Powered AC Input Limit Alarm
Provides Relay Contact Closures
at a Preset AC Input Level
Programmable HI or LO, Failsafe or Non-failsafe
Field Configurable Input Ranges
LED Trip and Input Indicators
Description
The Ultra Slim Pak G168 is a DIN rail mount, DC powered, AC
voltage or current input limit alarm with dual setpoints and two
contact closure outputs. The field configurable input and alarm
functions offer flexible setpoint capability. Input voltage spans
from 100mV to 250VAC and input current spans from 10mA to
100mA AC can be field configured. For current input spans of 1 to
5 Amps a 0.1 Ohm (5W) shunt resistor (Model# C006) is available.
The G168 is configurable as a single or dual setpoint alarm, with HI or
LO trips and failsafe or non-failsafe operation. Also included are
adjustable deadbands (0.25 to 5% of full scale input) for each setpoint.
The G168 will accept any DC voltage between 9 and 30VDC.
Diagnostic LEDS
The G168 is equipped with three front panel LEDs. The dual
function green LED is labeled INPUT and indicates line power and
input signal status. Active DC power is indicated by an illuminated
LED. If this LED is off, check DC power and the wiring connection.
If the input signal is more than 110% of the full scale range, the LED
will flash at 8 Hz. Below 0%, it flashes at 4 Hz. Two red LEDs indicate
the relay state for each setpoint. An illuminated red LED indicates
the tripped condition.
Output
The G168 is equipped with two SPDT (form C) relays, rated at
120VAC or 28VDC at 5 Amperes. Each of these relays is independently controlled by the field configurable setpoint and deadband.
Operation
The field configurable G168 limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe operation. Each of the
setpoints have a respective HI or LO deadband. In a tripped
condition, the setpoint is exceeded and the appropriate red LED
will illuminate. The trip will reset only when the process falls below
the HI deadband or rises above the LO deadband (see Figure 1).
For proper deadband operation, the HI setpoint must always be
set above the LO setpoint. In failsafe operation, the relay is
energized when the process is below the HI setpoint or above the
LO setpoint (opposite for non-failsafe). In the failsafe mode, a
power failure results in an alarm state output.
Flexible Power Supply Accepts 9 to 30 VDC
ASIC Technology for Enhanced Reliability
RoHS Compliant
Dynamic Deadband
Circuitry in the G168 prevents false trips by repeatedly sampling
the input. The input must remain beyond the setpoint for 100
milliseconds, uninterrupted, to qualify as a valid trip condition.
Likewise, the input must fall outside the deadband and remain
there for 100 milliseconds to return the alarm to an untripped
condition. This results in a “dynamic deadband” (based on time)
in addition to the normal deadband.
Configuration
Unless otherwise specified, the factory presets the Model G168 as
follows:
Input: Voltage
Range:
Output: Dual, SPDT
Failsafe: No
Deadband: A, B: 0.25%
The DC power input accepts any DC source between 9 and 30V;
typically a 12V or 24VDC source is used (see Accessories).
For other I/O ranges, refer to Table 1 and Figure 4 to reconfigure
switches SW1 and SW2 for the desired input type, range and
function.
1. With DC power off, position input switch "SW1-9, 10" for voltage
or current.
2. Set position 1 through 8 of “SW1” for the desired input range
(see Table 1).
3. Set position 1 and 2 of "SW2" to ON for a HI trip setpoint or
OFF for a LO trip (see Figure 4).
4. Set position 4 of "SW2" to ON for non-failsafe operation or OFF
for failsafe operation (e.g., alarm trips when power fails).
0-500mVAC
Trip: A:HI, B:LO

noitcnuF
2WSrotceleS
123 4
IHBpirT
IHApirT
efasliaF-noN
:yeK desolCroNO=1=
Figure 1: Limit alarm operation and effect of deadband.
Calibration
Note: To maximize thermal stability, final calibration should be
performed in the operation installation, allowing approximately 1
to 2 hours for warm up and thermal equilibrium of the system.
1. After configuring the dip switches, connect the input to a
calibrated AC source and apply power. Refer to the terminal
wiring (Figure 6).
2. Setpoint: set deadband at its minimum (fully counterclockwise)
before adjusting the setpoint. With the desired trip input applied,
adjust the setpoint until the relay trips. For HI trip calibration, start
with the setpoint above the desired trip (fully clockwise). For LO
trip calibration, start below the desired trip (fully counterclockwise).
Relay Protection & EMI Suppression
When switching inductive loads, maximum relay life and transient
EMI suppression is achieved using external protection (see Figures
2 and 3). Place all protection devices directly across the load and
minimize all lead lengths. For AC inductive loads, place a properly
rated MOV across the load in parallel with a series RC snubber. Use
a 0.01 to 0.1uF pulse film capacitor (foil polypropylene recommended) of sufficient voltage, and a 47 ohm, 1/2W carbon
resistor. For DC inductive loads, place a diode across the load (PRV
> DC supply, 1N4006 recommended) with (+) to cathode and (-) to
anode (the RC snubber is an optional enhancement).
Figure 2: DC Inductive Loads
Figure 3: AC Inductive Loads
3. Deadband: Set deadband to its minimum (fully counterclockwise). Set the setpoint to the desired trip. Adjust the input until
the relay trips. Readjust deadband to 5% (fully clockwise). Set the
input signal to the desired deadband position. Slowly adjust
deadband until the relay untrips
Table 1: G168 Input Range Settings Table 2: G168 Trip Settings
segnaR1WSrotceleS
egatloVtnerruC 123 45 6 78 9 01
Vm001Am01
Vm002Am02
Vm005Am05
V1Am001
V2
V5
V01
V02
V05
V001
V002
V052
epyTtupnI
tnerruC
egatloV
:yeK desolCroNO=1=

"B" LO Trip
"B" HI Trip
Off
On
"A" LO Trip
"A" HI Trip
Off
Not Used
On
Failsafe
Non-failsafe
Off
Not Used Not Used
On
Figure 4: G168 Function Selection Switch-Settings (SW4) Factory Default Settings
Figure 5: G168 Factory Calibration; 0-500mV,
A-HI/B-LO, Non-Failsafe
Figure 7: Mounting Multiple Modules
Figure 6: G168 Wiring Diagram
Note: All Ultra SlimPak modules are designed to operate in ambient
temperatures from 0 to 55°C when mounted on a horizontal DIN rail. If
five or more modules are mounted on a vertical rail, circulating air or
model HS01 Heat Sink is recommended. Refer to HS01 Technical
Bulletin (#721-0549-00) or contact the factory for assistance.

Specifications
Inputs
Voltage Input
Range: 100mV to 250VAC
Impedance: >100K Ohms
Overvoltage: 300VAC, max.
Current Input
Range: 10mA to 100mA AC
Impedance: 20 Ohms, typical
Overcurrent: 200mA AC, max.
Overvoltage: 60V peak (protected by
self resetting fuse)
Frequency Range: 40 to 400Hz
Common Mode (Input to Gnd):1800VDC, max.
LED Indicators
Input Range (Green)
>110% input: 8Hz flash
Setpoint (Red)
Tripped: Solid red
Safe: Off
Limit Differentials (Deadbands)
>50mV/5mA: 0.25% to 5% of span
<50mV/5mA: 1% to 5% of span
Response Time
Dynamic Deadband:
Relay status will change when proper
setpoint/process condition exists for 100msec.
Normal Mode (analog filtering):
<250mSec, (10-90%)
Setpoints
Effectivity:
Setpoints are adjustable over 100% of
the selected input span
Repeatability (constant temp.):
0.2% of full scale
Stability
Temperature:
Common Mode Rejection
DC to 60Hz: 120dB
Isolation
1800VDC between contacts, input & power
EMC Compliance (CE Mark)
EMC: EN61326-1:2013
Safety: EN61010-2:2013
Humidity (Non-Condensing)
Operating: 15 to 95% @45°C
Soak: 90% for 24hours @65°C
Temperature Range
Operating: 0 to 55°C (32 to 131°F)
Storage: -25 to 70°C (-13 to 158°F)
Power
Consumption: 1.5W typical, 2.5W max.
Supply Range: 9 to 30VDC, inverter isolated
+0.025% of full scale/°C, max.
Relay Contacts
2 SPDT (2 form C) Relays, 1 Relay per
setpoint
Current Rating (resistive):
120VAC: 5A; 240VAC: 2A; 28VDC: 5A
Material: Gold flash over silver alloy
Electrical Life:105 operations at rated load
Note: External relay contact protection is
required for use with inductive loads
(see Figures 2 & 3).
Mechanical Life: 10
Wire Terminations
Screw terminals for 12-22 AWG
Agency Approvals
CSA certified per standard C22.2, No. 0-M91
and 142-M1987 (File No. LR42272)
UL recognized per standard UL508
(File No.E99775)
CE Conformance per EMC directive 2004/
108/EC and Low Voltage directive 2006/
95/EC.
RoHS Compliant
7
operations
Ordering Information
Models & Accessories
Specify:
1. Model: G168-0001
2. Accessories: (see Accessories)
3. Optional Custom Factory Calibration; specify C620 with desired
input and output range.
Accessories
SlimPak “G” series modules will mount on standard TS32 (model MD02) or
TS35 (model MD03) DIN. In addition, the following accessories are available:
HS01 Heat Sink
MD03 TS35 x 7.5 DIN Rail
WV905 24VDC Power Supply (0.5Amp)
H910 24VDC Power Supply (1Amp)
H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C664 I/O Descriptive Tags
C006 Shunt Resistor (0.1W, 5A max.)