Eurotherm G118-0002 Data Sheet

Page 1
G118-0002
ULTRA SLIMPAK
®
G118-0002
DC Powered RTD Input Limit Alarm
Provides Relay Contact Closures
at a Preset RTD/Resistance Input Level
Programmable HI or LO, Failsafe or Non-failsafe Field Configurable Ranges for Platinum, Nickel
and Copper RTDs
Ultra Slim Housing for High Density Installations
Description
The Ultra SlimPak G118 is a DIN rail mount, RTD input limit alarm with dual setpoints and two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability. There are up to eight temperature ranges available for each RTD type to ensure accuracy and maximize setpoint resolution.
The G118 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint and a flexible DC power supply which accepts any voltage between 9 and 30VDC.
Diagnostic LEDS
The G118 is equipped with three front panel LEDs. The dual function green LED is labeled INPUT and indicates line power and input signal status. Active DC power is indicated by an illuminated LED. If this LED is off, check DC power and the wiring connection. If the input signal is more than 110% of the full scale range, the LED will flash at 8 Hz. Below 0%, it flashes at 4 Hz. Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped condition.
LED Trip and Input Indicators Flexible Power Supply Accepts 9 to 30 VDC ASIC Technology for Enhanced Reliability RoHS Compliant
Dynamic Deadband
Circuitry in the G118 prevents false trips by repeatedly sampling the input. The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This results in a “dynamic deadband” (based on time) in addition to the normal deadband.
Configuration
Unless otherwise specified, the factory presets the Model G118 as follows:
Input:
Range: 0 to 250°C
Output: Dual, SPDT
Failsafe: No
Deadband: A, B: 1.0%
The DC power input accepts any DC source between 9 and 30V; typically a 12V or 24VDC source is used (see Accessories).
Platinum (100 Ohm)
Trip: A:HI, B:LO
Output
The G118 is equipped with two SPDT (form C) relays, rated at 120VAC or 28VDC at 5 Amperes. Each of these relays is indepen­dently controlled by the field configurable setpoint and deadband.
Operation
The field configurable G118 limit alarm setpoints can be config­ured for HI or LO, failsafe or non-failsafe operation. Each of the setpoints has a respective HI or LO deadband. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the LO deadband (see Figure 1). For proper deadband operation the HI setpoint must always be set above the LO setpoint. In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.
For other I/O ranges, refer to Tables 1 through 3 and reconfigure switches SW1 and SW2 for the desired input type, range and function.
WARNING: Do not change switch settings with power applied. Severe damage will result!
1. With DC power off, position input switches 1 through 6 on “SW2” for RTD type (Table 1).
2. Set position 1 through 4 of input range switch “SW1” for the desired RTD type and input temperature range (Table 3).
3. Set position 5 and 6 of input range switch “SW1” to ON for a HI trip setpoint or OFF for a LO trip setpoint (Figure 4).
4. Set position 7 of input range switch “SW1” to ON for non-failsafe operation or OFF for failsafe operation (e.g. alarm trips upon power failure).
Page 2
Figure 1: Limit alarm operation and effect of deadband.
Calibration
1. After configuring the DIP switches, connect the input to a calibrated RTD source or a resistance decade box and apply power.
Note: To maximize thermal stability, final calibration should be performed in the operating installation, allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.
2. Setpoint Calibration: Before adjusting the setpoint, adjust the deadband pot to its minimum (fully counterclockwise). With the desired trip RTD resistance input applied, adjust the setpoint pot until the relay trips. For HI trip calibration, start with the setpoint pot above the desired trip (fully clockwise). For LO trip calibration, start with the setpoint pot below the desired trip (fully counterclockwise).
Relay Protection & EMI Suppression
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 and 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1uF pulse film capacitor (foil polypropylene recom­mended) of sufficient voltage, and a 47 ohm, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
Figure 2: DC Inductive Loads
Figure 3: AC Inductive Loads
3. Deadband Calibration: Set the deadband pot to its minimum (fully counterclockwise). Adjust the setpoint pot to the desired trip. Adjust the RTD resistance input until the relay trips. Readjust the deadband pots to 5% (fully clockwise). Set th RTD resistance input to the desired deadband position. Slowly adjust deadband (counterclockwise) until the relay untrips.
Table 1: G118 RTD Type Settings
2WSrotceleS

:yeK desolCroNO=1=
epyTDTR
123 45 6

01uC
001uC,001tP
406eFiN,005tP
0001tP
021iN
Table 2: G118 Trip Settings
noitcnuF
IHBpirT
IHApirT
efasliaF-noN
:yeK desolCroNO=1=
1WSrotceleS
567
Table 3: G118 Range Settings
egnaRtupnIDTR1WSrotceleS)smhO(ecnatsiseR
)58300.0=ahpla(0001,005,001tP 123 4 001tP*
)F¡221ot23(C¡05ot0
)F¡221ot85-(C¡05ot05-
)F¡212ot23(C¡001ot0
)F¡212ot841-(C¡001ot001-

)F¡284ot23(C¡052ot0

)F¡284ot823-(C¡052ot002-
 
)F¡2201ot23(C¡055ot0

01uC 123 4 01uC
001uC 123 4 001uC
021iN 12 34 021iN
406eFiN 123 4 406eFiN
:yeK desolCroNO=1=
)F¡2651ot23(C¡058ot0
)F¡851ot77(C¡07ot52
)F¡851ot22-(C¡07ot03-
)F¡842ot77(C¡021ot52
)F¡842ot49-(C¡021ot07-

)F¡005ot77(C¡062ot52

)F¡005ot823-(C¡062ot002-
)F¡761ot77(C¡57ot52
)F¡761ot31-(C¡57ot52-

)F¡203ot77(C¡051ot52
)F¡203ot841-(C¡051ot001-

)F¡005ot77(C¡062ot52

)F¡005ot823-(C¡062ot002-
)F¡68ot22-(C¡03ot03-
)F¡68ot211-(C¡03ot08-

)F¡212ot22-(C¡001ot03-
 
)F¡293ot22-(C¡002ot03-

)F¡806ot22-(C¡023ot03-
)F¡23ot04-(C¡0ot04-

)F¡221ot04-(C¡05ot04-
)F¡221ot823-(C¡05ot002-

)F¡212ot823-(C¡001ot002-

)F¡464ot823-(C¡042ot002-










4.911ot001
5.831ot001
5.831ot2.06
1.491ot001
1.491ot5.81
4.792ot001
3.093ot001
47.11ot0.01
47.11ot678.7
76.31ot0.01
76.31ot813.6
611.91ot0.01
611.91ot850.1
5.511ot001
5.511ot7.08
3.841ot001
3.841ot3.15
2.191ot001
2.191ot6.01
1.241ot4.99
1.241ot6.66
6.002ot4.99
5.303ot4.99
2.174ot4.99
0.406ot1.994
8.157ot1.994
8.157ot3.542
3.719ot3.542
6.5741ot3.542
ecnatsiserehtsemit01dna5era0001tPdna005tProfseulavecnatsiseR*
Page 3
Input Range See T able 3
"B" LO Trip "B" HI Trip
Off On
"A" LO Trip "A" HI Trip
Off On
Failsafe Non-failsafe
Off On
Not Used
Figure 4: G118 Input Range/Function Selection (SW1) Factory Default Settings
Figure 5: G118 Factory Cal; 0-250°C (Pt 100),
A-HI/B-LO, Non-Failsafe
Figure 7: Mounting Multiple Modules
Figure 6: Terminal Wiring Diagram for G118
Note: All Ultra SlimPak modules are designed to operate in ambient temperatures from 0 to 55°C when mounted on a horizontal DIN rail. If five or more modules are mounted on a vertical rail, circulating air or model HS01 Heat Sink is recommended. Refer to HS01 Technical Bulletin (#721-0549-00) or contact the factory for assistance.
Page 4
Specifications
Inputs
Sensors:
Pt100, Pt500, Pt1000 (0.00385Ohms/Ohm/°C);
Cu10, Cu100; Ni120, NiFe604 Sensor Connection: 3-wire. Input Ranges: See table 1.
Excitation Current (Max)
<2mA for Pt100, Pt500, Pt1000, Ni120,
Cu100 or NiFe604 <10mA for Cu10
Leadwire Resistance
40% of base sensor resistance or 100 Ohms
(whichever is less), maximum per lead.
Leadwire Effect
Less than 1% of selected span over entire
leadwire resistance range.
Input Protection
Normal Mode: Withstands ±5VDC. Common Mode (Input to Gnd): 1800VDC, max.
LED Indicators
Input Range (Green):
>110% input: 8Hz flash;
>-10% input: 4Hz flash Setpoint (Red):
Tripped: Solid red;
Safe: Off
Limit Differentials (Deadbands)
0.25% to 5% of span
Response Time
Dynamic Deadband:
Relay status will change when proper setpoint/ process condition exists for 100msec.
Normal Mode (analog filtering):
<250mSec, (10-90%)
Setpoints
Effectivity:
Setpoints are adjustable over 100% of the selected input span
Repeatability (constant temp.):
±0.2% of full scale
Stability
Line Voltage: ±0.01%/%, max. Temperature: ±0.05% of full scale/°C, max.
Common Mode Rejection
DC to 60Hz: 120dB >60Hz: 100dB
Isolation
1800VDC between contacts, input & power
EMC Compliance (CE Mark)
EMC: EN61326-1:2013 Safety: EN61010-2:2013
Humidity (Non-Condensing)
Operating: 15 to 95% @45°C Soak: 90% for 24 hours @65°C
Temperature Range
Operating: -15 to 55°C (5 to 131°F) Storage: -25 to 75°C (-13 to 158°F)
Power
Consumption: 1.5W typical, 2.5W max. Supply Range: 9 to 30VDC, inverter isolated
Relay Contacts
2 SPDT (2 form C) Relays, 1 Relay per
setpoint
Current Rating (resistive)
120VAC: 5A; 240VAC: 2A; 28VDC: 5A Material: Gold flash over silver alloy Electrical Life:10
Note: External relay protection is required for use with inductive loads (see Figures 2 & 3).
Mechanical Life: 10
Weight
0.56lbs.
Agency Approvals
CSA certified per standard C22.2, No. 0-M91
and 142-M1987 (File No. LR42272) UL recognized per standard UL508
(File No.E99775) CE Conformance per EMC directive 2004/
108/EC and Low Voltage directive 2006/ 95/EC.
RoHS Compliant
5
operations at rated load
7
operations
Ordering Information
Models & Accessories Specify:
1. Model: G118-0002
2. Accessories: (see Accessories)
3. Optional Custom Factory Calibration; specify C620 with desired
input and output range.
Accessories
SlimPak “G” series modules will mount on standard TS32 (model MD02) or TS35 (model MD03) DIN rail . In addition, the following accessories are available:
HS01 Heat Sink
MD03 TS35 x 7.5 DIN Rail
WV905 24VDC Power Supply (0.5 Amp)
H910 24VDC Power Supply (1Amp) H915 24VDC Power Supply (2.3 Amp)
MB03 End Bracket for MD03
C664 I/O Descriptive Tags
Schneider Electric Systems USA, Inc.
44621 Guilford Drive, Suite 100 Ashburn, VA 20147 703-724-7300
info@eurotherm.com or www.eurotherm.com/actionio
Action Instruments
Dimensions
Factory Assistance
For additional information on calibration, operation and installation contact our Technical Services Group:
703-724-7314
actionsupport@eurotherm.com
721-0651-00-H 09/06 Copyright© Eurotherm, Inc 2006
Chessell
Eurotherm
Loading...