Eurotherm EPC3000 User Manual

Page 1
EPC3000 Programmable Controllers
EPC3016, EPC3008, EPC3004
HA032842ENG Issue 2
Date: September 2017
Page 2
Page 3
Table of Contents EPC3016, EPC3008, EPC3004

Table of Contents

Table of Contents ........................................................................... 3
Safety Information ........................................................................ 10
Important Information................................................................................. 10
Safety and EMC ........................................................................... 11
Cybersecurity ............................................................................... 16
Introduction ................................................................................................ 16
Secure network topologies and good practices ......................................... 16
Security Features....................................................................................... 16
Principle of Secure by Default ............................................................. 16
HMI Access Level / Comms Config Mode ........................................... 17
HMI Passcodes.................................................................................... 17
Comms Config Level Passcode........................................................... 18
Ethernet security features .................................................................... 18
Communications watchdog.................................................................. 19
Configuration backup and recovery ..................................................... 19
Memory Integrity ........................................................................................ 19
Firmware .................................................................................................... 20
Achilles
Decommissioning....................................................................................... 20
®
Communications Certification..................................................... 20
Legal Information ......................................................................... 21
Introduction .................................................................................. 22
Controller Concept ..................................................................................... 22
Manual Concept......................................................................................... 22
Installation .................................................................................... 23
What Instrument Do I Have?............................................................................ 23
Unpacking Your Controller ......................................................................... 24
Order Codes .............................................................................................. 25
EPC3016 Hardware Order Codes ....................................................... 26
EPC3008 and EPC3004 Order Codes ................................................ 27
Dimensions ................................................................................................ 29
Installation.................................................................................................. 32
Panel Mounting the Controller ............................................................. 32
Panel Cut Out Sizes ............................................................................ 33
Recommended minimum spacing of controllers .................................. 33
To Remove the Controller from its Sleeve ........................................... 33
Wiring ........................................................................................... 34
Terminal Layout EPC3016 Controller............................................................... 34
EPC3016 Options ...................................................................................... 34
Terminal Layout EPC3008 and EPC3004 Controller ....................................... 35
EPC3008 and EPC3004 Options............................................................... 35
Isolation Boundaries .................................................................................. 36
EPC3008/EPC3004 Isolation............................................................... 36
EPC3016 Isolation ............................................................................... 36
Wire Sizes.................................................................................................. 37
Controller Power Supply ............................................................................ 37
Line/Mains Voltage Power Supply ............................................................. 37
Low Voltage Power Supply ........................................................................ 37
Primary Sensor Input (Measuring Input) .................................................... 38
Thermocouple Input............................................................................. 38
RTD Input............................................................................................. 38
Linear Input (mA, mV or V) .................................................................. 39
Two-Wire Transmitter Inputs ................................................................ 39
3 HA032842ENG Issue 2
Page 4
Table of Contents EPC3016, EPC3008, EPC3004
Secondary Sensor Input (Measuring Input) ............................................... 40
Secondary Thermocouple Input........................................................... 40
Secondary RTD Input .......................................................................... 40
Secondary Linear Input (mA, mV or V) ................................................ 40
Secondary Two-Wire Transmitter Inputs .............................................. 41
Input/Output 1 (IO1) ................................................................................... 42
Relay Output (Form A, normally open) ................................................ 42
Logic (SSR drive) Output ..................................................................... 42
Triac Output ......................................................................................... 42
Analogue Output.................................................................................. 43
Contact Input ....................................................................................... 43
Input/Output 2 (IO2) ................................................................................... 44
Relay Output (Form A, normally open) ................................................ 44
Logic (SSR drive) Output ..................................................................... 44
Triac Output ......................................................................................... 44
Analogue Output.................................................................................. 45
Contact Input ....................................................................................... 45
Input/Output 4 (IO4) ................................................................................... 46
Relay Output (Form A, normally open) ................................................ 46
Logic (SSR drive) Output ..................................................................... 46
Triac Output ......................................................................................... 46
Analogue Output.................................................................................. 47
Contact Input ....................................................................................... 47
Output 3 (OP3)........................................................................................... 47
General Information About Relays and Inductive Loads............................ 48
Current Transformer................................................................................... 49
Contact Closure Input (LA) ........................................................................ 49
Transmitter Power Supply.......................................................................... 50
Digital Inputs/Outputs................................................................................. 50
Example BCD Switch Wiring ............................................................... 50
Digital Communications Connections ........................................................ 51
EIA232 Wiring...................................................................................... 51
EIA485 Wiring...................................................................................... 52
EIA422 Wiring...................................................................................... 53
Ethernet Wiring .................................................................................... 53
Wiring Examples ........................................................................................ 54
Heat/Cool Controller ............................................................................ 54
CT Wiring Diagram .............................................................................. 55
Start Up Modes ............................................................................ 56
Start up............................................................................................................. 56
Start up Diagnostic mode................................................................................. 56
General Description of Front Panel Displays ................................................... 57
EPC3016.................................................................................................... 57
EPC3008.................................................................................................... 57
EPC3004.................................................................................................... 58
General Description of Operator Buttons................................................... 59
Button Layout....................................................................................... 59
Button Operation.................................................................................. 59
Start Up—New Unconfigured Controller .......................................................... 61
Quick Start Tables...................................................................................... 62
Quick Code Set 1................................................................................. 62
Quick Code Set 2................................................................................. 63
Quick Codes DIO................................................................................. 63
To Save or Discard Quick Codes ......................................................... 64
To Re-Enter Quick Code mode............................................................ 64
Start Up - New Configured Controller .............................................................. 65
Bar Graph ............................................................................................ 65
Setpoint................................................................................................ 65
Subsequent Start-ups ...................................................................................... 66
Start-up Modes .......................................................................................... 66
Standby...................................................................................................... 67
Auto-scaling of decimal point............................................................... 68
4 HA032842ENG Issue 2
Page 5
Table of Contents EPC3016, EPC3008, EPC3004
Operator Levels ........................................................................... 69
Overview .......................................................................................................... 69
Operator Level 1 .............................................................................................. 70
Manual Mode ............................................................................................. 70
System Messages...................................................................................... 71
Bargraph .................................................................................................... 71
Comms Configuration Active...................................................................... 71
Level 1 Operator Parameters..................................................................... 72
Level 1 Programmer Display...................................................................... 73
Programmer List .................................................................................. 73
Crows Foot Status Bar......................................................................... 73
Operator Level 2 .............................................................................................. 74
To Select Operator Level 2 ........................................................................ 74
Level 2 Operator Parameters..................................................................... 75
Level 2 Programmer Display...................................................................... 77
Programmer List .................................................................................. 77
Program Setup List .............................................................................. 78
Operator Level 3 .............................................................................................. 79
To Enter Level 3 ......................................................................................... 79
Level 3 Operator Parameters..................................................................... 80
To Return to a Lower Level ........................................................................ 80
Navigation Diagram ..................................................................... 81
Navigation Diagram.......................................................................................... 82
Configuration Level ...................................................................... 84
To Enter Configuration Level...................................................................... 84
To Return to Level 1............................................................................. 84
Function Blocks................................................................................................ 85
Configuration Level Parameters ................................................................ 86
To Select Configuration Level .................................................................... 87
Configuration and Level 3 Navigation Diagram ......................................... 88
Examples ............................................................................................. 89
Analogue Input List (a1 a2)........................................................................ 92
Units..................................................................................................... 95
Status................................................................................................... 96
I/O List (io) ................................................................................................. 97
Output Splitting .................................................................................. 101
Cycle Time and Minimum OnTime Algorithms................................... 102
DI/O List (O.d.IO) ..................................................................................... 103
CT List (Ct)............................................................................................... 104
Loop List (LOOP) ..................................................................................... 106
Loop - Main Sub-list ........................................................................... 107
Configuration Sub-List ....................................................................... 109
Setpoint Sub-list..................................................................................111
Feedforward Sub-list...........................................................................114
Autotune Sub-list ................................................................................116
PID Sub-list.........................................................................................118
OP Sub-list......................................................................................... 121
Diagnostics Sub-list ........................................................................... 123
Programmer List (PROG) ........................................................................ 125
Program Setup List (P.SEt) ...................................................................... 128
Alarms List (ALm) .................................................................................... 131
BCD List (bCd)......................................................................................... 135
Recipe List (RECP).................................................................................. 137
To Save Recipes................................................................................ 139
To Load a Recipe............................................................................... 139
Communications List (COmm)................................................................. 140
Main Sub List (mAIN)......................................................................... 141
Network Sub List (nWrk) .................................................................... 142
Broadcast Sub List (bCSt) ................................................................. 143
Maths List (mAth)..................................................................................... 144
5 HA032842ENG Issue 2
Page 6
Table of Contents EPC3016, EPC3008, EPC3004
Select Input........................................................................................ 146
Logic Operator List (LGC2)...................................................................... 147
8 Input Logic Operator List (LGC8).......................................................... 149
Timer List (tmr)......................................................................................... 151
Timer Modes...................................................................................... 152
Counter List (Cntr) ................................................................................... 155
Totaliser List (tOtL)................................................................................... 157
8 Input Analogue MUX List (AN.SW) ....................................................... 159
User Value List (u.VAL)............................................................................ 161
Input Monitor List (I.mon) ......................................................................... 162
Switchover List (SW.OV).......................................................................... 164
Logic OR List (OR)................................................................................... 166
Instrument List (INSt) ............................................................................... 167
Information Sub-List (INFO)............................................................... 168
Display Functionality Sub-List (HmI).................................................. 169
Security Sub-List (SEC) ..................................................................... 171
Diagnostics Sub-List (diAG)............................................................... 172
Modules Sub-List (mOdS) ................................................................. 176
Calibration Sub-List (CAL) ................................................................. 177
Remote Input List (REm.1) ................................................................ 178
Q Code List........................................................................................ 179
Configuration Using iTools ......................................................... 181
What is iTools? ............................................................................................... 181
What is an IDM?............................................................................................. 181
To Load an IDM........................................................................................ 181
Connecting a PC to the Controller ................................................................. 182
Using the Configuration Clip .................................................................... 182
Using the Communications Port .............................................................. 183
Using Option Comms............................................................................... 183
Starting iTools................................................................................................. 184
The 'Browser' List..................................................................................... 185
Instrument List ................................................................................... 186
Terminal Wiring ........................................................................................ 187
Programmer ............................................................................................. 188
To Set up a Stored Program Using iTools.......................................... 188
To Save and Load Stored Programs........................................................ 191
To Run, Reset and Hold a Program ................................................... 192
Graphical Wiring ...................................................................................... 194
Example 1: To Wire an Alarm............................................................. 195
Example 2: To Connect an Alarm to a Physical Output ..................... 195
Example 3: To Wire Sensor Break..................................................... 196
Example 4: To Configure a Bargraph................................................. 196
Example 5: To Wire a Retransmission Output ................................... 197
Applications.............................................................................................. 199
Heat Only Controller .......................................................................... 199
Heat/Cool Controller .......................................................................... 201
Valve Position Heat Only Controller................................................... 201
Flash Memory Editor................................................................................ 202
Parameter Promotion......................................................................... 203
User Defined Messages .................................................................... 205
Recipes.............................................................................................. 207
Watch Recipe Editor .......................................................................... 210
To Load a Custom Linearisation Table............................................... 212
Cloning..................................................................................................... 213
Save to File........................................................................................ 213
To Clone a New Controller ................................................................. 213
Clone Load Unsuccessful .................................................................. 214
Cold Start........................................................................................... 214
Alarms ........................................................................................ 215
What are Alarms?........................................................................................... 215
Alarm Types............................................................................................. 216
6 HA032842ENG Issue 2
Page 7
Table of Contents EPC3016, EPC3008, EPC3004
Absolute High .................................................................................... 216
Absolute Low ..................................................................................... 216
Deviation High ................................................................................... 216
Deviation Low .................................................................................... 217
Deviation Band .................................................................................. 217
Rising Rate of Change....................................................................... 217
Falling Rate of Change ...................................................................... 218
Digital High ........................................................................................ 218
Digital Low ......................................................................................... 218
Sensor Break ..................................................................................... 218
Hysteresis .......................................................................................... 219
Delay.................................................................................................. 219
Effects of Delay and Hysteresis ......................................................... 219
Inhibit ................................................................................................. 221
Standby Inhibit ................................................................................... 221
Latching ............................................................................................. 222
Blocking ............................................................................................. 222
To Set Alarm Threshold............................................................................ 223
Alarm Indication ....................................................................................... 223
To Acknowledge an Alarm ........................................................................ 224
Alarms Advanced ........................................................................................... 226
Programmer ............................................................................... 227
What is a Programmer? ................................................................................. 227
Programs........................................................................................................ 227
Segments ....................................................................................................... 228
Time To Target ......................................................................................... 228
Dwell ........................................................................................................ 228
Step.......................................................................................................... 228
Call........................................................................................................... 228
End........................................................................................................... 229
Standard Functionality ................................................................................... 230
Recovery Strategy ................................................................................... 230
Ramp back (Power outage during Dwell segments.)......................... 230
Ramp back (Power outage during Ramp segments) ......................... 230
Ramp back (Power outage during Time-to-target segments) ............ 231
Sensor Break Recovery ........................................................................... 231
Holdback .................................................................................................. 231
Servo To PV/SP ....................................................................................... 231
Event Outputs .......................................................................................... 231
Digital Inputs ............................................................................................ 232
Program Cycles ....................................................................................... 232
Configuration Mode Reset ....................................................................... 232
Program Selection ................................................................................... 232
Rules for Program Creation / Editing ....................................................... 233
Program & Segment Times...................................................................... 233
Resolution ................................................................................................ 234
Programmer Time Base Accuracy ........................................................... 234
Typical Loop to Programmer Graphical Wiring ........................................ 235
Communications ...................................................................................... 236
Modbus Address Ranges................................................................... 236
EI-Bisync Mnemonics ........................................................................ 237
To Set-up a Program................................................................................ 238
To Run/Hold the Program .................................................................. 240
Control ....................................................................................... 241
Types of Control............................................................................................. 242
PID Control .............................................................................................. 242
Reverse/Direct Action .............................................................................. 247
Loop Break............................................................................................... 247
Motorised Valve Positioning Control ........................................................ 248
Boundless (VPU) ............................................................................... 248
Motorised Valve Control in Manual mode .......................................... 248
7 HA032842ENG Issue 2
Page 8
Table of Contents EPC3016, EPC3008, EPC3004
Gain scheduling ....................................................................................... 249
On-Off Control.......................................................................................... 249
Feedforward ................................................................................................... 250
Disturbance feedforward.......................................................................... 250
Setpoint feedforward................................................................................ 251
Static or dynamic compensation .............................................................. 252
Split Range (heat/cool)................................................................................... 253
Cooling Algorithm..................................................................................... 254
Non-linear cooling.............................................................................. 254
Channel 2 (heat/cool) Deadband ....................................................... 255
Bumpless Transfer ......................................................................................... 256
Sensor Break ................................................................................................. 256
Operating Modes............................................................................................ 257
Start-up and Recovery ............................................................................. 257
Setpoint subsystem........................................................................................ 258
Remote/Local Setpoint Source Selection ................................................ 259
Local Setpoint Selection .................................................................... 259
Remote Setpoint ................................................................................ 259
Setpoint limits........................................................................................... 260
Setpoint Rate Limit................................................................................... 260
Target SP ................................................................................................. 260
Tracking ................................................................................................... 261
Back-calculated SP and PV ..................................................................... 261
Setpoint Integral Balance......................................................................... 261
Output Subsystem.......................................................................................... 262
Output selection (including Manual Station) ............................................ 262
Output Limiting......................................................................................... 262
Rate limiting ............................................................................................. 263
Power feedforward (line voltage compensation)...................................... 263
Autotuning ...................................................................................................... 264
Autotuning multiple zones........................................................................ 269
Digital Communications ............................................................. 270
Modbus RTU .................................................................................................. 270
EI-Bisynch Protocol........................................................................................ 270
Baud Rate.......................................................................................... 271
Parity.................................................................................................. 271
Communication Address .................................................................... 271
Comms Delay .................................................................................... 271
EI-Bisynch Limitations.............................................................................. 272
Ethernet Protocol ........................................................................................... 273
MAC address display ............................................................................... 273
IP Mode Settings...................................................................................... 273
Network Connection................................................................................. 273
Dynamic IP Addressing............................................................................ 273
Static IP Addressing................................................................................. 273
Broadcast Storm Protection ..................................................................... 274
Ethernet Rate Protection.......................................................................... 274
Additional information .............................................................................. 274
Bonjour..................................................................................................... 274
Auto discovery ......................................................................................... 274
To turn on AutoDiscovery......................................................................... 275
To turn on DHCP...................................................................................... 275
To set up an IP address for Ethernet via the front panel .......................... 276
iTools Setup ............................................................................................. 277
User Calibration ......................................................................... 278
Controller only Calibration.............................................................................. 278
To Calibrate the Analogue Input............................................................... 278
Using iTools ....................................................................................... 279
To Return to Factory Calibration ........................................................ 280
Two Point Offset....................................................................................... 281
Using the Controller HMI.......................................................................... 282
8 HA032842ENG Issue 2
Page 9
Table of Contents EPC3016, EPC3008, EPC3004
Calibration using a Dry Block or Equivalent............................................. 283
To Calibrate a Voltage or Current Analogue Output ....................................... 284
Using the Controller HMI.......................................................................... 284
Using iTools.............................................................................................. 285
To Calibrate the Current Transformer............................................................. 286
Notification Messages ................................................................ 287
Technical Specification ............................................................... 289
General .................................................................................................... 289
Environmental specifications, standards, approvals and certifications.... 290
Mechanical............................................................................................... 291
Dimensions ........................................................................................ 291
Weight................................................................................................ 291
Input and Outputs .................................................................................... 292
I/O and communication types ............................................................ 292
I/O specifications ............................................................................... 292
Inputs and outputs ............................................................................. 293
Remote (Aux) analogue input (EPC3016 only).................................. 293
Current transformer ........................................................................... 293
Contact closure inputs ....................................................................... 293
Logic I/O modules ............................................................................. 294
Logic I/O open collector type (EPC3008/3004) ................................. 294
Relays (form A modules and form C fixed built in) ............................. 295
Triac module ...................................................................................... 295
Isolated DC output module ................................................................ 296
Power supply and transmitter power supply ...................................... 296
Communications ................................................................................ 296
Operator interface .............................................................................. 297
Appendix EI-Bisync Parameters ................................................ 298

Issue Status of this manual

Issue 2 adds:
A chapter ’Navigation Diagram’
A section how to set up Ethernet Communications
More prominent default values
Minor improvements.
9 HA032842ENG Issue 2
Page 10
EPC3016, EPC3008, EPC3004 Safety Information

Safety Information

Important Information

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death
or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Note: Electrical equipment must be installed, operated, serviced and maintained
only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Note: A qualified person is one who has skills and knowledge related to the
construction, and operation of electrical equipment and its installation, and has received safety training to recognise and avoid the hazards involved.
HA032842ENG Issue 2 10
Page 11
Safety and EMC EPC3016, EPC3008, EPC3004

Safety and EMC

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Power down all equipment before starting the installation, removal, wiring, maintenance or inspection of the product.
Always use properly rated voltage sensing device to confirm the power is off.
Power line and output circuits must be wired and fused in compliance with local and national regulatory requirements for the rated current and voltage of the particular equipment. i.e. UK, the latest IEE wiring regulations, (BS7671), and USA, NEC Class 1 wiring methods.
Failure to follow these instructions will result in death or serious injury.
Reasonable use and responsibility
The safety of any system incorporating this product is the responsibility of the assembler/installer of the system.
The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein.
This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC.
Use in other applications, or failure to observe the installation instructions of this manual may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.
Failure to use approved software/hardware with our hardware products may result in injury, harm, or improper operating results.
11 HA032842ENG Issue 2
Page 12
Safety and EMC EPC3016, EPC3008, EPC3004
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not use the product for critical control or protection applications where human or equipment safety relies on the operation of the control circuit. This product must be installed, connected and used in compliance with prevailing standards and/or installation regulations. If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
Personnel
Electrical equipment must be installed, operated, serviced and maintained only by qualified personnel.
Enclosure of Live Parts
To help prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.
Live sensors
The controller is designed to operate if the temperature sensor is connected directly to an electrical heating element. However, you must ensure that service personnel do not touch connections to these inputs while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor must be mains rated for use in 230Vac +15% CATII.
Charged capacitors
Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. Avoid touching the exposed electronics of the instrument when withdrawing it from the sleeve.
Voltage rating.
The maximum continuous voltage applied between any of the following terminals must not exceed 230Vac +15%:
relay output to logic, dc or sensor connections
any connection to a protective earth ground
Power Isolation
The installation must include a power isolating switch or circuit breaker. This device must be in close proximity of the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.
Overcurrent protection
The power supply to the system must be fused appropriately to protect the cabling to the controller.
Conductive pollution
Electrically conductive pollution must be excluded from the enclosure in which the controller is installed. For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere in conditions of conductive pollution, fit an air filter to the air intake of the enclosure. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the enclosure. This product has been designed to conform to EN61010 installation category II, pollution degree 2. These are defined as follows: Pollution Degree 2. Normally only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected. Installation Category II (CAT II). The rated impulse voltage for equipment on nominal 230V supply is 2500V.
Grounding of the temperature sensor shield.
In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.
Failure to follow these instructions will result in death or serious injury.
12 HA032842ENG Issue 2
Page 13
Safety and EMC EPC3016, EPC3008, EPC3004
WARNING
UNINTENDED EQUIPMENT OPERATION
Safety and EMC
Safety and EMC protection can be seriously impaired if the unit is not used in the manner specified. The installer must ensure the safety and EMC of the installation. This instrument complies with the European Low Voltage Directive 2014/35/EU, by the application of the safety standard EN 61010. Electrostatic discharge precautions. Always observe all electrostatic precautions before handling the unit. When the controller is removed from its sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone directly handling the controller.
Service and repair.
This instrument has no user serviceable parts. Contact your supplier for repair
Electromagnetic compatibility.
This instrument conforms with the essential protection requirements of the EMC Directive 2014/35/EU. It satisfies the general requirements of the industrial environment defined in EN 61326.
Installation requirements for EMC.
To comply with the European EMC directive certain installation precautions are necessary:
General guidance. Refer to EMC Installation Guide, Part no. HA025464.
Relay outputs. It may be necessary to fit a suitable filter to suppress conducted
emissions.
Table top installation. If using a standard power socket, compliance with
commercial and light industrial emissions standard is required. To comply with conducted emissions standard, a suitable mains filter must be installed.
Wiring. It is important to connect the controller in accordance with the wiring data given in this guide. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring of installations complies with all local wiring regulations. For example, in the UK use the latest version of the IEE wiring regulations, (BS7671). In the USA use NEC Class 1 wiring methods.
Routing of wires.
To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded. In general keep cable lengths to a minimum.
Hazard of Incorrect Configuration.
Incorrect configuration can result in damage to the process and/or personal injury and must be carried out by a competent person authorised to do so. It is the responsibility of the person commissioning the controller to ensure the configuration is correct.
Loss of Communications
If the output is not wired, but written to by communications, it will continue to be controlled by the communications messages. In this case take care to allow for the loss of communications
Failure to follow these instructions can result in death, serious injury or equipment damage.
13 HA032842ENG Issue 2
Page 14
Safety and EMC EPC3016, EPC3008, EPC3004
WARNING
EQUIPMENT AND PERSONNEL PROTECTION
The designer of any control scheme must consider the potential failure modes
which could occur and provide a means to achieve a safe state during and after a failure.
Independent or redundant devices must be provided for critical control
functions.
The control scheme may include communication links. Consideration must be
given to the implications of unanticipated transmission delays or failures of the link.
Each implementation of this equipment must be individually and thoroughly
tested for its intended operation before being placed into service.
Failure to follow these instructions can result in death, serious injury or equipment damage.
WARNING
OVER TEMPERATURE PROTECTION
In temperature control applications a danger could be present if the heating remains constantly on. Apart from potentially spoiling the end product, this could damage the process machinery being controlled, or cause a fire hazard. Consider the following examples:
a temperature sensor becoming detached from the process
thermocouple wiring becoming short circuit
the controller operating with its heating output constantly on
an external valve or contactor sticking in the heating condition
the controller setpoint set too high.
The alarm relays within the controller will not give over-temperature protection under all conditions. The installer must, therefore, fit a separate over-temperature protection device, with an independent temperature sensor, to isolate the heating circuit should an over-temperature condition occur.
Failure to follow these instructions can result in death, serious injury or equipment damage.
14 HA032842ENG Issue 2
Page 15
Safety and EMC EPC3016, EPC3008, EPC3004
CAUTION
UNINTENDED EQUIPMENT OPERATION
Unpacking and storage - The packaging should contain an instrument mounted in its sleeve, two mounting brackets for panel installation and an Installation sheet. Certain ranges are supplied with an input adapter.
If upon receipt, the packaging or the instrument is damaged, do not install the product instead contact your supplier. If the instrument is to be stored before use, protect from humidity and dust in an
ambient temperature range of 20 to +70℃.
Cleaning - Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product.
Failure to follow these instructions can result in injury or equipment damage.
Symbols
Various symbols may be used on the controller. They have the following meaning:
W Refer to manual.
D Risk of electric shock.
O Take precautions against static.
P The RCM is a trademark owned by Australian and New Zealand Regulators." with
RCM mark
* Complies with the 40 year Environment Friendly Usage Period.
s Restriction of Hazardous Substances
15 HA032842ENG Issue 2
Page 16
Cybersecurity EPC3016, EPC3008, EPC3004

Cybersecurity

What’s in this Chapter
This chapter outlines some good practice approaches to cybersecurity as they relate to use of EPC3000-series controllers, and draws attention to several EPC3000-series features that could assist in implementing robust cybersecurity.

Introduction

When utilising Eurotherm EPC3000-series controllers in an industrial environment, it is important to take ‘cybersecurity’ into consideration: in other words, the installation’s design should aim to prevent unauthorised and malicious access. This includes both physical access (for instance via the EPC3000 front panel or HMI screens), and electronic access (via network connections and digital communications).

Secure network topologies and good practices

Overall design of a site network is outside the scope of this manual. The Cybersecurity Good Practices Guide, Part Number HA032968 provides an overview of principles to consider. This is available from www.eurotherm.co.uk.
Typically, an industrial controller such as the EPC3000 together with any associated
HMI screens and controlled devices should not be placed on a network with direct
access to the public Internet. Rather, good practise involves locating the devices on a firewalled network segment, separated from the public Internet by a so-called ‘demilitarized zone’ (DMZ).

Security Features

The sections below draw attention to some of the cybersecurity features of EPC3000-series controllers.

Principle of Secure by Default

Some of the digital communication features on the EPC3000-series can provide greater convenience and ease-of-use (particularly in regards to initial configuration), but also can potentially make the controller more vulnerable. For this reason, these features are turned off by default:
Comms ports and channels disabled by default
EPC3000-series controllers support a variety of digital communications (see "EPC3016 Options" on page 34, "EPC3008 and EPC3004 Options" on page 35 and "Communications List (COmm)" on page 140). By default, the ports and channels associated with any digital comms are closed to traffic, unless that method of communication is explicitly selected using the parameters in the mAIN menu (see "Main Sub List (mAIN)" on page 141).
16 HA032842ENG Issue 2
Page 17
Cybersecurity EPC3016, EPC3008, EPC3004
The only exception to this principle is for the configuration port on the left side face of the controller. This is a serial port, used with a bespoke Eurotherm-supplied ‘config clip’ cable, for communication with Eurotherm’s iTools software and for performing firmware upgrades (see "Using the Configuration Clip" on page 182). Whilst this serial port is always enabled, it is physically inaccessible when the controller is installed and mounted in the normal way. It can only be accessed by removing the controller from its mounting, thus disconnecting all other I/O connections.
Bonjour auto-discovery disabled by default
Ethernet connectivity is available as an option on EPC3000-series controllers (see "EPC3016 Options" on page 34 and "Auto discovery" on page 274"Auto discovery" on page 274), including the Bonjour service discovery protocol (see "Bonjour" on page 274). Bonjour enables the controller to be automatically discovered by other devices on the network without the need for manual intervention. However, for cybersecurity reasons, it is disabled by default, as it could be exploited by a malicious user to gain access to the controller.
See also section "Auto discovery" on page 274.

HMI Access Level / Comms Config Mode

As described in "Operator Levels" on page 69, EPC3000-series controllers feature tiered, passcode-restricted operator levels, so that available functions and parameters can be restricted to appropriate personnel.
Level 1 functions are the only ones that do not require passcode access, and are typically appropriate for routine operator use. The controller powers up in this level. All other levels are passcode-restricted. Level 2 makes an extended set of operational parameters available, typically intended for use by a supervisor. Level 3 parameters would typically be set when an authorised person was commissioning the device for use in a particular installation. Config level allows access to all the controller’s parameters. Passcode-restricted access to these parameters is also possible over digital communications, using Eurotherm’s iTools software ("Configuration Using iTools" on page 181),
At config level, it is also possible to customise the other levels from their defaults, restricting certain parameters to only be available at a higher level, or making certain parameters available at lower levels. In particular, you can configure the availability of setpoint program control parameters such as start/stop, auto/manual, setpoint, manual output, program edit and program run (see "Configuration Sub-List" on page 109).

HMI Passcodes

When entering passcodes via the HMI, the following features help protect against unauthorised access:
Each digit is obscured (replaced with an underscore character) after entry, to
help protect against an unauthorized person seeing the passcode as it’s typed in.
Passcode entry is locked after three invalid attempts. The time it stays locked for
is configurable (see "Security Sub-List (SEC)" on page 171). This helps protect against “brute force” attempts to guess the passcode.
17 HA032842ENG Issue 2
Page 18
Cybersecurity EPC3016, EPC3008, EPC3004
The controller records the number of successful and unsuccessful login attempts
for each level of passcode (see "Diagnostics Sub-list" on page 123). Regular auditing of these diagnostics is recommended, as a means to help detect unauthorized access to the controller.

Comms Config Level Passcode

The passcode for Config Level access via iTools has the following features to help protect against unauthorised access (see "Instrument List" on page 186 for more details):
If the passcode is not changed from its initial default value, or is changed to a
password that was used previously, an alert message is displayed.
By default, each passcode expires after 90 days, and needs to be changed. This
expiry period is configurable.
Passcode entry is locked after three invalid attempts. The time it stays locked for
is configurable. This helps protect against “brute force” attempts to guess the passcode.
The controller records the number of successful and unsuccessful login attempts
for each level of passcode. Regular auditing of these diagnostics is recommended, as a means to help detect unauthorized access to the controller.

Ethernet security features

Ethernet connectivity is available as an option on EPC3000-series controllers (see "EPC3016 Options" on page 34 and "EPC3008 and EPC3004 Options" on page 35). The following security features are specific to Ethernet:
Ethernet rate protection
One form of cyberattack is to try to make a controller process so much Ethernet traffic that this drains systems resources and useful control is compromised. For this reason, the EP3000-series includes an Ethernet rate protection algorithm, which will detect excessive network activity and help to ensure the controller’s resources are prioritized on the control strategy rather than the Ethernet. If this algorithm is
activated, the rate protection diagnostic parameter will be set to ON (see "Network Sub List (nWrk)" on page 142).
Broadcast Storm protection
A ‘broadcast storm’ is a condition which may be created by cyberattack: spurious network messages are sent to devices which cause them to respond with further network messages, in a chain reaction that escalates until the network is unable to transport normal traffic. The EPC3000-series includes a broadcast storm protection algorithm, which will automatically detect this condition, stopping the controller from
responding to the spurious traffic. If this algorithm is activated, the broadcast storm diagnostic parameter will be set to ON (see "Network Sub List (nWrk)" on page 142).
18 HA032842ENG Issue 2
Page 19
Cybersecurity EPC3016, EPC3008, EPC3004

Communications watchdog

EPC3000-series controllers include a ‘comms watchdog’ feature. This can be configured to raise an alert if any of the supported digital communications are not
received for a specified period of time. See the four watchdog Main Sub-list" on page 107. These provide a way to configure appropriate action if malicious action interrupts the controller’s digital communications.
parameters in "Loop -

Configuration backup and recovery

Using Eurotherm’s iTools software, you can ‘clone’ an EPC3000-series controller, saving all its configuration and parameter settings to a file. This can then be copied onto another controller, or used to restore the original controller’s settings—see "Cloning" on page 213.
For cybersecurity reasons, passcode-restricted parameters are not saved in the clone file when in operator mode (Level 1).
Clone files are digitally signed using an SHA-256 cryptographic algorithm, meaning that if the file contents is tampered with, it will not load back into a controller.

Memory Integrity

FLASH Integrity
When an EPC3000-series controller powers up, it automatically performs an integrity check on the entire contents of its internal flash memory. Additional periodic integrity checks are also performed in 256 byte blocks during normal runtime. If any integrity check detects a difference from what is expected, the controller will stop running and display a
Non-volatile Data Integrity
When an EPC3000-series controller powers up, it automatically performs an integrity check on the contents of its internal non-volatile memory devices. Additional periodic integrity checks are performed during normal runtime and when non-volatile data is being written. If any integrity check detects a difference from what is expected, the controller enters Standby mode and displays a appropriate (see "Notification Messages" on page 287 for more details).
FL.er alert (see "Notification Messages" on page 287).
RAM.S, PA.S', REG.S or OPT.S alert as
19 HA032842ENG Issue 2
Page 20
Cybersecurity EPC3016, EPC3008, EPC3004

Firmware

From time to time, to provide new functionality or address known issues, Eurotherm may make new versions of the EPC3000-series firmware available.
This firmware may be downloaded from the Eurotherm website, and transferred to an EPC3000 controller in the field, via a serial communications link, from a Windows PC running a firmware upgrade utility.
CAUTION
NON SCHNEIDER ELECTRIC FIRMWARE
There is a potential risk that an attacker could upgrade an EPC3000 with non-genuine firmware that contains malicious code. To mitigate this potential risk, genuine EPC3000 firmware upgrade utility executables are always supplied digitally signed with the publisher as Schneider Electric. Do not use a firmware upgrade utility if it has not been signed by Schneider Electric.
Failure to follow these instructions can result in injury or equipment damage.

Achilles® Communications Certification

The EPC3000-series range of controllers have been certified at Level 1 under the
®
Achilles established industry benchmark for the deployment of robust industrial devices recognized by the major automation vendors and operators.
Communications Robustness Test Certification scheme. This is an

Decommissioning

When an EPC3000-series controller is at the end of its life and being decommissioned, Eurotherm advises reverting all parameters to their default settings (see "Cold Start" on page 214 for instructions). This can help to protect against subsequent data and intellectual property theft if the controller is then acquired by another party.
20 HA032842ENG Issue 2
Page 21
Legal Information EPC3016, EPC3008, EPC3004

Legal Information

All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without prior written permission of the manufacturer.
Eurotherm, the Eurotherm by Schneider Electric logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower, EPack nanodac, piccolo, versadac, optivis, Foxboro, and Wonderware are trademarks of Schneider Electric its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice. The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
21 HA032842ENG Issue 2
Page 22
Introduction EPC3016, EPC3008, EPC3004

Introduction

Controller Concept

The EPC3000 is a range of programmable single loop process and temperature controllers which are certified for cybersecurity communications robustness. A full range of math, logic, totalizer and specialized functions is also available.
A simple "Quick Start" code is used to configure standard applications essential for controlling specific processes. This enables fast commissioning "Out of the Box" without the need for configuration software. Applications include (but are not limited to) heat or heat/cool temperature control, carbon potential control, dew point control, etc. These applications are pre-configured providing the user with a starting point for customising to an individual process.
Eurotherm iTools is a software package which is designed for this purpose by providing user function block wiring in addition to a range of other features. It is available as a free download from www.eurotherm.co.uk or can be ordered on a DVD.

Manual Concept

This manual is generally laid out in the following manner:
The first part explains mechanical and electrical installation and covers the same
Operation of the instrument, including Quick Start Configuration. In general the
Configuration of the instrument from the front panel
Configuration of the instrument using Eurotherm iTools configuration package
Description of different function blocks in the instrument, such as Control Loop,
Calibration procedure
Technical specification
This User Manual describes general control applications which may be configured using the Quick Start Codes.
topics as in the Installation and wiring sheet supplied with each instrument but in more detail.
descriptions in the manual assume that the controller is configured with no application loaded or with a heat or heat cool controller application loaded.
Programmer, Digital Communications
This User Manual describes general control applications which may be configured using the Quick Start Codes.
Specific applications such as Temperature control (Quick Start codes 1, 2 and 3), Carbon Potential control (Quick Start code 4) and Dew Point control (Quick Start code 5) are described in supplements to this manual. The supplement part numbers are HA033033, HA032987 and HA032842 respectively and are available from www.eurotherm.co.uk.
22 HA032842ENG Issue 2
Page 23
Installation EPC3016, EPC3008, EPC3004

Installation

What’s in this Chapter
A general description of the instrument
What is in the package
Order codes
Instrument dimensions and mechanically mounting in a panel

What Instrument Do I Have?

Thank you for choosing this controller.
The EPC programmable controller range provides precise control of industrial processes and is available in three standard DIN sizes:
1
⁄16 DIN Model Number EPC3016
1
⁄8 DIN Model Number EPC3008
1
⁄4 DIN Model Number EPC3004
Universal input(s) accept various thermocouples, RTDs or process inputs.
Universal input/output (I/O) can be configured for control, alarm, re-transmission outputs or contact inputs.
A changeover relay is available as standard in all controllers.
Controllers may be powered from either an ac line supply [100 - 230Vac +/-15%] or low voltage [24Vac/dc (nominal) supply] depending on the order code.
EIA485 (RS485) digital communications is available in EPC3008 and EPC3004 as standard and as an option in EPC3016.
Options available are:
1. A current transformer (CT) input plus a further contact input.
2. EtherNet communications protocol
3. EIA232/422 (RS232/422) digital communications using Modbus or EI-Bisynch protocols is available in EPC3016 to provide compatibility with previous products.
The controller may be ordered against a hardware ordering code only ("Order Codes" on page 25). In this case when it is new and first switched on 'out of the box' it will start in a 'Quick Configuration' mode ("Start Up—New Unconfigured Controller" on page 61). Alternatively, it may be ordered against both hardware and software codes, in which case it will be supplied configured and will start up directly showing the operator display ("Start Up - New Configured Controller" on page 65). Labels fitted to the sleeve show the ordering code, serial number, date of manufacture, and terminal connections for the hardware fitted.
23 HA032842ENG Issue 2
Page 24
Installation EPC3016, EPC3008, EPC3004
EPC3016
EPC3008 EPC3004
A full configuration mode, passcode protected, provides more detailed functionality to be configured ("Configuration Level" on page 84).
Two panel sealing versions are available:
Curved front. Panel sealing to NEMA 12X/IP65 qualified with indoor use only.
Washdown. Panel sealing to NEMA 4X/IP66 qualified with indoor use only.

Unpacking Your Controller

The controller is supplied with:
Controller as ordered fitted in its sleeve, two panel retaining clips and sealing
gasket mounted on the sleeve. The views below show the washdown version.
Component packet containing a snubber for a relay output ("General Information
About Relays and Inductive Loads" on page 48) and a 2.49 current input ("Linear Input (mA, mV or V)" on page 39). The quantity depends on the fitted modules.
resistor for a
Installation sheet Part Number HA032934 in English, French, German, Spanish,
Italian, Chinese and Russian
24 HA032842ENG Issue 2
Page 25
Installation EPC3016, EPC3008, EPC3004

Order Codes

When purchasing an EPC3000-series controller, use the order codes below to specify the product hardware options you require. Codes marked ‘future’ are intended for future product options and are currently left at their default values. Additionally, you can use ‘Quick Start’ order codes (see "Quick Start Tables" on page 62) to have the controller supplied pre-configured with certain software behaviour.
25 HA032842ENG Issue 2
Page 26
Installation EPC3016, EPC3008, EPC3004
Model
(see Note 1)
EPC3016 1/16 DIN Controller
Quick Start Codes EPC3016
1 Type
CC CP
P1
P10
Controller only 1 x 8 Segment Basic Programmer 1 x 24 Segment Advanced Programmer 10 x 24 Segment Advanced Programmer
2 Supply Voltage
VH
VL
100 - 230Vac +/-15% (48 to 62Hz) 24Vac +10%, -15% (48 to 62 Hz); 24Vdc +20,
-15%; 5% ripple
3 I/O 1
XX L2 R1
R2
D1 T1 T2
Not Fitted Logic Relay Output (without snubber) Relay (supplied with external snubber) DC Output Triac (without snubber) Triac (supplied with snubber)
4 I/O 2
XX L2 R1
R2
D1 T1 T2
Not Fitted Logic Relay Output (without snubber) Relay (supplied with external snubber) DC Output Triac (without snubber) Triac (supplied with external snubber)
5 Future
X Not fitted
7 Serial Comms Protocol
XX EI
MODBUS (Default) EI Bisynch
8
Ethernet, Comms & Remote SP
XX C1
C2
C3 CR
CE
None (Default) CT Input, Dig In, and RS232 CT Input, Dig In, and RS485 (3 wire) RS422 only (5 wire) CT Input, Dig In, RSP Input Digital Input, Ethernet
9 Future
XX Future
10 Tool Kit Blocks
XX TK
None (Default 50 wires) Enabled (includes 200 wires)
11 Future
XXX Future
12 Bezel
ST WD
Standard Washdown
13 Labels
XXXX Fnnnn
None (Default) Custom Label
14 Specials
XXXX None (Default)
15 Future
XX Future
16 Application
X 1 2 V
None (Default) Heat only Heat/Cool VPU
17 Input 1 Sensor Type
X M V 2 4 B J K L N R S T P W
Not required Linear 0 to 80mVdc Linear 0 to 10Vdc Linear 0 to 20mA Linear 4 to 20mA Type B Thermocouple Type J Thermocouple Type K Thermocouple Type L Thermocouple Type N Thermocouple Type R Thermocouple Type S Thermocouple Type T Thermocouple PT100 PT1000
18 Input 1 Range
X F 1
2
3
4
5
6
7
8
9
A
Not required Full range 0 to 100°C or 32 to 212°F or 273 to 373K 0 to 200°C or 32 to 392°F or 273 to 473K 0 to 400°C or 32 to 752°F or 273 to 673K 0 to 600°C or 32 to 1112°F or 273 to 873K 0 to 800°C or 32 to 1472°F or 273 to 1073K 0 to 1000°C or 32 to 1832°F or 273 to 1273K 0 to 1200°C or 32 to 2192°F or 273 to 1473K 0 to 1300°C or 32 to 2552°F or 273 to 1573K 0 to 1600°C or 32 to 2912°F or 273 to 1873K 0 to 1800°C or 32 to 3272°F or 273 to 2073K
19 Future
XX Future
21 CT Input Range
X 1 2 5 6 7
Not Used 10A 25A 50A 100A 1000A
22
Digital Input A Function
(see Note 1)
X W M R L K P T U V
Not Used Alarm Acknowledge Auto/Manual Programmer Run/Hold Keylock Loop Track Local Setpoint Select Programmer Reset Remote Setpoint Select Recipe Select
25 Units
X C F K
Not used (Default) Degrees Celsius (Default) Degrees Fahrenheit Kelvin
6 Future
XX Future
26 Future
XX Future
27 Warrant y
XX Standard warranty
28 Certificate of Conformity
XX CERT1
None required Supplied with Certificate of Conformity
23 Future
XX Future
20 Future
XX Future
16 17 18 19 20 21 22 23 24 25 26 27
28
Note 1 Requires purchase of Communications Option (Field 8) with “Dig In”
24 Future
XX Future

EPC3016 Hardware Order Codes

26 HA032842ENG Issue 2
Page 27
Installation EPC3016, EPC3008, EPC3004
Order Codes EPC3008 / EPC3004
Model
(see Note 1)
EPC3008 EPC3004
1/8 DIN Controller 1/4 DIN Controller
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15
1 Type
CC CP
P1
P10
Controller only 1 x 8 Segment Basic Programmer 1 x 24 Segment Advanced Programmer 10 x 24 Segment Advanced Programmer
2 Supply Voltage
VH
VL
100 - 230Vac +/-15% (48 to 62Hz) 24Vac +10%, -15% (48 to 62 Hz); 24Vdc +20,
-15%; 5% ripple
3 I/O 1
XX L2 R1
R2
D1 T1 T2
Logic Relay Output (without snubber) Relay (supplied with external snubber) DC Output Triac (without snubber) Triac (supplied with external snubber)
4 I/O 2
XX L2 R1
R2
D1 T1 T2
Not Fitted Logic Relay Output (without snubber) Relay Output (supplied with external snubber) DC Output Triac (without snubber) Triac (supplied with external snubber)
5 I/O 4
XX L2 R1
R2
D1 T1 T2
Not Fitted Logic Relay Output (without snubber) Relay Output (supplied with external snubber) DC Output Triac (without snubber) Triac (supplied with external snubber)
6 Future
XX Future
7 RS485 Function
XX EI
MODBUS (Default) EI Bisynch
8
Ethernet, 2nd Input & Option I/O
XX I8
IE (see Note 2)
None (Default) Second PV Input; 8 Digital Input/Outputs: Second PV Input;Ethernet (MODBUS TCP slave) + 4 x Digital I/O
9 Future
XX Future
10 Tool Kit Blocks
XX TK
None (Default 50 wires) Enabled (includes 200 wires)
11 Future
XXX Future
12 Bezel
ST WD
Standard Washdown
13 Labels
XXXX Fnnnn
None (Default) Custom Label
14 Specials
XXXX None (Default)
15 Future
XX Future
Note 1. Base EPC3008/4 Model includes RS485 Modbus RTU Slave communications, 1 Form C Relay, 2x Contact Closure Digital inputs, 1 Current Transformer Input, and 24V Transducer Power Supply
Note 2. Digital I/O on I8/IE cannot be used for PID control output

EPC3008 and EPC3004 Order Codes

27 HA032842ENG Issue 2
Page 28
Installation EPC3016, EPC3008, EPC3004
EPC3008/3004 Quick Start Codes
Quick Start Codes EPC3008 / EPC3004
16 17 18 19 20 21 22 23 24 25 26 27
28
16 Application
X
None (Default)
1
Heat only
2
Heat/ Cool
V
VPU
C
Carbon Potential Controller (requires PV2 and Zirconia)
D
Dew Point Controller (requires PV2 and Zirconia)
17 Input 1 Sensor Type
X
Not required
M
Linear 0 to 80mVdc
V
Linear 0 to 10Vdc
2
Linear 0 to 20mA
4
Linear 4 to 20mA
B
Type B Thermocouple
J
Type J Thermocouple
K
Type K Thermocouple Type L Thermocouple
L N
Type N Thermocouple
R
Type R Thermocouple
S
Type S Thermocouple
T
Type T Thermocouple PT100
P W
PT1000
18 Input 1 Range
Not required
X
Full range
F
0 to 100°C or 32 to 212°F or
1
273 to 373K 0 to 200°C or 32 to 392°F or
2
273 to 473K 0 to 400°C or 32 to 752°F or
3
273 to 673K 0 to 600°C or 32 to 1112°F
4
or 273 to 873K 0 to 800°C or 32 to 1472°F
5
or 273 to 1073K 0 to 1000°C or 32 to 1832°F
6
or 273 to 1273K 0 to 1200°C or 32 to 2192°F
7
or 273 to 1473K 0 to 1300°C or 32 to 2552°F
8
or 273 to 1573K 0 to 1600°C or 32 to 2912°F
9
or 273 to 1873K 0 to 1800°C or 32 to 3272°F
A
or 273 to 2073K
Note 1. Requires purchase of 2nd Input (Field 8)
Note 2. Requires purchase of Option I/O (Field 8)
Input 2 Sensor Type
19
(see Note 1)
X
Not fitted
M
Linear 0 to 80mVdc
V
Linear 0 to 10Vdc
2
Linear 0 to 20mA
4
Linear 4 to 20mA
B
Type B Thermocouple
J
Type J Thermocouple
K
Type K Thermocouple
L
Type L Thermocouple
N
Type N Thermocouple
R
Type R Thermocouple
S
Type S Thermocouple
T
Type T Thermocouple
P
PT100 PT1000
W Z
Zirconia (HiZ)
20 Input 2 Range
Not required
X
Full range
F
0 to 100°C or 32 to 212°F or
1
273 to 373K 0 to 200°C or 32 to 392°F or
2
273 to 473K 0 to 400°C or 32 to 752°F or
3
273 to 673K 0 to 600°C or 32 to 1112°F
4
or 273 to 873K 0 to 800°C or 32 to 1472°F
5
or 273 to 1073K 0 to 1000°C or 32 to 1832°F
6
or 273 to 1273K 0 to 1200°C or 32 to 2192°F
7
or 273 to 1473K 0 to 1300°C or 32 to 2552°F
8
or 273 to 1573K 0 to 1600°C or 32 to 2912°F
9
or 273 to 1873K 0 to 1800°C or 32 to 3272°F
A
or 273 to 2073K
(see Note 1)
21 CT Input Range
Not Used
X
10A
1
25A
2
50A
5
100A
6
1000A
7
22 Digital Input A Function
X
Not Used
W
Alarm Acknowledge
M
Auto/Manual
R
Programmer Run/Hold
L
Keylock
K
Loop Track
P
Local Setpoint Select
T
Programmer Reset
U
Remote Setpoint Select
V
Recipe Select
23 Digital Input B Function
X W M R L K P T U V
24
X
1
2
3
4
5
6
7
8
9
Not Used Alarm Acknowledge Auto/Manual Programmer Run/Hold Keylock Loop Track Local Setpoint Select Programmer Reset Remote Setpoint Select Recipe Select
Programmer I/O Configuration
Not Used/fitted
D1 to D8 Programmer Event Outputs 1 to 8
D1 to D4 = Programmer Event Outputs 1 to 4, D5 to D7 = BCD Inputs 1 t o3, D8 = Programmer Run/Hold. BCD Output to Program Number
D1 to D4 = Programmer Event outputs 1 to 4, D5 to D8 Programmer Run, Hold, Reset, Advance respectively
D1 to D4 = Programmer Event inputs 1 to 4, D5 to D7 Programmer Run/ Hold, Reset, Advance respectively, D8 Not Used. BCD Output to Program Number
D1 to D8 = BCD Inputs 1 to 8. BCD Output to Recipe Recall
D1 to D4 = BCD Inputs 1 to 4, D5 - D8 = Not used. BCD Output to Recipe Recall
D1 to D4 Programmer Run, Hold, Reset, Advance respectively, D5 - D8 = Not used
D1 to D3 Programmer Run, Hold, Reset respectively, D4
- D8 = Not Used
D1 to D4 = Programmer Event Outputs, D5 to D8 = Not Used
(see Note 2)
25 Units
X
Not used (Default)
C
Degrees Celsius (Default)
F
Degrees Fahrenheit
K
Kelv in
26 Future
XX Future
27 Warranty
XX Standard warranty
28 Certificate of Conformity
XX CERT1
None required Supplied with Certificate of Conformity
Accessory Order Codes
1
Model
EPCACC
1 Accessories
RES2R9 RES250 RES500 SNUBBER USBCONF CTR10A
CTR25A
CTR50A
CTR100A
ITOOLS
EPC Accessories
2.49 Ohm Resistor 250 Ohm Resistor 500 Ohm Resistor RC SNUBBER USB Backup lead Current transformer 10A Primary Current transformer 25A Primary Current transformer 50A Primary Current transformer 100A Primary Itools configuration Software
28 HA032842ENG Issue 2
Page 29
Installation EPC3016, EPC3008, EPC3004
Height
Width
Front View
Curved front Washdown Width including
latching clips
Width 49.4 mm
1.94 inch
48.1 mm
1.89 inch
50 mm
1.97 inch
Height 49.4 mm
1.94 inch
48.1 mm
1.89 inch
45 mm (1.77 in)
C
Side View
A
B
A Distance from panel to latching lug
13.7 mm
0.54 inch
B Distance from panel to button top
13.2 mm
0.52 inch
C Distance behind panel
90 mm
3.54 inch
Latching clip
Button top
Top View
45 mm
1.77 in

Dimensions

General views of the controllers are shown below together with overall dimensions
EPC3016 Controller
29 HA032842ENG Issue 2
Page 30
Installation EPC3016, EPC3008, EPC3004
Height
Width
Front View
Curved front Washdown Width including
latching clips
Width 49.4 mm
1.94 inch
48.1 mm
1.89 inch
50 mm
1.97 inch
Height 97.3 mm
3.83 inch
96.1 mm
3.78 inch
Latching
clips
92 mm
3.62 in
Side View
A
B
A Distance from panel to latching lug
15.1 mm
0.59 inch
B Distance from panel to button top
15.3 mm
0.60 inch
C Distance behind panel
90 mm
3.54 inch
Latching clip
Button top
C
Top View
45 mm
1.77 in
EPC3008 Controller
30 HA032842ENG Issue 2
Page 31
Installation EPC3016, EPC3008, EPC3004
Height
Width
Front View
Curved front Washdown Width including
latching clips
Width 97.3 mm
3.83 inch
97.3 mm
3.83 inch
98 mm
3.85 inch
Height 97.3 mm
3.83 inch
97.3 mm
3.83 inch
Latching
clips
92 mm
3.62 in
Side View
A
B
Latching clip
Button top
A Distance from panel to latching lug
15.3 mm
0.60 inch
B Distance from panel to button top
15.3 mm
0.60 inch
C Distance behind panel
90 mm
3.54 inch
C
Top View
92 mm
3.62 in
EPC3004 Controller
31 HA032842ENG Issue 2
Page 32
Installation EPC3016, EPC3008, EPC3004

Installation

This instrument is intended for permanent installation, for indoor use only, and enclosed in an electrical panel.
Select a location which is subject to minimum vibrations the ambient operating
temperature is within 0 and 55 non condensing.
The instrument can be mounted on a panel up to 15mm thick.
To ensure effective panel sealing, mount on a non-textured surface.
Please read the safety information in "Safety and EMC" on page 11 before proceeding. An EMC Booklet, part number HA025464, gives further installation information and can be downloaded from www.eurotherm.co.uk.
o
C (32 - 131oF) and operating humidity of 0 to 90% RH

Panel Mounting the Controller

1. Prepare a cut-out in the mounting panel to the size shown. If a number of controllers are to be mounted in the same panel observe the minimum spacing shown, see "Recommended minimum spacing of controllers" on page 33.
2. Carefully remove the panel retaining clips from the sleeve.
3. To achieve effective panel sealing, make sure the gasket is not twisted and is fitted behind the front bezel of the controller.
4. Insert the controller through the cut-out.
5. Spring the panel retaining clips back into place. Secure the controller in position by holding it level and pushing both retaining clips forward.
6. Peel off the protective film from the display.
7. In the unlikely event that it should be necessary to remove the sleeve from the panel, make sure that all power is turned off. Remove the controller from its sleeve. Very carefully unhook the panel retaining clips from the side using a small screwdriver.
The instrument includes polarizing features to help prevent the following:
a. The instrument being inserted upside down into sleeve.
b. Insertion of Low-Voltage PSU unit into High-Voltage PSU sleeve.
c. Insertion of other instruments that have a non-compatible terminal
assignment.
32 HA032842ENG Issue 2
Page 33
Installation EPC3016, EPC3008, EPC3004
EPC3016
EPC3008
45 mm, 0.0 + 0.6
1.77 in, 0.00, +0.02
45 mm, 0.0 + 0.6
1.77 in, 0.00, +0.02
45 mm, 0.0 + 0.6
1.77 in, 0.00, +0.02
EPC3004
92 mm 0.0 + 0.8
3.62 in 0.00, +0.03
92 mm 0.0 + 0.8
3.62 in 0.00, +0.03
38 mm (1.5in)
10 mm (0.4in)
(Not to scale)

Panel Cut Out Sizes

Recommended minimum spacing of controllers

Applies to all models

To Remove the Controller from its Sleeve

Ensure that the controller is powered down before attempting to remove it from its sleeve. It can then be removed from its sleeve by easing the latching clips outwards and pulling it forward out of the sleeve. When plugging it back into its sleeve, ensure
33 HA032842ENG Issue 2
that the latching clips click back into place to maintain the panel sealing.
If the Ethernet option is fitted, ensure that the Ethernet cable is removed from the rear of the controller before removing it from its sleeve.
Page 34
Wiring EPC3016, EPC3008, EPC3004
IO1
IO2
OP3
Sensor input
NO
NC
C
NO
C
NO C
Line/Mains Power Supply
100-230Vac +/15% 48 to 62Hz
Low Voltage Power Supply
24Vac/dc +20%/15%
Polarity not important
T/C Pt100
Pt1000
mA mV/1V/10V
Changeover relay output
Options
1A
1B
2A
2B
CT
C
LA
HD
HE
HF
3A
3B
3C
VI
V+
V
L
N
24
24

Option C1
EIA232
CT Input
1 x Digital Input
Option C2
EIA485
CT Input
1 x Digital Input
Option C3
EIA422
Option CR
Remote SP
CT Input
1 x Digital Input
Option CE
Ethernet
Digital Input

Wiring

What’s in this chapter
This chapter describes terminal connections and wiring.

Terminal Layout EPC3016 Controller

WARNING
POWER SUPPLY
Ensure that you have the correct supply for your controller. Check the order code of the controller supplied.
Failure to follow these instructions can result in injury or equipment damage.
34 HA032842ENG Issue 2

EPC3016 Options

Key to symbols used in the wiring diagrams
Logic (SSR drive) output
0-10V/0-20mA analogue output
Current transformer input
Relay output Changeover relay
Triac output
Contact input
output
Page 35
Wiring EPC3016, EPC3008, EPC3004
IO1
IO2
Line/Mains Voltage Power Supply
100–230Vac ±15% 48 to 62Hz
Low Voltage Power Supply
24Vac/dc +20%/15%
Polarity not important
Options
NO
C
NC
OP3
24V Transmitter power supply
IO4
DI2
DI1
C
C
Digital (Contact) input
Digital (Contact) input
CT
input
Digital Communications
COM
A(+)
B()
EIA485 (RS485)
IP2
Secondary Sensor Input
IP1
Primary Sensor Input
NO
2.49
2.49
1A
1B
2A
2B
LB
LC
4A
4B
5A
5B
D1
D2
D3
D4
D5
D6
D7
D8
DC
SI
S+
S
L
N
3A
3B
3C
HD
HE
HF
CT
C
LA
VI
V+
V
24
24
T/C T/C mV 1V 10V
Pt100 Pt1000
mA Pt100
Pt1000
mA
mV 1V 10V
NO
NO
C
NO
Secondary Sensor Input
Secondary Sensor Input
Option I8
PV Input
8 × Digital I/O
Option IE
PV Input
Ethernet
4 × Digital I/O
Digital I/O
D1 - D8
Voltage input
On (1) >4V, <35V
Off (0) >-1V, <+1V
Contact input On <100
Off >28K
Digital I/O
D1 - D4
Voltage input
On (1) >4V, <35V
Off (0) >-1V, <+1V
Contact input
On <100
Off >28K

Terminal Layout EPC3008 and EPC3004 Controller

WARNING
POWER SUPPLY
Ensure that you have the correct supply for your controller. Check the order code of the controller supplied.
Failure to follow these instructions can result in injury or equipment damage.
35 HA032842ENG Issue 2

EPC3008 and EPC3004 Options

Page 36
Wiring EPC3016, EPC3008, EPC3004
Serial/Ethernet
Comms
All logic inputs and
outputs
Primary PV input
CT measurement
Transmitter PSU
Secondary PV input
Relays and triacs
0-20mA/0-10V
isolated modules
Rectification
Power supply
circuits
System
circuits
300V ac
double
300V ac
double
300V ac
double
300V ac
double
300V ac
double
300V ac
double
Power
300V ac
basic
Serial/Ethernet
Comms
CT measurement
Relays and triacs
0-20mA/0-10V
isolated modules
Rectification
Power supply
circuits
300V ac
double
300V ac
double
300V ac
double
Power
PV input
All logic inputs and
outputs
300V ac
double
System
circuits
300V ac
basic

Isolation Boundaries

The drawings show double and basic isolation boundaries.

EPC3008/EPC3004 Isolation

EPC3016 Isolation

36 HA032842ENG Issue 2
Page 37
Wiring EPC3016, EPC3008, EPC3004
Line
Neutral
24V 24V

Wire Sizes

The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers help prevent hands or metal making accidental contact with live wires. The
rear terminal screws must be tightened to 0.5 Nm (4.4 lb⋅in).

Controller Power Supply

WARNING
POSSIBLE EQUIPMENT DAMAGE
Before connecting the instrument to the power line, make sure that the line voltage corresponds to the description on the identification label. If line/mains voltage (e.g. 230V) is connected to the 24V input the unit will be damaged and must be returned to your supplier for repair.
Use only copper conductors.
External fuse protection must be provided to the power supply input to the controller.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Recommended external fuse ratings are as follows:
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100–230Vac, fuse type: T rated 2A 250V.

Line/Mains Voltage Power Supply

100 to 230Vac, ±15%, 48 to 62 Hz
Power rating EPC3016: 6W; EPC3008 and EPC3004: max 9W

Low Voltage Power Supply

24Vac, 15%, +10%
24Vdc, 15%, +20% + 5% ripple voltage
The polarity is not important
Power rating EPC3016: 6W; EPC3008 and EPC3004: max 9W
37 HA032842ENG Issue 2
Page 38
Wiring EPC3016, EPC3008, EPC3004
-
+
V+
PRT PRT Lead Compensation

Primary Sensor Input (Measuring Input)

This input is available in all models.
CAUTION
MEASUREMENT INACCURACIES
Do not run input wires together with power cables.
When shielded cable is used, it should be grounded at one point only.
Any external components (such as zener barriers, etc) connected between sensor and input terminals may cause incorrect measurement due to excessive and/or un-balanced line resistance or possible leakage currents
The sensor input is not isolated from the logic outputs & digital inputs
Pay attention to line resistance; a high line resistance may cause measurement inaccuracies
A single sensor must not be connected to more than one instrument. Sensor break operation could be severely compromised
Failure to follow these instructions can result in injury or equipment damage.

Thermocouple Input

V-
Use the correct compensating cable (preferably shielded) to extend
thermocouple cabling, ensure that polarity is strictly followed throughout and that thermal junctions are avoided in any intermediate connections.

RTD Input

The resistance of the three wires must be the same. The line resistance may
cause measurement inaccuracies if it is greater than 22 ohms.
38 HA032842ENG Issue 2
Page 39
Wiring EPC3016, EPC3008, EPC3004
Shield
mA/mV/V Input
+
+
2.49
V+
V
5A
5B
2-wire transmitter
+
V+
V
+
2-wire transmitter
+
2.49
+
External power supply

Linear Input (mA, mV or V)

If shielded cable is used it should only be grounded in one place as shown
For a mA input connect the 2.49 burden resistor (R) supplied between the + and
input terminals as shown. The resistor supplied is 1% accuracy 50 ppm.

Two-Wire Transmitter Inputs

Using internal 24V power supply ( DIN and ¼ DIN only)
All models using an external power supply
39 HA032842ENG Issue 2
Page 40
Wiring EPC3016, EPC3008, EPC3004
+
S+
S
PRT PRT Lead Compensation
SI
S+
S
mA/mV/V Input
Shield
S+
S
+

Secondary Sensor Input (Measuring Input)

The secondary sensor input is not available in EPC3016 instrument.
CAUTION
MEASUREMENT INACCURACIES
Do not run input wires together with power cables.
When shielded cable is used, it should be grounded at one point only.
Any external components (such as zener barriers, etc) connected between sensor and input terminals may cause incorrect measurement due to excessive and/or un-balanced line resistance or possible leakage currents
The sensor input is not isolated from the logic outputs & digital inputs
Pay attention to line resistance; a high line resistance may cause measurement inaccuracies
A single sensor must not be connected to more than one instrument. Sensor break operation could be severely compromised
Failure to follow these instructions can result in injury or equipment damage.

Secondary Thermocouple Input

Use the correct compensating cable (preferably shielded) to extend thermocouple cabling, ensure that polarity is strictly followed throughout and that thermal junctions are avoided in any intermediate connections.

Secondary RTD Input

The resistance of the three wires must be the same. The line resistance may cause measurement inaccuracies if it is greater than 22 ohms.
40 HA032842ENG Issue 2

Secondary Linear Input (mA, mV or V)

If shielded cable is used it should be grounded in one place only as shown
For a mA input connect the 2.49 burden resistor (R) supplied between the + and input terminals as shown. The resistor supplied is 1% accuracy 50 ppm.
Page 41
Wiring EPC3016, EPC3008, EPC3004
S+
S
5A
5B
+
+
2-wire transmitter
+
2.49
S+
S
+
2-wire transmitter
+
2.49
+
External power supply

Secondary Two-Wire Transmitter Inputs

Using internal 24V power supply ( DIN and ¼ DIN only)
All models using an external power supply
41 HA032842ENG Issue 2
Page 42
Wiring EPC3016, EPC3008, EPC3004
1A
1B
1A
1B
+
-
1A
1B

Input/Output 1 (IO1)

I/O1 is available as standard in all models. It may be ordered as Contact Input, Triac Output, Logic Output, Analogue Output or Form A Relay Output.
The function of the I/O is fixed by the application ordered, or configured using the Quick Start Codes, "Start Up—New Unconfigured Controller" on page 61. Alternatively, the function can be changed in Configuration level ("I/O List (io)" on page 97) or through iTools ("The 'Browser' List" on page 185).

Relay Output (Form A, normally open)

Isolated output 300Vac CAT II
Contact rating: 2A 230Vac +15% resistive
Contact rating minimum: 100mA 12V
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Logic (SSR drive) Output

Not isolated from the sensor input, the current transformer input or the digital
inputs
Output ON state: 12Vdc at 40mA max
Output OFF state: <300mV, <100 µA
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Triac Output

Isolated output 300Vac CATII
Rating: 40mA to 0.75A rms, 30V rms to 230V rms +15% resistive load
42 HA032842ENG Issue 2
Page 43
Wiring EPC3016, EPC3008, EPC3004
1A
1B
+
1A
1B

Analogue Output

Output isolated 300Vac
Software configurable: 0–10Vdc, 0–20mA or 4–20mA.
Max load resistance: Voltage >450 Current <550
Calibration accuracy: % of reading + Offset
Voltage better than Current better than
+(0.5% + 50mV) +(0.5% + 100µA)
May also be configured as an isolated contact input

Contact Input

Not isolated from the current transformer input, the sensor input or logic outputs
Switching: 12Vdc at 40mA max
Contact open > 500. Contact closed < 150
43 HA032842ENG Issue 2
Page 44
Wiring EPC3016, EPC3008, EPC3004
2A
2B
2A
2B
+
2A
2B

Input/Output 2 (IO2)

I/O2 is available as standard in all models. It may be ordered as Contact Input, Triac Output, Logic Output, Analogue Output or Form A Relay Output.
The function of the I/O is fixed by the application ordered, or configured using the Quick Start Codes, "Start Up—New Unconfigured Controller" on page 61. Alternatively, the function can be changed in Configuration level ("I/O List (io)" on page 97) or through iTools ("The 'Browser' List" on page 185).

Relay Output (Form A, normally open)

Isolated output 300Vac CAT II
Contact rating maximum: 2A 230Vac +15% resistive
Contact rating minimum: 100mA 12V
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Logic (SSR drive) Output

Not isolated from the sensor input, the current transformer input or the digital
inputs
Output ON state: 12Vdc at 40mA max
Output OFF state: <300mV, <100 µA
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Triac Output

Isolated output 300Vac CATII
Rating: 40mA to 0.75A rms, 30V rms to 230V rms +15% resistive load
44 HA032842ENG Issue 2
Page 45
Wiring EPC3016, EPC3008, EPC3004
2A
2B
+
-
2A
2B

Analogue Output

Output isolated 300Vac
Software configurable: 0–10Vdc, 0–20mA or 4–20mA.
Max load resistance: Voltage >450 Current <550
Calibration accuracy: % of reading + Offset
Voltage better than Current better than
+(0.5% + 50mV) +(0.5% + 100µA)
May also be configured as an isolated contact input

Contact Input

Not isolated from the current transformer input, the sensor input or logic outputs
Switching: 12Vdc at 40mA max
Contact open > 500. Contact closed < 150
45 HA032842ENG Issue 2
Page 46
Wiring EPC3016, EPC3008, EPC3004
4A
4B
4A
4B
+
4A
4B

Input/Output 4 (IO4)

I/O4 is available as standard in EPC3008 and EPC3004. It is not available in EPC3016. It may be ordered as Contact Input, Triac Output, Logic Output, Analogue Output or Form A Relay Output.
The function of the I/O is fixed by the application ordered, or configured using the Quick Start Codes, "Start Up—New Unconfigured Controller" on page 61. Alternatively, the function can be changed in Configuration level ("I/O List (io)" on page 97) or through iTools ("The 'Browser' List" on page 185).

Relay Output (Form A, normally open)

Isolated output 300Vac CAT II
Contact rating maximum: 2A 230Vac +15% resistive
Contact rating minimum: 100mA 12V
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Logic (SSR drive) Output

Not isolated from the sensor input, the current transformer input or the digital
inputs
Output ON state: 12Vdc at 40mA max
Output OFF state: <300mV, <100 µA
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.

Triac Output

Isolated output 300Vac CATII
Rating: 40mA to 0.75A rms, 30V rms to 230V rms +15% resistive load
46 HA032842ENG Issue 2
Page 47
Wiring EPC3016, EPC3008, EPC3004
4A
4B
+
4A
4B
3A
3B
3C

Analogue Output

Output isolated 300Vac
Software configurable: 0–10Vdc, 0–20mA or 4–20mA.
Max load resistance: Voltage >450 Current <550
Calibration accuracy: % of reading + Offset
Voltage better than Current better than
+(0.5% + 50mV) +(0.5% + 100µA)
May also be configured as an isolated contact input

Contact Input

Output 3 (OP3)

Not isolated from the current transformer input, the sensor input or logic outputs
Switching: 12Vdc at 40mA max
Contact open > 500. Contact closed < 150
Output 3 is available in all models. It is a Form C (changeover) Relay. (In some earlier models this was referred to as AA Relay).
The function of the I/O is fixed by the application ordered, or configured using the Quick Start Codes, "Start Up—New Unconfigured Controller" on page 61. Alternatively, the function can be changed in Configuration level ("I/O List (io)" on page 97) or through iTools ("The 'Browser' List" on page 185).
Isolated output 300Vac CAT II
Contact rating: 2A 230Vac +15% resistive
The output switching rate must be set to prevent damage to the output device in
use. See "Cycle Time and Minimum OnTime Algorithms" on page 102.
47 HA032842ENG Issue 2
Page 48
Wiring EPC3016, EPC3008, EPC3004
A
B
Line
Neutral
A
B
Line
Neutral

General Information About Relays and Inductive Loads

CAUTION
RELAYS/TRIACS AND INDUCTIVE LOADS
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves. Through the internal contacts, these transients may introduce disturbances which could affect the performance of the controller.
For these types of load it is recommended that a 'snubber' is connected across the normally open contact of the relay switching the load. The snubber recommended consists of a series connected resistor/capacitor (typically 15nF/100). A snubber will also prolong the life of the relay contacts.
A snubber should also be connected across the output terminal of a triac output to help prevent false triggering under line transient conditions.
When the relay contact is open or it is connected to a high impedance load, the snubber passes a current (typically 0.6mA at 100Vac and 1.2mA at 230Vac).
You must ensure that this current will not hold on low power electrical loads. If the load is of this type the snubber should not be connected.
Failure to follow these instructions can result in injury or equipment damage.
48 HA032842ENG Issue 2
Page 49
Wiring EPC3016, EPC3008, EPC3004
CT
C
C
LA

Current Transformer

The current transformer input is an option in EPC3016 controller. It is supplied as standard in EPC3008 and EPC3004 controllers.
A further contact input (LA) shares a common terminal (C) with the CT providing up to three (EPC3016) and five (EPC3008 and EPC3004) contact inputs altogether.
C terminal is common to both the CT input and the contact input (LA). They are,
therefore, not isolated from each other, the sensor input or the logic outputs.
CT input current: 0–50mA rms (sine wave, calibrated) 50/60Hz
CT input resolution: 0.1A for scale up to 10A, 1A for scale 100A, 10A for scale up
to 1000A
CT input accuracy: +1% of reading.
A burden resistor, value 10, is fitted inside the controller.
RISK OF ELECTRIC SHOCK
It is recommended that the current transformer is fitted with a voltage limiting device to help prevent high voltage transients if the controller is unplugged (for example, two back-to-back zener diodes - the zener voltage should be between 3 and 10V, rated at 50mA).
Failure to follow these instructions will result in death or serious injury.

Contact Closure Input (LA)

This input is supplied with the current transformer, except on the Ethernet option in EPC3016 where LA is available but the CT is not.
Not isolated from the current transformer input, the sensor input or logic outputs
Switching: 12Vdc at 40mA max
DANGER
Contact open > 600. Contact closed < 300
The function of the I/O is fixed by the application ordered, or configured using the
Quick Start Codes, "Start Up—New Unconfigured Controller" on page 61. Alternatively, the function can be changed in Configuration level ("I/O List (io)" on page 97) or through iTools ("The 'Browser' List" on page 185).
49 HA032842ENG Issue 2
Page 50
Wiring EPC3016, EPC3008, EPC3004
5A
5B
+
-
24V
D1
D2
D3
D4
D5
D6
D7
D8
DC
C
8
24
C
1

Transmitter Power Supply

The Transmitter power supply is not available in the Model EPC3016.
It is fitted as standard in the Models EPC3008 and EPC3004.
Isolated output 300Vac CAT II
Output: 24Vdc, ±10%. 28mA max.

Digital Inputs/Outputs

Up to 8 digital inputs/outputs are available on the options terminals depending on the option fitted. These are marked D1 to D8.
Current sinking output. External DC PSU 15V minimum, 35V maximum
Voltage sensing logic input. High level input voltage 4V minimum. 35V maximum.
Low level input voltage 1V minimum, +1V maximum
Contact closure input. Contact closed 0 to 100. Contact open >28k.

Example BCD Switch Wiring

The diagram below shows an example of wiring a typical BCD switch using the first four digital inputs of EPC3008 or EPC3004 controllers which could be used to select a program number.
The BCD Inputs can be turned on in Level 3 or Configuration level, see "BCD List (bCd)" on page 135.
50 HA032842ENG Issue 2
Page 51
Wiring EPC3016, EPC3008, EPC3004
HF
HE
HD
Common
A(+)
B()
EPC3016
Twisted pair
Shielding
Ground at one end
Rx
Com
Tx
Master (PC)

Digital Communications Connections

On the EPC3008 and EPC3004, EIA485 (RS485) is standard. EIA232 (RS232) and EIA422 (RS422) are not supported.
On the EPC3016, EIA485 (RS485), EIA422 (RS422) and EIA232 (RS232) are supported via the option board.
ModbusRTU or Bisync protocol is used for compatibility with existing controllers.
Ethernet (ModbusTCP) is also supplied as an option in all controllers.
All instruments support EIA232 (RS232) via the configuration clip, however, this connection is not available when the instrument is fitted in a panel.
To help prevent earth ground loops, the cable shield should be grounded at one point only.
Isolated 300Vac CAT II.

EIA232 Wiring

EIA232 is available in EPC3016 only and is used to connect one master and one slave.
For 2-wire both master and slave ends act as Tx and Rx
51 HA032842ENG Issue 2
Page 52
Wiring EPC3016, EPC3008, EPC3004
HF
HE
HD
Com
A+
B
Twisted pair
Shielding
HF
HE
HD
EIA485
EIA232
RxB TxB RxA TxA Com
Tx Rx
Com
Daisy chain to further controllers
220 termination resistor R
T
on last
instrument in the line
Communication converter
(RS485 to RS232)
Com
Tx
Rx
R
T

EIA485 Wiring

EIA485 allows multi-slaves to be connected to the network. In practice a buffer is necessary to convert EIA485 connections from the controller to the EIA232 port of the PC. A suitable Communications Converter unit is recommended for this purpose. The use of a EIA485 board built into the computer is not recommended since this board may not be isolated and the RX terminals may not be biased correctly for this application. This may cause electrical noise problems or damage to the computer.
Connections using a suitable converter are shown in the following diagram.
Note: The device physical interface can only support up to 31 devices for each
segment. More than 31 devices will require additional buffering. For more details see the Communications Manual HA026230 which can be downloaded from www.eurotherm.co.uk.
52 HA032842ENG Issue 2
Page 53
Wiring EPC3016, EPC3008, EPC3004
CT
C
LA
HD
HE
HF
CT
C
LA
HD
HE
HF
RxA
RxB
Com
TxA
TxB
Tx Rx Com
Rx Tx
Com
NC
Rx+
Rx
Com
Tx+
Tx
NC
Rx+
Rx-
Com
Tx+
Tx
Twisted pair
Twisted pair
Shielded cable
220 termination resistor, R
T,
on
the last Rx of the converter unit
Daisy chain to further EPC301 controllers
220 termination resistor, R
T,
on the Rx terminals of the last instrument in the line
Communication
converter
EIA485
EIA232
Green
Amber

EIA422 Wiring

EIA422 (sometimes referred to as EIA485 4-wire) is available as an option in EPC3016 only. It allows up to 31 slaves to be connected to the network using separate transmit and receive twisted pairs. As with the previous example the use of a suitable communication converter is recommended to convert EIA422 to EIA232. The wiring connections are shown below.

Ethernet Wiring

An Ethernet networking capability is provided by an RJ45 connector, provided on the options board if this has been ordered
The connector has a pair of LED indicators.
Green on = network connection
Flashing amber = network activity
The connection is 10/100 base T, autosensing.
53 HA032842ENG Issue 2
Page 54
Wiring EPC3016, EPC3008, EPC3004
Solid State
Relay
e.g. ESWITCH
Heater fuse
Cooling fuse
Snubber
Cooling solenoid
T/C
Heater
Controller fuse
See Note below
+
-
1A
1B
2A
2B
L
N
3A
3B
3C
VI
V+
V-
N
L

Wiring Examples

Heat/Cool Controller

This example shows a heat/cool temperature controller where the heater control uses a SSR, triggered by a logic output on IO1, and the cooling control uses the relay, IO2.
DANGER
DISCONNECTING DEVICE
For permanently connected equipment, an isolating switch or circuit breaker must be included in the installation, and shall be in close proximity to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
Failure to follow these instructions will result in death or serious injury.
Note: A single switch or circuit breaker can drive more than one instrument.
54 HA032842ENG Issue 2
Page 55
Wiring EPC3016, EPC3008, EPC3004
Solid State Relay
e.g. ESWITCH
1A
1B
2A
2B
L
N
3A
3B
3C
VI
V+
V
N
L
L
CT
C
LA
HD
HE
HF
Heater Fuse
Heater
Current Transformer
Controller fuse
Thermocouple
+
-
Current Transformer (CT)

CT Wiring Diagram

This diagram shows an example of wiring for a CT input.
Note: A burden resistor value 10 is mounted inside the controller.
DANGER
RISK OF ELECTRIC SHOCK
To help prevent a build up of high voltages at the output of the CT if it is disconnected from the controller, it is recommended that a voltage limiting device be connected directly across the output of the CT. A suitable device is two back to back zener diodes, rated between 3 and 10V at 50mA, as shown in the diagram above.
Failure to follow these instructions will result in death or serious injury.
55 HA032842ENG Issue 2
Page 56
Start Up Modes EPC3016, EPC3008, EPC3004
3s
3s
A keyboard check will also be carried out. The controller will go into standby if the check does not complete as expected.
V.xxx
3004
V.xxx
1J4j4
V.xxx
1wmxx

Start Up Modes

What’s in this Chapter
This chapter describes:
What to expect when the controller is first switched on from new out of the box.
A general description of the display and button functions.
Power up after the instrument has been configured or commissioned.

Start up

Start Up (or Power Up) refers to the operation of the controller when Switched On.
EPC3000 range controllers are designed to be application based. Their start up modes will, therefore, vary depending on the way in which the controller was ordered and delivered. This chapter describes the different ways in which the controller can be ordered and delivered and how this affects the operation at power up.
1. Controller new 'out of the box' supplied unconfigured. "Start Up—New Unconfigured Controller" on page 61.
2. Controller new 'out of the box' supplied fully configured according to the order code. "Start Up - New Configured Controller" on page 65.
3. Subsequent start ups - Controller previously configured. Go to section "Subsequent Start-ups" on page 66.

Start up Diagnostic mode

In all cases the controller display will perform a diagnostic in which all bars of each character and every beacon is illuminated. In a configured controller the diagnostic display is followed by the firmware version number and the instrument type number, then a short summary of the Quick Codes. (A new unconfigured controller shows the Quick Codes only, see section "Start Up—New Unconfigured Controller" on page 61). Essentially the start up diagnostics is the same for each model.
The opening display is then dependent upon its configuration status and is described in subsequent sections.
The controller will read the idents of the hardware fitted. If a different hardware is detected a message will be displayed and the instrument will go into standby mode. To clear this message, either replace the module fitted with the expected module type OR the expected module parameter value is to be changed to match the fitted module parameter value.
56 HA032842ENG Issue 2
Page 57
Start Up Modes EPC3016, EPC3008, EPC3004
- Process Variable (Green, Red when in alarm)
- During navigation: parameter value
Engineering units of the process variable
(examples include ℃, ℉, K,%,%RH, %C, PH or blank)
Engineering units of the lower display
(examples include %, mA or blank)
Active setpoint
(RSP, SP, SP2)
When lit, indicates that user comms are active
When lit, indicates that manual mode has been selected
Output status
Alphanumeric display capable of presenting Cyrillic text
The parameter displayed can be selected via the
parameters in the HMI subclass of the instrument function block.
The ‘Home’ display, shows a scrolling message when
active.
Programmer ramp/dwell status
Flashes when any new alarm occurs. The beacon will be permanently lit when an alarm is acknowledged but is still active
4-digit PV
Engineering units of the process variable
(examples include ℃, ℉, K,%,%RH, %C, PH or blank)
Engineering units of the lower display
(examples include %, mA or blank)
4.5-digit PV
Alphanumeric display
Shows a numeric value such as setpoint or output value or a parameter mnemonic
Segmented bar graph
All other display content as per EPC3016
Alphanumeric display
Shows a numeric value such as setpoint or output value or a scrolling description of the parameter mnemonic
Flashes when any new alarm occurs. The beacon will be permanently lit when an alarm is acknowledged but is still active

General Description of Front Panel Displays

EPC3016

EPC3008

57 HA032842ENG Issue 2
Page 58
Start Up Modes EPC3016, EPC3008, EPC3004
5-digit PV
All other display content as per EPC3016 and EPC3008

EPC3004

The actual start up display that automatically follows depends on the way the controller has been supplied or re-configured and is described in subsequent sections.
58 HA032842ENG Issue 2
Page 59
Start Up Modes EPC3016, EPC3008, EPC3004
F1
ScrollPage
F2
Lower Raise

General Description of Operator Buttons

On EPC3016 only the 4 navigation buttons (Page, Scroll, Down, Up) are available. On EPC3008 and EPC3004 all 6 buttons (4 navigation and 2 function) are available.

Button Layout

Button Operation

Raise
The raise button increments parameter values to limits but there is no wrap-around.
Parameter enumerations, however, do wrap-around.
Lower
The lower button decrements parameter values to limits but there is no wrap-around.
Parameter enumerations, however, do wrap-around.
Page
In Operator levels 1 or 2 the Page button will select between the Home display or the Programmer Edit and Run lists (if one of the programmer features is enabled).
In Levels 3 or Config the Page button will scroll through list headers (no auto-repeat). If the Page button is pressed within a list, the display reverts to the top of the list. The top of the list shows the list header only with no initial parameters.
Page (held for >3 seconds)
The Goto parameter is selected directly. This operation can be performed from any display. If the Page is held for >3 seconds at power-up the Quick Start Mode is selected following the entry of a passcode.
Page+Raise
Scroll back the list headers (with auto-repeat)
Scroll
Select parameters in turn, returning to the first parameter in the list or to a list header if Level 3 or Configuration level is selected. If the button is held down the list will auto-repeat. In levels 1 and 2 this button also scrolls through promoted parameters when the HOME screen is selected.
Scroll+Raise
Scroll back through parameters from bottom to top (with auto-repeat).
59 HA032842ENG Issue 2
Page 60
Start Up Modes EPC3016, EPC3008, EPC3004
Page+Scroll - all variants
Jump directly to the "HOME page". The current operating level remains unchanged. If the HOME page is already selected, these buttons will perform the custom function as detailed in "Functionality of the F1 and F2 and Page + Scroll buttons" on page 170. The default is Alarm Acknowledge.
Raise+Lower (Run/Hold)
If a programmer option is enabled and a program is configured, a momentary press of these keys toggles between Run and Hold modes.
Raise+Lower (hold for >3 seconds - Mode)
If a programmer option is enabled and a configured program is running, holding these buttons will abort the program.
If the HOME page is selected and the Programmer is not running, holding these buttons will invoke the 'Mode' display where the Loop Mode parameter will allow selection of Auto or Manual mode.
F1 and F2
F1 and F2 buttons are not available in EPC3016.
The functionality of these buttons is set by the Instrument function block. The default settings are:
F1: Auto/Man
F2: Run/Hold
Note: A time-out applies to all displays. If no button presses are detected within a
timeout period (default 60s), the display will revert back to the Level 1 "HOME page".
60 HA032842ENG Issue 2
Page 61
Start Up Modes EPC3016, EPC3008, EPC3004

Start Up—New Unconfigured Controller

If the controller is new and ordered and supplied unconfigured it will start up in 'Quick Start Mode'. This is a built in tool which is provided to configure the product for the most commonly used functions such as the application type, input type, range, and digital input functions. The Quick Configuration code consists of two ‘SETS’ of five characters each. The upper section of the display shows the set selected, the lower section shows the five digits which make up the set. Each digit may result in multiple parameter values being set. The opening set is SET1 as shown.
Initially all characters are shown as an
X. This is generally the default character for
‘not fitted/none’ or ‘use default’. The first character, initially flashing, selects the Application Type as listed in the Quick Start Tables in the following sections. To select
the required application type press
or .
Note: Quick Code 1 will only be available if the correct hardware is fitted for the
application. For example, the VPU application must have IO1 and IO2 as relay, triac or logic outputs.
Press
to select the second character. The second character selects the ‘Input 1
Type’ as listed in the Quick Start Tables in the following sections. If hardware or features are not available then the character is skipped over when pressing scroll.
Continue to set up all 5 characters using the Quick Start Tables.
When the last character in SET1 has been entered the display will automatically go to SET2.
Adjust these in the same way as SET1.
At any time to return to the start of SET1, press
WARNING
HAZARD OF INCORRECT CONFIGURATION.
Incorrect configuration can result in damage to the process and/or personal injury and must be carried out by a competent person authorised to do so. It is the responsibility of the person commissioning the controller to ensure the configuration is correct.
Failure to follow these instructions can result in serious injury, or equipment damage.
More detailed features available in the product may also be configured by entering a Configuration Level. This is explained in "Configuration Level" on page 84, or by using iTools as explained in "Configuration Using iTools" on page 181. iTools is a configuration package available free of charge from Eurotherm by accessing www.eurotherm.co.uk.
61 HA032842ENG Issue 2
Page 62
Start Up Modes EPC3016, EPC3008, EPC3004

Quick Start Tables

The 1st digit in SET 1 will select an application which automatically configures relevant function block parameters and creates wires between function blocks to make a complete control strategy relevant to that application. Application ‘1’, Heat only controller; application ‘2’ heat/cool controller; application ‘V’ VPU heat only controller are generally covered by this manual. Other applications such as ‘C’ ­carbon potential and ‘D’ - dew point control are each provided as an addendum to the User Manual and are available from www.eurotherm.co.uk.
The digits will present "X" when not fitted and the HMI will skip over that field. Similarly, entering a value of "X" in a field will disable that feature, if appropriate.

Quick Code Set 1

Note: If no application is selected (1st character in SET 1 = X) the display will go
directly to the EXIT screen. If accepted the controller will take on a set of default values. Any further configuration may be carried out by accessing the Configuration Level ("Configuration Level" on page 84) or through iTools configuration software ("Configuration Using iTools" on page 181).
Note: For linear inputs the minimum/maximum input voltage/current will cause the
display to read range low/high respectively
Note: If the input 2 is not fitted Set 2 will be selected immediately after Input 1
Range has been set.
* Temperature, Carbon potential and dew point control are described as separate supplements to this manual and are available from www.eurotherm.co.uk. Part numbers HA033033, HA032987 and HA032994 respectively.
62 HA032842ENG Issue 2
Page 63
Start Up Modes EPC3016, EPC3008, EPC3004

Quick Code Set 2

Note: The Quick Code assumes that the CT input is monitoring the current of the
heat channel load which in all applications is wired to IO1.PV.
Note: If IO.1 module is a DC Output module then CT Input digit is not alterable. Note: If CT input is not set to X, the CT Input will be enabled and will monitor the
current; however, CT alarms will not be configured. This means that if CT alarms are required they must be wired by the user. A typical example of wiring alarms is shown in section "Example 1: To Wire an Alarm" on page 195.

Quick Codes DIO

Example of Quick Codes
SET1: 1. J. 3. X. X
SET2: X. M. W. X. C
The controller is configured for PID Heat Only, Input 1 Thermocouple Type J, Range
0–400, Input 2 and Range not used, CT Input not used, Digital Input LA will select Auto/Manual, Digital Input LB will select Global Acknowledge of Alarms, Temperature Units Degrees Celsius.
63 HA032842ENG Issue 2
Page 64
Start Up Modes EPC3016, EPC3008, EPC3004

To Save or Discard Quick Codes

When all characters have been entered the display will show:
If
No is selected (by pressing ) the display returns to SET1.
Press
or to select SAVE then either press to select or wait for 2
seconds to accept. This accepts the Quick Configuration Codes and the controller enters Operator Level 1.
OR
Press
seconds to accept
or to select Disc then either press to select or wait for 2
. This discards the last entered codes and returns the controller to
its previous settings.
Selecting either SAVE or diSc will result in the instrument performing a restart.

To Re-Enter Quick Code mode

It is possible to re-enter Quick Start mode, by holding down the Page key during power up.
It is then necessary to enter the configuration level passcode. See "To Select Configuration Level" on page 87.
If the configuration of the instrument is subsequently modified by a change made via Configuration Mode this will be shown by the quick code digits being separated by the dp dot (indicating that the codes shown may not reflect the current configuration). If the codes are then accepted the instrument is re-configured to satisfy the code settings.
Note: If the config clip is connected the instrument may be powered from the USB
port of the PC. In this case it is necessary to disconnect the config clip to re-enter Quick Start Mode. Alternatively, disconnect the power pins from the config clip. See "Using the Configuration Clip" on page 182.
Note: If a Cold Start (See "Cold Start" on page 214) has been invoked the
instrument will always start in Quick Code Mode without the need to enter the configuration passcode.
64 HA032842ENG Issue 2
Page 65
Start Up Modes EPC3016, EPC3008, EPC3004

Start Up - New Configured Controller

If a product has been ordered using the Order Code it will already be configured. When new, ‘out of the box’, it will then power up in operating Level 1.
Also, if it has previously been configured, for example, using the Quick Codes then it will start up in Operating mode.
The start up display is dependent upon the application or the way in which the controller is configured, see ‘Start-up Modes’ in the following section.

Bar Graph

Setpoint

The view shown above is generally referred to as the ‘HOME’ Display.
In EPC3008 and EPC3004 the HOME display normally consists of three lines. The upper line normally shows the Process Value "PV",
The centre line normally shows the Working Setpoint "WSP" if the controller is working in its normal Auto mode or the Output demand if it is in Manual Mode.
The lower line shows a scrolling message providing a longer description of the selected parameter. It may also display a further parameter value if this has been set up in the instrument block, see "Display Functionality Sub-List (HmI)" on page 169.
In EPC3008 and EPC3004 a bargraph may also be configured using iTools. The bargraph may be ‘soft’ wired to any convenient source such as PV input or output demand, see "Example 4: To Configure a Bargraph" on page 196.
EPC3016 has two lines of display. The line below the top one alternates between a mnemonic and the scrolling message. A bargraph is not available.
The Setpoint is defined as the value which the process is required to attain. The value of the setpoint may be obtained from a number of sources, for example, manually using the front panel keys, via the programmer function block, via an external analogue source, via digital communications. The working setpoint is, therefore, defined as the current setpoint derived from any of these sources.
65 HA032842ENG Issue 2
Page 66
Start Up Modes EPC3016, EPC3008, EPC3004

Subsequent Start-ups

When the controller is no longer new and has been in normal use it will start up in Level 1, even when it has been powered down in Operator level 2 or 3. If, however, it was powered down when in Configuration level it will power up in ‘Standby’ and show
a message - ‘ re-enter configuration level (with password - see "To Select Configuration Level" on page 87), then, either continue with changes to the configuration or accept existing changes by exiting configuration level. The reason for this is that the controller may have been part configured prior to shut down and either needs completion of the configuration or confirmation that no further changes are required.

Start-up Modes

The controller may start in manual or in automatic mode depending on the setting of the ‘Recovery Mode’ parameter, see section "Configuration Sub-List" on page 109.
If the Recovery Mode has been set to Manual (default) the controller will start in ‘Man’
mode. It will show the letter ‘ will be at the ‘Fallback Value’, see section "OP Sub-list" on page 121, but may then be changed using the raise or lower buttons. Auto mode may also be selected.
POWERED DOWN WHILST IN CONFIG MODE’. To clear the message
M’ and the ‘hand’ symbol in the display. Initially the output
If the Recovery Mode has been set to ‘Last’ the controller will start in either in Manual mode or Auto mode depending on whatever mode it was in prior to being powered off. ‘Auto’ mode is shown in the EPC3004 view in the previous section.
For further information on start up modes see section "Start-up and Recovery" on page 257.
66 HA032842ENG Issue 2
Page 67
Start Up Modes EPC3016, EPC3008, EPC3004

Standby

Standby is the term given when the instrument strategy is not controlling due to the following reasons:
If the instrument is being configured i.e. in Quick Code Mode, Configuration
Mode or a clone file is being loaded.
If the instrument has detected an unexpected condition (for example, was
powered down whilst in configuration mode, or fitted hardware does not match expected hardware). See "Start up Diagnostic mode" on page 56 for more information on unexpected conditions that will place the instrument into standby.
If the instrument is forced into standby via the
Instrument.Diagnostics.ForceStandby parameter, see "Subsequent Start-ups" on page 66.
When the instrument is in standby, the following occurs:
All outputs are placed into their 'Off' state, unless being used as Valve Raise (Up)
/ Lower (Down) in which case the Standby Action is configurable (Rest, Up, Down).
The control loop will be placed into Hold.
If an alarm has the Standby Inhibit parameter set to On, then the alarm is
inhibited (active alarms will be turned Off and new alarm conditions will not be acted upon).
If in standby due to the instrument being configured, a running program will reset.
WARNING
LOSS OF COMMUNICATIONS
If the output is not wired, but written to by communications, it will continue to be controlled by the communications messages. In this case take care to allow for the loss of communications.
Failure to follow these instructions can result in serious injury, or equipment damage.
67 HA032842ENG Issue 2
Page 68
Start Up Modes EPC3016, EPC3008, EPC3004

Auto-scaling of decimal point

The range of values displayed on the ‘top line’ will vary for each instrument version. If a value exceeds the display capabilities, the resolution will automatically be reduced by a factor of 10, up to the display limit in the table below. If the value cannot be displayed, HHHH or LLLL will be shown.
Auto-scaling is applied to parameter values being edited via the HMI.
Instrument Decimal
points
EPC3016 0 1999 9999
1 199.9 999.9
2 19.99 99.99
3 1.999 9.999
EPC3008 0 1999 19999
1 199.9 1999.9
2 19.99 199.99
3 1.999 19.999
EPC3004 0 19999 99999
1 1999.9 9999.9
2 199.99 999.99
3 19.999 99.999
4 1.9999 9.9999
Minimum Maximum
68 HA032842ENG Issue 2
Page 69
Operator Levels EPC3016, EPC3008, EPC3004

Operator Levels

What’s in this Chapter
This chapter describes the different operator levels:
Operator Level 1
Operator Level 2
Introduction to Operator Level 3
Return from a higher level to a lower level of operation

Overview

There are 5 levels of operation:-
1.
LEv1 - Level 1 has no passcode, the control is active and only the home list is
accessible.
2.
LEv2 - Level 2. The control is active and an extended home list is accessible.
3.
LEv3 - Level 3. The control is active and the complete operator parameter set is
shown and modifiable; the complete Configuration parameter set is shown, read only; the user calibration (two point cal) facility is available.
4.
ConF - Configuration level is used to setup the whole controller; the
configuration parameters are accessible; the operator parameters are available, without the need to switch to operator mode. The instrument calibration parameters are also available in this mode. See "User Calibration" on page 278.
Levels 2, 3 and Configuration can be restricted by passcodes.
5. In addition the Quick Start Mode (See "Start Up—New Unconfigured Controller" on page 61) is provided to configure the product in the minimum number of operations. It is only available at power up after the instrument is cold started or by holding the Page key during power up.
69 HA032842ENG Issue 2
Page 70
Operator Levels EPC3016, EPC3008, EPC3004
Press to increase the setpoint
The new setpoint is entered when the button is released and is indicated by a brief flash of the SP value
Process Value (PV)
Bargraph (not EPC3016)
Scrolling message
Setpoint (SP) (Required Temperature)
Press to decrease the setpoint

Operator Level 1

Operator Level 1 is entered:
1. After the Quick Code has been entered for those controllers supplied unconfigured
2. After power up when the controller has been configured
The display shown below is for a typical temperature controller.

Manual Mode

In general the current value of the process is shown in the upper display and, when in ‘Auto’ mode, the required value (Setpoint) is shown in the lower display. However, this may depend, for example, upon the application or if the controller is in Manual mode (see below).
Additional scrolling messages are shown, for example, when operator parameters are selected (see section "Level 1 Operator Parameters" on page 72). These may be standard descriptions of the parameter currently selected or they may be user specific messages which have been set up using iTools. (See "Parameter Promotion" on page 203).
In Operator Level 1 the controller may be placed into manual operation as follows:
By default in EPC3008 and EPC3004 Auto/Manual may be selected by the user
by toggling the F1 button.
By default in EPC3016 Auto/Manual may be selected by the user by pressing
and holding the
the A-M (Auto-manul select) parameter. Then press
between auto and manual.
and buttons for longer than 3 seconds. This will show
or to toggle
Manual is indicated in the HMI by showing the ‘Hand’ symbol and the character ‘
The current level of the output demand is shown as a percentage. This may be
increased or decreased by pressing the
Note: Alternative ways to select Auto/Manual may be configured and will be
explained in subsequent chapters of this manual.
70 HA032842ENG Issue 2
or buttons respectively.
M’.
Page 71
Operator Levels EPC3016, EPC3008, EPC3004

System Messages

In addition to standard (or customised) scrolling messages, System Messages may be shown at any time. A list of these is shown in "Notification Messages" on page 287 but a typical message may be ‘USING DEFAULT COMMS CONFIG PASSWORD’. This is shown if the Comms Config Password has not been changed from its default value. For example, it is possible to enter configuration mode via digital communications which is restricted by a passcode. This passcode is only available using iTools and should be changed from its default value to provide additional security. When this has been done the message will not appear in the HMI in operator level.
This particular message may also be disabled in Instrument Configuration mode, see "Security Sub-List (SEC)" on page 171.

Bargraph

In EPC3008 and EPC3004 a bargraph may also be shown which displays the configured value as a horizontal bar. This is set up in Configuration Level (See "Display Functionality Sub-List (HmI)" on page 169).

Comms Configuration Active

The scrolling message ‘COMMS CONFIGURATION ACTIVE’ will be displayed if, for example, iTools is connected to the controller and has been placed in configuration mode by iTools.
The character ‘ displayed as shown below.
Note: The displays shown above also apply if the controller is in Operator Levels 1,
2 or 3.
H’ signifies that the controller has been placed into Hold mode and is
71 HA032842ENG Issue 2
Page 72
Operator Levels EPC3016, EPC3008, EPC3004

Level 1 Operator Parameters

A minimal list of parameters is available in Operator Level 1 which is designed for day to day use. Access to these parameters is not restricted by a passcode.
Press to step through the list of available parameters. The mnemonic of the
parameter is shown in the lower display. Alternatively, press and hold then press
to scroll forward through parameters and to scroll back.
Press
to return to the Home display.
The value of the parameter is shown in the upper display. If the value is read/write
press or to adjust. If no key is pressed for 60 seconds the controller returns
to the HOME display. The navigation is shown diagrammatically for the first two parameters in the example below:
The parameters that appear depend upon the functions configured. The list can also be customised using iTools by adding or removing parameters. The table below shows an example of the list of parameters in Level 1. Parameters may be added to or deleted from this list, see "Parameter Promotion" on page 203.
Parameter Mnemonic
W.OUT WORKING OUTPUT
R-L Remote-local select
SP1 SETPOINT 1
SP2 SETPOINT 2
ai1.PV pv
ai2.PV pv
LD.I CT Load Current
Scrolling name Description Further
information
The output demand – 0% to 100% or 100% to +100%
Selects the Remote or Local setpoint source
The value which the process is required to attain as set by setpoint 1
The value which the process is required to attain as set by setpoint 2 if selected
The current value of the process (read only) read by the primary input IP1
The current value of the process (read only) read by the secondary input IP2
The current being supplied to the heater as measured by the CT
"Loop - Main Sub-list" on page 107
If the secondary input is used
If the CT is being used
72 HA032842ENG Issue 2
Page 73
Operator Levels EPC3016, EPC3008, EPC3004
pROg
list

Level 1 Programmer Display

By default, if the controller has the programmer installed, the status of a running program can be displayed .

Programmer List

Press the page button , the display will show
Repeatedly press
to read the currently running program.
Parameters displayed are (but not limited to depending on the program):
Parameter Mnemonic
p.num program number
p.cur current program
p.mode program mode
p.sp program setpoint
p.tim.l program time left
p.cyc.l program cycles left
s.num current segment number
s.type current segment type
s.tim.l segment time left
evt.x event x
p.advn program advance
Scrolling name Description
Alterable but does not affect the running program
Read only
Displays the current mode e.g. Run, Hold, Reset,
Read only
Read only
Read only
Read only
Read only
Read only
event off or on. Further events are shown if configured
Read only
By default the programmer parameters available in Level 1 are read only. It is possible, however, to provide programmer edit access to Level 1, see "Programmer List (PROG)" on page 125. If this has been done the lists of parameters is shown in section "Level 2 Programmer Display" on page 77.

Crows Foot Status Bar

The current status of the running program is displayed as follows:
State Ramp/Step Up Dwell Ramp/Step Down
Reset
Run
Hold/Holdback Flashing (1
second period 66% duty cycle)
Flashing (1 second period 66% duty cycle)
Flashing (1 second period 66% duty cycle)
Complete (Dwell End)
Not applicable Flashing (2
seconds period 66% duty cycle)
Not applicable
73 HA032842ENG Issue 2
Page 74
Operator Levels EPC3016, EPC3008, EPC3004
LVL2
goto
0___
code
00
w.out

Operator Level 2

To Select Operator Level 2

Operator level 2 is normally restricted by a passcode. By default the passcode is 0002 in a new controller. Enter Level 2 as follows:
Operation Action Display Notes
Select Level 2
1. Press and hold
until Goto is shown.
2. Press to choose
LEv 2 (Level 2).
Enter the passcode
Select Level 2 parameters
3. Press
4. Press or to
enter the correct digit value of the passcode
5. Press to accept
the value and move to the next digit
6. The controller will now show the top of the HOME list in Level 2
7. Repeatedly press
to enter
Press to move to the next digit.
The default passcode for level 2 is '0002'.
A special case exists if a security code has been configured as '0000'. If this has been done it is not necessary to enter a code and the controller will enter the chosen level immediately.
If an incorrect code is entered the display will return to HOME. After three wrong attempts the passcode entry system will lock out for a time set by the ‘Passcode Lockout Time’ set in the "Security Sub-List (SEC)" on page 171.
The list of available parameters is given in the table in the next section.
74 HA032842ENG Issue 2
Page 75
Operator Levels EPC3016, EPC3008, EPC3004

Level 2 Operator Parameters

Parameters available in level 1 are also available in level 2, but level 2 includes additional parameters for commissioning purposes and for more detailed operation.
Press to step through the list of available parameters. The mnemonic of the
parameter is shown in the lower display. Press
to return to the previous
parameter.
The value of the parameter is shown in the upper display. If the value is read/write
press
or to adjust. If no key is pressed for 60 seconds the controller returns
to the top of the HOME list.
By default the following table lists all possible parameters available in both Levels 1 and 2. Parameters associated with a particular feature will only be shown if that feature is configured.
Parameter Mnemonic
W.OUT WORKING OUTPUT
R-L Loop Remote/Local
SP.HI SETPOINT HIGH
SP.LO SETPOINT LOW
SP1 SETPOINT 1
SP2 SETPOINT 2
SP.UP Setpoint Rate up
SP.DWN Setpoint Rate down
AI1.PV PV
AI2.PV PV
TUNE AutoTune Enable
PB.H Ch1 Proportional
PB.C Ch2 Proportional
TI Integral Time
TD Derivative Time
cbh cutback high
cbl cutback low
Scrolling name Description Further
information
The output current demand – 0% to 100% or -100% to +100%
Selects the Remote or Local setpoint source
Maximum value allowed for the local setpoints (SP1 and SP2).
Minimum value allowed for the local setpoints (SP1 and SP2).
The value which the process is required to attain as set by setpoint 1
The value which the process is required to attain as set by setpoint 2 if selected
Limits the maximum rate at which the working setpoint can change in an increasing (upwards) direction.
Setpoint rate limiting is often used to prevent rapid bumps in controller output that may damage equipment or product, or cause upset to downstream processes
Limits the maximum rate at which the working setpoint can change in an increasing (downwards) direction.
The current value of the process (read only) read by the primary input IP1
The current value of the process (read only) read by the secondary input IP2
Starts an autotune
Level 1 & 2
Level 1 & 2
Level 1 & 2
Level 1 & 2
Level 1 & 2
Level 1 & 2
"Autotuning" on page 264
Channel 1 (heat) proportional band
Band
Channel 2 (cool) proportional band
Band
Integral time
Derivative time
High cutback
threshold
Low cutback
threshold
75 HA032842ENG Issue 2
Page 76
Operator Levels EPC3016, EPC3008, EPC3004
Parameter
Scrolling name Description Further
Mnemonic
MR Control Manual
HYS.H Control Ch1 On Off
HYS.C Control Ch2 On Off
C.DB Control Ch2
OUT.HI Output High Limit
OUT.LO Output low Limit
LD.I CT Load Current
LK.I CT Leak Current
LD.SP CT Load Threshold
Lk.SP CT Leak Threshold
oc.sp CT overcurrent
cs.id Customer ID
rec.no dataset to load
store dataset to save
Reset
Hysteresis
Hysteresis
Deadband
threshold
If the integral parameter is turned off the controller is working in proportional only or proportional + derivative. This parameter allows the output to be adjusted manually to offset and difference between SP and PV.
If channel 1 is configured for On/Off control this parameter allows a difference to be set between the output being on or off.
If channel 2 is configured for On/Off control this parameter allows a difference to be set between the output being on or off.
The Ch1/Ch2 Deadband is a gap in percent between output 1 going off and output 2 coming on and vice versa.
For on/off control this is taken as a percentage of the hysteresis.
To limit the maximum controller output
To limit the minimum controller output
This is the sampled RMS current measured during the on time of the heater.
The RMS current measured flowing through the load during the off states of the controller.
Sets a threshold to trigger an alarm if the load current is exceeded
Sets a threshold to trigger an alarm if the leak current is exceeded
Sets a threshold to trigger an over current alarm if the current measured exceeds a maximum limit set by the process
A user configurable non-volatile identification parameter
Selects which recipe dataset to load
Selects which of the 5 recipe dataset in which to store the current active parameters.
information
Level 1 & 2
The home list can be customized by adding up to 60 parameters; iTools will be required to configure the promoted parameters, see "Parameter Promotion" on page 203.
76 HA032842ENG Issue 2
Page 77
Operator Levels EPC3016, EPC3008, EPC3004
pROg
list

Level 2 Programmer Display

By default, if the controller has the programmer installed, the programmer can be edited and operated from the HMI.

Programmer List

Press the page button , the display will show
Repeatedly press
to read the currently running program. The program can be
Run, Held or Reset from this list.
Parameters displayed are (but not limited to depending on the program):
Parameter Mnemonic
p.num program number
p.cur current program
p.mode program mode
p.sp program setpoint
p.tim.l program time left
p.cyc.l program cycles left
s.num current segment number
s.type current segment type
s.tim.l segment time left
tsp target setpoin
r.rate ramp rate
evt.x event x
p.advn program advance
Scrolling name Description
Alterable, but does not run a program
Read only
The programmer can be changed to Run, Hold, Reset,
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Event off or on. Further events are shown if configured
Alterable YES/NO. Advances the program to the next segment
77 HA032842ENG Issue 2
Page 78
Operator Levels EPC3016, EPC3008, EPC3004
p.set
list

Program Setup List

By default programs can be set up in Level 2.
Press the page button
, the display will show
Repeatedly press
to read the currently running program. Programs can be
edited from this list.
Parameter Mnemonic
p.num program number
hb.sty holdback style
hb.typ holdback type
ramp.u ramp units
dwel.u dwell units
p.cyc program cycles
p.end program end type
s.num current segment
s.typ segment type
tsp target setpoint
r.rate ramp rate
ev.op event output
dur duration
r.time time to target
c.prog call program
c.cyc call cycles
Scrolling name Description
number
Alterable but does not run a program. If the program is running WORk is shown signifying the working program.
Alterable: PROG (holdback applies to the whole program). SEGm (holdback applies to each segment)
Alterable: OFF, LOW, HIGH, bANd. For a full definition see "Holdback" on page 231
Alterable: P.SEC (per second), P.mIN (per minute), P.HR (per hour)
Alterable: SECS, mINS, HrS
Alterable: The number of time a program repeats. CONt (continuous) or 1 to 9999
Default 1
Alterable: Behaviour when the program ends dWEL (dwell at current setpoint). RSEt (reset). tRAk (track)
Alterable:
RAtE, tImE, dWEL, Step, CALL, ENd
Alterable:
Alterable:
Alterable:
Alterable: Appears if the segment type is Dwell or Time
Alterable: Appears if the segment type is Time
Alterable: Appears if the segment type is Call
Alterable: Appears if the segment type is Call
The above is a summary the parameters which are displayed (but not limited to) and depends on the program. A full description of the parameter meanings and how to set up programs is given in the following sections:
Configuration chapter "Programmer List (PROG)" on page 125.
iTools chapter "Programmer" on page 188.
Programmer chapter "Programmer" on page 227
78 HA032842ENG Issue 2
Page 79
Operator Levels EPC3016, EPC3008, EPC3004
LVL3
goto
0___
code
LEV3
pass
A1
list
tC
IN.TYP

Operator Level 3

In Operator level 3 (and in Configuration Level) all parameters are organised in lists (or groups). Only parameters related to enabled functions are shown.
Each list may contain operator level and configuration parameters; the parameters are only shown when the instrument is in the appropriate mode. If a list does not contain at least one displayable parameter, it is skipped completely.
During navigation, the lower display shows the mnemonic code of the parameter or the List header. After 6 seconds, a scrolling string with either the parameter or the List description will be displayed.

To Enter Level 3

Operation Action Display Notes
Select Level 3
1. Press and hold until
LEv 3 is shown.
LEv1 is displayed first. Continue
to hold the button to obtain
LEv3
Enter the passcode
Select list headers
Select parameters in the list
2. Press
3. Press or to
enter the correct digit value of the passcode
4. Press to accept the
value and move onto the next digit
5. If the correct passcode has been entered the
message PASS will be displayed momentarily. The controller is now operating in Level 3.
6. Repeatedly press
7. Repeatedly press
to enter
Press to move to the next digit.
The default passcode for level 3 is '0003'.
A special case exists if a pass code has been configured as '0000'. If this has been done it is not necessary to enter a code and the controller will enter the chosen level immediately.
If an incorrect code is entered the display will return to HOME
If an incorrect code is entered the display will return to HOME. After three wrong attempts the passcode entry system will lock out for a time set by the ‘Passcode Lockout Time’ set in the "Security Sub-List (SEC)" on page 171.
This shows the Analogue Input List.
Press + the previous list header
This shows the Input Type.
to return to
To return to the HOME page relevant to the controller mode press the 'Home' key combination (Page+Scroll).
The HOME display is also selected after a timeout period with no key presses. The timeout defaults to 60 seconds but can be adjusted between 0 and 60 seconds. A setting of 0 means no timeout (see "Display Functionality Sub-List (HmI)" on page 169), so that the HMI remains in the selected level.
79 HA032842ENG Issue 2
Page 80
Operator Levels EPC3016, EPC3008, EPC3004

Level 3 Operator Parameters

The Operator Level 3 lists are essentially the same as configuration level. These are shown in the next chapter.

To Return to a Lower Level

From Level 3 you can select Level 1 or Level 2 as follows:
1. Press and hold until
2. Press
3. Press
or to select LEv1 (or LEv2)
to accept.
Goto is displayed
The display will briefly show PASS and will return to the selected level default display.
A security code is not required when going from a higher level to a lower level.
Note: if the controller had been switched off whilst operating in levels 2 or 3 it will
return to operator level 1 when switched on again. If it was switched off when in
configuration level it will start up with a message -
config mode
. See section "Subsequent Start-ups" on page 66.
P.CnF - powered down whilst in
80 HA032842ENG Issue 2
Page 81
Navigation Diagram EPC3016, EPC3008, EPC3004

Navigation Diagram

The Navigation Diagram shows the series of operations of the front panel buttons which are required to navigate to specific parameters.
For ease of access parameters are arranged in lists. Each list has a header and each
header is selected by repeated presses of the ’Page’ button
has a title, for example, the first header is the Analogue Input (AI LIST).
A list may have a number of instances. For example, if two Analogue Inputs are supplied then the list is split into 1 INST and 2 INST selected using the ’Raise’ and
’Lower’ buttons /
Similarly a list may have a number of Sub-Lists. For example, the LOOP list. The
sub-lists are selected by entering the first sub-list, using the ’Scroll’ button , then
using the ’Raise’ or ’Lower’ buttons to select the following sub-lists.
When the appropriate list or sub-list has been selected use the ’Scroll’ button to scroll through a list of parameters. Use the Page button to scroll back.
The Navigation Diagram which follows shows these button presses diagrammatically.
The Navigation Diagram generally includes all lists and all parameters available in configuration level. Some parameters may not be shown in Level 3 and only those lists and parameters which are required for a particular application are displayed on the controller.
.
. Each list header
81 HA032842ENG Issue 2
Page 82

Navigation Diagram

IN.TYP
LIN UNITS DEC.P
RNG.HI RNG.LO
MV.HI MV.LO SHUNT
PV.OFS FILT.T CJ.TYP SB.TYP SB.OUT CJC.IN
PV PV.ST MV.IN
TYPE STAT
IN THLD HYST
LATCH BLOCK DELAY
OUT ACK
INHIB
S.INHB
REF
RATE
RT.UNIT
FILT.T
ALm
LIST
1
INST
2
INST
TYPE STAT
IN THLD HYST
LATCH BLOCK DELAY
OUT ACK
INHIB
S.INHB
REF
RATE
RT.UNIT
FILT.T
RNG.HI RNG.LO
SP.HI SP.LO
SP.SEL
SP1 SP2
PSP.S
PSP
RSP.T RSP.HI RSP.LO RSP.EN
RSP TRM.HI TRM.LO
TRIM
RT.UNT
SP.UP SP.DWN RT.DIS RT.DNE RT.SVO TRk.PV TR.PRG TR.RSP SP.BAL
A-M R-L
MODE
SP.SRC
PV
TGT.SP
W.SP
W.OUT
HOLD TRACK F.MAN
I.HOLD
HEAT.T COOL.T
ACTN SP.SRC D.TYPe PB.UNT RECv.M BAD.TX MAN.TX AM.LVL Sp.lvl
m.lvl
LOOp
LIST
F.TYPE
DV F.GAIN F.BIAS F.LEAD
F.LAG
F.HI F.LO
F.HOLD
F.OP
FB.TRM
TUNE T.HI T.LO
T.CH2 T.ALGO T.STAT
Stage
Sgt.t
G.SCH
SET
BOUND
GS.HYS
PB.H PB.C
TI
TD CBH CBL
MR
OP.HI OP.LO HYS.H HYS.C PB2.H PB2.C
TI2 TD2
CBH2 CBL2
MR2
OP.HI2 OP/LO2 HYS2.H HYS2.C
L.BRK.T L.BRK.D
L.BRK
DEMO
DEV
TGT.OP W.OP.HI W.OP.LO
P.TERM
L.VOLT
W.PB.H
W.PB.C
W.TI
W.TD W.CBH W.CBL
W.MR
AT.LIM IN.HLD IN.TRA IN.MAN IN.AUT
M.RDY
FLBK.V OUT.HI OUT.LO
H.OUT
C.OUT MAN.OP TRK.OP CH2.DB
OP.UP OP.DWN OP.DIS PWR.FF
C.DB NLIN.C STEP.V
TT.H
TT.C
R.OP.HI
R.OP.LO.
R.OP.DI
mAIN
S.LIST
CFG
S.LIST
SP
S.LIST
FF
S.LIST
AtuN
S.LIST
PiD
S.LIST
OP
S.LIST
diAG
S.LIST
A1
LIST
1
INST
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT
M.O.T
CYCl.T
SENSE
INER
BKLSH
STBY
FLBK.V
io
LIST
io.1
INST
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT
M.O.T
CYCl.T
SENSE
INER
BKLSH
STBY
FLBK.V
io.2
INST
IDENT
TYPE
PV
OUT
SENSE
OP.3
INST
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT
M.O.T
CYCl.T
SENSE
INER
BKLSH
STBY
FLBK.V
io.4
INST
IDENT
TYPE
PV
SENSE
LA
INST
IDENT
TYPE
PV
SENSE
Lb
INST
IN.TYP
LIN UNITS DEC.P
RNG.HI RNG.LO
MV.HI MV.LO SHUNT
PV.OFS FILT.T CJ.TYP SB.TYP SB.OUT CJC.IN
PV PV.ST MV.IN
2
INST
State c.pot
Dew.pt
O2
Sat.lim
Out.st
Soot
Cof H2f
Pf Prb.in Tmp.in p.bias t.bias
Probe O2.typ O2.unt Co.idl
Min.t Soot.k
ZIRC
LIST
MAIN
s.list
CONF
s.list
Cln.en
Clean
Abrt.c
c.tmr
c.mv
c.rcov
c.rst Brnof c.frq
Max.t c.min.r c.max.r
CLN
s.list
z.run
z.abrt
Imped
z.max.r
z.thrs
z.rst
Imp
s.list
+
IDENT
TYPE
PV
SENSE
OUT
O.dIO
LIST
IDENT
TYPE
PV
SENSE
OUT
d1
INST
d2
INST
+
LOAD SAVE
E.ALT
RECP
LIST
CT.EN CT.SRC CT.RNG CT.LAT
LD.SP
LK.SP
OC.SP
LD.I
LK.I LD.ALM LK.ALM OC.ALM CT.ACK CT.HYS
Ct
LIST
E.ACCS
R.ACCES
RECOV SERVO
R.RESN
RESN
MAX.EV
R.EVT
PROG
LIST
P.NUM HB.STY HB.TYP HB.VAL RAMP.U DWEL.U
P.CYC
P.END
S.NUM S.TYPE
TSP R.RATE R.TIME
DUR
C.PRG.N
EV.OP
P.SET
LIST
BCD.1 BCD.2 BCD.3 BCD.4 BCD.5 BCD.6 BCD.7
BCD.8 BCD.OP BCD.ST
bCd
LIST
Enter CONF or LEV3 To LOOP list
From CT or ZIRC list
To COMMS list
Return to previous
d1 to d8
Zirconia list appears only if
purchased/enabled
Return to previous
1 to 6
EPC3016, EPC3008, EPC3004
82 HA032842ENG Issue 2
Page 83
EPC3016, EPC3008, EPC3004
OPER
N.IN IN.inv Op.inv
IN1 - 8
Op
STATE
INTF PROT
N.STA W.TIME W.ACTN W.RCOV W.FLAG
DELAY
T.FMT
BAUD PRTY NODE
A.DISC
IP.MD IP.A1-4 IP.S1-4 IP.G1-4 MAC1 -6
B.STM
R.PRT
M.FMT
O.COM
INST
mAIN
s.list
NWRK
s.list
ENABL
DEST
VALUE
BCST
s.list
COMM
LIST
INTF PROT
N.STA W.TIME W.ACTN W.RCOV W.FLAG
DELAY
T.FMT
BAUD PRTY NODE
A.DISC
IP.MD IP.A1-4 IP.S1-4 IP.G1-4 MAC1 -6
B.STM
R.PRT
M.FMT
F.COM
INST
mAIN
s.list
NWRK
s.list
ENABL
DEST
VALUE
BCST
s.list
OPER IN1.X IN2.X UNITS
RES L.LIM H.LIM FBACK
FB.VAL
SEL
IN1
IN2
OUT STATE
MATH
LIST
1
INST
2
INST
OPER IN1.X IN2.X UNITS
RES L.LIM H.LIM FBACK
FB.VAL
SEL
IN1
IN2
OUT STATE
OPER
IN1 IN2
FBACK
INV OUT
STATE
Lgc2
LIST
1
INST
2
INST
OPER
IN1 IN2
FBACK
INV OUT
STATE
+
OPER
N.IN IN.inv Op.inv
IN1 - 8
Op
STATE
Lgc8
LIST
1
INST
2
INST
h.lim l.lim
Fback Fb.val In.sel
In1–in8
Out
State
res
1
INST
2
INST
h.lim l.lim
Fback Fb.val In.sel
In1–in8
Out
State
res
AN.Sw
LIST
+
Units
Res h.lim l.lim Value statu
u.VAL
LIST
1
INST
2
INST
Units
Res h.lim l.lim Value statu
In Max Min
Thold d.abv t.abv Alm.d
Alm.tm
Al.op reset In.st
I.mon
LIST
1
INST
2
INST
In Max Min
Thold d.abv t.abv Alm.d
Alm.tm
Al.op reset In.st
In1 In2 In3 In4 In5 In6 In7 in8 out
OR
LIST
1
INST
2
INST
In1 In2 In3 In4 In5 In6 In7 in8 out
Type Time
e.time
In
Out
trigd
tmr
LIST
Enbl
Dir
r.cry
o.flow
Clock Targt Count Reset o.clr
Cntr
LIST
Total
In
Units
Res Alm.sp Alm.op
Run
Hold
reset
tOtL
LIST
In.hi In.lo Sw.hi Sw.lo
In.1
In.2 f.val f.typ
Sel.in
b/mod
Out
stat
Sw.OV
LIST
Lang
t.unit
i.num
i.type
Psu i.ver cm.id Cs.id
L2.p L3.p
Cfg.p c.pas.d c.pas.e
p.lock
c.mem
INSt
LIST
INFO
s.list
SEC
s.list
New.al
g.ack
Smpl.t
t.fmt f.stby e.stat
R,cnt
diAG
s.list
Io.f Io1.e Io2.f Io2.e Io4.f Io4.e Opt.f Opt.e
mOdS
s.list
Id Stat Mode
c.val
CAL
LIST
in Rng.hi Rng.lo Scl.hi Scl.lo Time.o
Res
Units
Out
stat
Rem.1
LIST
h.disp H.TIME K.LOCK BG.TYP BG.MAX BG.MIN
BG.PV F1.FN F2.FN PS.FN
HmI
s.list
1 to 4
Return to previous
Return to previous
1 to 4
Fixed Comms Option Comms
Toolkit Enabled (The Toolkit Enabled includes lists from Math to Switch Over)
To AN
SWITCH
list
From TOTALISER list
From RECIPE list
Return
to AI list
1 to 8
1 to 4
1 to 3
83 HA032842ENG Issue 2
Page 84
Configuration Level EPC3016, EPC3008, EPC3004
CONF
goto
0___
code
CONF
pass
A1
list
tC
IN.TYP

Configuration Level

Configuration of the instrument through the front panel is particularly useful where relatively small changes are required on site, possibly during commissioning. For larger or more detailed changes the use of Eurotherm iTools configuration package is recommended and this is described in the next chapter.
What’s in this Chapter
This chapter describes how to configure the controller through the HMI.
Lists all parameters which are available in each function block

To Enter Configuration Level

The procedure is similar to that shown in "To Enter Level 3" on page 79.
Operation Action Display Notes
Select Level 3
1. Press and hold
until LEv 3 is shown.
LEv1 is displayed first. Continue to hold the button to obtain LEv3
Enter the passcode
Select list headers
Select parameters in the list
2. Press
CONF
3. Press
4. Press or to
enter the correct digit value of the passcode
5. Press to accept
the value and move onto the next digit
6. If the correct passcode has been entered the
message PASS will be displayed momentarily. The controller is now operating in Config Level.
7. Repeatedly press
8. Repeatedly press
to select
to enter
Press to move to the next digit.
The default passcode for Configuration level is '0004'.
A special case exists if a security code has been configured as '0000'. If this has been done it is not necessary to enter a code and the controller will enter the chosen level immediately.
If an incorrect code is entered the display will return to HOME
If an incorrect code is entered the display will return to HOME. After three wrong attempts the passcode entry system will lock out for a time set by the ‘Passcode Lockout Time’ set in the "Security Sub-List (SEC)" on page 171.
This shows the Analogue Input List.
Press + previous list header
This shows the Input Type
to return to the

To Return to Level 1

From Configuration level it is not possible to select Level 2 or Level 3.
1. Press and hold until
2. Press
84 HA032842ENG Issue 2
to accept
Goto LEv1 is displayed
Page 85
Configuration Level EPC3016, EPC3008, EPC3004
Inputs
Control
Processes
Outputs
Control block
Loop List
Alarms block
AL LIst
Timer block
tmr List
CT Alarm
CT List
Digital
Communications
Comm List
Input/output 1
io List
Output 2
io List
Output 3
io List
Output 4
io List
To plant actuators
EIA232,
EIA425
Ethernet
Sensor input
(AI List)
Setpoint
Loop SP List
Digital Input A
IO List
Digital Input B
IO List
Current
transformer
CT List
TC
RTD
mA
V

Function Blocks

The controller is made up of a number of hardware and software function blocks. Each block has inputs and outputs which are wired together in software (soft wired) to match the application for which the controller is intended.
The following diagram shows an example of function blocks which make up a typical controller.
The Temperature (or Process Value, PV) is measured by the sensor and compared with a Setpoint (SP) set by the user.
The purpose of the control block is to reduce the difference between SP and PV to zero by providing a compensating output to the plant via the output driver blocks.
The timer and alarms blocks may be made to operate on a number of parameters within the controller, and digital communications provides an interface for data collection, monitoring and remote control.
The way in which each block performs is defined by its internal parameters. Some of
85 HA032842ENG Issue 2
these parameters are available to the user so that they can be adjusted to suit the characteristics of the process which is to be controlled.
These parameters are found in lists in Configuration Level.
The controller can also be configured using iTools as described in "Configuration Using iTools" on page 181. iTools is proprietary software designed to configure Eurotherm instruments and may be downloaded from www.eurotherm.co.uk.
Page 86
Configuration Level EPC3016, EPC3008, EPC3004

Configuration Level Parameters

In Configuration Level all parameters are organised in lists (in the same way as Operator Level 3). Only parameters related to enabled functions are shown.
Each list may contain operator level and configuration parameters; the parameters are only shown when the instrument is in the appropriate mode. If a list does not contain at least one displayable parameter, it is not shown.
During navigation, the centre display (lower display in EPC3016) shows the mnemonic code of the parameter or the List header. A scrolling string with either the parameter or the List description is displayed in the lower section of the display.
86 HA032842ENG Issue 2
Page 87
Configuration Level EPC3016, EPC3008, EPC3004
Conf
goto
0___
code
Conf
pass
Conf
list
A1
list
A2
S.list
tC
IN.TYP
mV
IN.TYP

To Select Configuration Level

WARNING
HAZARD OF INCORRECT CONFIGURATION
Incorrect configuration can result in damage to the process and/or personal injury and must be carried out by a competent person authorised to do so. It is the responsibility of the person commissioning the controller to ensure the configuration is correct.
In configuration level the controller does not control the process or provide alarm indication. Do not select configuration level during a live process.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Operation Action Display Notes
Select Level 3 followed by Configuration level
1. Press and hold
until Lev3 is shown
then press select ConF.
to
LEv1 is displayed first. Continue to hold the button to obtain LEv3
Enter the passcode
Select list headers
Select sub-lists if sub-lists are appropriate
Select parameters in a list
Change a parameter value
2. Press
3. Press or
to enter the correct digit value of the passcode
4. If the correct passcode has been entered the message
PASS will be displayed momentarily. The controller is now operating in the selected level.
5. Repeatedly press
6. Press
the first sub-list (if these are available)
7. Press or
to scroll forwards or backwards through sub-lists
8. Repeatedly press
to enter
to select
9. Press or
Press to move to the next digit.
The default passcode for configuration level is '0004'.
A special case exists if a passcode has been configured as '0000'. Then, it is not necessary to enter a code and the controller will enter the chosen level immediately.
If an incorrect code is entered the display will return to HOME. After three wrong attempts the passcode entry system will lock out for a time set by the ‘Passcode Lockout Time’ set in the ‘Instrument Security’ menu, see "Security Sub-List (SEC)" on page 171.
The first list is the Analogue Input List.
Some list headers are split into sub-lists. For example, if the secondary input is used parameters associated with this list are shown under the sub-list A2.
This shows the Input Type
Values cannot be changed if they are read only.
Parameter values are shown in the ‘Menus’ in subsequent sections.
When in the ‘top’ list header, press + to return to the beginning of the lists.
When in a parameter list, press +
87 HA032842ENG Issue 2
to return to the previous parameter
Page 88
Configuration Level EPC3016, EPC3008, EPC3004
1
2
AB
C
bcd
Io1
Io2 OP.3
Io4
LA
Lb
d1
d8
mAIN
Conf
cLn
IMP
mAIN CFG
SP
FF
AtuN
PId
OP
diAG
Run
Setup
1
2 3
4
5
6
RECP
Comm
F.Com
mAIN
Netw
Bcast
1
8
O.Com
mAIN
Netw
C
D
Toolkit
Enabled
A
INFO
HmI
SEC
diaG
mOds
CAL
Or
INSt
Rem.1
Math
Lgc2
1
2 3 4
1
2
3 4
Lgc8
tmr
1
2
Cntr
tOtL
An.SW
SwOV
u.VAL
I.Mon
1
2
3
4
1
2
3
1
2
B
O.dIO
A1
ALm
Prog
P.Set
LOOP
Zirc
Ct
io
Bcast
Always Present
Dependent upon HW or feature options
Instrument Blocks Toolkit Blocks
Yes
No
D

Configuration and Level 3 Navigation Diagram

The full navigation diagram for Level 3 and Configuration Levels are shown in section "Navigation Diagram" on page 82. The diagram below is included to serve as a quick check to show the order of the list headers.
88 HA032842ENG Issue 2
Page 89
Configuration Level EPC3016, EPC3008, EPC3004
More Instances
First parameter
More parameters

Examples

Press
to scroll through each list header (the name of the function block) in turn
Pressing on one of these headers will do the following depending upon the
function block being accessed:
1. Display the first parameter (see Recipes).
2. Display the instance selection (see IO for named instances or Alarm for numbered instances).
3. Display the subclass selection (see Loop).
When at 2 or 3 above, pressing up and down will cycle through the instances/subclasses.
The following examples show how to navigate through different function blocks
Example 1: no additional instances and no sub-classes
The CT list is an example of a class which contains no additional instances and no sub-classes. In other words it is a simple list of parameters under the heading CT which set up the current transformer.
1. Press
until the list is displayed
2. Then press to scroll through the parameters.
3. To change the value of a selected read/write (R/W) parameter press
or .
Example 2: multiple instances and no sub-classes (named)
The io List is an example of a class which contains multiple instances and no sub-classes. The instances are named instances, such as io.1, io.2, OP.3 etc (see "I/O List (io)" on page 97). The list of parameters for each instance are not necessarily the same.
The navigation diagram for this type of function block is shown below:
1. Press
2. Press to select the first instance of the
to scroll to the io List
io parameters. This is displayed as
io.1 and INST and denotes that this is the first instance of parameters in that
category
3. Press again to scroll through parameters for
io.1 or, to select the next
and subsequent instances press
89 HA032842ENG Issue 2
Page 90
Configuration Level EPC3016, EPC3008, EPC3004
More Instances
First parameter
More parameters
More Instances
First parameter
More parameters
More Instances
First subclass
First parameter
4. Press
5. To change the value of a selected read/write (R/W) parameter press
to scroll back
or
Example 3: multiple instances and no sub-classes (numbered)
The Alarm List is also an example of a class which contains multiple instances and no sub-classes. The instances in this case are numbered instances, such as 1 to 6 "Alarms List (ALm)" on page 131. The list of parameters for each instance are not necessarily the same.
Example 4: single instance and multiple sub-classes
The Loop List is an example of a class that has a single instance and multiple sub-classes. A sub-class (or List) groups parameters under meaningful sub-headings. For example, all parameters associated with the setpoint are grouped
together in the SP List (displayed as
S.LIST). Each subclass will be different.
The navigation diagram for this type of function block is shown below:
Example 5: multiple instances and multiple sub-classes
The communications list is an example of a class which has multiple instances and multiple sub-classes. The instances are Fixed and Option and the Sub Lists are Main, Network, Broadcast.
90 HA032842ENG Issue 2
Page 91
Configuration Level EPC3016, EPC3008, EPC3004
Parameter Navigation
1. Press to select parameters in a list
2. Press
or to change the parameter value (if not read only).
Some parameters are analogue in which case the value can be changed between limits.
Some parameters are enumerated which means they have a mnemonic associated with them which can be selected from a list.
The following pages list all parameters which are available in the controller in their respective lists. Parameters are only shown in the controller if the feature has been supplied and enabled.
Notes:
R/W = Read/Write
Conf R/W = Read/Write in configuration level only
Conf only R/W = Shown in configuration level only
L3 R/W = Read/Write in configuration level and level 3
R/O = Read Only in all levels
L3 R/O = Read only in configuration level and level 3
Enumerated values
In the value column for enumerated values in the following tables, the associated numeric value is shown. This is the value that would need to be written if a 3rd party comms master was being used. For example:
tC (0)
mV (1)
V (2)
mA (3)
RTD (4)
91 HA032842ENG Issue 2
Page 92
Configuration Level EPC3016, EPC3008, EPC3004
+
IN.TYP
LIN UNITS DEC.P
RNG.HI RNG.LO
MV.HI MV.LO SHUNT
PV.OFS FILT.T CJ.TYP SB.TYP SB.OUT CJC.IN
PV PV.ST MV.IN
A1
LIST
1
INST
IN.TYP
LIN UNITS DEC.P
RNG.HI RNG.LO
MV.HI MV.LO SHUNT
PV.OFS FILT.T CJ.TYP SB.TYP SB.OUT CJC.IN
PV PV.ST MV.IN
2
INST
Return to CONF
Enter CONF level
To next list (
io)
There are 2 instances of the AI list if the second analogue input is fitted

Analogue Input List (a1 a2)

The first press of after entering Level 3 or Configuration, will show the
‘ANALOGUE INPUT LIST’. From this list you can configure the input type and other characteristics of Input 1 (and Input 2, if fitted).
A1 instance 1 of the AI list contains the parameters available for IP1
A2 instance 2 of the AI list contains the parameters available for IP2. The IP2 input is
an option in EPC3008 and EPC3004. It is not available in EPC3016.
Access to the Analogue Input parameter list is summarised below. The full Navigation Diagram is shown in section "Navigation Diagram" on page 82.
The parameters in the following list are identical for both
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
INST Analogue input
in.typ Input Type
92 HA032842ENG Issue 2
Parameter Name Va lue Description Access
1 Input 1 List (IP1) Conf R/W 2 Input 2 List (IP2) EPC3008 and EPC3004 only. tC 0 Thermocouple
Default: Thermocouple
mV 1 milli volts V 2Volts mA 3 milli amps RTD 4 Platinum resistance thermometer zirc 5 High Impedance Zirconia probe (only available on the secondary
input)
1 and 2
L3 R/O
Conf R/W
L3 R/O
Page 93
Configuration Level EPC3016, EPC3008, EPC3004
Parameter
Parameter Name Va lue Description Access
Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
Lin Linearisation
type
units Units
DEC.P Resolution
RNG.HI Range high
RNG.LO Range low
mv.hi input high limit
mV.lo input low limit
shunt shunt value
PV.OFS PV offset
J 0 Thermocouple type J Conf R/W k 1 Thermocouple type K
Default: Type K
L 2 Thermocouple type L r 3 Thermocouple type R b 4 Thermocouple type B n 5 Thermocouple type N t 6 Thermocouple type T s 7 Thermocouple type S CSt.1 8 Custom linearisation 1. To download special linearisation tables
see "To Load a Custom Linearisation Table" on page 212.
CST.2 9 Custom linearisation 2. Two tables may be downloaded into the
EPC3000 series controllers.
100 10 Resistance thermometer type PT100 Only shown for 1000 11 Resistance thermometer type PT1000
LIN 12 Linear Only shown if the Sqr 13 Square root
See section "Units" on page 95 for a list of units used throughout Conf R/W
nnnnn nnnn.n nnn.nn nn.nnn n.nnnn
mV: -800.0
to 800.0 V: -10.00 to
10.00 mA: -800.00
to 800.00
1.00 to
1000.00
0.0 A simple offset is provided to adjust the process variable by a
0
The number of decimal points shown in the display.
1
Range none to four decimal points.
2
Default: nnnn.n
3
4
Range high limit. Used to limit ranges of Thermocouple and RTD input types, and scale mV, V and mA inputs. AI2 also includes Zirconia.
Default tc 500; mV 40; V 10; mA 20; RTD 500; Zirconia 2000
Range low limit. Used to limit ranges of Thermocouple and RTD input types, and scale mV, V and mA inputs. AI2 also includes Zirconia.
Default tc 0; mV 0; V 0; mA 4; RTD 0; Zirconia 0
High limit for mV, mA or V inputs
Default: mV 40; V 10; mA 20
Low limit for mV, mA or V inputs
Default: mV 0; V 0; mA 4
Value of the shunt resistor for mA inputs.
Default: 2.49Ω.
fixed amount across its span. This can be used to compensate for known thermocouple and other tolerances which may exist in multi instrument installation so that all instruments read the same value.
See also "Calibration using a Dry Block or Equivalent" on page 283 which describes the two point calibration adjust method. This may be used to apply a linear correction to the temperature reading.
Default: 0.0
L3 R/O
mV, V or mA inputs
input is RTD
L3 R/W
Conf R/W
L3 R/O
Conf R/W
L3 R/O
Conf only R/W
Not shown for thermocouple or RTD inputs
Conf only R/W
Conf R/W
L3 R/W
93 HA032842ENG Issue 2
Page 94
Configuration Level EPC3016, EPC3008, EPC3004
Parameter
Parameter Name Va lue Description Access
Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
FILT.T Filter time
constant
CJ.TYP CJC type
SB.TYP SENSOR
break type
sb.out SENSOR
break output
CJC.IN CJC Temperature
PV PV
PV.ST PV Status
MV.IN measured value
0 to 60 Some industrial installations can cause electrical noise to be
introduced into the process measurement. This could be due, for example, to EMC or mechanical linkages. A filter is provided to reduce the frequency of electrical noise seen by the instrument. The effect of electrical noise can be reduced by increasing the filter time constant, but a compromise must be achieved as it could affect the closed loop response of the system.
The larger the number, the slower the measured temperature will be to respond to fluctuations.
Default: 1.6s
AutO 0 A thermocouple measures the temperature difference between
the measuring junction (hot junction) and the reference junction (cold junction). Auto uses the measurement of the temperature made by the instrument where the thermocouple is connected to its rear terminals.
Default: Auto
0 1 The reference junction is held at a fixed known temperature of 0
degrees usually by an external ice point method
50 2 The reference junction is held at a fixed known temperature of 50
degrees usually by an external hot box method
off 3 CJC is turned off. This could be used, for example, where a
thermocouple measurement is made by an external transmitter which does not linearise the thermocouple curve.
Off 0 The controller continuously monitors the impedance of a
transducer or sensor connected to the input. Off means sensor break is not detected.
LO 1 Sensor break is detected if impedance at the terminals is above a
low threshold (typically between 3 to 5KOhms)
Default: Low
HI 2 Sensor break is detected if impedance at the terminals is above a
high threshold (typically between 12 to 20KOhms)
OFF 0 No sensor break detected Conf R/O On 1 Sensor break detected. If the sensor break requires to activate a
soft alarm the sensor break output parameter can be wired to a Digital High Alarm. (see section "Example 1: To Wire an Alarm" on page 195.
The CJC temperature is a measure of the temperature at the instrument terminals. It is relevant only for thermocouple inputs and is provided as a diagnostic aid.
Process value is the displayed value on the instrument, usually the measured temperature when the instrument is controlling a temperature loop.
The state of the PV is continuously monitored.
See section "Status" on page 96 for a list of enumerated values
This is the measured value in units of mV or ohms, dependent upon input type. The value measured at the rear terminals can be useful as a diagnostic aid to determine if the thermocouple or linear input sensor is wired correctly.
Conf R/W
L3 R/W
Conf R/W
L3 R/O
Only shown for thermocouple inputs.
Conf R/W
L3 R/O
Conf R/O
L3 R/O
Conf R/O
L3 R/O
Conf R/O
L3 R/O
Conf R/O
L3 R/O
94 HA032842ENG Issue 2
Page 95
Configuration Level EPC3016, EPC3008, EPC3004

Units

The list below applies to all function blocks which contain Units
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
units Units
Parameter Name
Val ue Description Access
None 0 No units will be displayed Conf R/W AtmP 1
V 2Volts mV 3 Millivolts A 4Amps mA 5 Milliamps PH 6pH mmHG 7 Millimeter of mercury PSi 8 Pounds per square inch bAr 9Bar mBar 10 millibar P.RH 11 Per cent relative humidity PErc 12 Per cent mmwG 13 Millimeter Water Gauge inwG 14 Inches water gauge inWW 15 Not used OhmS 16 Resistance (ohms) PSIG 17 Pounds per square inch gauge P.O2 18 Per cent O
PPm 19 Parts per million P.CO2 20 Per cent CO
P.CP 21 Per cent carbon P.SEc 22 Per cent per second
Temperature units. ℃, ℉, K are set in the Instrument Info list section "Instrument List (INSt)" on page 167.
2
2
L3 R/W
95 HA032842ENG Issue 2
Page 96
Configuration Level EPC3016, EPC3008, EPC3004

Status

The list below applies to all function blocks which contain global status enumeration.
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
Parameter Name
Val ue Description Access
Good 0 The process variable is working correctly Conf R/W Off 1 Channel is configured to be off O.rng 2 When the input signal exceeds the upper input limit by more than 5% the PV
will flash indicating over range.
If the value is too high to fit the number of digits on the display "HHHH" will flash (refer to "Auto-scaling of decimal point" on page 68 for display capability for each instrument size).
U.rng 3 When the input signal exceeds the lower input limit by more than 5% the PV
will flash indicating under range.
If the value is too high to fit the number of digits on the display "LLLL" will flash (refer to "Auto-scaling of decimal point" on page 68 for display capability for each instrument size).
Hw.s 4 Input hardware status is unknown. Rng 5 The input status is set to Ranging at the point of an analogue input
configuration change. It will remain in Ranging until an exit from a config induced instrument restart.
OFLw 6 Process variable overflow, possibly due to calculation attempting to divide a
number by a relatively small number
Bad 7 The PV is not reading correctly which could be due to an open sensor. Hwc 8 The hardware capabilities have been exceeded at the point of configuration,
for example configuration set to 0 to 40V when input hardware is capable of up to 10V
Ndat 9 Insufficient input samples to perform calculation
L3 R/W
96 HA032842ENG Issue 2
Page 97
Configuration Level EPC3016, EPC3008, EPC3004
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT M.O.T CYC.T SENSE
INER
BKLSH
STBY
FLBK.V
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT M.O.T CYC.T SENSE
INER
BKLSH
STBY
FLBK.V
io
LIST
io.1
INST
io.2
INST
IDENT
TYPE
PV
OUT
SENSE
OP.3
INST
IDENT
TYPE
PV VAL.HI VAL.LO OUT.HI OUT.LO
OUT M.O.T CYC.T SENSE
INER
BKLSH
STBY
FLBK.V
io.4
INST
IDENT
TYPE
PV
SENSE
LA
INST
IDENT
TYPE
PV
SENSE
Lb
INST
+
From previous list (
AI)
To next list
(O.diO)
Return to previous list header

I/O List (io)

The following modules may be fitted in the controller:
None
Logic I/O module
Form A relay
Triac
Isolated DC output
Output 1 beacon is operated from IO(1) when it is configured as an output.
Output 2 beacon is operated from IO(2) when it is configured as an output.
Output 3 beacon is operated from OP(3).
Output 4 beacon is operated from IO(4) when it is configured as an output.
Access to the Input/Output parameter list is summarised below. The full Navigation Diagram is shown in section "Navigation Diagram" on page 82.
97 HA032842ENG Issue 2
The following table includes all available input/output parameters but the ones displayed depend on how each I/O is configured.
Page 98
Configuration Level EPC3016, EPC3008, EPC3004
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
IDent IO HARDWARE ID
type type of io
PV process
val.hi demand high
val.lo demand low
out.hi output high
out.lo output low
out output
Parameter Name
variable
Valu e Description Access
None 0 This displays the type of IO hardware fitted. Choices are: Conf R/O L.IO 1 Logic input/output ReLY 2 Relay ssr 3Triac dc.OP 4 DC output L.iP 5 Logic input OnOF 10 On off output Conf R/W tpo 11 Time proportioning output up 15 Valve position raise Down 16 Valve position lower
Valve positioning UP/DOWN works across pairs of outputs ie:-
UP : DOWN IO.1 : IO.2 IO.2 : OP3 OP3 : IO.4
di 5 Contact closure input mA.OP 0 mA output V.OP 1 Voltage output
For an Input type : The measured process variable
For an Output type : The demanded output value
Percentage PID demand value giving maximum output - "OUT.H" ­Allows for "Output Splitting"
Default: 100.0
Percentage PID demand value giving minimum output - "OUT.L" ­Allows for "Output Splitting"
Default: 0.0
The maximum average output power that can be supplied from this output - Allows for "Output Splitting"
Default: 100% for TPO; 20 for mA; 10 for V i.e. the highest possible value for selected type.
The minimum average output power that can be supplied from this output - Allows for "Output Splitting"
Default: 0
For Digital Output Types
A value of 0 indicates that the output is low (relay de-energised) A value of 1 indicates that the output is high (relay energised).
For DC Output Types
This is the physical output value after the PV has been mapped via the demand range parameters onto the output range.
L3 R/O
L3 R/O
Conf R/W
L3 R/W
Conf R/W
L3 R/W
Only shown for DC or time proportioning output
Conf R/O
L3 R/O
98 HA032842ENG Issue 2
Page 99
Configuration Level EPC3016, EPC3008, EPC3004
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
m.o.t min on time
cycl.t cycle time
sense sense of io
Parameter Name
Valu e Description Access
auto to 150.00
Auto to 600
NORm 0 Output normal.
INV 1 Output inverted
0 Minimum pulse time in seconds. This value sets the minimum
duration between any two switching events. Although it is named 'MinOnTime', it applies to both on and off pulses equally.
A contactor datasheet will often specify the minimum pulse time that will help to ensure correct energizing and de-energizing of the contactor. This may be the lowest value you should consider using as a MinOnTime.
Auto(0) - Automatically sets the minimum on time for the output hardware as follows:
Relay = 1s (time proportioning) or 0.1s (VP raise/lower),
Logic = 0.05s (time proportioning), 0.1s (VP raise/lower)
Alternatively, a value may be set manually but it should be noted that this value will be clipped if it is below the minimum permissible value for the hardware that is fitted (relay or logic - see settings above).
For VP raise/lower outputs, smaller values of MinOnTime may actually produce less actuator activity. This is because the larger the MinOnTime, the larger the valve movement, and thus the lower the output resolution. This may lead to increased hunting. Generally values less than 0.5s should be used.
Default: Auto
0 This value sets the time proportioning output (TPO) and cycle time in
seconds. It is defined as the period of time between output repetitions.
When this parameter is Auto (0), which is the default setting, the TPO algorithm will run in a so-called Constant Ripple Mode. Under this regime, the cycle time will be automatically and continuously adjusted depending on the output demand. This is to maintain the amount of ripple in the process at an approximately constant amplitude. The benefit of this is that actuations are reduced on average, which can increase the lifetime of contactors and relays. As suggested, a demand of 50% will produce the shortest cycle time of 4*MinOnTime, and the cycle time is extended the further the demand moves away from 50%. You should therefore choose a MinOnTime that gives an appropriate minimum cycle time.
Alternatively, you can set a value of cycle time directly. When a value is set, the algorithm will run in a so-called Constant Cycle Time Mode. Under this regime, the algorithm will try to keep the cycle time constant, assuming constant demand. Note that the cycle time will be extended if the demand is such that the cycle time cannot be achieved without violating the MinOnTime. In this case, the effective cycle time will be extended just enough to help ensure the MinOnTime and the demand are both achieved.
There are a number of factors that may influence the setting of an appropriate CycleTime and it is often a trade off. For example, a longer cycle time may extend the lifetime of contactors but reduce the lifetime of heating elements. A longer cycle time will also increase the amount of ripple in the process variable.
Default: Auto
This is the normal setting for control.
Output off when the PID demand is off. For control this is when PV>SP.
For a Digital Input the input is active when the input is = 1
Default: Normal
This is the normal setting for alarms.
Output off is when the alarm is active.
Output on is when the alarm is in-active.
For a Digital Input the input is active when the input is = 0
Conf R/W
L3 R/W
Conf R/W
L3 R/W
Conf R/W
99 HA032842ENG Issue 2
Page 100
Configuration Level EPC3016, EPC3008, EPC3004
Parameter Mnemonic
Press to select in turn Press or to change values (if read/write, R/W)
iner inertia
bklsh backlash
stby standby action
flbk.v fallback value
Parameter Name
Valu e Description Access
0.0 to 30.0 Time taken in seconds for the valve motor to stop after power is
removed. 0.0 to 30.0 seconds.
Applies to valve position outputs only.
Default: 0.0
0.0 to 30.0 Time in seconds to take up any backlash in the valve actuator
linkage. 0.0 to 30.0 seconds.
Applies to valve position outputs only.
Default: 0.0
Determines the valve positioning output action (Rest, Raise, Lower) when the instrument is in Standby Mode
Rest 0 The valve will remain in the current position
Default: Reset
Up 1 The valve will open. Applies to io1 Down 2 The valve will close. Applies to io2
Valve positioning UP/DOWN works across pairs of outputs ie:-
UP : DOWN IO.1 : IO.2 IO.2 : OP3 OP3 : IO.4
0.0 Fallback value which is to be outputted when the status is BAD,
Default: to the value of OUT.L
L3 R/W
L3 R/W
Conf R/W
Conf R/W
100 HA032842ENG Issue 2
Loading...