Eurotherm AP1080, AP1090 Data Sheet

Page 1
Action PAK
®
AP1080 & AP1090
DC Input, Field Configurable Limit Alarms
AP1080 (Single Trip, DPDT, 5A)
AP1090 (Single/Dual Trip, 2 SPDT, 5A)
Field Configurable Input Ranges for DC Voltage
and Current
Exclusive “Dynamic Deadband” Prevents
False Trips
Description
Action Pak models AP1080 single setpoint and AP1090 dual setpoint limit alarms offer flexible, wide-ranging DC input capabil­ity. Voltage spans from 10mV to 200 volts and current spans from 1mA to 100mA can be field configured. Bipolar inputs are also accepted. Both models offer configurable latching, failsafe and HI/ LO operation. The AP1080 and AP1090 also include 0.25%-50% adjustable deadbands and selectable 120/240VAC power.
Models AP1080-2000 function diagnostic LED. The green center LED indicates line power and input signal status. Active line power is indicated by an illuminated LED. If the center LED is off, check line power and the wiring connection. If the input signal is above 100% full scale, the LED will flash at approximately 8Hz. Below 0%, the flash rate is approximately 4Hz.
Output Selection
The single setpoint AP1080 and the dual setpoint AP1090 provide the following relay outputs:
and AP1090-2000 are equipped with a dual
Provides Relay Contact Closures
at a Preset DC Input Level
Setpoints Programmable HI or LO Selectable Failsafe/Latching Operation
Selectable 120/240VAC Input Power
(9 to 30 VDC Available)
In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite for non­failsafe). In the failsafe mode, the relays go to the tripped condition when the power fails.
Dynamic Deadband
The input must remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the
input must fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped condition. This effectively results in a “dynamic deadband” - based on time -in addition to the normal deadband.
Options
U Urethane coating of internal circuitry for protection
from corrosive atmospheres.
P Top mounted, ten-turn dial(s) for setpoint adjustment.
C620 Factory calibration of input range, set points and output
relays. Not available with option P.
AP1080 Single Trip (DPDT, 5A) AP1090 Single/Dual Trip (2 SPDT, 5A)
Setpoints are top accessed multi-turn potentiometers (or option "P" provides top mounted ten-turn dials).
Operation
The field configurable AP1080 and AP1090 limit alarm setpoints can be configured for HI, LO, latching or fail-safe trip operation. Non-latching HI and LO setpoints have respective HI and LO deadbands. In a tripped condition, the setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below the HI deadband or rises above the LO deadband (see figure 1). To reset a latched setpoint the signal must be in the safe region and the line power turned off for at least 5 seconds. For proper deadband operation, a HI setpoint must always be set above the LO setpoint.
Configuration
The factory presets models AP1080 and AP1090 as follows:
AP1080
Input 0-20mA 0-20mA Output Single, DPDT Dual, SPDT
Trip HI A: HI, B: LO Latching No No Failsafe Yes No Deadband 0.25% A/B: 0.25%
Power 120VAC 120VAC
For other I/O ranges, remove the four base screws and case to access the configuration switches.
Replace the cover before applying power.
Refer to Figure 5 for switch locations.
AP1090
Page 2
Figure 1: Limit alarm operation and effect of deadband.
Input
1. Position input jumper “W2” for Current or Voltage inputs.
I
V
Current
I
V
Voltage
2. Set position 1 of the Mode Selector for Unipolar or Bipolar operation. Unipolar is the default.
b) Setpoint B (1090 only): Type (HI/LO); Units (mA, mV, V); Deadband (%)
c) Latching (ON/OFF)
d) Failsafe (ON/OFF)
Note that if a deadband entry is not specified, the default entry will be used.
Relay Protection and EMI Suppression
When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external protection (see Figures 2 & 3). Place all protection devices directly across the load and minimize all lead lengths. For AC inductive loads, place a properly­rated MOV across the load in parallel with a series RC snubber. Use a 0.01 to 0.1mF pulse film capacitor (foil polypropylene recom­mended) of sufficient voltage, and a 47ohm, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply, 1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).
ON
>
12 3
BP
4
Unipolar
5
ON
>
BP
2345
1
Bipolar
6
6
Note: A bipolar span selection will double any span from Table 1
±
(e.g., 10V unipolar span =
10V bipolar span)
3. Using Table 1, configure positions 1 through 4 of the Input Range Selector for the desired maximum setpoint input. Round desired maximum input values to the next highest range (e.g., 0­120V = 200V range).
Output
Configure the Mode Selector for the required function. See Figure 6.
Power
Configure the AC jumpers for either 120 or 240 VAC operation. See Figure 4.
Calibration
Note: To maximize thermal stability, final calibration should be performed in the operating installation, allowing approximately 1­2 hours for warmup and thermal equilibrium of the system.
Setpoint: Set deadband at its minimum (factory default - 20 turns Counter Clockwise) before adjusting the setpoint. With the speci­fied trip voltage or current input applied, adjust setpoint until the relay trips. For HI trip calibration, start with the setpoint above the desired trip. For LO trip calibration, start below the desired trip.
Table 1: AP1080-2000 and 1090-2000
Input Ranges
Deadband: Set deadband to its minimum (factory default - fully
CCW). Set setpoint to desired trip. Adjust voltage/current input until relay trips. Readjust deadband to 50% (20 turns CW). Set voltage/current input to desired deadband position. Slowly adjust deadband until relay untrips.
Note that Custom Calibration (option C620) is available from the factory (settings MUST be within specifications):
a) Setpoint A: Type (HI/LO); Units (mA, mV, V); Deadband (%)
*Note: Use Jumper (W2) to configure either voltage or current input.
All unipolar input ranges are zero based.
Page 3
Figure 2: DC Inductive Loads
Figure 3: AC Inductive Loads
Figure 4: 120/240 VAC Selection
ON = Closed
Figure 5: AP1090-2000 Factory Calibration 0-20mA, Dual HI/
LO, Non-Latching, Non-Failsafe.
Mounting
All Action Paks feature plug-in installation. Mod els AP1080 and AP1090 use an 11­pin base, either molded socket (M011) or DIN rail socket (MD11).
Dimensions
Dimensions are in millimeters (inches)
1
Unipolar
BipolarOnOff
"A" Hi Trip
"A" Low TripOnOff
"B" Hi Trip
"B" Low TripOnOff
3
2
*
45
6
*
Single Trip (A)
Dual Trip TripOnOff
Non-Failsafe
FailsafeOnOff
Latching
Non-LatchingOnOff
Figure 6: Mode Selection Dual Trip/A: HI, B: LO, Non-
Latching, Non-Failsafe *AP1090-2000 only.
Mark III
M011 (Track/Surface)
MD11 (DIN Rail)
Page 4
Specifications
r
Inputs:
Voltage Input: Range: 10mV to 200V Impedance: >100K Ohms Overvoltage: 400V, Max.
Current Input:
Range: 1mA to 100mA Impedance: 20 Ohms, Typical
Overcurrent: 200mA, Max. Overvoltage: 60VDC Common Mode
(Input to Ground):
1000VDC, max
LED Indications:
Input Range (Green)
>100% input: 8Hz flash
<0% input: 4Hz flash Setpoint (Red) Tripped: Solid red Safe: Off
Limit Differential (Deadband):
>50mV/5mA: 0.25% to 50% of span
<50mV/5mA: 1% to 50% of span
Response Time:
Dynamic Deadband:
Relay status will change when proper
setpoint/process condition exists uninterrupted for 100msec
Normal Mode (analog filtering):
<250msec, (10-90%)
Setpoint:
Effectivity: Setpoints are adjustable over 100% of the selected input span
Repeatability (Constant Temp):
>50mV/5mA: 0.1% of full scale <50mV/5mA: 0.2% of full scale
Stability:
Line Voltage: ±0.01%/%, max
Temperature: ±0.05% of full scale/°C, max.
Common Mode Rejection:
DC to 60Hz: 120dB
Isolation:
1000VDC between contacts, input & power
ESD Susceptibility:
Meets IEC 801-2, Level 2 (4KV)
Humidity:
Operating: 15 to 95% (@45°C)
Soak: 90% for 24 hours (@65°C)
Temperature Range:
Operating: 0 to 60°C (32 to 140°F)
Storage: -15 to 70°C (5 to 158°F)
Power:
Consumption: 2W typical, 5W max
Standard: Selectable 120/240VAC (±10%, 50-60Hz)
Optional: 9 to 30VDC Inverter-Isolated
Relay Contacts:
AP1080: DPDT (2 Form C) AP1090: 1 SPDT (1 Form C) per setpoint Current Rating (resistive)
120VAC: 5A; 240VAC: 2A; 28VDC: 5A Material: Silver-Cadmium Oxide Electrical Life: 10
5
operations at rated load
Note: External relay contact protection is required for use with inductive loads.
See relay protection section (Fig 2 & 3).
7
Mechanical Life: 10
operations
Latch Reset Time:
5 seconds (with power removed)
Weight:
AP1080: 0.46lbs AP1090: 0.62lbs
Agency Approvals:
CSA certified per standard C22.2, No. 0-M1982, (File No. LR42272-8,9)
UL recognized per standard UL 508, (File No. E99775)
Ordering Information
Specify:
1. Model: AP1080-2000, AP1090-2000
2. Options: U, P (see text)
3. Line Power (see specs.)(All power supplies are transformer-isolated from the internal circuitry.)
4. C620 Custom Calibration? (see Options)
Accessories:
M801-0000 Retaining Spring M011-A 11 pin Track Mount Socket M004-0000 4 ft Long Channel Track MD11-0000 11 pin DIN Mount Socket
Printed on recycled pape
Action Instruments
Pin Connections
10 (B) C 11 (B) N.C.
Chessell
1 AC Power (Hot) 2 No Connection 3 AC Power (Neu) 4 Input (+) 5 Input (-) 6 (A) N.O. 7 (A) C 8 (A) N.C. 9 (B) N.O.
Key:
N.O. = Normally Open C = Common N.C. = Normally Closed DC Power: Pin 1 = (+)
Pin 3 = (-)
*
Contacts are in the “normal” state
when the relay is de-energized.
Eurotherm
Loading...