Euro-Line AER518SC, AER522SC, AER518SCL Technical Data & Service Manual

TECHNICAL DATA & SERVICE MANUAL
OUTDOOR UNIT:
AER518SC AER518SCL AER522SC
SPLIT SYSTEM AIR CONDITIONER
Model No. Product Code No.
AER518SC 387007114
AER518SCL
AER522SC
387007140 387007142
®
IMPORTANT! Please read before installation
This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical codes.
• Pay close attention to all warning and caution notices given in this manual.
•The unit must be supplied with a dedicated electrical line.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If necessary, get help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions.
In case of improper installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
• During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units.
When wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLYA QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death.
Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection different from the ground connection.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
• Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line.
When transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers.
When installing... ... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support.
... In a room
Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.
... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.
... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE:
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas.
When servicing
• Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate the room during the installation or testng the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources.
WARNING
CAUTION
WARNING
2
Table of Contents
Page
1. OPERATING RANGE
2. SPECIFICATIONS
2-1 Unit specifications 5 2-2 Major Component specifications 8
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
5. PERFORMANCE DATA
5-1 Performance Charts 14 5-2 Cooling Capacity 18
6. ELECTRICAL DATA
6-1 Electrical characteristics 21 6-2 Electric Wiring Diagram 24 6-3 System Wiring Diagram 26
4
5
11
13
14
21
3
1. OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum
Minimum
32°C D.B. / 23°C W.B. 19°C D.B. / 14°C W.B.
43°C D.B.
(*)19°C D.B.
(*) SCL MODEL : -15°C D.B.
4
2. SPECIFICATIONS
V
g
g
g
z
e
2-1 Unit Specifications
AER518SC
Power source
oltage ratin
Performance * AWR518CL
Capacity
Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Operation Sound Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
kW
BTU/h
220 - 240V ~ 50H
230V
Cooling
5,00
17063
760
2,3
Cooling
198 ~ 264
10,00
2200
96
2,3
46
1(Hi)
Rotary (Hermetic)
R407C / 1760 Capillary tub
64
Flare type
7,5
6,35 (1/4")
12,7(1/2")
Dimensions & Wei
Unit dimensions Height mm
Package dimensions Height mm
Weight Net kg
Shipping volume
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating: Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
ht
Width mm Depth mm
Width mm Depth mm
Shipping kg
630 830 305 713 994 413
52
3
m
DATA SUBJECT TO CHANGE WITHOUT NOTICE
5
57
0,29
AER518SCL
V
g
g
g
e
z
Power source
oltage ratin
Performance * AWR518CL
Capacity
Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Operation Sound Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
kW
BTU/h
220 - 240V ~ 50H
230V
Cooling
5,00
17063
760
2,3
Cooling
198 ~ 264
10,00
2200
96
2,3
46
1(Hi)
Rotary (Hermetic)
R407C / 1670 Capillary tub
64
Flare type
7,5
6,35 (1/4")
12,7(1/2")
Dimensions & Wei
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating: Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
630 830 305 713 994 413
52 57
m
3
0,29
DATA SUBJECT TO CHANGE WITHOUT NOTICE
6
AER522SC
V
g
g
g
z
e
Power source
oltage ratin
Performance * AWR518CL
Capacity
Air circulation (High) m³/h Moisture removal (High) Liters/h
Electrical Ratin
Available voltage range V Running amperes A Power input W Power factor % C.O.P. W/W Compressor locked rotor amperes A
Features
Fan speed Compressor Refrigerant / Amount charged at shipment g Refrigerant control Operation Sound Hi dB-A Refrigerant tubing connections Max. allowable tubing length at shipment m Refrigerant Narrow tube mm(in.) tube diameter Wide tube mm(in.)
kW
BTU/h
220 - 240V ~ 50H
230V
Cooling
5,90
20134
830
3,3
Cooling
198 ~ 264
13,00
2750
92
2,1
70
1(Hi)
Rotary (Hermetic)
R407C / 2400 Capillary tub
67
Flare type
7,5
6,35 (1/4")
15,88 (5/8")
Dimensions & Wei
ht
Unit dimensions Height mm
Width mm Depth mm
Package dimensions Height mm
Width mm Depth mm
Weight Net kg
Shipping kg
Shipping volume
Remarks:
Rating conditions are: Cooling: Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating: Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
835 850 305 913
1000
400 67,0 76,0
m
3
0,37
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7
2-2 Major Component Specifications
r
r
A
A
A
5
A
Outdoor Unit: AER518SC
Compressor
Type Compressor model Nominal output W Compressor oil…Amount cc. Coil resistance (Ambient temp. 25°C)
Safety devices Type
Overload relay Operating Temp. Open °C
Close °C
Operating amp.(Ambient temp.25°C)
Run capacitor µF
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 20 °C )
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
VAC
VAC
Rotary (Hermetic)
80807045B C-2RN170H5W
1700
FV68S…800
SG6S-51B5P OR / KFG6S-51SB5P - 1
Ω Ω Ω
WHT-YEL: 111,8 / 120,5
Internal thermal protector
C-R: 1,353
C-S: 3,422
Internal protecto
-
utomatic opening
utomatic reclosining
-
40
400
Propelle
1…. Ø 400
6…900 / 6...912
50 / 42,7
BRN-WHT: 89,1 /
YEL - PNK : 55,9 / 60,
130 ± 8 / 130 ± 5
83 ± 15
2
440
98,5
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
External Finish
luminium plate fin / Copper tube
2
2
m
crylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
8
1,8
0,508
Outdoor Unit: AER518SCL
A
A
r
r
A
A
Compressor
Type Compressor model Nominal output W Compressor oil…Amount cc. Coil resistance (Ambient temp. 25°C)
Safety devices Type
Overload relay Operating Temp. Open °C
Close °C
Operating amp.(Ambient temp.25°C)
Run capacitor µF
Crank case heater
Fan & Fan Motor
Type Q'ty ……. Dia. Fan motor model…Q'ty No. Of poles…rpm (230 V, High) Nominal output W Coil resistance (Ambient temp. 20 °C )
VAC
Rotary (Hermetic)
80242335 C-RN190H5B
1900
FV68S…2100
Ω Ω
C-R: 0,921
C-S: 2,843
Internal protecto
-
utomatic opening
utomatic reclosining
-
40
400
240 V - 30 W
Propelle
1…. Ø 400
SMEN 5192672
OR / KFG6S-51SA5P - 1
6…910 / 6…908
43 / 40
Ω Ω
BRN-WHT: 83,4 /
WHT-PNK: 218,7 / 201
98,5
Safety devices Type
Operating temp. Open °C
Close °C
Run capacitor µF
Heat Exch. Coil
Coil Rows Fin pitch mm Face area
External Finish
Internal thermal protector
130 ± 5
83 ± 15
2
VAC
440
luminium plate fin / Copper tube
2
1,8
m
2
0,508
crylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE
9