Euro-Line FC512CL, AE512SC, AE512SCL Technical And Service Manual

FC512CL - AE512SC FC512CL - AE512SCL
7(&+1,&$/6(59,&(0$18$/
63/,76<67(0$,5&21',7,21(5
0.8180.029.0 05/99
®
WARNING
CAUTION
WARNING
CAUTION
Table of Contents
Page
1.OPERATING RANGE..............................................................................................................................1
2.SPECIFICATIONS
2-1.Unit Specifications..........................................................................................................................2
2-2.Major Component Specifications....................................................................................................4
2-3.Other Component Specifications....................................................................................................7
3.DIMENSIONAL DATA..............................................................................................................................9
4.REFRIGERANT FLOW DIAGRAM .........................................................................................................12
5.PERFORMANCE DATA
5-1.Performance charts .......................................................................................................................13
5-2.Air Throw Distance Chart ..............................................................................................................14
5-3.Cooling Capacity ...........................................................................................................................15
6.ELECTRICAL DATA
6-1.Electrical Characteristics................................................................................................................16
6-2.Electric Wiring Diagrams................................................................................................................17
7.FUNCTION
7-1.Room Temperature Control ...........................................................................................................20
7-2.Freeze Prevention .........................................................................................................................21
7-3.Outdoor Fan Speed Control ..........................................................................................................22
8.TROUBLESHOOTING
8-1.Check before and after troubleshooting ........................................................................................23
8-2.Air conditioner does not operate ....................................................................................................24
8-3.Some part of air conditioner does not operate ..............................................................................28
8-4.Air conditioner operates, but abnormalities are observed .............................................................31
8-5.If a sensor is defective ...................................................................................................................32
9.CHECKING ELECTRICAL COMPONENTS
9-1.Measurement of Insulation Resistance..........................................................................................33
9-2.Checking Continuity of Fuse on PCB Ass'y....................................................................................34
9-3.Checking Motor Capacitor .............................................................................................................34
10.DISASSEMBLY PROCEDURE FOR INDOOR UNIT
10-1.Removing Air Intake Grille..............................................................................................................35
10-2.Removing Side Panels...................................................................................................................36
10-3.Access and Removal of Electrical Component Box.......................................................................36
10-4.Removing Flap Motor.....................................................................................................................37
10-5.Removing Evaporator (=Indoor Heat Exchange Coil)....................................................................37
10-6.Removing Fan and Fan Motor........................................................................................................39
ii
1
1.OPERATING RANGE
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. –15°C D.B.
For COOLING ONLY model : AE512SC
For LOW AMBIENT cooling model : AE512SCL
2
2.SPECIFICATIONS
2-1.Unit Specifications
Indoor Unit FC512CL Outdoor Unit AE512SC
Power Source 220–240V ~ 50Hz Voltage rating 220/230/240 V Performance Cooling
Capacity kW 3.45 / 3.50 / 3.50
BTU/h 11,800 / 11,900 / 11,900
Air circulation (High)
m
3
/h
700
Moisture removal (High) Liters/h 1.5
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 6.0 / 6.0 / 6.1 Power input W 1,270 / 1,310 / 1,350 Power factor % 96 / 95 / 92 C.O.P. W/W 2.7 / 2.7 / 2.6 Compressor locked rotor amperes A 32 / 33 / 35
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 /900 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 44 / 40 / 35
Outdoor : Hi dB-A 48 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Air Clean Filter Optional / Optional
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 530
Width mm 900 750
Depth mm 190 270 Package dimensions Height mm 296 593
Width mm 1,011 895
Depth mm 813 348 Weight Net kg 23.5 35.5
Shipping kg 30.0 38.0 Shipping volume
m
3
0.24 0.18
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
3
Indoor Unit FC512CL Outdoor Unit AE512SCL
Power Source 220–240V ~ 50Hz Voltage rating 220/230/240 V Performance Cooling
Capacity kW 3.45 / 3.50 / 3.50
BTU/h 11,800 / 11,900 / 11,900
Air circulation (High)
m
3
/h
700
Moisture removal (High) Liters/h 1.5
Electrical Rating Cooling
Available voltage range V 198 ~ 264 Running amperes A 6.0 / 6.0 / 6.1 Power input W 1,270 / 1,310 / 1,350 Power factor % 96 / 95 / 92 C.O.P. W/W 2.7 / 2.7 / 2.6 Compressor locked rotor amperes A 32 / 33 / 35
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer ON/OFF 24 hours & Daily program,1-hour OFF Fan speeds Indoor / Outdoor 3 and Auto /Auto (Hi,Me,Lo) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R407C /900 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 44 / 40 / 35
Outdoor : Hi dB-A 48 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Air Clean Filter Optional / Optional
Dimensions & Weight Indoor Unit Outdoor Unit
Unit dimensions Height mm 680 530
Width mm 900 750
Depth mm 190 270 Package dimensions Height mm 296 593
Width mm 1.011 895
Depth mm 813 348 Weight Net kg 23.5 35.5
Shipping kg 30.0 38.0 Shipping volume
m
3
0.00 0.18
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B.
4
2-2.Major Component Specifications
2-2-1.Indoor Unit
Indoor Unit FC512CL
Controller PCB
Part No. POW-K185GS-N Controls Microprocessor Control circuit fuse 250 V 3 A
Remote Control Unit RCS-5PS3E
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 2 ... ø130 / L180 Fan motor model ... Q'ty K48407-M01416 ... 1 No. of poles ... rpm (230 V, High) 4 ...1,160 Nominal output W 20 Coil resistance (Ambient temp. 20°C) GRY-WHT :311±7%
WHT-VLT :97.6±7%
VLT-YEL :97.6±7%
WHT-PNK :425±7%
——
Safety devices Type Internal protector
Operating temp. Open °C 145±5
Close Automatic reclosing
Run capacitor µF 1.5
VAC 440
Flap Motor
Model M2LJ24ZE31 Rating AC 208 / 230 V, 50 / 60 Hz No. of poles ... rpm 8 ... 2.5 / 3.0 Nominal output W 3 / 2.5 Coil resistance (Ambient temp. 20°C) k16.45 ± 15%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.8 Face area
m
2
0.192
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
5
2-2-2.Outdoor Unit
Outdoor Unit AE512SC
Compressor
Type Rotary (Hermetic) Compressor model C-R110H5H80619445-S Nominal output W 1,100 Compressor oil ... Amount cc SUNISO 4GSD-T ...550 Coil resistance (Ambient temp. 25°C) Ω C–R :1.962
C–S :5.38
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA98596-9201 CS-7C115 Operating temp. Open °C 145±5 115±3
Close °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 21A —
Run capacitor µF 25.0
VAC 400
Crank case heater —
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø400 Fan motor model ... Q'ty K35610-M01402 ... 1 No. of poles ... rpm (230 V, High) 6 ...760 Nominal output W 20 Coil resistance (Ambient temp. 20°C) BRN-WHT :256±7%
YEL-WHT :227±7%
PNK-YEL :103±7%
Safety devices Type Internal protector
Operating temp. Open °C 150±10
Close °C Automatic reclosing
Run capacitor µF 2.0
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area
m
2
0.379
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
Outdoor Unit AE512SCL
Controller PCB
Part No. POW-CL128E Control circuit fuse 250 V 3.15 A
Compressor
Type Rotary (Hermetic) Compressor model C-R110H5H80619445-S Nominal output W 1,100 Compressor oil ... Amount cc SUNISO 4GSD-T ...550 Coil resistance (Ambient temp. 25°C) Ω C–R :1.962
C–S :5.38
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA98596-9201 CS-7C115 Operating temp. Open °C 145±5 115±3
Close °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 21A —
Run capacitor µF 25.0
VAC 400
Crank case heater 240 V 20 W
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø400 Fan motor model ... Q'ty UE6T-21H5P-S ... 1 No. of poles ... rpm (230 V, High) 6 ...770 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT-BRN :264.5
WHT-VLT :227.9
VLT-YEL :22.53
YEL-PNK :42.37
Safety devices Type Internal fuse
Operating temp. Open °C 145±2
Close °C —
Run capacitor µF 2.0
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.3 Face area
m
2
0.379
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
2-3.Other Component Specifications
7
Power Relay (PR) G7L-2A-TUB
Coil rating AC 200–240V, 50/60Hz Coil resistance (at 23°C) 21 ±15% Contact rating AC 220V, 25A
Outdoor Unit AE512SC
Transformer (TR) ATR-H85
Rating Primary AC 230V, 50/60Hz
Secondary 11V, 0.727A
Capacity 8VA
Coil resistance (at 21°C) Primary (WHT – WHT): 214 ±10%
Secondary (BRN – BRN): 1.58 ±10%
Thermal cut-off temp. 145°C, 2A, 250V
Thermistor (Coil sensor TH1) PBC-41E-S14
Resistance k –20°C40.1 ±5% 20°C 6.5 ±5%
–10°C24.4 ±5% 30°C 4.4 ±5%
0°C15.3 ±5% 40°C 3.0 ±5%
10°C 9.9 ±5% 50°C 2.1 ±5%
Thermistor (Room sensor TH2) KTEC-35-S6
Resistance k 10°C10.0 ±4% 30°C 4.0 ±4%
15°C 7.9 ±4% 35°C 3.3 ±4% 20°C 6.3 ±4% 40°C 2.7 ±4% 25°C 5.0 ±4% 50°C 1.8 ±4%
Indoor Unit FC512CL
8
Thermistor (Coil sensor TH1) PBC–41E–S4
Resistance k –20°C40.1±5% 20°C 6.5±5%
–10°C24.4±5% 30°C 4.4±5%
0°C15.3±5% 40°C 3.0±5%
10°C 9.9±5% 50°C 2.1±5%
Power Relay (PR) G7L-2A-TUB
Coil rating AC 200–240V, 50/60Hz Coil resistance (at 23°C) 21 ±15% Contact rating AC 220V, 25A
Transformer (TR2) ATR-J65
Rating Primary AC 230V, 50Hz
Secondary 19V, 0.315A
Capacity 6VA
Coil resistance (at 22°C) Primary (WHT – WHT): 455 ±10%
Secondary (BRN – BRN): 2.85 ±10%
Thermal cut-off temp. 145°C
Outdoor Unit AE512SCL
9
3.DIMENSIONAL DATA
Indoor Unit FC512CL
Remote control unit
86
74 74
Center of tubing hole ø75 (4 places)
Wide tube ø12.7 (1/2") Narrow tube ø6.35 (1/4")
Drain hose ø26
74 74
900
86
41
41
190
680
18.5
61
172.5
Unit : mm
10
Outdoor Unit AE512SC
276
4 – ø12 holes
312
Air intake
Air discharge
608 60
530
38088
17
750
380 273
4 – ø3.3 holes
270
6193
Wide tube service valve ø12.7 (1/2")
Narrow tube service valve ø6.35 (1/4")
Unit : mm
Loading...