Minimum Separation Distances for Terminals in mm
Location Balanced Flue
A Below an opening Appliance
rated heat
input
0-7kw
>7-14kw
> 14-32kw
>32
300
600
1500
2000
B Above an opening (1) 0-32kw
>32kw
300
600
C Horizontally to an opening (1) 0-7kw
>7-14kw
>14kw
300
400
600
D Below gutters, soil pipes or drain
pipes
300
E Below eaves
300
F Below balcony or car port roof
600
G From a vertical drain pipe or soil
pipe
300
Minimum Separation Distances for Terminals in mm
Location Balanced Flue
H From an internal or external corner
or to a boundry alongside the
terminal
600
I Above ground,roof or balcony level 300
J From a surface or a boundary facing the
terminal
600
K From a terminal facing the terminal 600
L From an opening in the car port into the
building
1200
M Vertically from a terminal on the same
wall
1200
N Horizontally from a terminal on the
same wall
300
P From a structure on the roof
1500
Q Above the highest point of
intersection with the roof
600
R Flue should not penetrate shaded area 600
S Flue should not penetrate shaded area
200
Note (1)
An opening means an openable element, such as an openable window, or a fixed opening such as an air
vent. However, in addition, the outlet should not be nearer than 300mm to an opening into the building fabric
formed for the purpose of accommodating a built in element, such as a window frame.