Eurogauge LAS31Z1, LAS33Z1 User Manual

Tank Full
Alarm Point
Tank Empty
Alarm Point
Bund Full
Alarm Point
Tank
FillPoint
LAS Unit - Battery or AC/DC Version
User Guide
EUROGAUGE
EUROGAUGE
User Guide
LAS Level Alarm System
...the level people
Specification
LAS31Z1 - AC/DC Version
Supply:
85 to 265Vac; 50/60Hz; 4VA, +24Vdc
Indicators:
Tank Full - Red Tank Empty - Red Bund Full - Red Power - Amber
Controls:
Test Button simulates alarm conditions Mute Button mutes alarm sounder Relays: SPCO 250V; 3A non-inductive load. de-energises upon alarm – remains de-energised until alarm clears
Sounder: Internal piezo-electric sounder (90db @ 0.6metre) Sensor:
Floatswitch x 3, 5m cable with 1” BSP tank connector
Housing: Polycarbonate ABS enclosure Dimensions: 176mm x 125mm x 76mm Protection: IP65 Cable Entry: 5 Pg11 glands for 6-8mm cable Weight: 0.60kg
WARNING: NOT FOR USE ON LIQUIDS IN STORED WITHIN HAZARDOUS AREAS
A Flameproof version (EEX D) is available to order, please contact Afriso Eurogauge Lt d for further det ails.
LAS33Z1 - Battery Version
Battery:
+9V PP3 Alkaline 6 LR 61, 6 AM 6, MN 1604
Indicators:
Tank Full - Red Tank Empty - Red Bund Full - Red
Controls:
Test Button simulates alarm conditions Mute Button mutes alarm sounder
Sounder: Internal piezo-electric sounder (90db @ 0.6metre) Sensor:
Floatswitch x 3, 5m cable with 1” BSP tank connector
Housing: Polycarbonate ABS enclosure Dimensions: 176mm x 125mm x 76mm Protection: IP65 Cable Entry: 5 Pg11 glands for 6-8mm cable Weight: 0.60kg
...the level people
LAS Level Alarm System
The LAS3 Alarm provides Tank Full, Tank Empty and Bund Full audible and visual alarms for oil storage tanks. The LAS31Z1 is powered from a 85 to 265V ac or 24Vdc supply and the LAS33Z1 from a 9V replaceable battery . Simple floatswitches mounted in the tank and bund area are used to provide the alarm signals.
The LAS31Z1 provides a continuous display of alarm conditions while the LAS33Z1 is powered on by an alarm signal or whenever the Test button is pressed. Once the LAS33Z1 has been powered on by an alarm signal the corresponding alarm lamp lights and the sounder operates. If the alarm is not acknowledged by pressing the Mute button the unit will sleep after 5 minutes and will wake every hour operating the sounder for 5 seconds and the alarm lamp for 10 seconds. This continues until the alarm condition is cleared or until the battery is exhausted (around 240hrs with a new battery). Acknowledging the alarm immediately turns the sounder off and the alarm lamp off after 30 seconds and puts the LAS33Z1 into sleep mode. When there are no alarms present the LAS33Z1 is switched off. On pressing the Test button all alarm lamps light and the sounder operates, releasing the Test button turns
the alarms off. Any existing alarms will be displayed for 30 seconds before turning off.
Note: We reserve the right to amend these specifications without prior notice.
Unit 4, Satellite Business Village
Fleming Way, Crawley
West Sussex. RH10 9NE
Tel: +44 (0)1293 658360
Fax: +44 (0)1 293 528270
www.eurogauge.co.uk
sales@eurogauge.co.uk
· RADAR and MICROPULSE
· ULTRASONICS
· PRESSURE TRANSMITTERS
· VIBRATION SWITCHES
· CAPACITANCE
· Float Level Switches
· Conductivity
· Rotary Paddle
· Magnetostrictive
· Self-powered gauges
· Oil/water Alarms
· Leak Detectors
· Pressure and Temperature
Declaration of Conformity
LAS Series Level Alarm System
This is to certify that the above named product(s) fully complies with the Electromagnetic Compatability Directive 89/336/EEC and the Low V oltage Directive 73/23/EEC of the European Union and with the requirements of the normative sections of the following harmonised European Standards.
EN61000-6-3: Electromagnetic Compatibility - Generic Emission Standard. EN61000-6-1: Electromagnetic Compatibility - Generic Immunity Standard. EN 61010-1: Safety requirements for electrical equipment for measurement,
Signed :
Position: Technical Services Manager Date: 12/12/2005
This declaration applies to the following part number(s):
LAS31Z1: LAS 3 85-265Vac/24Vdc version. LAS33Z1: LAS 3 9V Battery Version.
D. C Ward
LAS3 Typical Installation
4/4
1/4
User Guide
PKVA
Extension
Cable
Connector
Extension Cable (2 Core) supplied by Installer
Weight
Cable Gland
Adjust Cable
Gland to set
Alarm Point
LAS 3
Alarm Unit
Float
Circlip
Turn Float
upside down
for Low
Level Alarm
(remove
Circlip
to alter)
Float Sw itch Ass embly
175
76
125
Fixing centres:- 160 x 110mm
EUROGAUGE
EUROGAUGE
User Guide
LAS Level Alarm System
Installation & Electrical Connections
The alarm unit is designed for four-screw wall mounting on a 160mm x 110mm pitch.
It is recommended that the unit is not mounted in a location where it is exposed to direct sunlight.
All wiring must be in suitable cable for the site conditions.
The installation must comply with the relevant regulations of the electrical supply authority concerned together with any other statutory requirements which may affect the complete installation.
...the level people
Battery Version
...the level people
Float Switch Installation
Pass the float switch lead through the tank/cable gland assembly to give the desired alarm switchpoint and tighten the cable gland.
Fit the float switch assembly through the 1" BSP tank gland in the tank.
Should the float switch lead require extension, fit a PVKA extension cable connector to the float switch lead and run the length of additional cable from the PKV A connector to the T A3 unit.
LAS Level Alarm System
Live
Neutral
Earth
+24Vdc
Closed when Tank Full
Open when Tank Full
24Vdc or 85-265Vac Version
0V
Common
Tank Full
Alarm
Contacts
Tank Empty
Alarm
Contacts
Bund Full
Alarm
Contacts
2/4
Float Switch
IP1 IP2 IP3
Open when Bund Full Common
Closed when Bund Full Open when Tank
Empty
Common Closed when Tank Empty
‘All Alarm contacts are voltage free’
Float Switch
IP1 IP2 IP3
Tank Full
Tank Empty
Float Switch
Float Switch
Tank Full
Tank Empty
Float Switch
Float Switch
Dimensions
Bund Full
Bund Full
3/4