EURO AJPI PASUBIO Use And Maintenance Manual

Use and maintenance
manual for pellet
stove
Dear Customer
We thank you and we are honored that you have chosen one of our products. Please read this manual carefully; in it you will find all the information and helpful tips for using the product with
the maximum safety and efficiency. The manual supplied with the stove should be guarded and in case of loss or destruction of the same it is necessary to request a copy from your dealer or from the company, specifying the serial number of the stove, on the back wall.
Summary
1 Misconduct 2 Safety 3 Warnings 4 Regulations and declaration of conformity 5 Warranty 6 Liability 7 Installation 8 Specifications 9 First ignition 10 Modes of Operation 11 The menu 12 Alarms 13 Maintenance, cleaning, testing the stove 14 Spare Parts 15 Wiring Diagram 16 Duct 17 Notes
Pag 2 Pag 3 Pag 3 Pag 4 Pag 4 Pag 5 Pag 5 Pag 11 Pag 14 Pag 16 Pag 21 Pag 30 Pag 35 Pag 38 Pag 40 Pag 41 Pag 43
1 Misconduct
In this section we will draw up a list of some small rules to follow for the correct working of the stove and safety.
All the operations not provided for in the manual and not authorized by a technician recommended by the company, must be considered dangerous. Otherwise the ZF company does not assume any responsibility both civil and criminal.
Strictly prohibited
- Not observing the use and maintenance manual.
- Using the stove for any other use not provided for ( exclusively for heating).
- Touching the surfaces of the stove when it is hot.
- Use of the stove by children or disabled without assistance.
- Use of the stove by people who don’t know the safety regulations.
- Feeding pellets manually into the brazier.
- Working the stove with broken or not compliant parts (irregular flue, splintered glass, non-
original spare parts, etc.)
- In case of misfire, restarting the stove without first having emptied the brazier.
- In case of misfire, restarting the stove without first having waited 10-15 minutes.
- Throwing away unburnt pellets (still burning), after having cleaned the brazier.
- Feeding pellets recycled from the firebox or brazier.
- Neglecting stove cleaning ( glass and flue included).
- Cleaning the stove with water ( water could filter through the inside of the stove and
damage its electric parts).
- Igniting the stove in case of any component failure.
- Exposing oneself for a long time directly to the hot air of the stove.
- Exposing animals, plants and any inflammables to the air of the stove.
- Placing any kind of object on the stove.
- Placing any washing or object on the stove to dry.
- Infringing the parameters of the stove.
- Installing the stove in not specific conditions and environments.
- Using the appliance as an incinerator and fuels other than those recommended.
- Using a quality of pellet that doesn’t meet the regulations DIN 51731.
- Not executing the maintenance operations provided for.
- Staying within 2 meters from the stove in case of misfire for the first 10 minutes.
- Making the stove work with the door open.
- Touching the stove when barehanded.
2 Safety
- The installation of the stove, the flue, electrical connections, checking its operation, should
always be carried out by authorized and qualified personnel.
- Install the stove in accordance with the regulations of the local area, region or state.
- For the proper use of the stove and electronic parts, you must follow the instructions in the
user's manual.
- The stove must be fed exclusively on pellets with a diameter of 6 mm DIN 51731.
- Incorrect installation or poor maintenance (not conforming to the provisions in this booklet,
"Use and Maintenance") can cause damage to people and property. In this case the company ZF is released from any civil or criminal liability.
- Before performing any operation, the user must have read and understood all the contents of
this manual "Use and Maintenance".
- Tampering and misuse of the stove can be dangerous for the user’s safety. In these cases, the
ZF Company disclaims any civil or criminal liability, resulting from damage to people and property.
- When the stove is in operation, most of the surface is very hot (glass, handles, tubes and
shells); must then use the appropriate protections for the contact.
- It is forbidden to operate the stove with broken glass, the open door or any defective part
(fans, motors, etc..).
- Before carrying out any cleaning or maintenance, disconnect the stove from the power
supply with the power switch; after that, remove the cable on the back of the same, check the cooling of the entire internal and external structure, and the ash in the combustion room.
- In case of fire in the flue: switch off the stove, disconnect the power supply from the mains
and never open the door of the stove. Call the authorities (fire brigade).
- The stove must be electrically powered by a system with grounding conductor, as provided
by law 73/23 and 93/68 EEC.
3 Warnings
- Turn the stove off in case of failure or malfunctioning.
- Never feed pellets manually into the brazier.
- Make sure the brazier is empty before igniting the stove (even in case of previous misfire).
- Every initiative or operation not provided for in this manual must be considered dangerous.
In this case the ZF company does not assume any responsibility both civil and criminal.
- Do not clean the interior and exterior parts of the stove with water.
- Do not expose plants, animals, things and people to the hot air blast of the stove for too long.
- Install the stove in suitable locations for the prevention of fire and already pre-arranged for
safety.
- The storage of the stove and the lining of all its parts (even those in ceramic) must be effected in
rooms without humidity and sheltered from bad weather.
- Avoid setting the body of the stove directly on the floor. In case of wooden or inflammable
floors always put an insulating material between the stove and the floor.
- The pellet stove is not a cooking top to cook or heat up food and drink.
- Carry out all operations in maximum safety.
- Do not place any object on the stove.
- Do not place any washing or object or beings (animals, plants, etc.) to dry.
4 Regulations and declaration of conformity
The company states that ZF stove complies with the following directives and regulations for the CE marking European Directive:
2004/108 CE (EMC Directive) and subsequent amendments. 2006/95 CE (Directive on the safety of electrical equipment LVD) and subsequent amendment. 305/2011 (the Construction Products Regulations CPR) and subsequent amendments.
European Standards: EN 55014-1; EN 55014-2; EN 61000-3-2; EN 61000-3-3; EN 60335-1; EN 60335-2-102; EN 62233; EN 14785.
The installation and use of the stove must be met in all the local and national laws and all European standards.
5 Warranty
Warranty conditions
ZF Ltd located in Dino Fochesato Street n.1 Meledo of Sarego (VI) guarantees its products for 2 years from the date of purchase, for manufacturing defects or faults. This warranty is void if the lack of conformity is not reported within 2 months from the date of its detection. ZF Ltd limits its liability to the supply of the stove, which has to be installed in accordance with the best working standards, following the instructions contained in the provided manual supplied with the product and in accordance with the laws in force. The installation must be carried out by qualified staff under the responsibility of the person who instructs him, who will assume responsibility for the final installation and the consequent good working of the installed product. ZF Ltd disclaims any liability in case of non-observance of these precautions. The installer will have to issue a Declaration of conformity of the installation in accordance with the best working standards, in accordance with the laws in force.
Examples of installation technicians:
- Authorized Service Centers technicians
- Technicians and companies associated Anfus (National Association Stove Fitting)
- Technicians adherent to national school training plans Fuspa
- Your trusted technicians (qualified thermotechnics)
Territorial expansion of the warranty: Italian territory
Validity of the warranty
The warranty is valid on condition that:
- The buyer sends within 8 days from the date of purchase the coupon in his possession
completed in its entirety. The date of purchase must be validated by the possessor of a valid tax record issued by the seller
- The apparatus is installed by qualified staff, in accordance with the laws in force and the
instructions contained in the provided manual
- The apparatus is used as illustrated in the provided manual
- The manufacturer’s certificate, validated by the tradesman, has been filled in and signed by
the customer
- The presence of the document certifying warranty, filled in and accompanied with the tax
record issued by the tradesman, to show to the ZF Ltd Technical Assistance Center in case of assistance
Forfeiture of the warranty
The warranty is not valid in the following cases:
- The above warranty terms have not been observed
- The installation is not carried out in full obedience of the laws in force and the instructions
contained in the provided manual
- Non-maintenance or wrong maintenance of the product by the customer
- The presence of electrical systems and/or plumbing’s not in accordance with the laws in
force
- Damages caused by weathering, chemical and electrochemical agents, improper use of the
product, natural calamities, modifications or tampering with the product, electrical system or flue faults, use of non-original spare parts, sudden change in voltage or overloaded power supply or other causes not attributable to the product
- The combustion of materials not in keeping with the type and the quality indicated in the
use and maintenance manual supplied with the stove.
- Damages caused during transport. We invite you to properly check your goods at the
moment of receipt. In case of anomalies, inform immediately the tradesman and mark them in the transport document and the copy which will be retained by the carrier.
The warranty covers possible changes and the necessary labour for the change (with the exception of products installed outside the Italian territory). In case of products installed outside the Italian territory only the Italian warranty is valid, therefore the local importers or dealers are not obliged to recognize warranty interventions on what has not been purchased through them. In these cases the spare parts will be sent directly from our headquarter and the replacement and maintenance costs will be debited to the customer by the area technicians.
The ZF Ltd company is not responsible for possible damages caused, directly or indirectly, to people, things, animals due to a total or partial failure to comply with the rules contained in the use and maintenance manual supplied with the stove.
Limited warranty
Electric and electronic components, fans, motors and printed circuit board are not included in the warranty. The warranty covers these components for a 12-months from the date of purchase.
Warranty exclusion
All components of the stove subject to wear and tear are excluded from the warranty:
Gaskets Ceramic/ tempered glass Linings and grills Varnished details Chromate/gilded Satin Majolica Handles Power lines Vermiculite Refractory material Cast-iron brazier
- Chromatic variations, crackles and slight dimensional differences of the parts in majolica are
not contestable as they are all physical features of the materials not attributable to the manufacturing process
- The details of the installation for the production of sanitary water not furnished by ZF Ltd
- Finally, all interventions carried out by qualified technicians aimed at the adjustment and
setting of the product due to the type of combustible used or the typology of installation requested by the customer
- In case of replacement of faulty components under warranty, any warranty extension won’t
be provided. Any type of refund during the machine downtime won’t be provided
- The warranty is valid only for the buyer and cannot be transferred to a third-party
Warranty interventions
The request for intervention must be submitted to the tradesman within 2(two) months from the detection of the fault; warranty intervention, as law prescribes, provides for the repair of the product without any charge at the customer’s expense.
6 Liability
The ZF company disclaims any liability whether civil or criminal, for any damage that may directly or indirectly result from non-compliance, partial or total, of the instructions contained in the booklet "manual of use and maintenance."
The ZF company disclaims any liability whether civil or criminal, arising out of incorrect or improper use of the stove by the end user, reclines any civil or criminal liability in the case of unauthorized repairs and the use of non-original parts, also not liable for damage to the stove due to transport and does not recognize compensation for forced stopping of the stove. The manufacturer disclaims any responsibility or liability direct or indirect result of:
- Failure to follow instructions contained in the booklet
- Inadequate maintenance and cleaning
- Installation Errors
- Non-compliance with safety regulations
- Installation by unqualified and untrained personnel
- Installation not in accordance with the regulations in force in the country
- Use of non-original spare parts
- Exceptional Events (weather, power surges, strange places of installation)
- The ZF Ltd does not grant any compensation for direct or indirect damage caused or
depending on the product.
In the above cases the warranty is void.
7 Installation
Notice for the installer
The installation of the stove must be carried out by qualified technicians who have to install the stove in accordance with the European laws and the laws in force in the place, Region or State.
The stove must be electrically powered by a system in accordance with the regulation 72/23 and 93/68 CEE on the power grid.
The stove must be sized according to the environment in which it is installed.
The stove must be positioned vertically.
The stove mustn’t be installed in bedrooms, bathrooms or where there is another heating system
without a self-sufficient air flow (chimney, etc.).
Environment and distances
It is essential to check the environment where the stove will operate for an optimal working.
- The volume of the house or the working environment mustn’t be smaller than 30m³.
- There must be a permanent air opening outwards in the installation room, at least 800cm²,
non-obstructed and protected by a permanent grill.
- The air can be taken by the rooms
contiguous to the room where the stove has been installed on condition that there are air intakes, not located in the bedroom, bathroom or where there are inflammable materials.
- If the stove is installed in a room with wooden or inflammable floor, you must protect the
floor by using (besides the anti-vibration dampers) also an insulating slab, projecting at least 20 cm on the sides and 40 cm on the front.
- It is compulsory the presence of a suitable
fumes evacuation system in the environment where the stove is placed.
- It is not compulsory to connect the air pipe of
the stove directly outside (see figure), but it is necessary to guarantee at least 50m³/h of air.
Grill 800cm² .
- The electrical system must be in accordance
with the law; check the efficiency of the earthing circuit in a particular manner. The transmission line must be suited to the power of the apparatus.
- When you place the stove in a room you must check that the walls are not inflammable and
that inflammable materials such as curtains, wallpaper, etc have not been applied on the walls. You must place the stove sideways, at a distance less than 20 cm and less than 10
cm at the back. If there is an internal flue it’s advisable to keep a distance of 10cm between
the flue and the wall.
- Do not place inflammable materials at a distance less than 1 meter from the stove.
- We also recommend to keep out of the furnace radiation area, anyway at a distance of at
least 1 m from the warming block, all types of combustible or inflammable materials such as: beams, wooden fittings, curtains, inflammables.
Flue
The flue of a pellet stove is a very important component because it affects the correct working of the stove.
The flue must be only for the stove and cannot be used for
other apparatus; you can’t make fixed or movable openings
to connect other air adduction pipes and pipes for plant­engineering use.
The flue must be equipped with a chamber for the gathering of solid materials and possible condensations, placed under the entrance of the flue outlet duct, so that you can easily open it and inspect it from an airtight small door.
The installer has to make sure the opening do not cross inflammable materials, or in the absence of alternative solutions, he has to use an insulating protection on the pipe ( with wall junctions with a diameter of 13 cm at least, insulating the pipe with insulating materials 1,5-5 cm thick, with a suitable thermal conductivity), even if it passes near inflammable materials ( minimum distance 200 mm).
As for the assembly of the pipes you must always use pipes and junctions with hermetically sealed gaskets.
It’s important that the curvature of 90° provides for a T junction with inspection; we advise you to use a curve of 45°.
Using nets or filters at the extremity of the flue or any extremity which could turn into a nest is forbidden. Use only extremity in accordance with the regulation.
The horizontal segments must have a minimum inclination of 3% upward.
As for the connection of the flue, the horizontal segment must be minimum and you
mustn’t exceed 3 meters, the number of direction changes, including that owing to the use of the T element, mustn’t be bigger than 4, never exceed 6 m of pipes, use curves of 45°
and obey the regulations UNI 10683, using pipes in accordance with the law.
Examples of connections with isolated and non-isolated external pipes Connections that provide for the use of pipes not larger than 20 cm in diameter, which must have
at the base an inspection system and a draught less than 10 Pa. The internal section must be uniform, preferably circular; the sides of the pipe must be smooth as much as possible and without narrowings; the curves must be regular and without discontinuities; the pipes mustn’t be subjected to deviations from the axis higher than 45°.
It is compulsory the installation of a windproof roof in accordance with the regulations . The T inspection, placed at the base, can also be placed inside the house ( better if external).
NB: This system always guarantees the fumes evacuation, also in case of non-electric tension
Connection with multiple junctions
Link that is only done in cases of particular disadvantages in rankings. In this case the horizontal section must have a minimum slope of 3% upwards and must not exceed 3 meters, the vertical section that goes from the stove to the second curve must be at least 1.5 meters long. The T inspection, at the base, can also be applied inside the house (preferably external). If there is a fireplace, it must have a preferably circular internal section; the square or rectangular sections must have rounded corners with a radius of at least 20mm, rectangular sections, with a maximum ratio of
1.5 between the sides, they must have a constant internal section, free and independent; at the base there must be an inspection hole. Always make a minimum draught of 10Pa and comply with the UNI 10683.
NB: In case of obstruction of the pipe, due to failures, or bird's nest, the stove will go on the block (see the Alarms section) and it will be necessary to clean or repair the pipe, and ventilate the environment as quickly as possible, otherwise, it will saturate with smoke.
NOTE: The cleaning of the pipe should be done annually.
Chimney pot
The chimney pot must meet the following requirements:
- Have section and internal form equivalent to that of the fuel.
- Have a useful outlet section not less than twice that of the fuel.
- Be constructed so as to prevent the penetration of rain, snow, foreign bodies in the fuel in
such a way that in the event of winds in any direction and inclination, the discharge of the combustion products is assured (windproof chimney pot).
- The chimney pot must be positioned so as to ensure adequate dispersion and dilution of
the combustion products and, however, outside the reflux area. This area has different sizes and shapes, depending on the angle of slope of the roof, so it is necessary to adopt the minimum heights (see figure).
- The chimney pot must be windproof and exceed the height of the ridge or, where it is not
possible, stick to the values indicated in the table.
- Any buildings or other obstacles, which exceed the height of the chimney pot must not be
close to the same chimney.
Draught
The draught in the stove is crucial to have a good performance in specific adverse weather conditions (rain, fog, snow, altitude, cold, wind), and it is conditioned by the position of the fuel. Adverse weather conditions that impact negatively on the draft are manifold; particularly burdensome is the wind, which can be: ascending, horizontal, descending.
- Ascending wind increases the depression and consequently the draught.
- Horizontal wind: it increases the depression, only in the case of a successful installation in
the direction of the wind.
- Descending wind decreases the depression and consequently the draught.
The flue, if disposed on the upwind side, increases the overpressure and consequently, in the opposite situation, increases the depression, decreasing the draught.
To overcome these drawbacks, the installer must act directly on the stove, modifying the parameter to adjust the speed of fume extraction and conduct a review of all safety devices. This is particularly delicate, it must always be carried out by authorized personnel. The ZF company disclaims any liability, whether civil or criminal, for failure to control by the installer with all safety devices.
Distances and positioning
Roof pitch
Distance between the top and
the chimney
Minimum height of the
chimney
(Measured from the block)
β
A
H
15°
<1,85 >1,85
50 centimeters beyond the top
1 meter from the roof
30°
<1,5 >1,5
50 centimeters beyond the top
1,3 meters from the roof
45°
<1,3 >1,3
50 centimeters beyond the top
2 meters from the roof
60°
<1,2 >1,2
50 centimeters beyond the top
2,6 meters from the roof
8 Specifications
Note: The data reported in the table may vary substantially depending on the pellets used (calorific
value). To calculate the power of the stove to be installed, depending on the needs, take into account that 1 kW = 9.2 m2 (with h = 2.70 m.).
Characteristics
Model PASUBIO
Thermal power introduced (at rated power)
6,82 kW
Thermal power introduced (at reduced power)
3,43 kW
Nominal thermal power (at rated power)
6,20 kW
Reduced thermal power (at reduced power)
3,17 kW
Yield (at rated power)
90,89 %
Yield (reduced power)
92,49 %
Flue gas temperature (at rated power)
104,6 °C
Flue gas temperature (at reduced power)
68,4 °C
Carbon dioxide at rated power
6,89 %
Carbon dioxide at reduced power
4,95 %
CO at 13% O2 (at rated power)
140,8 mg/m³
CO at 13% O2 (at reduced power)
580,2 mg/m³
Fumes speed (rated power)
6,9 g/s
Fumes speed (reduced power)
4,7 g/s
Min. and Max. draft
10 Pa – 12 Pa
Pellets tank capacity
17 Kg
Pellet consumption (at rated power)
1,4 Kg/h
Pellet consumption (at reduced power)
0,7 Kg/h
Pellets autonomy (at rated power)
12 h
Pellets autonomy (at reduced power)
24 h
Air inlet diameter
Ø 48 mm
Fumes outlet diameter
Ø 80 mm
Voltage and frequency of power supply
220V~ 50/60Hz
Electrical power absorbed Min - Max
150 W -380 W
Fuel
Wood
Kind of fuel
Pellet
Size of the fuel
Ø 6 mm - Length 20 mm ± 20%
Weight of the stove
Kg 103,5
The pellet
To obtain the maximum performance, the ZF company advices you to use quality pellets that is prescribed by the regulations DIN51731.
Length: 20mm ± 20% Diameter: 6mm Calorific value: 4.9 ÷ 5.3 kWh / kg
The pellets must be stored in a dry place away from heat sources. The ZF company assumes no responsibility for malfunction due to the use of poor quality pellets.
9 First ignition
Warning
The first ignition will have to be carried out by a qualified technician who will have to check:
- That all regulations mentioned above and current regulations in the place of installation
have been enforced.
- The correct installation: of the stove, the flue, the chimney pot.
- That there is no risk of damage to the stove or to the room of installation. In case of
problems the ZF company disclaims any liability both civil and criminal.
First steps
Check that there are no objects on the stove (manual included) and proceed as follows:
- Fill the hopper with pellets, opening the upper door and closing it again, making sure that
no foreign body is in the hopper. Take off the cover of the hopper only during its charging.
- Check that the brazier is well positioned in its seat.
- Check that the door is hermetically closed.
- Supply power, throw the switch (placed in the back down below); the control display will
light up.
9.1 User interface
The console unity permits to talk to the controller by simply pressing some buttons. A display and other LED indicators inform the operator that the stove is working. In programming mode are displayed the different parameters that can be modified by pressing some buttons.
9.2 Console description
In the figure below it is described the use of the standard console that can be supplied to be fitted horizontally.
9.3 Function of the buttons
Button
Description
Mode
Action
1
Temperature
increment
WORK/OFF
It increments the room temperature value
PROGRAMMING
It modifies/increments the selected parameter
2
Temperature
decrement
WORK/OFF
Decrement of the room temperature value
PROGRAMMING
It modifies/decrements the selected parameter value
3
SET/MENU
-
Enter the menu
SET/MENU
Enter the next submenu level
PROGRAMMING
It sets the selected menu and passes to the next entry
4
ON/OFF
WORK
Pressed for 2 seconds, it turns on and off the stove
PROGRAMMING
It passes to the next level of the menu and all modifications carried out are memorized
BLOCK
It unblocks and turns off the stove
5
Power
decrement
WORK/OFF
It reduces the value of the stove power
PROGRAMMING
It passes to the next submenu entry and all modifications carried out are saved
MENU
It passes to the next submenu entry
6
Power
increment
WORK/OFF
It increases the value of the stove power
PROGRAMMING
It passes to the previous submenu entry and all modifications carried out are saved
MENU
It passes to the previous submenu entry
9.4 Meaning of the LED
Led
Meaning when turn on
Icon
CHRONO
Chrono enabled
ALARM
Stove on the alert
GLOW PLUG
Glow plug on
AUGER
Auger in motion
FUMES ASPIRATOR
Fumes aspirator on
HEAT EXCHANGER-PUMP
Heat exchanger- pump on
NOT USED
Not used
9.5 Display
Display
Function
Conditions
Visualization
DISPLAY
Power
state
parameter
name
OFF
OFF+ROOM TEMPERATURE+WORK POWER+HOUR
ON
ON+ ROOM TEMPERATURE+WORK POWER+HOUR
LOAD
FED PELLET+ ROOM TEMPERATURE+WORK POWER+HOUR
WORK
ROOM TEMPERATURE+WORK POWER+HOUR
PROGRAMMATION
SELECTED PARAMETER
10 MODES OF OPERATION
Premise
The installer must make the first start by taking precautions, and must ensure that the safety devices are working properly (Vacuum gauge, hopper temperature protection etc. ..). Any anomalies with the installation can not be attributed directly to the ZF company. The installer must carry out any other evidence he deems necessary and verify the operation of the buttons on the console.
10.1 Igniting the stove
Once the installation of the stove and the mandatory verification of the safety are over, operation phase begins. To power the stove, simply connect the cable to the electrical outlet, press the power
switch located on the back of the stove at the bottom, moving from position 0 to position 1 as shown in (Figure 1)
Figure 1
Before switching on the stove, the display appears as shown in Figure 2.
Figure 2
To turn on the stove, press on P4 for a few seconds. The successful ignition is indicated in the display with the message "START" as (Figure 3). This phase lasts for a time given by the parameter PR01.Under these conditions, the stove will go in the state of preheating, the glow plug turns on (shown by the glow plug LED) and so does the fan fume extraction. Malfunctions during the ignition phase are shown on the display and the heater goes into an alarm state. (refer to chapter 9).
Figure 3
10.2 Pellet uploading
After about 1 minute the uploading phase begins, the display scrolls the message "LOAD PELLET". In a first step the auger provides to load the pellets in the brazier for a time given by the parameter PR40 (auger LED lit), the speed of the fumes is defined by parameter PR42 and the glow plug is always lit (glow plug LED lit). In the second phase, after the time of the parameter PR40 has passed, the auger turns off (auger LED off) for a time given by the parameter PR41, while the speed of the fumes and the glow plug remain in the previous state. If the stove does not power up after this phase, the auger turns on for a period given by the parameter PR04, the fumes speed is given by the parameter PR16 and the glow plug is lit. (Figure 4).
Figure 4
14:15
22.5°c p-2
14:15
22.5°c p-2
14:15
22.5°c p-2 Load
10.3 Fire Present
After the fume temperature has reached and exceeded the value contained in the parameter PR13, the system goes into power mode displaying "FLAME LIGHT" on the display. In this phase it is checked that the temperature remains stable for a predefined time given by parameter PR02. The fumes speed is given by the parameter PR17, the auger will turn on for a time given by the parameter PR05 (auger LED flashing on) and the glow plug is switched off (glow plug LED off). (Figure 5) Any anomalies will stop the board and this will report the error. (refer to chapter 9).
Figure 5
10.4 Stove on working mode
After the flue fumes temperature has reached and exceeded the value contained in PR13 and maintained it for at least a time PR02, the stove goes into working mode which is the normal operating. The display will show the word "WORK". The power is set by holding down the P5 and P6 and the room temperature can be set by pressing the P1 and P2. (Figure 6). If the fumes temperature reaches the threshold set by parameter PR15, the fan air exchanger lights. (led exchanger on).
Figure 6
During this phase, after a time given by the parameter PR03, the stove performs a cleaning of the brazier. The display will scroll the inscription " CLEANING FIRE-POT ", the auger is turned on (auger LED on) with a speed given by the parameter PR09, the fumes fan speed given by parameter PR08. (Figure 6a) Once the given time by the parameter PR12 has passed, the stove is back in working state.
Figure 6a
14:15
22.5°c p-2
14:15
22.5°c p-2 Flame
14:15
22.5°c p-2 CLEANING
10.5 Changing the heating power set
During normal operation of the stove (Work) you can change the heat power output by using the buttons P5 (Decrease) and P6 (Increase). The power level set is shown on the display. (Figure 7) To exit
from the set wait 5 seconds without performing any operation on the keyboard, or press P3.
Figure 7
10.6 Changing the room temperature
To change the room temperature it is sufficient to act on the button P1. The display shows the set room temperature (SET temperature). Thus acting on the buttons P1 (increase) and P2 (decrease) it is possible to change the value. After about 5 seconds the value is stored and the display returns to the normal mode, or press P3 to exit. (Figure 8).
Figure 8
10.7 The room temperature reaches the set temperature (SET temperature)
When the room temperature has reached the set value, the heating power of the stove is automatically decreased to the minimum. Under these conditions, the display shows the message " MODULAT-". (Figure 9). If the room temperature falls below the set one (Set temperature) the stove goes back to "Work" mode and the power previously set (Set power).
Figure 9
03
set
power
30.0°
c
Set room temp
14:15
22.5°c P-2 work
Modulat-
10.8 Stand by
If enabled in the menu, standby function allows you to turn off the stove once the conditions explained below are met. It is enabled if, at a given time by the parameter PR44, the room temperature is higher than the set temperature (Set environment) plus the parameter PR43. The display shows " STANDBY " and the remaining minutes. (Figure 10).
Figure 10
At the end of the time given by the parameter PR44, the display shows the message "WAIT COOLING" In this state, the stove has turned off the auger (auger LED off), the heat exchanger switches off when it reaches the threshold given by the parameter PR15 and the LED ON \ OFF flashes. (Figure 10a).
Figure 10a
When the fumes temperature reaches the threshold given by the parameter PR13, the stove goes into stand-by mode and runs "WAIT COOLING-" on the display. The auger is off (auger LED off), the exchanger is off (exchanger LED off), as well as the fumes fan. (Figure 10b).
Figure 10b
If the room temperature drops below the set temperature (Set environment) minus the threshold given by the parameter PR43, the stove will switch on again.
Standby
WAIT COOLING
WAIT COOLING -
10.9 Switching off the stove
To turn off the stove just press the button P4 long. The display shows the message "CLEANING FINAL". (Figure 11). The motor of the auger stops (auger LED off), the fumes fan speed is given by the parameter PR08.
Figure 11
The fan of the heat exchanger (heat exchanger LED lit) will remain active until the fumes temperature drops below the value set by parameter PR15. After a time given by parameter PR39, if the fumes temperature appears to be below the threshold given by the parameter PR10, the stove shuts off, displaying the message "OFF". (Figure 11a).
Figure 11a
11 THE MENU
You can enter the menu by pressing the P3 button. The menu is subdivided into different entries and levels that allow you to enter the settings and the programming of the board.
11.1 User menu
The following table synthetically describes the structure of the menu dwelling, in this paragraph, upon the selections available to the user.
Level 1
Level 2
Value
M1 - set clock
-
01- Day of the week
M-T-W-T-F-S-S
02- Hours clock
0-23
03- Minutes clock
0-59
04- Day clock
1-31
05- Month clock
1-12
06- Year clock
00-99
14:15
22.5°c P-2 CLEANING FINAL
14:15
22.5°c P-2 off
Level 1
Level 2
Level 3
Value
M2 - set time
M2-1 - enable time
01 - enable time
on/off
M2-2 – daily programming
01 - day time
on/off
02 - start 1 day
OFF-0-23:50
03 - stop 1 day
OFF-0-23:50
04 - start 2 day
OFF-0-23:50
05 - stop 2 day
OFF-0-23:50
M2-3 – weekly programming
01 - week time
on/off
02 - start Prg 1
OFF-0-23:50
03 - stop Prg 1
OFF-0-23:50
04 - Monday Prg1
on/off
05 – Tuesday Prg 1
on/off
06 - Wednesday Prg 1
on/off
07 - Thursday Prg1
on/off
08 - Friday Prg 1
on/off
09 - Saturday Prg 1
on/off
10 – Sunday Prg 1
on/off
11 - start Prg 2
OFF-0-23:50
12 - stop Prg 2
OFF-0-23:50
13 - Monday Prg2
on/off
14 - Tuesday Prg 2
on/off
15 - Wednesday Prg 2
on/off
16 - Thursday Prg 2
on/off
17 - Friday Prg 2
on/off
18 - Saturday Prg 2
on/off
19 - Sunday Prg 2
on/off
20 - start Prg 3
OFF-0-23:50
21 - stop Prg 3
OFF-0-23:50
22 - Monday Prg 3
on/off
23 - Tuesday Prg 3
on/off
24 - Wednesday Prg 3
on/off
25 - Thursday Prg 3
on/off
26 - Friday Prg 3
on/off
27 - Saturday Prg 3
on/off
28 - Sunday Prg 3
on/off
29 - start Prg 4
OFF-0-23:50
30 - stop Prg 4
OFF-0-23:50
31 - Monday Prg 4
on/off
32 - Tuesday Prg 4
on/off
33 - Wednesday Prg 4
on/off
34 - Thursday Prg 4
on/off
35 - Friday Prg 4
on/off
36 - Saturday Prg 4
on/off
37 - Sunday Prg 4
on/off
M2-4 - week-end programming
01 – week-end time
on/off
02 - start week-end 1
OFF-0-23:50
03 - stop week-end 1
OFF-0-23:50
04 - start week-end 2
OFF-0-23:50
05 - stop week-end 2
OFF-0-23:50
M2-5 - exit
set
Level 1
Level 2
Value
M3 – Select language
01 - Italian
set 02 - English
set 03 - French
set 04 - German
set 05 - Spanish
set 06 - Portuguese
set
Level 1
Level 2
Value
M4 - Stand-by
01 -stand - by
On/off
Level 1
Level 2
Value
M5– Buzzer
01– buzzer
On/off
Level 1
Level 2
Value
M6 – First load
01 first load
90” Level 1
Level 2
Level 3
Value
M7 – stove state
01 – stove state
01 – auger state
info
02 - T minutes
info
03 – Thermostat state
info
04 – Fumes state
info
05 – Fumes extraction revolutions state
info
Level 1
Level 2
Value
M8 – technician settings
01 – access key
set
Level 1
Level 2
Value
M9 – exit
01 - exit
set
11.2 Menu M1 - SET CLOCK
Set the current hour and date. The board is equipped with a lithium battery that allows the internal clock a life of more than 3/5 years. To enter the general programming menus, press the P3 button. The M1 entry will be selected by pressing P5 (decrement) or P6 (increment) and the message
Menu 01 set clock” will
pass on the display. Press the P3 button again to enter the menu (figure 12)
Figure 12
Menu 01 set clock
Figure 12a
Select the desired day and press the P3 button (figure 12a). You can set hour (figure 12b), minutes (figure 12c), day (figure 12d), month (figure 12e) and year (figure 12f) by pressing the P1 button
(increment) and P2 button (decrement) and confirming by pressing the P3 button.
Figure 12b
Figure 12c
Figure 12d
Figure 12e
Menu 01 Friday day
14: _ Menu 01 hour clock
:15 _ Menu 01 Minutes clock
18 Menu 01 day clock
04 Menu 01 month clock
Figure 12f
11.3 Menu M2 - Set time
The menu visualized on the display “M2-1 CHRONO ENABLE” allows to totally enable and disable
all clock thermostat functions. Press the P3 button to enter and then press P1 or P2 to select On or Off. Press the P3 button to confirm
(figure 13).
Figure 13
Submenu M2 - 2 - Day program
Once selected the menu M2-2 CHRONO DAYLY”, you can slide the different parameters of the daily time programming, time enable included, by pressing P3 button first and then P1 and P2 (figure 13a).
Figure 13a
You can set two sections of functioning, the first one with START1 Day and STOP1 Day and the second one with START2 Day and STOP2 Day, delimitated by the times set according to the
following table, where the setting “OFF” indicates the clock to ignore the order. Press the P1 button
(increment) and the P2 button (decrement) to select. Press P3 to confirm.
DAY PROGRAM
Menu level
Selection
Meaning
Possible values
M2-2-01
DAY TIME
Enable daily time
ON/OFF
M2-2-02
START 1 Day
Activation hour
OFF-0-23:50
M2-2-03
STOP 1 Day
Deactivation hour
OFF-0-23:50
M2-2-04
START 2 Day
Activation hour
OFF-0-23:50
M2-2-05
STOP 2 Day
Deactivation hour
OFF-0-23:50
14 Menu 01 year clock
m--2--1 CHRONO ENABLE
m--2--2 CHRONO DAYLY
Submenu M2- 3- Weekly program
The menu “M2-3 Weekly program” allows to enable/disable and to set the functions of the weekly clock thermostat. The weekly function has 4 independent programs. Moreover, the clock ignores the
corresponding order by setting “OFF” in the entry “time”. The following tables synthesize the weekly
program function. Press the P3 button to enter the next function and confirm the value. Press the button P4 if you want to exit the menu.
ENABLE WEEKLY TIME
Menu level
Selection
Meaning
Possible values
M2-3-01
WEEKLY TIME
Enable weekly time
ON/OFF
PROGRAM 1
Menu level
Selection
Meaning
Possible values
M2-3-02
START PRG 1
Activation hour
OFF-0-23:50
M2-3-03
STOP PRG 1
Deactivation hour
OFF-0-23:50
M2-3-04
MONDAY PRG 1
on/off
M2-3-05
TUESDAY PRG 1
on/off
M2-3-06
WEDNESDAY PRG 1
on/off
M2-3-07
THURSDAY PRG 1
on/off
M2-3-08
FRIDAY PRG 1
on/off
M2-3-09
SATURDAY PRG 1
on/off
M2-3-10
SUNDAY PRG 1
on/off
PROGRAM 2
Menu level
Selection
Meaning
Possible values
M2-3-11
START PRG 2
Activation hour
OFF-0-23:50
M2-3-12
STOP PRG 2
Deactivation hour
OFF-0-23:50
M2-3-13
MONDAY PRG 2
on/off
M2-3-14
TUESDAY PRG 2
on/off
M2-3-15
WEDNESDAY PRG 2
on/off
M2-3-16
THURSDAY PRG 2
on/off
M2-3-17
FRIDAY PRG 2
on/off
M2-3-18
SATURDAY PRG 2
on/off
M2-3-19
SUNDAY PRG 2
on/off
PROGRAM 3
Menu level
Selection
Meaning
Possible values
M2-3-20
START PRG 3
Activation hour
OFF-0-23:50
M2-3-21
STOP PRG 3
Deactivation hour
OFF-0-23:50
M2-3-22
MONDAY PRG 3
on/off
M2-3-23
TUESDAY PRG 3
on/off
M2-3-24
WEDNESDAY PRG 3
on/off
M2-3-25
THURSDAY PRG 3
on/off
M2-3-26
FRIDAY PRG 3
on/off
M2-3-27
SATURDAY PRG 3
on/off
M2-3-28
SUNDAY PRG 3
on/off
Day of reference
Day of reference
Day of reference
PROGRAM 4
Menu level
Selection
Meaning
Possible values
M2-3-29
START PRG 4
Activation hour
OFF-0-23:50
M2-3-30
STOP PRG 4
Deactivation hour
OFF-0-23:50
M2-3-31
MONDAY PRG 4
on/off
M2-3-32
TUESDAY PRG 4
on/off
M2-3-33
WEDNESDAY PRG 4
on/off
M2-3-34
THURSDAY PRG 4
on/off
M2-3-35
FRIDAY PRG 4
on/off
M2-3-36
SATURDAY PRG 4
on/off
M2-3-37
SUNDAY PRG 4
on/off
Submenu M2- 4 – weekend program
It allows to enable/disable and to set the clock thermostat functions during the weekend ( days 6 and 7, that is Saturday and Sunday). Press the P3 button in the entry “ weekend time” to enable and set “on” by pressing the P1 button (increment) or P2 button (decrement). You can set the period of functioning for Saturday by setting Start1 weekend and Stop1 weekend, while you can set the functioning of the stove for Sunday by setting Start2 weekend and Stop2 weekend.
WEEKEND PROGRAM
Menu level
Selection
Meaning
Possible values
M2-4-01
WEEKEND TIME
Enable weekend time
ON/OFF
M2-4-02
STAR 1 WEEKEND
Activation hour
OFF-0-23:50
M2-4-03
STOP 1 WEEKEND
Deactivation hour
OFF-0-23:50
M2-4-04
STAR 2 WEEKEND
Activation hour
OFF-0-23:50
M2-4-05
STOP 2 WEEKEND
Deactivation hour
OFF-0-23:50
11.4 Menu M3 – Language selection
It allows to select one of the available languages (figure 14). Press the P1 button (increment) to pass to
the next language, press the P2 button (decrement) to step back. Press P3 to confirm.
Figure 14
11.5 Menu M4 - Stand-by
It allows to enable or disable the Stand-by mode (figure 15). Once selected the Menu M4 by pressing P3,
press P1 (increment) or P2 (decrement) to pass from
“on” to “off” and vice versa.
As for the functioning, make reference to the stand-by paragraph, chapter 7.8.
Figure 15
Day of reference
MENU 03 SELECT LANGUAGE
MENU 04 mode standby
11.6 Menu M5 – Buzzer
It allows to enable or disable the buzzer of the controller during the alarms signalling (figure 16). Press P1 or P2 to enable or disable, press P3 to confirm.
Figure 16
11.7 Menu M6 – First load
This function is available only when the stove is turned off and allows to load the auger at the first ignition of the stove (figura 17), when the pellet tank is empty. After having selected the menu M6, the message “P1 to load” will pass on the display (figure 17a). Then press P1 (increment). The fumes fan turns on at top speed, the auger turns on ( auger LED turned on) and they are still turned on until the end of the time indicated on the display (figura 17b), or until you press the P3 button.
Figure 17
Figure 17a
Figure 17b
MENU 05 MODE BUZZER
MENU 06 FIRST LOAD
OFF MENU 06 P1 TO LOAD
90” 22,5°C p-2 FIRST LOAD
11.8 Menu M7 – Stove state
Once entered the menu M7, by pressing the P3 button, the state of some variables during the functioning of the stove passes on the display. The following table is an example of the visualization on the display and the meaning of these values (figure 18).
State visualized
Meaning
3,1”
Auger pellet load state
52’
Time out
Toff
Thermostat state
106°
Fumes temperature
1490
Fumes extraction speed
Figure 18
11.9 Menu M8 – Technician settings
This menu entry is for the technician who installs the stove. After having put the access key (figura20a), it allows to set different parameters of the stove functioning by pressing the P1 button (increment) and P2 button (decrement) (Figure 19- 19a).
Figure 19
Figure 19a
MENU 07 STOVE STATE
MENU 08 SET TECHNIC
00
MENU 08 KEY ACCESS
In the event that a malfunction occurs, the board intervenes and signals the irregularities, lighting the LED Alarm (Alarm LED lit) and producing acoustic signals. There are the following alarms:
Alarm origin
Display view
Energetic Black-out
AL 1 BLAC-OUT
Flue gas temperature sensor
AL 2 PROBE EXHAUST
Fumes overheating
AL 3 HOT EXHAUST
Encoder fumes failure
AL 4 FAN FAILURE
Misfire
AL 5 NO LIGHTIN-
Pellet absence
AL 6 NO PELLET
Overheating thermal safety
AL 7 SAFETY THERMAL
No depression
AL 8 FAILURE DEPRESS
Each alarm condition causes the immediate shutdown of the stove
The alarm state is reached after the time PR11, EXCEPT THE ALARM OF BLAC-OUT, and can be reset by pressing and holding the button P4. Whenever an alarm is reset, a shutdown phase of the stove is initiated for safety. During the alarm phase the alarms LED will always be lit (Alarm LED lit) and when enabled the buzzer will sound intermittently. If you fail to reset the alarm, the stove will shut down anyway, always displaying the alarm message.
12.1 Energetic Black out
During the working status of the stove, electricity may be missing. Upon restart, if the period of the outage is less than the parameter PR48, the stove restarts on WORK mode, otherwise the alarm is activated. The display scrolls the message "Al 1 BLAC-OUT " (Figure 20) and the stove goes off.
Figure 20
12.2 Fumes temperature sensor Alarm
It occurs in the case where the flue probe proves faulty. The stove goes into alarm, the alarms LED lights up (Alarm LED lit). The Stove will show, "Al 2 PROBE EXHAUST " on the display (Figure 21) and
will go into shutdown. In this case, reset the alarm by pressing the On / Off button and contact your authorized service center.
Figure 21
12 ALARMS
Al1
BLAC OUT
Al2
PROBE EXHAUST
12.3 Fumes temperature Alarm
It occurs in the case where the flue probe detects a temperature higher than a set value fixed and not changeable via parameter. The display shows the message "Al 3 HOT EXHAUST " as (Figure 22)
and the stove goes off. Electrically disconnect the stove and call your authorized service center.
Figure 22
12.4 Encoder smoke Alarm faulty
It happens in case there is a fault in the fumes fan. The stove goes into alarm state and the inscription "Al 4 FAN FAILURE " (Figure 23) will scroll across the display. It occurs in the case in which the fume extractor is faulty or in the case where the fan speed of the fumes expulsion is not detected
by the board. In this case, reset the alarm by pressing the On / Off button and contact an authorized service center.
Figure 23
12.5 Misfire Alarm
It occurs when the ignition phase fails. That is what happens if the time given by the parameter PR01 passes without the fumes temperature not exceeding the parameter PR13. The display will scroll the
inscription "Al 5 NO LIGHTIN- and the stove goes into alarm (figure 24). Wait for completion of the cooling cycle, clean the brazier and proceed with a new ignition.
Figure 24
12.6 Pellets absence Alarm
It occurs when, in working phase, the flue gas temperature falls below the parameter PR13. The
display will scroll the inscription"Al 6 NO PELLET" and the stove goes into alarm state (Figure 25).
Figure 25
Al3
HOT EXHAUST
Al4
FAN FAILURE
Al6
NO
PELLET
Al5
NO
LIGHTIN-
12.7 Safety thermal over-temperature alarm
It occurs when the general safety thermostat detects a temperature above the trigger threshold. The thermostat intervenes and stops the auger, as it comes right after its feeding phase, and the
controller intervenes indicating the alarm status (alarm LED lit) by displaying the message "Al 7 SAFETY THERMAL " (Figure 26), and the stove goes off.
Figure 26
Check that the thermal protection of the tank didn't activate, if this has intervened please make sure that there are no obstructions to the back and front openings of the stove or to the air outlet grill, which prevent the smooth passage of air. Once this is done, reset the safety thermostat, which is located in the back of the stove (Figure 27), under the master switch, covered by a plastic lid screwed on, remove the cap, press the button put the cap back; restart the stove and check if the environment fan is working correctly. If the alarm persists, call the Authorized Service Provider.
Figure 27
12.8 Alarm absence depression
It occurs when the external pressure switch component detects a pressure / depressor below the trigger threshold. The pressure switch operates by turning the auger off, being these two electrically connected in series, and the controller signals the alarm status (alarm LED lit) displaying AL 8 FAILURE DEPRESS on the display (Figure 28). The stove goes into shutdown mode. Remove
power, thoroughly clean: the brazier, the combustion chamber, the passage of smoke and the flue; If the alarm persists, call the Authorized Service Provider.
Figure 28
12.9 Display message SERV
When the message "SERV" appears, the stove has reached 1400 hours of operation. We recommend
that you call your authorized service center for routine maintenance. (Figure 29)
Figure 29
Al7
SAFETY THERMAL
Al8
FAILURE DEPRESS
14:15
22.5°c P-2
serv
Alarm that can occur during the working phase of the stove:
Message on the
display
Reason
Solution
ALAR
NO
FIRE
The pellet is over.
Reload the pellets in the tank
The auger does not load
Check that there are no pellet obstructions
The draught is not enough
Check that there are no obstructions in the flue and air inlet
The fumes probe is broken or disconnected
Call an authorized service The pellet feed auger is broken
Call an authorized service
The fume extractor is broken
Call an authorized service
Power failure
Turn on the stove again
Alarm that can occur during the ignition phase of the stove:
Message on the
display
Reason
Solution
ALAR
NO
ACC
The flame did not ignite
Replace the pellet with a higher quality one, if the problem persists, call the authorized service
Plug disconnected or faulty
Call an authorized service
The flame did not send the fumes on right temperature within the prescribed time
The pellet is finished, refill the tank, switch the stove on, if the problem persists, call the authorized service
The draught is not enough
Check that there are no obstructions in the flue and air inlet
The pellet feed auger is broken
Call an authorized service
The fume extractor is broken
Call an authorized service
12.10 Remote Control Description (Optional)
The remote allows you to control the following functions:
Pressing the button 1 The temperature is increased from a minimum value of 7 ° C to a maximum value of 40 ° C Pressing the button 2
Temperature decreases from a maximum value of 40 ° C to a minimum value of 7 °C
Pressing the button 3
It turns on / off the stove
Pressing the button 4
Joker can be matched to a specific function Pressing the button 5 Power is decreased from a maximum value of 5 to a minimum of 1
Pressing the button 6
Power is increased from a minimum value of 1 to a maximum of 5
13 Maintenance, cleaning, testing the stove
All cleaning and inspections must be carried out when the stove is cold, with the plug disconnected, using gloves and mask. The ZF company does not assume civil or criminal liability, in case you clean or test the stove when this is on, still warm, with the voltage supply switched on and without proper protective equipment.
Daily cleaning
Brazier Cleaning
The cleaning of the brazier is crucial for the proper operation of the stove; it should be performed daily before each start. Lift the brazier from its seat, clean the inside of the brazier with a brush by removing combustion residues and free all the air passages with a screwdriver or a pointed tool (not supplied with the stove). This operation is particularly necessary when using a pellet of poor quality; it is also good to check and clean the brazier support, if there are residues inside they should be removed with a spoon or with a vacuum cleaner. A good cleaning of the brazier ensures good combustion and, consequently, a high yield of the stove.
Cleaning the combustion chamber and ash drawer
The cleaning of the ash and combustion chamber should be made when the ash reaches the edge of the same drawer; it is strictly forbidden to light the stove if the ash goes beyond it. Every day when you clean the brazier also check if the drawer is empty. This maintenance must be done when the stove is cold; it is prohibited to use water to cool the ash or to clean the inside of the stove. You can use the vacuum cleaner, the drawer must be replaced correctly and get to the bottom and there should be no residue of ash in front of or underneath it, if residues are present, it could be interfering with the closing of the door, therefore create an air leak in the combustion chamber.
Cleaning the glass
The glass is self-cleaning and then, while the stove is in operation, a film of air flows along the surface of the same, taking away the ash and dirt; Nevertheless after a few hours, a grayish flap will appear and it has to be cleaned at the first shutdown of the stove. The dirt the glass also depends on the quality and quantity of pellets used. When this is done, always observe if the gray seal around the glass is in good condition; if you fail to control the efficiency of this seal the operation of the stove may be compromised. Pellets of poor quality, dirty brazier, may nevertheless cause more dirt in the glass.
Attention: in case of broken or damaged glass, do not try to turn on the stove.
Monthly cleaning
Open the door of the stove, by means of a vacuum cleaner remove all the ash, also clean the residues attached to the inner walls of the stove with a brush.
Remove the brazier to proceed with the removal of interior walls.
Remove the internal bulkhead, taking it by the two lower edges, if this operation proves to be difficult , use an extraction forceps.
Remove the two side supports by turning up after you have done this remove the beat flame top.
To remove the beat flame top, take it with one hand in the middle, pull in a linear way down once you see all the spin box, rotate to remove it from the combustion chamber of the stove. Take the vacuum cleaner and clean the inside.
At the bottom of the combustion chamber behind the support of the brazier there is another bulkhead to remove, grab her by the edge and pull up.
Removed this piece, the two rear bulkheads are released, to remove them, simply take them off. Even at this stage take the vacuum cleaner to clean the entire inner part of the stove, if present of the residue pasted, carry a brush to remove it from all surfaces.
When all surfaces are clean, remove the ash collection drawer and thoroughly clean even the latter.
Finally, use a screwdriver to remove the cap that is located under the ash drawer and thoroughly clean even this vain.
Check all the interior, and then proceed with the reassembly of all components, paying attention to correct repositioning, cleaning and physical state. Do not reassemble broken or damaged parts may cause undesired operation of the stove.
Summary scheme of the cleaning and maintenance of the stove
Daily
Every 2 days
Once every 1000 Kg
Seasonal
1400 hours
Executed by
Brazier
x
User
Ash drawer x x
User
Glass x
User
Suction Line
x Technician
Flue
x Technician
Fumes pipe
x Technician
Pellet tank
x
Technician/ User
Ash chamber
x
x
User
Door gasket
Check
x Technician
The ZF company disclaims any liability whether civil or criminal, arising from the use of non-original spare parts, also informs that the use of these voids the warranty on the stove. You will find the complete list of spare parts and related code to communicate at the time of the request below.
14 Spare parts
Pos.
Alternative Code
Title
Q.ty
Notes
1
R2000046
Angolare stufa
2
2
R2000047
Pannello esterno DX
1 3
R2000048
Pannello esterno SX
1
4
R2000050
Sportello umidificazione
1 5
R2000051
Sportello carico pellet Sp. 30/10
1 6
R2000052
Griglia centrale
1 7
R2000054
Cornice porta
1
8
R2000056
Piastra di spessoramento 20/10
1
9
R2400353
Perno aggancio porta 6/8 kW nitrurato
1
10
R2400420
Serbatoio pellet 29 litri 17 Kg 2010/A
1 11
R2400448
Cerniera per porta Ø 12 X 34 2010/A
2 12
R2400483
Piedino antivibrante 40x20+perno M8
4 13
R2400486
Bussola per coclea
2 14
R2400508
Fissaggio coclea x stufa 6/8/12 kW
1
15
R2400513
Vetro ceramico 205x413 40/10 K 2010/A
1 16
R2400573
Boccola isolante Teflon 2010/A
1
17
R2400671
Cavo alimentaz.3x075 nerp 2mt SCHUKO
1 18
R2400737
Staffa fissaggio candela
1 19
R2400742
Omega per flat
1 20
R2600044
Leva estrai maniglia stufe EA
1
21
R2600400
Cavo Flat 16VIE L=120cm FL16V1200FFZZ
1 22
R2600401
Termostato Sic-Vano Pellet TDTQWGS10000
1
23
R2600402
Pressostato Sic. 39Pa TDPNP04MBAR00
1 24
R2600404
Display LCD Bianco con Dec Neu PF047_E01
1 25
R2600414
Corpo 6/9 kW
1 26
R2600415
Deflettore superiore
1
27
R2600416
Batti fiamma post sx
1 28
R2600417
Batti fiamma post dx
1
29
R2600418
Batti fiamma alluminato
1 30
R2600419
Telaio porta EA 310 X 587 X 20
1 31
R2600420
Ferma vetro superiore
1 32
R2600421
Ferma vetro laterale dx
1
33
R2600422
Ferma vetro corto centrale
1 34
R2600423
Ferma vetro corto inferiore
1
35
R2600424
Ferma vetro laterale sx
1 36
R2600425
Tappo inferiore
1 37
R2600427
Staffa supporto serbatoio-coclea
1 38
R2600428
Staffa supp. motore-coclea
1
39
R2600430
Braciere 6/9 kW EA
1 40
R2600431
Convogliatore ceneri
1
41
R2600433
Staffa aspiarazione-sostegno 2014
1 42
R2600435
Tubo coclea EA 6-8-11-13
1
43
R2600437
Fianco sx convogliatore
1 44
R2600438
Fianco dx convogliatore
1
45
R2600439
Fondo convogliatore
1 46
R2600446
Supporto interruttore
1 47
R2600447
Maniglia porta EA
1 48
R2600450
Pannello posteriore
1
49
R2600455
Cassetto cenere
1 50
R2600509
Collettore inox uscita fumi Ø 80 X 200
1
51
R2600512
Ventilatore Ø 80X304 M POLI SCHERMATI DX
1 52
R2600516
Ventilatore est. fumi PL21 dis.022434-00
1 53
R2600518
Flangia raccordo Ø 80 H=50 dis.017023-02
1 54
R2600526
Staffa serbatoio sx
1
55
R2600527
Staffa serbatoio dx
1 56
R2600533
Turbolatore sx
1
57
R2600534
Turbolatore dx
1 58
R2600535
Mensola porta stufa
1 59
R2600579
Riduttore velo d'aria
1 60
R2600580
Copertura per velo d’aria inferiore
1
61
R2600627
Modulo Alimentazione polysnap BZ01001
1 62
R2600631
Scheda Madre N100
1
63
R2600632
Motoriduttore SPG 2 RPM
1 64
R2600638
SONDA AMBIENTE SONTC0851PLCP x N100
1 65
R2600639
SONDA FUMI SOTCJ0880ACCF x N100
1 66
R2600662
Vaschetta umidificazione stampata 15/10
1
67
R2600663
Coclea x stufa mod. 6-9-11-13 kW
1 68
R2600674
Resistenza .HDL Ø 9,9 L=130 mm x N100
1
69
R2600706
Nastro tex-tape black adesivo
1 70
R2600707
Treccia artica nera D12mm
1 71
R2600709
Tubetto silicone
1 72
R2600720
Tubo candela 2014
1
73
R2600726
Base stufa baldo
1
74
R2600728
Sotto-top inferiore Sp. 30/10
1 75
R2600729
Top stufa pasubio
1
Hereinafter the diagram for the connection between the different electric parts and the motherboard of the stove is represented.
TSP= safety thermostat vain pellets
15 Wiring diagram
16 Duct
The duct system allows to carry and distribute the heat generated from the heater also in other environments different from the one where the machine is positioned.
Connection
The connection to the heater can be of two types:
- Connecting on top of the stove only through a tube
- Connection on the back of the stove using two pipes
The company Z.F. LTD recommend using smooth tubes, with sweeping curves that is isolated and insulated to prevent heat loss along the way, also should not exceed 10 meters in overall length of the system because in this case it incurs the loss of heat produced from the stove.
Regulation
The adjustment of the channeling can happen in two ways depending on the type of stove you have:
- Manual Adjustment
- Automatic Adjustment
Automatic Adjustment
The adjustment of the air flow in this case is managed directly on the main display of the heater, through the pressure of a few buttons, allowing independent adjustment of the two additional fans. For each of the two fans are different possible types of regulation (see table below). To change the parameters, press on button 1 (fan 2) and button 2 (fan 3).
Setting
Fan 2
Fan 3
A
Corresponding to the selected power
Corresponding to the selected power
0
Fan off
Fan off
1
Fixed speed preset
Fixed speed preset
2
Fixed speed preset
Fixed speed preset
3
Fixed speed preset
Fixed speed preset
4
Fixed speed preset
Fixed speed preset
5
Fixed speed preset
Fixed speed preset
Below is an example of installation of ducted heater in a home environment.
17 Notes
Notes
Information on disposal or recycling of the product at the end
of its life cycle
(for the member states of the EU)
This product falls within the ambit of the Directive 2002/96/CE, also named WEEE ( or RAEE), concerning the electric equipment wastes. The aim of the directive is to prevent, so to reduce, the wastes production derived from that equipment and to promote reuse, recycling and other forms of reutilization, in order to protect environment and public health from possible harmful effects. The symbol of the barred dustbin indicates that the product is subjected to the Directive: therefore at the end of its life cycle, it can’t be disposed like mixed municipal waste but it must be assigned to specialized collection structures, as prescribed by local regulations or by the dealer. The importer and the dealer are responsible for collection and disposal, both in case in which these are carried out directly and in case in which these are carried out through a collective collection system. Every explanation and every other information will be provided by the dealer/ technician where this product has been bought or by the local authority responsible for waste management.
Declaration of conformity
Declare under our sole responsibility that the product
Description - Pasubio
Year of construction 2014
It is conform to European standard; 2006/95/CE, 2004/108/CE; 305/2011
Z.F. SRL Unipersonale il 29/10/2014
Via Dino Fochesato,1 Zorzetto Graziano 36040 Meledo di Sarego Vicenza Italy
Tel +39 0444 820933
Loading...