Characteristics of the output circuit ............................................................. 30
TECHNICAL DATA .......................................................................................................................................... 31
GENERAL SYSTEM CHARACTERISTICS ........................................................... 31
Exclusion of liability and warranty .....................................................................................................145
Page 7
English
INTRODUCTION
Contents of this manual
In this manual the usage of the programmable safety system MSC and the related expansion modules is described.
It covers:
• System description
• Installation procedure
• Connections
• Signals
• Troubleshooting
• Usage of the configuration software
Important safety precautions
This safety warning symbol indicates a potential hazard for the safety of personnel.
Failure to follow instructions marked with this symbol may signify a serious hazard
for the personnel.
This symbol indicates an important instruction.
MSC achieves the following safety levels: SIL 3, SILCL 3, PL e, cat. 4, type 4 as per the
applicable standards. However the final SIL and PL safety categories for the application are dependent on the number of safety components, their parameters and the
connections made, as per the risk analysis.
Read the section "Applicable standards" carefully.
Undertake a comprehensive risk analysis to determine the corresponding safety level
for the specific application based on the applicable standards.
The programming/configuration of the MSC system is the sole responsibility of the
installer or the user.
The system must be programmed/configured as per the application-specific risk
analysis and all applicable standards.
After programming/configuration and installation of the MSC system and all related
devices, a complete application safety check must be undertaken (see "CHECKING the
system", page 75).
After adding new safety components, the complete system must be checked (see
"CHECKING the system", page 75).
EUCHNER is not liable for these processes or for the related risks.
To ensure the correct usage of the modules connected to the MSC system within the
stated application, reference should be made to the operating instructions/manuals
and the related product and/or application standards.
The ambient temperature in the installation location for the system must match the
operating temperature parameters that are stated on the product label and in the
specifications.
In the event of safety-related questions, if necessary contact the responsible safety
authorities in your country or the responsible specialist association.
Page 8
English
Abbreviations and symbols
EN IEC 61131-2
Programmable controllers – Part 2:
Equipment requirements and tests
EN ISO 13849-1
Safety of machinery.
Safety related parts of control systems. General principles for design
EN IEC 61496-1
Safety of machinery. Electro-sensitive protective equipment. Part 1: General
requirements and tests
EN IEC 61508-1
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: General requirements
EN IEC 61508-2
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Requirements for electrical/electronic/programmable electronic safety-related systems
EN IEC 61508-3
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Software requirements
EN IEC 61784-3
Industrial communication networks: Function safety fieldbuses
EN IEC 62061
Safety of machinery. Functional safety of safety-related electrical, electronic
and programmable electronic control systems
M-A1 = Memory card forMSC-CB (accessory)
MSCB = Proprietary bus for expansion modules
EUCHNER Safety Designer (SWSD) = MSC configuration software for Windows
OSSD = Output Signal Switching Device
MTTFd = Mean Time to Dangerous Failure
PL = Performance Level (acc. to EN ISO 13849-1)
PFHd = Probability of Dangerous Failure per Hour
SIL = Safety Integrity Level (acc. to EN 61508)
SILCL = Safety Integrity Level Claim Limit (acc. to EN 62061)
SW = Software
Applicable standards
MSC complies with the following European directives:
• 2006/42/EC "Machinery Directive"
• 2004/108/EC "EMC Directive"
• 2006/95/EC "Low Voltage Directive"
and corresponds to the following standards:
Table 1
Page 9
English
OVERVIEW
MSC is a modular safety system and comprises a base unit (MSC-CB), which can
be configured using the graphic user interface in EUCHNER Safety Designer, and
various expansion modules that can be connected to MSC-CB via the proprietary
MSCB bus.
The base unit MSC-CB, which can also be used as a standalone device, has 8 safety inputs and 2 separate, programmable dual-channel outputs.
The following expansion modules are available: FI8FO2 with inputs and outputs,
FI8, FM4, FI16, SPM0, SPM1 and SPM2 with only inputs, AC-FO2 and AC-FO4 with
only outputs as well as AZ-FO4 and AZ-FO4O8 with positively driven safety relays.
Expansion modules for connection to the commonest industrial fieldbus systems for
diagnostics are also available: CE-PR (PROFIBUS), CE-CO (CanOpen), CE-DN (DeviceNet), CE-EI (ETHERNET/IP), CE-EI2 (ETHERNET/IP-2PORT), CE-PN (Profinet), CE-EC (ETHERCAT), CE-MR (Modbus RTU), CE-MT (Modbus/TCP).
MSC makes it possible to monitor the following safety sensors and command
switches:
Optoelectronic sensors (safety light curtains, scanners, safety-light barriers), mechanical switches, safety mats, emergency stop buttons, two-hand controls, which
are all managed via one single, flexible device that can be expanded.
The system is only allowed to comprise a single base unit MSC-CB and a maximum
of 14 electronic expansion modules, of which not more than four are allowed to
be of the same type.
With 14 expansion modules the system can have up to 128 inputs, 16 dualchannel safety outputs and 28 status outputs. The communication between the
base unit (MASTER) and expansion modules (SLAVES) is via the MSCB 5-way bus
(proprietary bus from EUCHNER) that is on the rear side of every module.
In addition, 8 inputs and 16 outputs are available and can be controlled using
sensors (via the fieldbus).
Using the MSC expansion modules FI8, FI16 and FM4, the number of inputs in the
system can be increased such that more external devices can be connected. FM4
also provides 8 outputs of type OUT_TEST.
With the expansion modules AC-FO2 and AC-FO4, the system has 2 or 4 OSSD
pairs to control devices that are connected downstream of the MSC system.
FI8FO2 has 8 inputs and 2 OSSD outputs.
The expansion modules in the CE series make it possible to connect the commonest industrial fieldbus systems for diagnostics and data transmission. CE-EI, CE-EI2,CE-PN, CE-MT and CE-EC also have an Ethernet connection. CE-US makes it
possible to connect devices with a USB port.
CE-CI1, CE-CI2 are modules in the MSC family that make it possible to connect
MSC-CB to expansion modules further away (<50m). Two CE-CI modules are con-
nected at the required distance using a screened cable (can be ordered from
EUCHNER or as per the table for the technical cable data).
Page 10
English
The following can be monitored (up to PLe) using the expansion modules for
speed monitoring SPM0, SPM1 and SPM2:
Standstill, overspeed, speed range
Direction of motion, rotary motion/linear motion
Up to 4 speed limits can be defined for each logical output (axis).
Each module has two logical outputs that can be configured via EUCHNER Safety
Designer. In this way up to two independent axes can be monitored.
The safety modules AZ-FO4 and AZ-FO4O8 have 4 separate safety relay outputs
and the corresponding 4 inputs for the external device monitoring contacts (EDM).
Two settings are available for the outputs (configuration via the software
EUCHNER Safety Designer):
2 pairs of connection contacts (2 normally open contacts per output with 2
corresponding feedback loop inputs).
4 separate individual connection contacts (1 normally open contact per out-
put with 1 corresponding feedback loop input).
Only the module AZ-FO4O8 has 8 programmable signal outputs.
Using the software EUCHNER Safety Designer, complex logic can be configured using logical operators and safety functions such as muting, timers, counters etc.
defined.
All this is achieved using a straightforward, intuitive graphic user interface.
The configuration undertaken on the PC is transferred to the MSC-CB via a USB
connection. The file is saved in the MSC-CB and can also be saved on the proprietary M-A1 memory card (accessory). In this way it is possible to copy the configuration to a different MSC-CB module quickly.
The MSC system is certified for the highest safety level included in the applicable in-
• CD-ROM with the free-of-charge software EUCHNER Safety Designer, this multi-
lingual manual (PDF format) and other product literature
• Multilingual installation instructions
Notice: The plug connector for the rear of the MSCB and the M-A1 memory card can
be ordered separately as accessories.
The scope of delivery of the expansion modules includes:
• Multilingual installation instructions
• Rear MSCB plug connector.
Notice: The MSCB plug connector supplied and a further MSCB plug connector for
the connection to the MSC-CB are required to install an expansion module. This can
be ordered separately as an accessory.
Page 12
English
INSTALLATION
Mechanical mounting
Mount the modules of the MSC system on a 35-mm DIN rail as follows:
1. Connect together a number of rear 5-pin MSCB plug connectors to suit the
number of modules to be installed.
2. Mount the row of plug connectors assembled in this manner on the DIN rail
(first hook on at the top).
3. Mount modules on the rail and during this process place the contacts on
the base of the module over the related plug connector. Carefully push in
module until it noticeably engages.
4. To remove the module, the catch on the rear of the module must be pulled
down with the aid a screwdriver and the module lifted and pull off upward.
12a
2b34
Figure 1
Page 13
English
Calculation of the safety distance for an item of ESPE that is connect-
1
The modules of the MSC system are equipped with
terminal blocks for the electrical connections. Each
module can have 8, 16 or 24 terminals.
Each module also has an MSCB plug connector on the
rear (for the communication with the base unit and
the other expansion modules).
Tightening torque for terminals: 0.6–0.7 Nm
1
ed to the MSC system
All electro-sensitive protective equipment (ESPE) that is connected to the MSC system
must be arranged at a distance that is at least the minimum safety distance S such that
the hazardous point can only be reached after the machine's hazardous movement has
stopped.
The European standard:
- ISO 13855:2010 (EN 999:2008) Safety of machinery – Positioning of safeguards with
respect to the approach speeds of parts of the human body
contains formulas for the calculation of the correct safety distance.
Specific information in relation to the correct arrangement can be found in the instal-
lation instructions for each safety device.
It is to be noted that the total reaction time is dependent on:
the reaction time of MSC + the reaction time of ESPE + the reaction time of machine
(i.e. the time the machine requires to stop the hazardous movement from when the
stop signal is sent).
Electrical connections
Install safety modules in a housing that meets degree of protection IP54 as a minimum.
Connect module in electrically isolated state.
The power supply for the modules must be 24 VDC 20 % (PELV, as per EN 60204-1
(chapter 6.4)).
MSC is not allowed to be used to supply external devices.
The same ground connection (0 VDC) is to be used for all system components.
A procedure is described that permits system planners to determine the minimum safety distance between protective
equipment, in particular ESPE (e.g. light curtains), safety mats or pressure-sensitive floors and two-hand controls, and a
specific hazardous point. It contains a rule for the arrangement of protective equipment based on the approach speed and
time taken by the machine to stop, where corresponding extrapolation is possible, such that also interlocking devices without guard locking are also included.
It is recommended to use separate power supplies for the safety module and for
other electrically powered devices (electric motors, inverters, frequency converters)
or other sources of interference.
Cables for connections with a length of more than 50 m must have a cross-section
of at least 1 mm² (AWG16).
The connections in the MSC system are listed in the table below:
Page 15
English
USB connection
The MSC base unit MSC-CB has a USB
2.0 port for the connection to a PC on
which
the configuration software EUCHNER
Safety Designer is installed.
A USB cable of appropriate size is
available as an accessory.
Figure 2 – USB 2.0 port on the front
LABEL WITH TECHNICAL DATA
M-A1 LABEL
Figure 3 – M-A1
MSC configuration memory (M-A1)
An optional backup memory card (called
M-A1) can be installed in the MSC base
unit MSC-CB for backing up the software
configuration parameters.
Every new project that is transferred from
the PC to MSC-CB is written to the memory
card M-A1.
Always switch off MSC-CB before logging onto or logging off from the MA1.
Insert card in the slot on the rear of the
MSC-CB (direction as shown in Figure 3 –
M-A1).
MULTIPLE LOAD function
To configure several MSC-CB modules
without using a PC and the USB port, the
required configuration can be saved on
one memory card M-A1 and then downloaded from there to the MSC-CB modules
to be configured.
If the file on the M-A1 memory card is not identical to the file in the MSC-CB, the con-
figuration data in the MSC-CB are overwritten and therefore permanently deleted.
WARNING:ALL THE DATA THAT WERE IN THE MSC-CB WILL BE LOST.
Page 16
English
RESTORE function
If the module MSC-CB is faulty, it can be replaced with a new module. As the entire configuration is saved on the M-A1 memory card, it is only necessary to insert this card in the
new module and switch on the MSC system, the backed up configuration will then be
loaded immediately. In this way interruptions in operation can be reduced to a minimum.
FI8FO2
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND - Power supply 0 VDC
-
5
OSSD1_A
Output
Safety output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
8
OUT_STATUS1
Output
Programmable digital output
PNP active high
9
OSSD2_A
Output
Safety output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
12
OUT_STATUS2
Output
Programmable digital output
PNP active high
13
OUT_TEST1
Output
Output for short circuit detection
PNP active high
14
OUT_TEST2
Output
Output for short circuit detection
PNP active high
15
OUT_TEST3
Output
Output for short circuit detection
PNP active high
16
OUT_TEST4
Output
Output for short circuit detection
PNP active high
17
INPUT1
Input
Digital input 1
Input as per EN 61131-2
18
INPUT2
Input
Digital input 2
Input as per EN 61131-2
19
INPUT3
Input
Digital input 3
Input as per EN 61131-2
20
INPUT4
Input
Digital input 4
Input as per EN 61131-2
21
INPUT5
Input
Digital input 5
Input as per EN 61131-2
22
INPUT6
Input
Digital input 6
Input as per EN 61131-2
23
INPUT7
Input
Digital input 7
Input as per EN 61131-2
24
INPUT8
Input
Digital input 8
Input as per EN 61131-2
The LOAD and RESTORE functions can be deactivated using the software (see Figure 32).
The expansion modules must be assigned addresses during installation so they can
be used (see NODE_SEL).
Each time M-A1 is used, it is to be carefully checked whether the configuration selected
is the configuration prepared for this specific system. Undertake a complete function
check on the system comprising the MSC and all devices connected to it (see
CHECKING the system).
Table 2
Page 17
English
FI8
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC - Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND - Power supply 0 VDC
-
5
INPUT1
Input
Digital input 1
Input as per EN 61131-2
6
INPUT2
Input
Digital input 2
Input as per EN 61131-2
7
INPUT3
Input
Digital input 3
Input as per EN 61131-2
8
INPUT4
Input
Digital input 4
Input as per EN 61131-2
9
OUT_TEST1
Output
Output for short circuit detection
PNP active high
10
OUT_TEST2
Output
Output for short circuit detection
PNP active high
11
OUT_TEST3
Output
Output for short circuit detection
PNP active high
12
OUT_TEST4
Output
Output for short circuit detection
PNP active high
13
INPUT5
Input
Digital input 5
Input as per EN 61131-2
14
INPUT6
Input
Digital input 6
Input as per EN 61131-2
15
INPUT7
Input
Digital input 7
Input as per EN 61131-2
16
INPUT8
Input
Digital input 8
Input as per EN 61131-2
Table 3
FM4
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC - Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND - Power supply 0 VDC
-
5
INPUT1
Input
Digital input 1
Input as per EN 61131-2
6
INPUT2
Input
Digital input 2
Input as per EN 61131-2
7
INPUT3
Input
Digital input 3
Input as per EN 61131-2
8
INPUT4
Input
Digital input 4
Input as per EN 61131-2
9
OUT_TEST1
Output
Output for short circuit detection
PNP active high
10
OUT_TEST2
Output
Output for short circuit detection
PNP active high
11
OUT_TEST3
Output
Output for short circuit detection
PNP active high
12
OUT_TEST4
Output
Output for short circuit detection
PNP active high
13
INPUT5
Input
Digital input 5
Input as per EN 61131-2
14
INPUT6
Input
Digital input 6
Input as per EN 61131-2
15
INPUT7
Input
Digital input 7
Input as per EN 61131-2
16
INPUT8
Input
Digital input 8
Input as per EN 61131-2
17
OUT_TEST5
Output
Output for short circuit detection
PNP active high
18
OUT_TEST6
Output
Output for short circuit detection
PNP active high
19
OUT_TEST7
Output
Output for short circuit detection
PNP active high
20
OUT_TEST8
Output
Output for short circuit detection
PNP active high
21
INPUT9
Input
Digital input 9
Input as per EN 61131-2
22
INPUT10
Input
Digital input 10
Input as per EN 61131-2
23
INPUT11
Input
Digital input 11
Input as per EN 61131-2
24
INPUT12
Input
Digital input 12
Input as per EN 61131-2
Table 4
Page 18
English
FI16
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC - Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND - Power supply 0 VDC
-
5
INPUT1
Input
Digital input 1
Input as per EN 61131-2
6
INPUT2
Input
Digital input 2
Input as per EN 61131-2
7
INPUT3
Input
Digital input 3
Input as per EN 61131-2
8
INPUT4
Input
Digital input 4
Input as per EN 61131-2
9
OUT_TEST1
Output
Output for short circuit detection
PNP active high
10
OUT_TEST2
Output
Output for short circuit detection
PNP active high
11
OUT_TEST3
Output
Output for short circuit detection
PNP active high
12
OUT_TEST4
Output
Output for short circuit detection
PNP active high
13
INPUT5
Input
Digital input 5
Input as per EN 61131-2
14
INPUT6
Input
Digital input 6
Input as per EN 61131-2
15
INPUT7
Input
Digital input 7
Input as per EN 61131-2
16
INPUT8
Input
Digital input 8
Input as per EN 61131-2
17
INPUT9
Input
Digital input 9
Input as per EN 61131-2
18
INPUT10
Input
Digital input 10
Input as per EN 61131-2
19
INPUT11
Input
Digital input 11
Input as per EN 61131-2
20
INPUT12
Input
Digital input 12
Input as per EN 61131-2
21
INPUT13
Input
Digital input 13
Input as per EN 61131-2
22
INPUT14
Input
Digital input 14
Input as per EN 61131-2
23
INPUT15
Input
Digital input 15
Input as per EN 61131-2
24
INPUT16
Input
Digital input 16
Input as per EN 61131-2
Table 5
Page 19
English
AC-FO4
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND - Power supply 0 VDC
-
5
OSSD1_A
Output
Safety output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
8
OUT_STATUS1
Output
Programmable digital output
PNP active high
9
OSSD2_A
Output
Safety output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
12
OUT_STATUS2
Output
Programmable digital output
PNP active high
13
24 VDC
-
Power supply 24 VDC
24 VDC outputs,
power supply*
14
24 VDC
-
Power supply 24 VDC
-
15
GND - Power supply 0 VDC
0 VDC outputs*
16
GND - Power supply 0 VDC
-
17
OSSD4_A
Output
Safety output 4
PNP active high
18
OSSD4_B
Output
PNP active high
19
RESTART_FBK4
Input
Feedback loop/restart 4
Input as per EN 61131-2
20
OUT_STATUS4
Output
Programmable digital output
PNP active high
21
OSSD3_A
Output
Safety output 3
PNP active high
22
OSSD3_B
Output
PNP active high
23
RESTART_FBK3
Input
Feedback loop/restart 3
Input as per EN 61131-2
24
OUT_STATUS3
Output
Programmable digital output
PNP active high
Table 6
Page 20
English
AC-FO2
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND
-
Power supply 0 VDC
-
5
OSSD1_A
Output
Safety output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
8
OUT_STATUS1
Output
State of the outputs 1A/1B
PNP active high
9
OSSD2_A
Output
Safety output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
12
OUT_STATUS2
Output
State of the outputs 2A/2B
PNP active high
13
24 VDC
-
Power supply 24 VDC
24 VDC output, power supply*
14
not used - -
-
15
GND
-
Power supply 0 VDC
0 VDC output*
16
not used - -
-
Table 7
SPM0 – SPM1 – SPM2
TERMINAL
SIGNAL
TYPE
DESCRIPTION
ACTION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL0
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" as per EN 61131-2)
4
GND
-
Power supply 0 VDC
-
5
PROXI1_24V
Output
Connections for the
1st proximity switch
(see page 27)
Power supply 24 VDC to PROXI1
6
PROXI1_REF
Output
Power supply 0 VDC to PROXI1
7
PROXI1 IN1 (3 WIRES)
Input
PROXI1 NO contact
8
PROXI1 IN2 (4 WIRES)
Input
PROXI1 NC contact
9
PROXI2_24V
Output
Connections for the
2nd proximity switch
(see page 27)
Power supply 24 VDC to PROXI2
10
PROXI2_REF
Output
Power supply 0 VDC to PROXI2
11
PROXI2 IN1 (3 WIRES)
Input
PROXI2 NO contact
12
PROXI2 IN2 (4 WIRES)
Input
PROXI2 NC contact
13
not used
-
Not connected
-
14
not used - -
15
not used - -
16
not used - -
* This terminal must be connected to the power supply so that the module func-
tions correctly.
Table 8
Page 21
English
ENCODER CONNECTIONS WITH RJ45 PLUG CONNECTOR (SPM1, SPM2)
Pin
SPMTB
SPMH
SPMS
Twisted *
1
Input
n.c.
n.c.
n.c. 2 GND
GND
GND
3 n.c.
n.c.
n.c.
Twisted *
4 A A
A
5
/A
/A
/A
6 n.c.
n.c.
n.c.
Twisted *
7 B B
B
8
/B
/B
/B
Table 9
* If twisted-pair cables are used.
Figure 4 – Connection examples
Page 22
English
AZ-FO4
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24 VDC
-
Power supply 24 VDC
-
2
NODE_SEL1
Input
Node selection
Input ("type B" as per EN 61131-2)
3
NODE_SEL2
Input
Input ("type B" as per EN 61131-2)
4
0 VDC
-
Power supply 0 VDC
-
5
REST_FBK1
Input
Feedback loop/restart 1
Input (as per EN 61131-2)
6
REST_FBK2
Input
Feedback loop/restart 2
Input (as per EN 61131-2)
7
REST_FBK3
Input
Feedback loop/restart 3
Input (as per EN 61131-2)
8
REST_FBK4
Input
Feedback loop/restart 4
Input (as per EN 61131-2)
9
A_NO1
Output
Normally open contact
channel 1
10
B_NO1
Output
11
A_NO2
Output
Normally open contact
channel 2
12
B_NO2
Output
13
A_NO3
Output
Normally open contact
channel 3
14
B_NO3
Output
15
A_NO4
Output
Normally open contact
channel 4
16
B_NO4
Output
Table 10
Page 23
English
AZ-FO4O8
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24 VDC - Power supply 24 VDC
-
2
NODE_SEL1
Input
Node selection
Input ("type B" as per
EN 61131-2)
3
NODE_SEL2
Input
Input ("type B" as per
EN 61131-2)
4
0 VDC - Power supply 0 VDC
-
5
REST_FBK1
Input
Feedback loop/restart 1
Input (as per EN 61131-2)
6
REST_FBK2
Input
Feedback loop/restart 2
Input (as per EN 61131-2)
7
REST_FBK3
Input
Feedback loop/restart 3
Input (as per EN 61131-2)
8
REST_FBK4
Input
Feedback loop/restart 4
Input (as per EN 61131-2)
9
A_NO1
Output
Normally open contact channel 1
10
B_NO1
Output
11
A_NO2
Output
Normally open contact channel 2
12
B_NO2
Output
13
A_NO3
Output
Normally open contact channel 3
14
B_NO3
Output
15
A_NO4
Output
Normally open contact channel 4
16
B_NO4
Output
17
SYS_STATUS1
Output
Programmable digital output 1
PNP active high
18
SYS_STATUS2
Output
Programmable digital output 2
PNP active high
19
SYS_STATUS3
Output
Programmable digital output 3
PNP active high
20
SYS_STATUS4
Output
Programmable digital output 4
PNP active high
21
SYS_STATUS5
Output
Programmable digital output 5
PNP active high
22
SYS_STATUS6
Output
Programmable digital output 6
PNP active high
23
SYS_STATUS7
Output
Programmable digital output 7
PNP active high
24
SYS_STATUS8
Output
Programmable digital output 8
PNP active high
Table 11
Example for the connection of the MSC system to the machine control
Figure 5
Page 24
English
CHECK LIST AFTER INSTALLATION
With the MSC system, faults can be detected in the individual modules.
To ensure the trouble-free operation of the system, the following checks are to be undertaken during setup and at least once a year:
1. Undertake complete system CHECK (see "CHECKING the system")
2. Check whether all cables are inserted correctly and the terminal blocks are tightened
properly.
3. Check whether all LEDs (indicators) illuminate correctly.
4. Check whether all sensors connected to the MSC system are positioned correctly.
5. Check whether the MSC system is properly fastened to the DIN rail.
6. Check whether all external indicators (lamps) function correctly.
After installation, maintenance or changing the configuration, undertake system
CHECK as described in section "CHECKING the system" on page 75.
>
Page 25
English
FLOW CHART
Mechanical mounting
Electrical connections
between the MSC modules and
external sensors
Preparation of the diagram
Validation
software OK?
NO
YES
Download the
diagram to MSC-CB
Configuration check
(incl. complete system
CHECK
see page 66 „Project
validation“)
on MSC-CB OK?
NO
YES
Disconnect the connec-
tion via USB
Switch on the
system
Connection
via USB to MSC-CB
Page 26
English
SIGNALS
NODE_SEL1 (terminal 3)
NODE_SEL0 (terminal 2)
NODE 0
0 (or not connected)
0 (or not connected)
NODE 1
0 (or not connected)
24 VDC
NODE 2
24 VDC
0 (or not connected)
NODE 3
24 VDC
24 VDC
INPUTS
MASTER_ENABLE
The base unit MSC-CB has two inputs: MASTER_ENABLE1 and MASTER_ENABLE2.
These signals must both be set permanently to logic level 1 (24 VDC) so that the
MSC system functions correctly. If you need to deactivate the MSC system, these inputs can be set to logic level 0 (0 VDC).
NODE_SEL
The inputs NODE_SEL0 and NODE_SEL1 (on the expansion modules) are used to assign an
address to the expansion modules using the connections given in Table 12:
Table 12
Two modules of the same type are not allowed to be assigned the same address.
Page 27
English
Proximity switch input on speed monitoring modules SPM
Configuration with combined proximity switches on one axis (Figure 5)
The SPM module can be configured in the "Combined proximity switch" mode for a
measurement using two proximity switches on one axis.
The Performance Level PLe can be achieved under the following conditions:
The proximity switches must be mounted such that the signals produced overlap.
The proximity switches must be mounted such that at least one proximity switch is
always actuated (active).
Figure 6
Additional information:
Proximity switches with a PNP output must be used.
Proximity switches with a normally open output (NO, output active if switch actuat-
ed) must be used.
In the conditions stated above the DC is 90%
Both proximity switches must be of the same type with a MTTF > 70 years.
Page 28
English
RESTART_FBK
OPERATING
MODE
EDM
RESTART_FBK
AUTOMATIC
With
K1_K2 con-
trol
K2
K1
24V
ext_Restart_fbk
Without
K1_K2 con-
trol
24V
ext_Restart_fbk
MANUAL
With
K1_K2 con-
trol
K2
K1
24V
ext_Restart_fbk
Without
K1_K2 con-
trol
24V
ext_Restart_fbk
Using the RESTART_FBK signal input, MSC can monitor a feedback loop signal (External
Device Monitoring – EDM) from external contactors; both manual and automatic forms of
starting can be programmed (see list of the possible connections in Table 13).
If necessary, the response time of contactors must be monitored using an additional
device.
The command switch for starting (RESTART) must be installed outside the danger ar-
ea in a place from which there is a clear view of the danger area and the entire working area affected.
It must not be possible to actuate the command switch from inside the danger area.
Table 13
Page 29
English
OUTPUTS
The maximum number of inputs that can be controlled by
each OUT_TEST output:
The maximum permissible length of the cable on the
OUT_TEST output is 100 m.
OUT_STATUS
The OUT_STATUS signal is a programmable digital output for the indication of the state
of:
• An input
• An output
• A node on the logic diagram that has been designed with the aid of the software
EUCHNER Safety Designer.
OUT_TEST
The inputs and the cables can be monitored for short circuits or overload states using the
OUT_TEST signals (Figure 7).
Figure 7
OSSD (MSC-CB, FI8FO2)
The OSSD outputs (Output Signal Switching Device) are short-circuit proof, monitored for
cross circuit and supply:
• In the ON state: Uv -0.75 V – Uv (where Uv = 24 V ± 20 %)
• In the OFF state: 0–2 V eff.
The maximum load of 400 mA @ 24 V corresponds to a minimum ohmic load of 60 .
The maximum capacitive load is 0.82 F, the maximum inductive load 30 mH.
OSSD (AC-FO2, AC-FO4)
The OSSD outputs (Output Signal Switching Device) are short-circuit proof, monitored for
cross circuit and supply:
• In the ON state: Uv -0.75 V – Uv (where Uv = 24 V ± 20 %)
• In the OFF state: 0–2 V eff.
The maximum load of 400 mA @ 24 V corresponds to a minimum ohmic load of 60 .
The maximum capacitive load is 0.82 F, the maximum inductive load 30 mH.
It is not allowed to connect external devices to the outputs, except if this arrange-
ment is foreseen in the configuration undertaken in the software EUCHNER Safety
Designer.
Each OSSD output can be configured as shown in Table 14:
Page 30
English
Automatic
The output is only activated, as per the configuration defined by EUCHNER Safety Designer, if 24 VDC are applied to the related input RESTART_FBK.
Manual
The output is only activated, as per the configuration defined by EUCHNER Safety Designer,
if there is the logical transition 0-->1 on related input RESTART_FBK.
Monitored
The output is only activated, as per the configuration defined by EUCHNER Safety Designer,
if there is the logical transition 0-->1-->0 on related input RESTART_FBK.
Table 14
Excitation voltage
17–31 VDC
Switching voltage, min.,
10 VDC
Switching current min.
20 mA
Switching voltage max. (DC)
250 VDC
Switching voltage max. (AC)
400 VAC
Switching current, max.
6 A
Response time
12 ms
Mechanical life contacts
> 20 x 106
SAFETY RELAY (AZ-FO4/AZ-FO4O8)
Characteristics of the output circuit
The modules AZ-FO4/AZ-FO4O8 have safety relays with positively driven contacts with
1 normally open contact and 1 normally closed feedback loop contact. The modules
AZ-FO4/AZ-FO4O8 contain 4 safety relays.
Table 15
To ensure correct isolation and to prevent the risk of premature aging or damage to
the relay, each output cable is to be protected using a 4 A quick-blow fuse. In addition, the load characteristics must correspond to the information in Table 15.
Page 31
English
TECHNICAL DATA
Parameter
Value
Standard
PFHd
See table with technical
data for the related module
EN IEC 61508:2010
SFF
99.8%
HFT
1
Safety standard
Type B
SILCL
3
EN IEC 62061:2005
Type
4
EN IEC 61496-1:2013
PL
e
EN ISO 13849-1
EN IEC 62061:2005
DC
avg
High
MTTFd (years)
30 ÷ 100
Category
4
Device mechanical life
20 years
Degree of contamination
2
GENERAL SYSTEM CHARACTERISTICS
Safety-related parameters
Page 32
English
General data
Number of inputs max.
128
Number of outputs max.
16
Number of expansion modules max.
14
Number of expansion modules of the same type max.
4
Rated voltage
24 VDC 20 %/supply class II (LVLE)
Overvoltage category
II
Digital INPUTS
PNP active high (EN 61131-2)
OSSD (MSC-CB, FI8FO2, AC-FO2, AC-FO4)
PNP active high – 400 mA @ 24 VDC max. (per OSSD)
Digital OUTPUTS
PNP active high – 100mA @ 24 VDC max.
Response time (ms)
This response time is dependent on the following parameters:
1) Number of expansion modules installed
2) Number of operators
3) Number of OSSD outputs
The correct response time is calculated by the software
EUCHNER Safety Designer (see project report).
Fault reaction time (ms)
The fault reaction time corresponds to the reaction time,
except on SPM modules with an Encoder/proximity switch
interface. In this case the fault reaction time is 2 s.
= max. filter time related to the settings on the project inputs (see section
"INPUTS").
Housing
Page 33
English
MSC-CB
PFHd (EN IEC 61508:2010)
6.06 E-9
Rated voltage
24 VDC 20 %
Power dissipation
3 W max.
Module enable (no./description)
2/PNP active high "type B" as per EN 61131-2
Digital INPUTS (no./description)
8/PNP active high as per EN 61131-2
INPUT FBK/RESTART (no./description)
2/EDM control system/automatic or manual operation possible
using RESTART pushbutton
Test OUTPUT (no./description)
4/For checking for short circuits, overload states
Digital OUTPUTS (no./description)
2/Programmable – PNP active high
OSSD (no./description)
2 pairs/Output signal switching devices – PNP active high
400 mA @ 24 VDC max.
SLOT for M-A1
Available
Connection to PC
USB 2.0 (Hi Speed) – cable length max.: 3 m
Connection to expansion module
Via proprietary 5-way bus MSCB from EUCHNER
PFHd (EN IEC 61508:2010)
5.72 E-9
Rated voltage
24 VDC 20 %
Power dissipation
3 W max.
Digital INPUTS (no./description)
8/PNP active high as per EN 61131-2
Test OUTPUT (no./description)
8/For checking for short circuits, overload states
Digital OUTPUTS (no./description)
2/Programmable – PNP active high
OSSD (no./description)
2 pairs/Static safety outputs:
PNP active high - 400 mA @ 24 VDC max.
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
FI8FO2
Page 34
English
FI8/FI16
Model
FI8
FI16
PFHd (EN IEC 61508:2010)
4.45 E-9
4.94 E-9
Rated voltage
24 VDC 20 %
Power dissipation
3 W max.
Digital INPUTS (no./description)
8
16
PNP active high as per EN 61131-2
Test OUTPUT (no./description)
4/For checking for short circuits, overload states
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
PFHd (EN IEC 61508:2010)
5.56 E-9
Rated voltage
24 VDC 20 %
Power dissipation
3 W max.
Digital INPUTS (no./description)
12
PNP active high as per EN 61131-2
Test OUTPUT (no./description)
8/For checking for short circuits, overload states
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
Model
AC-FO2
AC-FO4
PFHd (EN IEC 61508:2010)
4.09 E-9
5.84 E-9
Rated voltage
24 VDC 20 %
Power dissipation
3 W max.
Digital OUTPUTS (no./description)
2 4 Programmable – PNP active high
OSSD (no./description)
2
4
Safe switch outputs: PNP active high – 400 mA @ 24 VDC max.
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
FM4
AC-FO2/AC-FO4
Page 35
English
AZ-FO4/AZ-FO4O8
Model
AZ-FO4
AZ-FO4O8
PFH
(EN IEC 61508:2010)
2.9 E-9
2.94 E-9
Rated voltage
24 VDC ± 20 %
Power dissipation max.
3 W max.
Switching voltage
240 VAC
Switching current
6 A max.
Normally open contacts
4
INPUT FBK/RESTART (no./description)
4/EDM control/automatic or manual operation possible using
RESTART pushbutton
Digital OUTPUT (no./description)
-
8/Programmable output
PNP active high
Response time
12 ms
Mechanical life contacts
> 40 x 106
Connection
Terminal blocks
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
Page 36
English
SPM0/SPM1/SPM2
State
Overspeed
Standstill
Speed
range
Safe state
Overspeed
No standstill
Out of range
Model
SPM0
SPM1
SPM2
PFH 5.98 E-9
-
-
PFH
(TTL/B)
-
7.82 E-9 (SPM1TB)
9.66 E-9 (SPM2TB)
PFH
(sin/cos)
-
7.94 E-9 (SPM1S)
9.89 E-9 (SPM2S)
PFH
(HTL24)
-
6.70 E-9 (SPM1H)
7.42 E-9 (SPM2H)
Rated voltage
24 VDC ± 20 %
Power dissipation max.
3 W
Encoder interface
-
TTL (models SPM1TB/SPM2TB)
HTL (models PM1H/SPM2H)
sin/cos (models SPM1S/SPM2S)
Encoder connections
-
RJ45
Encoder input signals electrically isolated as per EN 618005
Rated insulation voltage 250 V
Over voltage category II
Rated impulse withstand voltage 4.00 kV
Number of Encoders max.
-
1
2
Encoder frequency max.
-
500 kHz (HTL: 300 kHz)
Configurable Encoder limits
-
1 Hz … 450 kHz
Proximity switch type
PNP/NPN – 3/4-wire
Proximity switch connections
Plug-in terminals
Configurable
limit ranges
1 Hz … 4 kHz
Number of proximity switches
max.
2
Frequency max. proximity
switch
5 kHz
Max. number of axes
2
Frequency spacing standstill/overspeed
> 10 Hz
Spacing thresholds
> 5 %
Connection to MSC-CB
Via proprietary 5-way bus MSCB from EUCHNER
Page 37
English
MECHANICAL DIMENSIONS
114.5 mm
108 mm
22.5 mm99 mm
Figure 8
Page 38
English
SIGNALS
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
COM
ENA
IN1–8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
BLUE
YELLOW
RED/GREEN
YELLOW
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
ON
Red
ON
ON
M-A1 detected
OFF
OFF
OFF
ON
(max. 1 s)
ON
(max. 1s)
OFF
Red
OFF
OFF
Writing/loading the diagram
to/from M-A1
OFF
OFF
OFF
Flashes 5
times
Flashes 5
times
OFF
Red
OFF
OFF
SWSD is requesting connection: no
internal configuration
OFF
OFF
OFF
Flashing
slowly
OFF
OFF
Red
OFF
OFF
SWSD is requesting connection:
(expansion module or node number not correct) (see System layout)
OFF
OFF
OFF
Flashing
quickly
OFF
OFF
Red
OFF
OFF
SWSD is requesting connection:
(expansion module missing or not
ready), (see System layout)
Flashing
quickly
OFF
OFF
Flashing
quickly
OFF
OFF
Red
OFF
OFF
SWSD connected, MSC-CB stopped
OFF
OFF
OFF
ON
OFF
OFF
Red
OFF
OFF
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
COM
IN1–8
ENA
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
BLUE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
ON
OFF
OFF
Operation
OK
ON = MSC-CB
connected to PC
OFF = Other
INPUT state
ON
MASTER_ENABLE1 and
MASTER_ENABLE2
active
OFF
other
RED
if output OFF
GREEN
if output ON
ON
waiting for
RESTART
Flashing
NO feedback
loop
OUTPUT
state
EXTERNAL FAULT
DETECTED
ON
OFF
ON
erroneous
external
connection
detected
ON = MSC-CB
connected to PC
OFF = Other
Only the number
for the INPUT with
the erroneous
connection flash-
es
Figure 9 – MSC-
CB
Base unit MSC-CB (Figure 9)
Table 16 – Start indication
Table 17 – Dynamic indication
Page 39
English
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
Red
ON
ON
SIGNIFICAN
CE
LED
RUN
IN FAIL
EXT FAIL
IN1–8
SEL
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
YELLOW
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting
for the first message from
the base unit
OFF
OFF
INPUT state
Indicates the sig-
nal table
NODE_SEL0/1
RED
if output OFF
GREEN
if output ON
ON
waiting for
RESTART
Flashing
NO feed-
back loop
OUTPUT
state
FLASHING
if no INPUT or OUTPUT is
requested by the configuration
ON
erroneous external connec-
tion detected
Only the number for
the INPUT with the er-
roneous connection
flashes
ON
if INPUT or OUTPUT is requested by the configuration
Figure 10 –
FI8FO2
FI8FO2 (Figure 10)
Table 18 – Start indication
Table 19 – Dynamic indication
Page 40
English
FI8 (Figure 11)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–8
GREEN
RED
RED
ORANGE
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–8
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting for the first message from the base unit
OFF
OFF
Indicates the signal
table NODE_SEL0/1
INPUT state
FLASHING
if no INPUT or OUTPUT is requested by
the configuration
ON
erroneous external
connection detected
Only the number for the INPUT
with the erroneous connection
flashes
ON
if INPUT or OUTPUT is requested by the
configuration
Figure 11 –
FI8
Table 20 – Start indication
Table 21 – Dynamic indication
Page 41
English
FM4 (Figure 12)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–12
GREEN
RED
RED
ORANGE
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–12
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting for the first message from the base unit
OFF
OFF
Indicates the signal
table NODE_SEL0/1
INPUT state
FLASHING
if no INPUT or OUTPUT is requested by
the configuration
ON
erroneous external
connection detected
Only the number for the INPUT
with the erroneous connection
flashes
ON
if INPUT or OUTPUT is requested by the
configuration
Figure 12 –
FM4
Table 22 – Start indication
Table 23 – Dynamic indication
Page 42
English
FI16 (Figure 13)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–16
GREEN
RED
RED
ORANGE
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1–16
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting for the first message from the base unit
OFF
OFF
Indicates the signal
table NODE_SEL0/1
INPUT state
FLASHING
if no INPUT or OUTPUT is requested by
the configuration
ON
erroneous external
connection detected
Only the number for the INPUT
with the erroneous connection
flashes
ON
if INPUT or OUTPUT is requested by the
configuration
Figure 13 –
FI16
Table 24 – Start indication
Table 25 – Dynamic indication
Page 43
English
AC-FO2 (Figure 14)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
Red
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting for the first
message from the base unit
OFF
Opera-
tion OK
OFF
Opera-
tion OK
Indicates the signal
table NODE_SEL0/1
RED
if output OFF
ON
waiting for
RESTART
OUTPUT
state
FLASHING
if no INPUT or OUTPUT is requested
by the configuration
GREEN
if output ON
Flashing
NO feedback
loop
ON
if INPUT or OUTPUT is requested by
the configuration
Figure 14 –
AC-FO2
Table 26 – Start indication
Table 27 – Dynamic indication
Page 44
English
AC-FO4 (Figure 15)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
Red
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the module is waiting for the first
message from the base unit
OFF
Opera-
tion OK
OFF
Opera-
tion OK
Indicates the signal
table NODE_SEL0/1
RED
if output OFF
ON
waiting for
RESTART
OUTPUT
state
FLASHING
if no INPUT or OUTPUT is requested
by the configuration
GREEN
if output ON
Flashing
NO feedback
loop
ON
if INPUT or OUTPUT is requested by
the configuration
Figure 15 –
AC-FO4
Table 28 – Start indication
Table 29 – Dynamic indication
Page 45
English
AZ-FO4 (Figure 16)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
Red
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
NORMAL OPERATION
OFF
if the module is waiting
for the first message
from the base unit
FLASHING
if no INPUT or OUTPUT
is requested by the configuration
ON
if INPUT or OUTPUT is
requested by the configuration
OFF
operation OK
OFF
operation OK
Indicates the sig-
nal table
NODE_SEL0/1
RED
if contact open
ON
waiting for
RESTART
GREEN
if contact closed
FLASHING
fault feedback loop
external switchgear
Figure 16 –
AZ-FO4
Table 30 – Start indication
Table 31 – Dynamic indication
Page 46
English
AZ-FO4O8 (Figure 17)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Switch on – initial
CHECK
ON
ON
ON
ON
Red
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the module is
waiting for the first
message from the
base unit
FLASHING
if no INPUT or
OUTPUT is requested by the configuration
ON
if INPUT or OUTPUT
is requested by the
configuration
OFF
operation OK
OFF
operation OK
Indicates the sig-
nal table
NODE_SEL0/1
RED
if contact open
ON
waiting for
RESTART
OUTPUT state
GREEN
if contact closed
FLASHING
fault feedback
loop external
switchgear
Figure 17 –
AZ-FO4O8
Table 32 – Start indication
Table 33 – Dynamic indication
Page 47
English
SPM0, SPM1, SPM2 (Figure 18)
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Switch on – initial CHECK
ON
ON
ON
ON
ON
ON
ON
SIGNIFICANCE
LED
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the module is waiting for the first message from the base
unit
FLASHING
if no INPUT or
OUTPUT is requested
by the configuration
ON
if INPUT or OUTPUT
is requested by the
configuration
OFF
operation OK
OFF
operation OK
Indicates the
signal table
NODE_SEL0/1
ON
Encoder con-
nected and oper-
ational
ON
proximity switch
connected and
operational
OFF
axis in normal
speed range
ON
axis at standstill
FLASHING
axis at elevated
speed
Figure 18 – SPM1, SPM2
Table 34 – Start indication
Table 35 – Dynamic indication
* IF SPM0 MODULE NOT FITTED
Page 48
English
TROUBLESHOOTING
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
COM
IN1–8
ENA
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
BLUE
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
Flashes
2 or 3 times
OFF
OFF
OFF
OFF
Red
OFF
OFF
Send module to
EUCHNER for repair
OSSD
output error
OFF
Flashes 4
times
OFF
OFF
OFF
OFF
Flashes 4 times
(only the LED corre-
sponding to the
output in the
ERROR mode)
OFF
OFF
• Check OSSD1/2 con-
nections
• If the problem per-
sists, send MSC-CB to
EUCHNER for repair.
Error during
communication
with expansion
module
OFF
Flashes 5
times
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart system.
• If the problem per-
sists, send MSC-CB to
EUCHNER for repair.
Error in
expansion
module
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart system.
• Check which module
is in the ERROR mode.
Error M-A1
OFF
Flashes 6
times
OFF
Flashes 6
times
OFF
OFF
OFF
OFF
OFF
Replace M-A1
Figure 19 –
MSC-CB
Base unit MSC-CB (Figure 19)
Table 36 – Troubleshooting MSC-CB
Page 49
English
FI8FO2 (Figure 20)
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
SEL
IN1–8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
Flashes
2 or 3
times
OFF
Indicates the
physical address of the
module
OFF
Red
OFF
OFF
Send module to
EUCHNER for repair
Compatibility error
OFF
Flashes
5 times
OFF
Flashes 5
times
Flashes 5 times
Flashes 5
times
Flashes 5
times
• Firmware version
not compatible with
MSC-CB. Send to
EUCHNER for firmware upgrade.
OSSD output error
OFF
Flashes
4 times
OFF
OFF
Flashes 4 times
(only the LED corre-
sponding to the out-
put in the ERROR
mode)
OFF
OFF
• Check OSSD1/2
connections
• If the problem per-
sists, send FI8FO2
to EUCHNER for repair.
Error during communication with base
unit
OFF
Flashes
5 times
OFF
OFF
OFF
OFF
OFF
• Restart system.
• If the problem per-
sists, send FI8FO2
to EUCHNER for repair.
Error in another
expansion module or
MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
OFF
• Restart system.
• Check which module
is in the ERROR
mode.
Expansion module of
the same type with
the same address detected
OFF
Flashes
5 times
Flashes
5 times
OFF
OFF
OFF
OFF
• Change address of
the module (see
NODE_SEL)
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3
times
OFF
OFF
OFF
OFF
• Send to EUCHNER
for repair
Figure 20 –
FI8FO2
Table 37 – Troubleshooting FI8FO2
Page 50
English
FI8 (Figure 21)
SIGNIFICANCE
LED
RECTIFICATION MEASURE
RUN
IN FAIL
EXT FAIL
SEL
IN1–8
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
Flashes
2 or 3
times
OFF
Indicates the
physical address
of the module
OFF
Send module to EUCHNER
for repair
Compatibility error
OFF
Flashes
5
times
OFF
Flashes 5
times
• Firmware version not
compatible with MSC-CB.
Send to EUCHNER for
firmware upgrade.
Error during communication with base unit
OFF
Flashes
5
times
OFF
OFF
• Restart system.
• If the problem persists,
send FI8 to EUCHNER for
repair.
Error in another expansion module or MSC-CB
OFF
ON
OFF
OFF
• Restart system.
• Check which module is
in the ERROR mode.
Expansion module of
the same type with the
same address detected
OFF
Flashes
5
times
Flashes
5 times
OFF
• Change address of the
module (see
NODE_SEL)
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3 times
OFF
• Send to EUCHNER for
repair
Figure 21 –
FI8
Table 38 – Troubleshooting FI8
Page 51
English
FM4 (Figure 22)
SIGNIFICANCE
LED
RECTIFICATION MEASURE
RUN
IN FAIL
EXT FAIL
SEL
IN1–12
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
Flashes
2 or 3
times
OFF
Indicates the
physical address
of the module
OFF
Send module to EUCHNER
for repair
Compatibility error
OFF
Flashes
5
times
OFF
Flashes 5
times
• Firmware version not
compatible with MSC-CB.
Send to EUCHNER for
firmware upgrade.
Error during communication with base unit
OFF
Flashes
5
times
OFF
OFF
• Restart system.
• If the problem persists,
send FM4 to EUCHNER
for repair.
Error in another expansion module or MSC-CB
OFF
ON
OFF
OFF
• Restart system.
• Check which module is
in the ERROR mode.
Expansion module of
the same type with the
same address detected
OFF
Flashes
5
times
Flashes
5 times
OFF
• Change address of the
module (see
NODE_SEL)
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3 times
OFF
• Send to EUCHNER for
repair
Figure 22 – FM4
Table 39 – Troubleshooting FM4
Page 52
English
FI16 (Figure 23 – FI16)
SIGNIFICANCE
}
RECTIFICATION MEASURE
RUN
IN FAIL
EXT FAIL
SEL
IN1–16
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
Flashes
2 or 3
times
OFF
Indicates the
physical address
of the module
OFF
Send module to EUCHNER
for repair
Compatibility error
OFF
Flashes
5
times
OFF
Flashes 5
times
• Firmware version not
compatible with MSC-CB.
Send to EUCHNER for
firmware upgrade.
Error during communication with base unit
OFF
Flashes
5
times
OFF
OFF
• Restart system.
• If the problem persists,
send FI16 to EUCHNER
for repair.
Error in another
expansion module
or MSC-CB
OFF
ON
OFF
OFF
• Restart system.
• Check which module is
in the ERROR mode.
Expansion module of
the same type with the
same address detected
OFF
Flashes
5
times
Flashes
5 times
OFF
• Change address of the
module (see
NODE_SEL)
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3 times
OFF
• Send to EUCHNER for
repair
Figure 23 – FI16
Table 40 – Troubleshooting FI16
Page 53
English
AC-FO2/AC-FO4 (Figure 24)
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
Flashes
2 / 3
times
OFF
Indicates the
physical address of the
module
Red
OFF
OFF
Send module to EUCHNER
for repair
Compatibility error
OFF
Flashes
5 times
OFF
Flashes 5 times
Flashes 5
times
Flashes 5
times
• Firmware version not
compatible with MSC-CB.
Send to EUCHNER for
firmware upgrade.
OSSD output error
OFF
Flashes
4 times
OFF
Flashes 4 times
(only the LED corre-
sponding to the out-
put in the ERROR
mode)
OFF
OFF
• Check OSSD1/2 connec-
tions
• If the problem persists,
send AC-FO2/AC-FO4 to
EUCHNER for repair.
Error during communication with base
unit
OFF
Flashes
5 times
OFF
OFF
OFF
OFF
• Restart system.
• If the problem persists,
send AC-FO2/AC-FO4 to
EUCHNER for repair.
Error in another expansion module or
MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
• Restart system.
• Check which module is in
the ERROR mode.
Expansion module of
the same type with
the same address detected
OFF
Flashes
5 times
Flashes
5 times
OFF
OFF
OFF
• Change address of the
module (see NODE_SEL)
Power supply failed on
OSSD3/4 (only AC-FO4)
ON
OFF
ON
Red flashing
Flashing
OUTPUT
state
• Connect terminal 13 and
14 to power supply
STATUS output overload or short circuit
OFF
OFF
ON OSSD state
CLEAR
state
Flashing
• Check STATUS cable
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes 3
times
OFF
OFF
OFF
• Send AC-FO2/AC-FO4 to
EUCHNER for repair
Figure 24 –
AC-FO2/AC-FO4
Table 41 – Troubleshooting AC-FO2/AC-FO4
Page 54
English
AZ-FO4 (Figure 25)
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
Internal fault
OFF
Flashes 2/3
times
OFF
Indicates the
physical address
of the module
Red
OFF
• Send module to
EUCHNER for repair
Compatibility error
OFF
Flashes 5
times
OFF
Flashes 5 times
Flashes 5
times
• Firmware version not
compatible with MSCCB. Send to EUCHNER
for firmware upgrade.
Relay output error
OFF
Flashes 4
times
OFF
Flashes 4 times
(only the LED corre-
sponding to the output
in the ERROR mode)
OFF
• If the problem persists,
send module to
EUCHNER for repair.
Error during communication with base
unit
OFF
Flashes 5
times
OFF
OFF
OFF
• Restart system.
• If the problem persists,
send module to
EUCHNER for repair.
Error in another
expansion module or
MSC-CB
OFF
ON
OFF
OFF
OFF
• Restart system.
• Check which module is
in the ERROR mode.
Expansion module of
the same type with
the same address detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
• Change address of the
module (see
NODE_SEL)
External feedback
loop error relay category 4
ON
OFF
Flashes 4
times
Flashes 4 times
(only the LED corre-
sponding to the output
in the ERROR mode)
• Check terminal 5, 6, 7,
8.
Internal node
detection error
OFF
Flashes 3
times
OFF
Flashes 3 times
OFF
OFF
• Send module to
EUCHNER for repair
Figure 25 –
AZ-FO4
Table 42 – Troubleshooting AZ-FO4
Page 55
English
AZ-FO4O8 (Figure 26)
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
SEL0/1
RELAY1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Internal fault
OFF
Flashes
2/3 times
OFF
Indicates the
physical ad-
dress of the
module
Red
OFF
• Send module to
EUCHNER for repair
Compatibility
error
OFF
Flashes 5
times
OFF
Flashes 5 times
Flashes 5
times
Flashes 5 times
• Firmware version not
compatible with
MSC-CB. Send to
EUCHNER for firmware upgrade.
Relay output
error
OFF
Flashes 4
times
OFF
Flashes 4 times
(only the LED corre-
sponding to the output
in the ERROR mode)
OFF
OFF
• If the problem per-
sists, send module to
EUCHNER for repair.
Error during
communication
with base unit
OFF
Flashes 5
times
OFF
OFF
OFF
OFF
• Restart system.
• If the problem per-
sists, send module to
EUCHNER for repair.
Error in another
expansion module
or MSC-CB
OFF
ON
OFF
OFF
OFF
OFF
• Restart system.
• Check which module
is in the ERROR
mode.
Expansion module
of the same type
with the same address detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
• Change address of the
module
(see NODE_SEL)
External feedback
loop error relay
category 4
ON
OFF
Flashes 4
times
Flashes 4 times
(only the LED corresponding to the
output in the ERROR mode)
OFF
• Check terminal 5, 6,
7, 8.
Internal node
detection error
OFF
Flashes 3
times
OFF
Flashes 3
times
OFF
OFF
OFF
• Send module to
EUCHNER for repair
Short circuit or
overload detected
OFF
OFF
ON
OFF
OSSD state
CLEAR
state
Flashing
• Check output con-
nections
Figure 26 –
AZ-FO4O8
Table 43 – Troubleshooting AZ-FO4O8
Page 56
English
SPM0, SPM1, SPM2 (Figure 27)
SIGNIFICANCE
LED
RECTIFICATION
MEASURE
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Internal fault
OFF
Flashes 2
or 3 times
OFF
Indicates the
physical address of the
module
OFF
OFF
OFF
• Send module to
EUCHNER for repair
Compatibility error
OFF
Flashes 5
times
OFF
Flashes 5
times
Flashes 5
times
Flashes 5
times
• Firmware version not
compatible with
MSC-CB. Send to
EUCHNER for firmware upgrade.
Internal Encoder
fault
OFF
Flashes
3 times
OFF
Flashes
3 times
OFF
OFF
• Replace Encoder
• Send to EUCHNER for
repair
Internal proximity
switch fault
Flashes
3 times
OFF
Flashes
3 times
• Replace proximity
switch
• Send to EUCHNER for
repair
Internal node
detection error
OFF
Flashes
3 times
OFF
Flashes
3 times
OFF
OFF
OFF
• Send module to
EUCHNER for repair
Expansion module
of the same type
with the same address detected
OFF
Flashes 5
times
Flashes 5
times
OFF
OFF
OFF
• Change address of
the module
(see NODE_SEL)
Encoder not connected, but requested by configuration
OFF
OFF
Flashes
3 times **
Flashes
3 times **
OFF
OFF
• Check connection
and power supply for
the Encoder/proximity switch
• Check input fre-
quency (in range)
Proximity switch not
connected, but requested by configuration
OFF
OFF
Flashes
3 times **
OFF
Flashes
3 times **
OFF
Figure 27 – SPM1, SPM2
Table 44 – Troubleshooting SPM1/SPM2
* IF SPM0 MODULE NOT FITTED
** IF ERROR ON A SINGLE CHANNEL, THE FOLLOWING ERROR INFORMATION IS INDICATED IN SUCCESSION:
FIRST THE ERROR, THEN THE ERRONEOUS CHANNEL.
Page 57
English
SOFTWARE EUCHNER SAFETY DESIGNER
Using the application software EUCHNER Safety Designer (SWSD), you can design logic
for the safety components connected to the control system and the MSC-CB expansions.
The MSC system and the related expansion modules monitor and control the safety components connected.
EUCHNER Safety Designer is based on a graphical user interface using which the connections between the various components can be defined. It is described in the following:
Installing the software
PC HARDWARE – requirements
• RAM: 256 MB
(adequate for running Windows XP SP3 + Framework 4.0)
• Hard disk: > 500 MB free storage capacity
• USB port: 1.1, 2.0 or 3.0
• CD-ROM drive
PC SOFTWARE – requirements
- Windows XP with Service Pack 3 installed (or higher).
Microsoft Framework 4.0 (or higher) must be installed on the PC
EUCHNER Safety Designer is installed as follows:
• Insert installation CD.
• Wait until the software installation program is started by the AutoRun function.
Alternatively change to the folder D:/.
• Double-click the file SetupDesigner.exe.
After the installation is complete, a window appears in which the user is prompted to
close the installation program.
Page 58
English
General
If EUCHNER Safety Designer has been installed correctly, an icon is added to the desk-
top.
To start the program: double-click this icon. =>
The following start screen is displayed:
Figure 28
You can now start to create projects.
Page 59
English
Default toolbar
The default toolbar is shown in Figure 29. The significance of the buttons is given in the
following:
Figure 29
1 -> CREATE NEW PROJECT
2 -> EDIT CONFIGURATION (layout of the various modules)
The menu bar shown below is also available as an alternative.
Figure 30
Creating a new project (configuring MSC system)
To start a new project, select the button on the default toolbar. The window for the
project information is displayed (Figure 31).
Figure 31
Then a window appears in EUCHNER Safety Designer in which only the module MSC-CB is
shown.
Using the list boxes at the top of the screen (select expansion module) you can add the
modules necessary for the system. The node can be selected using the list box at the bottom of the screen.
SELECT EXPANSION MODULE (to add to the configuration)
SELECT NODE (from 0 to 3) Select to deactivate updating from M-A1
Figure 32
Page 61
English
EDITING CONFIGURATION (layout of the various modules)
You can edit the system layout by selecting the button.
The Configuration window is displayed again (Figure 29).
Editing user parameters
You can edit the project information by selecting the button.
The dialog box for entering the project information appears (Figure 33). It is not necessary to log off from MSC for this action. As a rule this feature is used when a new user
needs to prepare a new project (also on the usage of a project prepared previously).
Figure 33
Page 62
English
Tool windows for ITEMS, OPERATORS, CONFIGURATION
1
2
3
Four large tool windows are displayed on the left and right side of the main window (see Figure 34):
Figure 34
4
1 > "ITEMS" tool window
This window contains the various function blocks that make up the project.
These blocks are divided into four different types:
- Input- Speed monitoring
- Output- Comments
2 > "OPERATOR" TOOL WINDOW
This window contains the various function blocks for linking the objects in point
1. These blocks are divided into seven different types:
- Logic- Timer
- Muting- Guard lock
- Memories- Miscellaneous
- Counters
3 > "CONFIGURATION" TOOL WINDOW
This window contains the description of the project layout.
4 > "VISUAL CONFIGURATION" TOOL WINDOW
This window contains the graphic illustration of the project layout.
Page 63
English
Preparing the diagram
After the selection of the system layout, you can configure the project.
The logic diagram is prepared with the aid of the DRAG & DROP function:
• Select the objects required from the windows described above (the individual objects
are described in more detail in the following) and drag to the design workspace.
• After the selection of an object, the PROPERTY window is activated where you must
complete the fields as necessary.
• You can set a specific numeric value on a slider (e.g. Filter) using the left and right ar-
row keys on the keyboard, or by clicking on the ends of the slider.
• Objects can be linked together by selecting the required pin using the mouse and then
dropping the link on the pin to be connected using Drag & Drop.
• If the PAN function (panning workspace in the window) is needed, select object to be
panned and pan using the arrow keys on the keyboard.
• You can make connections between elements a long way apart using the "Interpage
In/Out" in "Operator/Miscellaneous" component. The "Interpage Out" element must be
assigned a name that corresponds to the related "Interpage In" element to establish the
required connection.
Figure 35
• If an object needs to be duplicated, first you must select it and then you can copy and
paste it by pressing CTRL+C/CTRL+V on the keyboard.
• An object or a link is deleted by selecting the object or the link and then pressing DEL
on the keyboard.
Using the right mouse button
On input/output blocks
Copy/paste
Delete
Delete all assigned connections
Alignment with other function blocks (with multiple selection)
Help
Monitor mode: show/hide the property window
Status block: activate/deactivate the negation on the input pin
Page 64
English
On operator blocks
DESIGN
WORKSPACE
WINDOW
WITH
OBJECT
PROPERTIES
Start point for
the connection
Copy/paste
Delete
Alignment with other function blocks (with multiple selection)
Help
Activate/deactivate the negation on the input pin
Monitor mode: show/hide the property window
On terminals
Alignment with other function blocks (with multiple selection)
On connections (wires)
Delete
Indication of the entire path for a connection (network)
Figure 36
Page 65
English
Example for a project
Figure 37 shows an example of a project in which the module MSC-CB is connected to only two safety components (INTERLOCK and E-STOP).
The inputs (1, 2, 3) on the module MSC-CB for connecting the contacts on the safety
components are highlighted in yellow on the left. The MSC outputs (from 1 to 4) are activated as per the conditions that are defined in INTERLOCK and E-STOP (see page 81 E–
STOP and page 83 INTERLOCK).
Click a block to select it and activate the PROPERTY window on the right where you can
configure the activation and test parameters for the block.
Figure 37
At the end of the project preparation phase (or during intermediate steps), you can save
the actual configuration using the button on the default toolbar.
Page 66
English
Project validation
The completed project must now be validated. This check is made by running the
VALIDATE command ( button on the default toolbar).
Figure 38
If the validation is successful, a sequential number is assigned to the input and output of
the project. This number then appears also in the REPORT and in the MONITOR in
EUCHNER Safety Designer.
The configuration is only transferred after successful validation.
The validation function only checks whether the programming is appropriate for the
properties of the MSC system. However, this check does not guarantee that the device has been programmed such that all safety requirements for the application are
met.
Page 67
English
Project report
The system layout can be printed together with the properties of the individual blocks (
button on the default toolbar).
Page 68
English
This definition of the PL and the other related parameters as per EN ISO 13849-1 re-
late only to the functions that have been implemented by EUCHNER Safety Designer
in the MSC system, whereby it is assumed that the configuration has been undertaken correctly.
The data for all devices connected to the MSC in the application must be taken into
account in the actual PL of the entire application and the related parameters.
This task is only allowed to be undertaken by the design engineer or the installer.
Connecting to MSC
After you have connected the module MSC-CB to the PC via the USB cable, establish con-
nection using the button. A window with a password prompt appears. Type password
(see "Password protection").
Figure 39
Sending the configuration to the MSC system
Click the button on the default toolbar to send the saved configuration from the PC
to the MSC-CB after the related command is executed. In the MSC-CB the project is saved
in the internal memory and (if fitted) on the M-A1 memory card (password required: level
2).
This function is only available after the successful validation of the project.
Downloading a configuration file (project) from MSC-CB
Click the button on the default toolbar to download a project from the MSC-CB to the
configuration software EUCHNER Safety Designer.
EUCHNER Safety Designer displays the project saved in the MSC-CB (password level 1 is
adequate).
If the project is to be used for other modules of type MSC-CB, the components con-
nected in each case are to be checked (see "System layout" on page 70).
Then undertake a "Project validation" (page 66) and a "CHECKING the system"
(page 75).
Page 69
English
Configuration LOG
The creation date and the CRC (four-digit hexadecimal code) for a project saved
in the MSC-CB are contained in the configuration file (project).
Up to five sequential events can be recorded in this log. Then the results are over-
written starting with the oldest event.
The log file can be displayed using the button on the default toolbar (password required: level 1).
Figure 40
Page 70
English
System layout
The actual layout of the MSC system can be checked using the button (password required: level 1). A pop-up window with the following content appears:
- Modules connected
- Firmware version for the individual modules
- Node number (physical address) of the individual modules.
Figure 41
If there is an error in one of the modules detected, the following window appears.
In the example below the node number of module FI8 is not correct (indicated by
red text).
Figure 42
Disconnecting the system
Click the button to disconnect the PC from the MSC-CB. After the disconnection of
the system, then system is reset and restarted with the project transferred.
If the system does not comprise all the modules foreseen in the configuration, this
incompatibility is indicated on the module MSC-CB and the module is not started.
(See SIGNALS).
Page 71
English
MONITOR (real-time I/O status – text form)
Click the button to activate the monitor (password required: level 1).
A pop-up window with the following content appears (in real-time):
- Status of the inputs (if the object has two or more input connections to MSC, only the first is
indicated in the MONITOR as active; see example shown)
- Input diagnostics
- OSSD state
- OSSD diagnostics
- Status of the digital outputs
- OUT TEST diagnostics.
Figure 43 – Monitor (text form)
Page 72
English
MONITOR (real-time I/O status – text – graphic)
Click the button to activate/deactivate the monitor (password required: level 1).
Based on the color of the links (Figure 33) the diagnostics can be read (in real-time) as
follows:
RED = OFF
GREEN = ON
DASHED ORANGE = Connection error
DASHED RED = ENABLE pending (e.g. RESTART)
Position the mouse pointer on the link to display the diagnostics.
Figure 44 – Monitor (graphic)
Page 73
English
Password protection
To upload and save the project, you must enter a password in EUCHNER Safety Designer.
The default password must be changed to prevent tampering (password level 2) or
so that the configuration loaded in MSC is not visible (password level 1).
Password level 1
All operators who use the system MSC-CB must have a level 1 PASSWORD.
Using this password it is only possible to display the LOG file, the layout of the system,
the real-time MONITOR and upload processes.
On the initialization of the system for the first time the operator must use the password ""
(ENTER key).
System planers who know the level 2 password can assign a new password for level 1 (alphanumeric, max. 8 characters).
Operators who know this password are authorized to upload the project (from MSC-
CB to PC), to edit or to save it.
Password level 2
System planers who are authorized to work on the preparation of the project must know
the level 2 PASSWORD. On the initialization of the system for the first time the operator
must use the password "SAFEPASS" (upper case).
System planers who know the level 2 password can assign a new password for level 2 (alphanumeric, max. 8 characters).
Using this password the project can be uploaded (from PC to MSC-CB), edited and
saved. In other words, complete control of the PC => MSC system is possible using
this password.
On UPLOADING a new project, you can change the level 2 password.
Should one of these passwords no longer be available, please contact EUCHNER to
request an unlock file (if the unlock file is saved in the correct folder, the button
appears on the toolbar). Press the button to reset the level 1 and 2 passwords to
their original values. This password is only provided to the system planner and can
only be used once.
Page 74
English
Password change
Click the button to change the PASSWORD after the connection has been established
using the level 2 password.
A window (Figure 45) appears in which the new password can be selected. Type old and
new password in the related fields (max. 8 characters). Click OK.
At the end of the process, disconnect to restart the system.
If an M-A1 memory card is fitted, the new password is also saved on this memory card.
Figure 45
Page 75
English
CHECKING the system
After the project has been validated, uploaded to the module MSC-CB and all safety
components have been connected, the system must be checked for correct operation.
This check is made by forcing a status change for each safety component connected to
MSC to check whether the status of the outputs also actually changes.
The following example is intended to explain the CHECK process.
Figure 46
(t1) In the normal operating status (INTERLOCK closed) Input1 is closed, Input2 is
open and the INTERLOCK output set to the "HIGH" logic level. In this mode the
safety outputs (OSSD1/2) are active and a supply voltage of 24 VDC is present
at the related terminals.
(t2) If the INTERLOCK is opened physically, the state of the inputs changes and
therefore also the outputs of the INTERLOCK block: (OUT = 0 VDC--->24 VDC).
The state of the safety outputs OSSD1/2 changes from 24 VDC to 0 VDC. If
this change is detected, the moving INTERLOCK is connected correctly.
You will find more detailed information on the correct installation of external sen-
sors/components in the installation manual.
This check must be undertaken for each safety component in the project.
Page 76
English
OBJECT-SPECIFIC FUNCTION BLOCKS
OUTPUT OBJECTS
OSSD (safety outputs)
The OSSD outputs do not require any
maintenance. Output1 and Output2
supply 24 VDC with an input of "1"
(TRUE) and 0 VDC with an input of "0"
(FALSE).
Each OSSD pair has an input for
RESTART_FBK. This input must always be connected as described in the paragraph RESTART_FBK.
Parameters
Manual Reset: If selected, a reset can be requested on every change in the input signal.
Otherwise the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1.
With the monitored reset the transition from 0 to 1 and then back to 0
is checked.
Enable Status: If selected, the OSSD
can be connected to a STATUS.
STATUS output
Using the STATUS output (not a safety output) every
point in the diagram can be monitored by connecting it to the input. The output supplies 24 VDC with
an input "1" (TRUE) and 0 VDC with an input of "0"
(FALSE).
WARNING: The STATUS output is NOT a safety output.
Page 77
English
FIELDBUS PROBE
Using this element the status of any point on the
diagram can be indicated on the fieldbus.
Up to 16 sensors can be used; the bit used to indicate the state must be entered for each sensor.
The states are indicated on the fieldbus using two
bytes.
(You will find more detailed information in the
fieldbus manual on the CD-ROM "EUCHNER Safety
Designer".)
WARNING: The FIELDBUS OUTPUT is NOT a safety output.
Page 78
English
RELAY
The output relay is a relay output with a normally open contact. The relay outputs are
closed if the input IN is "1" (TRUE), otherwise they are open (FALSE).
Parameters
Category. There are three categories of relay out-
puts:
Category 1. Outputs with a category 1 relay.
Each module AZ-FO4/AZ-FO4O8 can have up to
four of these outputs.
automatic starting. The external device monitoring (EDM) cannot be activated with manual
starting, only with automatic starting. If, however, manual starting with external device
monitoring is required, special logic must be
used (see information below).
Page 79
English
Output for the OTE (Output Test Equipment)
Activation: this is necessary for category 2 configurations for signaling dangerous fail-
ures as per EN 13849-1: 2006 / DAM1 (in preparation).
OTE output: normally ON. If there is a fault in the internal feedback or the external de-
vice monitoring (EDM) => OFF. This signal makes it possible to stop hazardous movements, or at least to indicate the fault to the operator.
Usage of the automatic start (A) or manual start (B) (category 2)
Figure 47
Category 4. Outputs with a two category 4 relays. Each
module AZ-FO4/AZ-FO4O8 can have up to two of these
outputs. The relays are operated in pairs for this output.
Properties:
2 dual-channel outputs.
Double internal relays are monitored.
Each output can be set to manual or automatic start-
ing.
To avoid affecting the result of the calculation of the PL, the inputs (sensors or safety
components) must correspond to the same or a higher category as the other devices
in the chain.
Page 80
English
Example of usage with only the internal relay
and monitored solenoid valves
Example of usage with external
contactors and feedback
Manual Reset: If selected, a reset can be requested each time the IN input signal drops
out. Otherwise the output is activated directly corresponding to the state of the IN input.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset
the double transition from 0 to 1 and then back to 0 is checked.
Enable Status: If selected, the relay outputs can be connected to a STATUS.
Enable external K reading: If activated, the switching times for external contactors can be
read and checked:
For category 1 it is not possible to check the external contactors.
For category 4 the check on the external contactors is obligatory (always activat-
ed).
External K delay (ms): Set maximum delay on the contactors. Using this value the maxi-
mum delay between switching the internal relay and the switching of the external contactors (on activation and deactivation) can be defined.
Page 81
English
INPUT OBJECTS
E–STOP
The input status of an emergency stop device can be
checked using the E-STOP function block. If the
emergency stop button is pressed, the OUTPUT output is "0" (FALSE), otherwise the OUTPUT output is "1"
(TRUE).
Parameters
Input Type:
- Single NC – makes it possible to connect emergen-
cy stop devices with one normally closed contact
- Dual NC – makes it possible to connect emergency
stop devices with two normally closed contacts.
Manual Reset: If selected, a reset can be requested on
every activation of the emergency stop. Otherwise the
activation of the output will correspond directly to
the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset
the double transition from 0 to 1 and then back to 0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
Output Test: Using this option you can select which test output signals are to be sent to
the emergency stop device. Short circuits between the wires can be detected by means of
this additional test. For this purpose it is necessary to configure the test output signals
(from the test output signals available).
Page 82
English
StartUp Test:If selected, the test is undertaken on switching on the external components
(emergency stop). This test is undertaken by pressing and releasing the emergency stop
to carry out one complete function test and to activate the output. This test is only requested on starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the emergency stop. The filter can be set to between 3 and 250 ms and removes any contact bounce. The time set for the filter affects the calculation of the total response time of
the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the emergency stop is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two signals that are received from the emergency stop.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 83
English
INTERLOCK
The input status of a moving safety guard or a
safety door is checked by the INTERLOCK function block. If the moving safety guard or the
safety door is opened, the OUTPUT output is "0"
(FALSE), otherwise the OUTPUT output is "1"
(TRUE).
Parameters
Input Type:
- Double NC – makes it possible to connect
components with two normally closed contacts
- Double NC/NO – makes it possible to connect
components with one normally open contact
and one normally closed contact.
Connect inactive input (OUTPUT output is
"0" (FALSE)) as follows:
- NO contact to terminal that has been assigned to the input IN1.
- NC contact to terminal that has been assigned to the input IN2.
Manual Reset:If selected, a reset can be requested on every activation of the moving
safety guard or the safety door. Otherwise the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset
the double transition from 0 to 1 and then back to 0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by opening the moving safety guard or the safety door to carry
Page 84
English
out one complete function test and to activate the output. This test is only requested on
starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the external contacts.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 85
English
SINGLE INTERLOCK
The input status of a moving safety guard or a safety door is checked by the SINGLE INTERLOCK function block. If the moving safety guard or the safety
door is opened, the OUTPUT output is "0" (FALSE),
otherwise the OUTPUT output is "1" (TRUE).
Parameters
Manual Reset:If selected, a reset can be requested
on every activation of the moving safety guard or
the safety door. Otherwise the activation of the
output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored".On the selection of the manual reset, the system only checks the signal transition
from 0 to 1. With the monitored reset the double transition from 0 to 1 and then back to
0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by opening the moving safety guard or the safety door to carry
out one complete function test and to activate the output. This test is only requested on
starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 86
English
LOCK FEEDBACK
Using the LOCK FEEDBACK function block the
state of the guard locking inputs for a moving
safety guard or a safety door is checked. If the
inputs signal that the guard locking is locked,
the OUTPUT output is "1" (TRUE), otherwise the
OUTPUT output is "0" (FALSE).
Parameters
Input Type:
- Single NC – makes it possible to connect
components with one normally closed contact
- Double NC – makes it possible to connect
components with two normally closed contacts.
- Double NC/NO – makes it possible to connect
components with one normally open contact and one normally closed contact.
Connect inactive input (guard locking unlocked, OUTPUT output is "0" (FALSE)) as fol-
lows:
- NO contact to terminal that has been assigned to the input IN1.
- NC contact to terminal that has been assigned to the input IN2.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the external contacts.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 87
English
KEY LOCK SWITCH
Using the KEY LOCK SWITCH function block the
input status of a manual key-operated switch is
checked. If the key is not turned, the OUTPUT
output is "0" (FALSE), otherwise the OUTPUT
output is "1" (TRUE).
Parameters
Input Type:
- Single NO – makes it possible to connect
components with one normally open contact
- Double NC – makes it possible to connect
components with two normally closed contacts.
Manual Reset:If selected, a reset can be re-
quested on every activation of the command.
Otherwise the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and
"Monitored". On the selection of the manual reset, the system only checks the signal transition
from 0 to 1. With the monitored reset the double transition from 0 to 1 and then back to
0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
Page 88
English
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by opening and activating the key lock switch to carry out one
complete function test and to activate the output. This test is only requested on starting
the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the external contacts.
Enable Error Out: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 89
English
ESPE (optoelectronic safety light curtain or optoelectronic safety laser scanner)
Using the ESPE function block the input status
of an optoelectronic safety light curtain (or
safety light scanner) is checked. If the area
protected by the light curtain is occupied (outputs on the light curtain FALSE), the OUTPUT
output is "0" (FALSE). Conversely, if this area is
not occupied and the outputs on the light curtain are "1" (TRUE), the OUTPUT output is "1"
(TRUE).
Parameters
Manual Reset:If selected, a reset can be requested each time the area protected by the
safety light curtain is occupied. Otherwise the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset
the double transition from 0 to 1 and then back to 0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
The OUT TEST signals cannot be used for the static safety output ESPE, as the test signals
are generated by the ESPE.
StartUp Test:If selected, the test is undertaken on switching on the safety light curtain.
This test is undertaken by occupying and clearing the area protected by the safety light
curtain to carry out one complete function test and to activate the output. This test is only requested on starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the safety light curtain. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the safety light curtain is checked.
Page 90
English
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the safety light curtain.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 91
English
FOOTSWITCH
Using the FOOTSWITCH function block the input status of a safety footswitch is checked. If
the footswitch is not pressed, the OUTPUT output is "0" (FALSE), otherwise the OUTPUT output is "1" (TRUE).
Parameters
Input Type:
- Single NC – makes it possible to connect
footswitches with one normally closed contact
- Single NO – makes it possible to connect
footswitches with one normally open contact
- Double NC – makes it possible to connect
footswitches with two normally closed contacts
- Double NC/NO – makes it possible to con-
nect footswitches with one normally open
contact and one normally closed contact.
Connect inactive input (OUTPUT output is "0" (FALSE)) as follows:
- NO contact to terminal that has been assigned to the input IN1.
- NC contact to terminal that has been assigned to the input IN2.
Manual Reset: If selected, a reset can be requested on every activation of the safety
footswitch. Otherwise the activation of the output will correspond directly to the input
conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset
the double transition from 0 to 1 and then back to 0 is checked.
Page 92
English
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 and Input2 are used for the function block, Input3 must be used for the reset
input.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by pressing and releasing the footswitch to carry out one complete function test and to activate the output. This test is only requested on starting the
machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
With Simultaneity: If selected, the simultaneous switching of the signals received from
the external contacts is checked.
Simultaneity (ms): This control is only available if the previous parameter has been se-
lected. Using this value you can define the maximum time (in ms) between the switching
of the two different signals that are received from the external contacts.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 93
English
MOD-SEL (operating mode selection)
Using the MOD-SEL function block the status of the inputs on an operating mode selector switch (up to 4 inputs) is checked: If
only one IN input is "1" (TRUE), the corresponding OUTPUT output is also "1" (TRUE).
In other cases, i.e. if all IN inputs are "0"
(FALSE) or more than one IN input is "1"
(TRUE), all OUTPUT outputs are "0" (FALSE).
Parameters
Input Type:
- Double switch – makes it possible to connect operating mode selector switches with
two switch positions
- Triple switch – makes it possible to connect operating mode selector switches with
three switch positions
- Quadruple switch – makes it possible to connect operating mode selector switches with
four switch positions
Filter (ms):This parameter makes it possible to filter the signals that are received from
the operating mode selector switch. The filter can be set to between 3 and 250 ms and
removes any contact bounce. The time set for the filter affects the calculation of the total
response time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 94
English
PHOTOCELL
Using the PHOTOCELL function block the status
of the inputs for an optoelectronic safety light
barrier is checked. If the beam from the light
barrier is obscured (output on the light barrier
FALSE), the OUTPUT output is "0" (FALSE). If,
conversely, the beam is not obscured (output
on the light barrier TRUE), the OUTPUT output
is "1" (TRUE).
Parameters
Manual Reset: If selected, a reset can be re-
quested on every activation of the safety light
barrier. Otherwise the activation of the output
will correspond directly to the input conditions.
There are two types of reset: "Manual" and
"Monitored". On the selection of the manual reset, the system only checks the signal transition from 0 to 1. With the monitored reset the double transition from 0 to 1 and then
back to 0 is checked.
A test output is obligatory and can be selected using one of the 4 possible
OUT_TEST outputs.
Warning: If RESET is selected, the next input must be used. Example: If INPUT1 is
used for the function, INPUT2 must be used for the RESET.
The reaction time for the light barrier must be > 2 ms and < 20 ms.
Output Test: Using this option you can select which test output signals are to be sent to
the test input on the light barrier. Short circuits between the wires can be detected and
rectified by means of this additional check. For this purpose it is necessary to configure
the test output signals (from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by covering and clearing the light barrier to carry out one complete function test and to activate the output. This test is only requested on starting the
machine (on switching on the module).
Page 95
English
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 96
English
TWO-HAND
Using the TWO-HAND function block the status of the inputs for a two-hand control
switch is checked. Only if both pushbuttons
are pressed within 500 ms, is the OUTPUT
output "1" (TRUE), otherwise the OUTPUT
output is "0" (FALSE).
Input Type:
- Double NO – makes it possible to connect
a two-hand switch with one normally open
contact for each pushbutton
(EN 574 III A).
- Quadruple NC/NO – makes it possible to
connect a two-hand switch with a dualchannel normally closed/normally open
contact for each pushbutton
(EN 574 III C).
Connect inactive input (OUTPUT output is "0" (FALSE)) as follows:
- NO contact to terminal that has been assigned to the input IN1.
- NC contact to terminal that has been assigned to the input IN2.
Output Test: Using this option you can select which test output signals are to be sent to
the component contacts. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by pressing (within 500 ms) and releasing both pushbuttons to
carry out one complete function test and to activate the output. This test is only requested on starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from
the operating mode selector switch. The filter can be set to between 3 and 250 ms and
removes any contact bounce. The time set for the filter affects the calculation of the total
response time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description:Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 97
English
SENSOR
Using the SENSOR function block the input status for a sensor (not a safety sensor) is
checked. If the beam from the sensor is obscured (output on the light barrier FALSE), the
OUTPUT output is "0" (FALSE). Conversely, if
this beam is not occupied and the output on
the sensor is "1" (TRUE), the OUTPUT output is
"1" (TRUE).
Parameters
Manual Reset: If selected, a reset can be re-
quested each time the area protected by the
sensor is occupied. Otherwise the activation of
the output will correspond directly to the input
conditions.
There are two types of reset: "Manual" and
"Monitored". On the selection of the manual reset, the system only checks the signal transition from 0 to 1. With the monitored reset the double transition from 0 to 1 and then
back to 0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 is used for the function block, Input2 must be used for the reset input.
Output Test: Using this option you can select which test output signals are to be sent to
the sensor. Short circuits between the wires can be detected and rectified by means of
this additional check. For this purpose it is necessary to configure the test output signals
(from the test output signals available).
StartUp Test:If selected, the test is undertaken on switching on the sensor. This test is
undertaken by occupying and clearing the area protected by the sensor to carry out one
complete function test and to activate the output. This test is only requested on starting
the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from the
sensor. The filter can be set to between 3 and 250 ms and removes any contact bounce. The
time set for the filter affects the calculation of the total response time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 98
English
S-MAT (switch mat)
Using the S-MAT function block the status of
the inputs for a switch mat is checked. If the
there is a person on the footmat, the OUTPUT
output is "0" (FALSE), otherwise, i.e. if the
footmat is clear, the OUTPUT output is "1"
(TRUE).
Parameters
Manual Reset: If selected, a reset can be re-
quested on every activation of the switch mat.
Otherwise the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and
"Monitored". On the selection of the manual
reset, the system only checks the signal transition from 0 to 1. With the monitored reset the
double transition from 0 to 1 and then back to
0 is checked.
If Manual Reset is selected, the next Input must be used. Example: If Input1 and In-
put2 are used for the function block, Input3 must be used for the reset input.
The usage of two test outputs is obligatory. Each OUT TEST output can only be con-
nected to one S-MAT input (it is not allowed to connect two inputs in parallel).
The S-MAT function block cannot be used for two-wire components or terminating
resistors.
Output Test: Using this option you can select which test output signals are to be sent to
the S-MAT contact. Short circuits between the wires can be detected and rectified by
means of this additional check. For this purpose it is necessary to configure the test output signals (from the test output signals available). The test signals are obligatory.
StartUp Test:If selected, the test is undertaken on switching on the external components.
This test is undertaken by standing on and clearing the switch mat to carry out one complete function test and to activate the output. This test is only requested on starting the
machine (on switching on the module).
Page 99
English
Filter (ms):This parameter makes it possible to filter the signals that are received from
the external contactors. The filter can be set to between 3 and 250 ms and removes any
contact bounce. The time set for the filter affects the calculation of the total response
time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Page 100
English
SWITCH
Using the SWITCH function block the input status
for a pushbutton or switch (NOT A SAFETY
SWITCH) is checked. If the pushbutton is pressed,
the OUTPUT output is "1" (TRUE), otherwise the
OUTPUT output is "0" (FALSE).
Parameters
Manual Reset: If selected, a reset can be request-
ed on every activation of the device. Otherwise
the activation of the output will correspond directly to the input conditions.
There are two types of reset: "Manual" and "Monitored". On the selection of the manual reset, the
system only checks the signal transition from 0 to
1.
With the monitored reset the double transition from 0 to 1 and then back to 0 is checked.
WARNING: If Manual Reset is selected, the next Input must be used. Example: If In-
put1 is used for the function block, Input2 must be used for the reset input.
Output Test: Using this option you can select which test output signals are to be sent to
the switch.
Short circuits between the wires can be detected and rectified by means of this additional
check. For this purpose it is necessary to configure the test output signals (from the test
output signals available).
StartUp Test:If selected, the test is undertaken on switching on the switch. This test is
undertaken by opening and closing the switch to carry out one complete function test
and to activate the output. This test is only requested on starting the machine (on switching on the module).
Filter (ms):This parameter makes it possible to filter the signals that are received from the
switch. The filter can be set to between 3 and 250 ms and removes any contact bounce.
The time set for the filter affects the calculation of the total response time of the module.
Enable Out Error: If selected, an error detected by the function block is signaled.
Item Description: Here you can enter a functional description for the component. The text
is displayed in the upper part of the symbol.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.