EUCHNER ESM-BL2xx User Manual

Emergency Stop Sa fety Relay E SM-BL2..
User Information
Correct Use
Features
Function
ESM-BL2.. is the low-cost emergency stop safety relay with which machines and systems can be safely switched off by disconnect­ing the power supply. Internal fault monitoring takes place during restarting via the start button.
Applications for the ESM-BL2.. include single or dual-channel emergency stop circuits and guard monitoring on machines and systems.
2 safe, redundant relay outputs
Connection of:
- Emergency stop buttons
- Safety switches
- Non-contact safety switches
Single and dual-channel operation possible
Feedback loop for monitoring downstream contactors or expansion modules
Cyclical monitoring of the output contacts
Indication of the switching state via LED
The emergency stop safety switching device ESM-BL2.. is designed for safe isolation of safety circuits according to EN 60204-1 and can be used up to safety category 3, PL d according to EN ISO 13849-1.
The internal logical system closes the safety contacts when the start button is pressed.
When the safety switch is opened, the positively driven safety contacts are opened and safely switch the machine off. It is ensured that a single fault does not lead to a loss of the safety function and that every internal fault is detected by cyclical self-monitoring no later than when the system is switched off and switched on again. Only a fault in the safety switch itself is not detected. This must be checked regularly as part of a maintenance plan.
- Manual start
- Automatic start
Short circuit and earth fault monitoring
Up to PL d, SILCL 2, category 3
Fig. 1 Block diagram ESM-BL2..
(not for plug-in terminals)
Installation
Safety Precautions
Electrical Connection
As per EN 60204-1, the device is intended for installation in control cabinets with a minimum degree of protection of IP54. It is mounted on a 35-mm DIN rail according to DIN EN 60715 TH35.
Installation and commissioning of the device must be performed only by authorized personnel.
Observe the country-specific regulations when installing the device.
The electrical connection of the device is only allowed to be made with the device isolated.
The wiring of the device must comply with the instruc­tions in this user information, otherwise there is a risk that the safety function will be lost.
When the 24 V version is used, a safety transformer according to EN 61558-2-6 or a power supply unit with electrical isolation from the mains must be connected.
External fusing of the contacts (4 A slow-blow or 6 A quick-action or 10 A gG) must be provided.
A maximum length of the control lines of 1000 meters with a line cross section of 0.75 mm2 must not be ex­ceeded.
The line cross section must not exceed 2.5 mm2.
If the device does not function after commissioning, it must be returned to the manufacturer unopened. Open­ing the device will void the warranty.
Fig. 2 Installation / removal
It is not allowed to open the device, tamper with the de­vice or bypass the safety devices.
All relevant safety regulations and standards are to be observed.
The overall concept of the control system in which the device is incorporated must be validated by the user.
Failure to observe the safety regulations can result in death, serious injury and serious damage.
A1: Power supply A2 : Power supply S11: DC 24V control voltage S21: Control line 13-14: Safety contact 1 23-24: Safety contact 2
Fig. 3 Connections
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de
1
Emergency Stop Sa fety Relay E SM-BL2..
User Information
Applications
Emergency Stop Circuit
Starting Behavior
Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as shown in Fig. 1 to Fig. 9.
Fig. 1:
Two-channel emergency stop circuit without fault monitoring of the emergency stop button and the supply cables.
(up to category 3, PL d)
Fig. 2:
Single-channel emergency stop circuit without fault monitoring of the emergency stop button and the supply cables.
(up to category 1, PL c)
Fig. 3:
Two-channel sliding guard monitoring with positively driven limit switches.
(up to category 3, PL d)
Notice:
In order to activate earth fault monitoring, S10 must be con­nected to PE (protective earth) on the AC115/230V devices. With AC/DC 24 V, connect PE only to the power supply unit according to EN60204-1.
Fig. 4:
Manual start.
Warning:
Safety contacts switch immediately when the power supply is connected.
Fig. 5:
Automatic start (e.g. for applications with a
safety door).
Feedback Loop
Safety contacts
Commissioning Procedure
Fig. 6:
Feedback loop for monitored manual start:
The feedback loop monitors contactors or the expansion modules .
Fig. 8:
Connecting load to safety contacts.
(Figure shows example. Voltage „+V“ according to techn.
data)
Note: The items listed under “Electrical connection” must be observed during commissioning.
1. Wiring emergency stop circuit:
Wire the emergency stop circuit according to the required Performance Level determined (see Fig. 1 to Fig. 3).
2. Wiring start circuit:
Wire the start circuit according to Fig. 4 or Fig. 5 to set the starting behavior.
Warning: If “Automatic start” is set, bear in mind that the safety con-
tacts will switch immediately after the power supply is connected. If “Manual start” is set, the start button must be opened after wiring.
3. Wiring feedback loop:
If your application provides for external contactors or ex­pansion modules, connect them to the device according to Fig.6 or Fig.7.
4. Wiring power supply: Connect the power supply to terminals A1 and A2.
5. Starting the device:
Switch the operating voltage on.
Warning:
If the “Automatic start” starting behavior is set, the safety contacts will close immediately.
If the “Manual start” starting behavior is set, close the start button to close the safety contacts.
LEDs K1 and K2 are lit.
6. Triggering safety function:
Open the emergency stop circuit by actuating the con­nected safety switch. The safety contacts open immedi­ately.
7. Reactivation:
Close the emergency stop circuit. If “Automatic start” is selected, the safety contacts will close immediately.
If the “Monitored manual start” starting behavior is set, close the start button to close the safety contacts.
Warning: Wiring only in de-energized state.
Fig. 7:
Feedback loop for automatic start: The feedback loop monitors contac-
tors or the expansion modules .
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de