The most current version of this manual can be found at www.EubankWallmount.com.
IMPORTANT
Manufactured By:
(229) 273-3636 • Fax (229) 273-5154
1
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev.10
Eubank TH Series Heat Pump I&O Manual
Part #03698
09/2018 Rev. 10
How To Use This Manual
This manual is intended to be a comprehensive guide to the installation of the Eubank® TH Series family of
vertical packaged heat pumps. It contains installation, troubleshooting, maintenance, warranty, and application
information. The information contained in this manual is to be used by the installer as a guide only. This manual
does not supersede or circumvent any applicable national or local codes. For information on the efciency,
cooling and heating performance, please refer to the TH Series Product Data Sheets. The most current version
of all literature can be found on our website at www.EubankWallMount.com.
If you are installing the heat pump unit, rst read Chapter 1 and scan the entire manual before beginning the
installation as described in Chapter 2. Chapter 1 contains general, descriptive information and provides an
overview which can speed up the installation process and simplify troubleshooting.
If a malfunction occurs, follow this troubleshooting sequence:
1. Make sure you understand how the heat pump unit works (Chapters 1 & 3).
2. Identify and correct installation errors (Chapter 2).
3. Refer to the troubleshooting information in Chapter 4.
4. Identify defective part(s). (Chapter 5).
If you are still unable to correct the problem, contact the Factory at 1-800-841-7854 for additional assistance.
Please read the following “Important Safety Precautions” before beginning any work. Failure to follow
these rules may result in death, serious bodily harm, property damage and damage to the equipment.
Important Safety Precautions
1. USE CARE when LIFTING or TRANSPORTING equipment.
2. TRANSPORT the UNIT UPRIGHT. Laying it down on its side may cause oil to leave the compressor and
breakage or damage to other components.
3. TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on the
equipment. LINE VOLTAGES ARE HAZARDOUS or LETHAL.
4. OBSERVE and COMPLY with ALL applicable PLUMBING, ELECTRICAL, and BUILDING CODES and
ordinances.
5. SERVICE may be performed ONLY by QUALIFIED and EXPERIENCED PERSONS.
* Wear safety goggles when servicing the refrigeration circuit
* Beware of hot surfaces on refrigerant circuit components
* Beware of sharp edges on sheet metal components
* Use care when recovering or adding refrigerant
6. Use COMMON SENSE - BE SAFETY-CONSCIOUS
This is the safety alert symbol . When you see this symbol on the unit and in the instruction manuals be
alert to the potential for personal injury. Understand the signal word DANGER, WARNING, CAUTION and
IMPORTANT. These words are used to identify levels of the seriousness of the hazard.
DANGERFailure to comply will result in death or severe personal injury and/or property damage.
WARNING
Failure to comply could result in death or severe personal injury and/or property damage.
CAUTIONFailure to comply could result in minor personal injury and/or property damage.
IMPORTANT
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
Used to point out helpful suggestions that will result in improved installation, reliability
or operation.
Your equipment is covered by a LIMITED WARRANTY against
defects in material and workmanship.
This is a vertical, wallmount unit designed for many different
applications in both residential and commercial settings. It is
self-contained and arrives completely assembled, factorycharged and wired. The unit is 100% run-tested at the factory
to ensure proper operation. Your unit is supplied with highquality copper tubing and enhanced aluminum-finned coils for
high heat transfer efficiency and long life. The unit cabinet is
constructed of G-90 galvanized steel. All exterior surfaces are
finished with a baked-on polyester coating. This will provide
excellent corrosion protection in most applications. However,
if the unit is installed in an area with a corrosive atmosphere,
such as near an industrial plant or on the seacoast, additional
coating should be considered to extend the life of the coils
and cabinet.
This unit was designed for up to 105ºF of ambient temperature
for the cooling mode; for heating mode, this unit was designed
for up to 78ºF of room temperature and minimum 15ºF ambient
temperature.
INSPECTION AND UNPACKING
A thorough inspection of the shipping container should
be made immediately upon receiving your unit. Look for
any punctures or openings. If it appears as if damage has
occurred, it should be noted on the freight bill before signing.
The delivering carrier should be contacted immediately to
inspect damage, and no installation work should begin until
this inspection is completed.
DANGER
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT,
POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD
SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK,
INJURY, DEATH, OR DAMAGE TO EQUIPMENT.
SAFETY RULES
WARNING
FAILURE TO FOLLOW THESE RULES AND INSTRUCTIONS
COULD CAUSE A MALFUNCTION DESTRUCTION OF
EQUIPMENT WHICH COULD RESULT IN PROPERTY DAMAGE,
SERIOUS BODILY INJURY, OR DEATH.
1. Installation and repair MUST be done by a qualified person.
The equipment should be inspected before use and at least
once annually by a professional service person.
2. AVOID ELECTRICAL SHOCK! Turn power OFF when
servicing. There may be more than one disconnect switch
to de-energize unit.
3. Close cover(s) before returning breaker(s) to “ON” position.
4. Please observe good safety practices by wearing personal
protective equipment such as gloves and safety glasses
to avoid injury.
5. Installation MUST conform to local codes. In the absence
of local codes, refer to the National Electrical Code (NEC),
ANS/NFPA No. 70-1993 and recommendations made by
the National Board of Fire Underwriters.
In all cases, the equipment MUST be installed in accordance
with the installation instructions described in this manual.
WARNING
IMPROPER INSTALLATION MAY DAMAGE EQUIPMENT, CAN
CREATE HAZARD, AND WILL VOID THE WARRANTY
OPERATING INSTRUCTIONS
If heating and cooling functions are controlled by separate
thermostats, turn the furnace thermostat to the “OFF” position
during the cooling season to prevent simultaneous operation
of the heating and cooling systems. Reverse the procedure
during the heating season.
If the same thermostat controls both heating and cooling
functions, set the thermostat to either HEAT or COOL as
desired.
Set the desired temperature on your thermostat and set
the fan switch to “ON” (for continuous air circulation) or to
“AUTOMATIC” (for air circulation only when the heat pump
system is operating).
IMPORTANT
Wait at least three (3) minutes after turning the air conditioner
off before trying to restart. If an attempt is made to start the
compressor before the refrigerant pressures are equalized,
the compressor motor may trip on its overload. An additional
waiting period will be required before restarting.
MAINTENANCE
1. Always install and keep filters clean. Check filters every 2
weeks. Clean or replace if necessary. The factory-installed
filter is located behind the center front access panel.
TO CHANGE SYSTEM FILTER:
A. Turn the power to the unit off at the unit disconnect. The
disconnect is located on the front of the unit behind a
small access door.
B. Remove the front center access door from the unit.
C. Remove and replace the filter with the type and size
indicated in the table below.
D. Replace the access door and turn on the power to the unit
NOTE: If your system has a filter grille installed in the return
air opening, the unit filter should have been discarded during
installation.
The filter installed into the return air grille assembly should be
replaced with the same size and type provided with the grille.
If your system is equipped with a fresh air intake, the filter for
the fresh air assembly is accessed through the front center
panel. The filter is a permanent washable type.
Unit Model QTYFilter Size - In (mm)Type
36116 x 30 x 1 (406 x 762 x 25) (Standard) Disposable
36116 x 30 x 2 (406 x 762 x 51) (Optional) Pleated
42,48,60120 x 30 x 1 (508 x 762 x 25) (Standard) Disposable
42,48,60120 x 30 x 2 (508 x 762 x 51) (Optional) Pleated
WARNING
SERIOUS INJURY MAY RESULT IF WATER SPRAY IS
DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR
POWER SOURCE.
3
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
TO CLEAN FRESH AIR INTAKE FILTER:
A. Follow steps A and B at left
“TO CHANGE SYSTEM FILTER”.
B. Gently pull out the filter from the
bottom.
C. Wash the filter with water.
D. Reinstall the filter, by sliding it into the
retaining rail.
E. Replace the access door and turn the
power on to the unit.
2. Keep the outdoor coil clean. Wash it down with a garden
hose if necessary.
BE SURE THE UNIT DISCONNECT IS IN THE “OFF”
POSITION AND THAT ALL ELECTRICAL POWER TO
THE UNIT IS TURNED OFF BEFORE CLEANING THE
SYSTEM.
3. Since the heat pump is located outdoors, it is exposed to
all weather elements. Treat it with a good automobile paste
wax twice a year (in the spring and fall).
Check with your contractor if you have any questions regarding
the maintenance or operation of your unit.
INSTALLATION (A: CODES)
The installer SHALL comply with all local, state, and federal
codes and/or regulations pertaining to this type of equipment
and its installation. Such codes and/or regulations should take
precedence over any recommendations contained herein.
Installations SHALL be made in accordance with the National
Electrical Code, local codes, and recommendations made by
the National Board of Fire Underwriters.
INSTALLATION (B: UNIT SITE SELECTION)
1. To eliminate noise from being transmitted into noise
sensitive areas, the unit should NOT be installed on walls
adjoining bedrooms, sleeping quarters, or adjacent to
windows.
2. Locating the unit as close as possible to the main duct
system or area to be conditioned, will prevent lengthy duct
runs and unnecessary thermal and air-pressure losses.
3. The clearance to combustibles is 0” on all sides, and 1/4”
for the first three (3) feet of supply duct.
4. The condenser air inlets (left, right and bottom inlets)
SHALL be located at least 8” away from walls or other
obstructions for unrestricted airflow.
5. The condenser air outlet should be located at least 6’
away from any obstructions to prevent recirculation of
condenser air.
6. Bottom of the unit SHALL be located at least 12” away from
the ground or other obstructions for unrestricted airflow.
7. Service clearance is 28” from the electrical box access
panel located on the front of the unit and 28” from the
center, upper, and lower front access panels.
8. The wall selected for unit installation MUST be able to or
be made to safely support the weight of the unit.
9. Do NOT locate where heat, lint or exhaust fumes will be
discharged on the unit (as from dryer vents).
INSTALLATION (C: UNIT PREPARATION)
1. TH Series model units have top rain flashing built onto
the unit. The bottom-mounting flange for all models is
shipped separately and in place. (Refer to “Section J. Unit
Installation” for the recommended use of the bottom flange.)
2. Electrical entrances are located on the right side and left
side of all TH Series units. Refer to “Section H. Electrical
Hook-up” for details.
3. Bend the lids of return and supply opening to form a return
and supply air collars and install air gaskets.
4. The supply and return air ducts should be checked to be
sure they:
e. Match the openings on the unit to be installed.
f. Have the same distance between them vertically as
the openings on the unit to be installed.
5. Return and supply grilles must be used when the return
and supply are not ducted. When a supply grille is used
in the installation, the louver spacing must be no greater
than 5/8 inch.
6. If the factory-installed filter is used on your installation,
access to the filter is made through the center panel on
the front of the unit.
IF A REMOTE FILTER IS USED, SUCH AS A FILTER
GRILLE, THE FACTORY-INSTALLED FILTER MUST BE
REMOVED AND DISCARDED.
INSTALLATION (D: DUCTWORK)
1. Properly-sized duct systems are critical for satisfactory
operation of any air conditioning system. All ductwork
MUST be correctly sized for the design air flow requirement
of the equipment.
2. The recommended operation duct static is to deduct 0.07”
W.C. for any size of heater 5 kW to 20 kW on factory or
field-installed heaters.
3. Ductwork routed through wall cavities, as well as any duct
not in conditioned space, MUST be insulated. Supply
ducting routed through exterior walls MUST be insulated
with 1” insulation to the back of the unit.
4. Supply and return air ducts should be flush with the exterior
wall and sized to fit over the unit duct collars in order to
compress the collar air gasket.
5. If supply duct is flashed to the exterior of a building
constructed with combustible material, the flashing MUST
be insulated in order to maintain the required clearances
to combustible materials. Required clearance is 1/4” for
the first three (3) feet of supply duct.
INSTALLATION (E: FILTERS)
1. One-inch disposable filters are supplied standard in each
unit. Two-inch disposable filters can also be used and
are available as an option. The filter rack is adjustable
to accommodate 2” filters. The filter rack on this series is
adapted by removing the 1” filter brackets. Refer to the
Maintenance section for the procedures for changing the
filters.
2. If a filter grille is used in the installation, the filter should be
properly sized to allow a maximum velocity of 400 FPM.
WHEN A FILTER IS USED, THE FACTORY-INSTALLED
FILTER MUST BE REMOVED.
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
4
INSTALLATION (F: ELECTRICAL POWER)
The installer MUST check available power to make certain
it matches the unit nameplate rating and that constant
voltage can be maintained to the unit. Unsatisfactory and
unsafe performance could otherwise result. The local power
company should be contacted about questions concerning
power supply.
INSTALLATION (G: BREAKER/DISCONNECT)
These units are standard equipped from the factory with a
unit disconnect. This is in the form of a circuit breaker (230V
models) or disconnect (460V models). If an optional electric
heat kit is to be installed, follow the instructions included with
the heater assembly. See Figure 1 for reference.
WARNING
ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY
A QUALIFIED, LICENSED ELECTRICIAN. IMPROPER
ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN
CREATE A HAZARD AND WILL VOID WARRANTY.
INSTALLATION (H: ELECTRICAL HOOKUP)
The line voltage electrical service can be routed through the
right side panel or left side panel. Each area is supplied with
two line voltage knock-outs (1/2” – 3/4” and 1” – 1 1/4”). Low
voltage wiring can be routed through the right side panel.
NOTE: When routing line voltage through the return air
compartment, conduit MUST be used (even though this is a dry
area) to comply with the NEC code. Refer to the ELECTRICAL
DATA tables for minimum wire size and maximum breaker
size. All wire sizes listed under the dual-feed circuit column
are based on no more than three (3) conductors in the same
conduit. If two circuits or more than three (3) conductors are
to be routed in the same conduit, the ampacity of the wire size
listed MUST be derated. Refer to Article 310 of the NEC code
for adjustment factors. Be sure to install a ground wire of the
proper size to the unit’s equipment ground lug.
The blower motor must be powered by 240V or 277V supply.
If the unit is supplied by 460V power, and a neutral connection
is unavailable, the motor may be powered by a 460V to 277V
or 240V transformer.
powered fresh air option, seven (7) conductor thermostat wires
should be run to the unit. Thermostat wire should be sized as
shown on the table below.
STAGING OF ELECTRIC HEAT
Units with electric heat assemblies are wired for two stage
heat in normal operation. The first stage is refrigerant heat
(Y and G terminals are energized and the O terminal is deenergized). The second stage is auxiliary resistance heat (W is
energized). TH Series units are equipped with an emergency
heat lock-out relay. This will disable the compressor when the
E terminal is energized. Do not install a jumper between the W
and E terminals; this would keep the compressor contacts from
being energized and prevent the compressor from operating.
INSTALLATION (J: UNIT INSTALLATION)
TH UNITS ARE FOR USE IN 1-STORY BUILDINGS ONLY.
1. As previously stated, the wall that the unit is to be installed
onto MUST be strong enough to support the unit under the
condition for which it will be used. For example, a unit to
be installed on a building that is intended to be transported
will require more wall strength than a unit installed at
a permanent site. Existing walls may need additional
reinforcement. NEVER RELY ON EXTERIOR SIDING
OR PLYWOOD TO SUPPORT THE UNIT. Figure 2 below
represents a typical installation of a single-story stud wall at
a permanent site. Since building materials and techniques
vary with regions and intended use, a building contractor
and/or local building code official MUST be consulted for
suitable construction methods.
2. Locate and attach the lower mounting bracket in the desired
location on the building.
3. Apply a suitable amount of caulk or silicone across the
entire length of the top rain flashing and side mounting
flanges.
4. Remove the flanges on both ends of the pallet and slide the
unit approximately 2” off the rear of pallet. Lift unit gently
into location with fork truck, taking care to align unit with
lower mounting bracket.
5. While allowing a small portion of weight on the lower
bracket, push the unit against the wall and fasten
appropriately.
INSTALLATION (I: LOW VOLTAGE WIRING)
230 volt, 1- and 3-phase units are equipped with dual-primary
voltage transformers for 208/240 volt operation. These models
are factory wired to the 240 volt tap. For 208 volt operation
connect the factory-installed black wires from the 240 volt tap
to the 208 volt tap. The acceptable voltage range of the tap
is as follows.
TapVoltage Range
240 Volt253 - 216
208 Volt220 - 187
Six (6) conductor thermostat wires should be run from the
thermostat location to the unit. If the unit is equipped with a
Unit ModelAB
363971
42/48/604286 1/2
MOUNTING FLANGE BOLT
PATTERN DIMENSIONS
5
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
SPECIAL NOTES FOR UNIT INSTALLATION
1. Minimum 12” clearance at the bottom of the unit for
unrestricted airflow
2. Ensure the ambient temperature uniformity around unit
3. Intake and discharge of the outdoor air flow must not be
restricted or altered
4. All insulation and sealing related to the installation must
be completed properly
5. External Static pressure should not exceed the minimum
value in the AHRI Standard 390
INSTALLATION (K: CONDENSATE DRAIN)
A 3/4” drain hose is located on the bottom side of the unit. The
drain may be extended for condensate removal to comply with
local codes (use fitting size or larger). Install a condensate
trap on this line.
INSTALLATION (L: OPTIONS)
Eubank wallmount air conditioners and heat pumps have the
ability to equip a variety of options:
• Electric Heat 5-20kW
• Sound Attenuation Module
• Powered Ventilation Damper
• Low Ambient Packages
• Economizer
• Lead Lag Controllers
Option kits must be installed according to the respective
installation manual to ensure safe and reliable operation.
Installation manuals are included with the option kit or can be
found on the Eubank website, www.EubankWallMount.com.
INSTALLATION (M: SEQUENCE OF OPERATION)
COOLING MODE
Low-voltage thermostat terminal R is connected to Y, O, and
G, at the unit low-voltage terminal board.
The system reversing valve is energized during the cooling
mode. Power is supplied to the reversing valve solenoid
through the low-voltage O terminal. The low-voltage Y terminal
to the control will energize the contactor latch coil (causing
the contactor to energize the compressor). The low-voltage
Y terminal to the control will also energize the control’s timer.
During the cooling mode, the defrost thermostat is open (coil
temperature is above 30°F) and will not allow the time to be
accumulated to initiate the defrost mode. The outdoor fan is
wired through the N/C points of the control’s relay and the
N/O points of the contactor. The fan motor will be energized
whenever the contactor is energized (except during defrost).
HEATING MODE
Low-voltage terminal R is connected to Y and G, at the unit
low-voltage terminal board.
The system reversing valve is not powered during the heating
mode. With the thermostat system switch turned to heat. The
Y terminal will energize the compressor, outdoor fan, and the
indoor blower.
DEFROST MODE
To prevent ice build-up on the coil during the heating mode, as
the outdoor coil temperature falls below 30°F ±5°F, an outdoor
defrost thermostat closes. (This thermostat is located on a coil
tube.) When the thermostat closes, the timer on the defrost
control starts accumulating the compressor run time. After the
selected time (30, 60,or 90 minutes) has been accumulated,
the controller will start the defrost cycle regardless of the
outside temperature. During the defrost cycle, the system
is switched back into the cooling mode by the control deenergizing the reversing valve solenoid. The N/C pole of the
control fan relay is opened, turning off the outdoor fan to allow
the outdoor coil to be warmed (defrosted) faster. The defrost
control energizes the indoor auxiliary heat relays through the
E terminal to temper the indoor supply air. This terminal should
be connected to E (second-stage heat) on the thermostat.
After the defrost thermostat reaches 65°F ±5°F, the defrost
cycle will end. The control will not allow the defrost to continue
longer than 10 minutes.
DEFROST TIME SELECTION
The defrost control has three selectable time intervals: 30, 60
and 90 minutes. The timing is factory set at 60 minutes. This
timing has been determined by testing to provide the best
operating efficiency. In areas where the humidity is lower than
normal, the timer may be set to a higher time (90 minutes). To
change the time, move the timer jumper to the postmarked
30 for 30 minutes, 60 for 60 minutes, or 90 for 90 minutes.
DEFROST TEST POST
The defrost control has test posts to speed up the defrost time
setting by a factor of 256.
If you want to initiate a defrost without waiting for the time to
accumulate, you can jumper the two test pins (marked test).
If the coil temperature is above 30°F you will need to jumper
the DFT (defrost thermostat) terminals to simulate a closed
thermostat. The defrost cycle should occur in 7 seconds for
a 30-minute setting, 14 seconds for a 60-minute setting, and
17 seconds for an 90-minute setting. If the jumper is removed
immediately when the defrost cycle starts, the cycle will end if
the defrost thermostat is opened (coil above 65°F). If the test
pins remain jumped, and the defrost thermostat is closed, the
defrost will end in 2.3 seconds, which is the 10-minute default.
DURING THE ABOVE TEST, DO NOT CONTACT OR SHORT
ANY OTHER PIN. THIS MAY DAMAGE THE CONTROL.
INSTALLATION (N: HIGH-PRESSURE LOCKOUT)
FIELD CHARGING
Compared to a cooling-only unit, a heat pump is difficult to
field charge correctly without the use of charging scales. It
is recommended the charge be weighed in with an accurate
charging scale. The correct charge weight can be found on
the unit name plate.
TH Series units may be equipped with a high-pressure switch.
This switch is wired through a lockout relay to lock out the
system if the high side pressure exceeds 650 psi. The high
side pressure MUST be below 450 psi before the system can
be reset.
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
6
EXPLODED PARTS DRAWING - 36/42/48/60
7
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
PART NUMBER
DESCRIPTION
1
COMP-BZP31-001
ZP31K5EPFV130
X
1
3020004
ZP31K5ETF5130
X
1
3020005
ZP31K5ETFD130
X
1
COMP-BZP44-001
ZP44K5EPFV130
X
1
COMP-BZP44-003
ZP44K5ETF5130
X
1
COMP-BZP44-004
ZP44K5ETFD130
X
1
COMP-BZP54-001
ZP54K5EPFV130
X
1
COMP-BZP54-003
ZP54K5ETF5130
X
1
COMP-BZP54-004
ZP54K5ETFD130
X
2
COND-H436
OUTDOOR COIL
XXX
2
3070001
OUTDOOR COIL
XXXXX
X
3
550505
DISTRIBUTOR 3 CIRCUIT-OD COIL
XXX
3
550517
DISTRIBUTOR 6 CIRCUIT-OD COIL
XXXXX
X
4
T36-EVAP
EVAP COIL
XXX
4
3070002
EVAP COIL
XXXXX
X
5
550517
DISTRIBUTOR 6 CIRCUIT-EVAP
XXX
5
550521
DISTIBUTOR 9 CIRCUIT-EVAP
XXXXX
X
6
TXV410-E3
TXV VALVE
XXX
6
TXV410-E5-HP
TXV VALVE
XXXXX
X
6A
550792
REVERSING VALVE
7
61508
BI-FLOW FILTER DRIER
XXXXXXXXX
8
T36-0008
FAN SHROUD HV36
XXX
8
T60-0008
FAN SHROUD HV48-60
XXXXX
X
9
421508
MOTOR MOUNT OD FAN
XXX
9
259109
MOTOR MOUNT OD FAN
XXXXX
X
10
025015/3010014
MOTOR OD 230V 825 RPM
X
X
10
025018
MOTOR OD 460V 1/4 HP 825 RPM
X
10
351145
MOTOR OD 230V 1075 RPM 1/2 HP
XXX
X
10
351146
MOTOR OD 460V 1/2 HP
X
X
11
259114
OD FAN BLADE 22" HV36-60
XXXXXXXXX
12
359104
1/3 HP ECM BLOWER MTR 230V/277V
XXX
12A
3010020
1/3 HP ECM MODULE
XXX
12
359105
1/2 HP ECM BLOWER MTR 230V/277V
XXXXX
X
12A
3010021
1/2 HP ECM MODULE
XXXXX
X
12B
T36-0131
ECM MODULE BRACKET
XXXXXXXXX
13
050001
R.BLOWER WHEEL 98-7T CW
XXX
13A
050000
L.BLOWER WHEEL 98-7T CCW
XXX
13
3020002
R.BLOWER WHEEL 100-9T CW
XXXXX
X
13A
3020003
L.BLOWER WHEEL 100-9T CCW
XXXXX
X
14
421506
BLWR MTR BRKT
XXXXXXXXX
14A
454280
BLWR MTR BRKT GROMMET TUBE
XXXXXXXXX
14B
454282
BLWR MTR BRKT WASHER TUBE
XXXXXXXXX
14C
454284
BLWR MTR BRKT MOUNTING SLEEVE
XXXXXXXXX
14D
454236
BLWR MTR BRKT WASHER
XXXXXXXXX
14E
750058
BLWR MTR BRKT BOLT(1/4-20)
XXXXXXXXX
15
T36-0000B
ASSEMBLY LEFT SIDE PANEL HV36
XXX
15A
T36-0135
OD.GRILL INLET LEFT SIDE HV36
XXX
15
T60-0008
ASSEMBLY LEFT SIDE PANEL HV48-60
XXXXX
X
15A
T60-0091
OD.GRILL INLET LEFT SIDE HV48-60
XXXXX
X
15B
T36-0126
ERV INTAKE AIR PANEL
XXXXXXXXX
16
T36-0001B
ASSEMBLY RIGHT SIDE PANEL HV36
XXX
16A
T36-0134
OD.GRILLINLET RIGHT SIDE HV36
XXX
16
T60-0001B
ASSEMBLY RIGHT SIDE PANEL HV48-60
XXXXX
X
16A
T60-0081
OD.GRILL INLET RIGHT SIDE HV48-60
XXXXX
X
17
T36-0007B
TOP HV36
XXX
17
T60-0007B
TOP HV48-60
XXXXX
X
18
T36-0012
ASSEMBLY REAR PANEL HV-36
XXX
18
T60-0012
ASSEMBLY REAR PANEL HV48-60
XXXXX
X
19
T36-0003
ASSEMBLY DIVIDER DECK HV-36
XXX
19
T60-0003
ASSEMBLY DIVIDER DECK HV48-60
XXXXX
X
20
T36-0005
ASSEMBLY BLOWER DECK HV36
XXX
20
T60-0005
ASSEMBLY BLOWER DECK HV48-60
XXXXX
X
21
2022-0006P
ASSEMBLY DRAIN PAN HV36
XXX
21
2023-0006P
ASSEMBLY DRAIN PAN HV48-60
XXXXX
X
22
T36-0098
BASE PAN ASSEMBLY HV36
XXX
22
T60-0098
BASE PAN ASSEMBLY HV48-60
XXXXX
X
23
T36-0018
BLOWER FLANGE HV36
XXX
23
T60-0018
BLOWER FLANGE HV60
XXXXX
X
24
T36-0010B
UPPER FRONT PANEL HV36
XXX
24
T60-0010B
UPPER FRONT PANEL HV48-60
XXXXX
X
24A
2022-5062
DISCONNECT ACCESS DOOR HV36-60
XXXXXXXXX
24B
70518
DISCONNECT ACCESS DOOR LATCH HV36-60
XXXXXXXXX
25
T36-0011B
MIDDLE FRONT PANEL (no fresh air) HV36
XXX
25
T36-0011EB
MIDDLE FRONT PANEL (economizer f/a) HV36
XXX
25
T36-0011FB
MIDDLE FRONT PANEL (barometric f/a) HV36
XXX
36S
36T
36D
42/48S
42/48T
42/48D
60S
60T
60D
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
8
Loading...
+ 17 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.