Eubank TH Series, TH36-42-48-60 Installation & Operation Manual

Heat Pump Product Manual
Vertical Wall-Mount Heat Pumps
Installation & Operation Manual
TH Series 10 EER Vertical Wall-Mount Heat Pumps
MODELS:
TH36-42-48-60
This manual may include information for options and features which may not be
included on the unit being installed. Refer to the unit data label or Model Identication
to determine which features and options this unit is equipped with.
INSTALLER: Afx the instructions on the inside of the building adjacent to the thermostat. END USER: Retain this manual for future reference.
A Division of the AIRXCEL® Commercial/Industrial Group
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015
E-mail: eubanksales@airxcel.com • Internet: www.EubankWallmount.com
The most current version of this manual can be found at www.EubankWallmount.com.
IMPORTANT
Manufactured By:
(229) 273-3636 • Fax (229) 273-5154
1
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev.10
Eubank TH Series Heat Pump I&O Manual
Part #03698
09/2018 Rev. 10
How To Use This Manual
This manual is intended to be a comprehensive guide to the installation of the Eubank® TH Series family of vertical packaged heat pumps. It contains installation, troubleshooting, maintenance, warranty, and application information. The information contained in this manual is to be used by the installer as a guide only. This manual does not supersede or circumvent any applicable national or local codes. For information on the efciency, cooling and heating performance, please refer to the TH Series Product Data Sheets. The most current version of all literature can be found on our website at www.EubankWallMount.com.
If you are installing the heat pump unit, rst read Chapter 1 and scan the entire manual before beginning the installation as described in Chapter 2. Chapter 1 contains general, descriptive information and provides an overview which can speed up the installation process and simplify troubleshooting.
If a malfunction occurs, follow this troubleshooting sequence:
1. Make sure you understand how the heat pump unit works (Chapters 1 & 3).
2. Identify and correct installation errors (Chapter 2).
3. Refer to the troubleshooting information in Chapter 4.
4. Identify defective part(s). (Chapter 5).
If you are still unable to correct the problem, contact the Factory at 1-800-841-7854 for additional assistance.
Please read the following “Important Safety Precautions” before beginning any work. Failure to follow these rules may result in death, serious bodily harm, property damage and damage to the equipment.
Important Safety Precautions
1. USE CARE when LIFTING or TRANSPORTING equipment.
2. TRANSPORT the UNIT UPRIGHT. Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components.
3. TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on the equipment. LINE VOLTAGES ARE HAZARDOUS or LETHAL.
4. OBSERVE and COMPLY with ALL applicable PLUMBING, ELECTRICAL, and BUILDING CODES and ordinances.
5. SERVICE may be performed ONLY by QUALIFIED and EXPERIENCED PERSONS.
* Wear safety goggles when servicing the refrigeration circuit * Beware of hot surfaces on refrigerant circuit components * Beware of sharp edges on sheet metal components * Use care when recovering or adding refrigerant
6. Use COMMON SENSE - BE SAFETY-CONSCIOUS
This is the safety alert symbol . When you see this symbol on the unit and in the instruction manuals be alert to the potential for personal injury. Understand the signal word DANGER, WARNING, CAUTION and IMPORTANT. These words are used to identify levels of the seriousness of the hazard.
DANGER Failure to comply will result in death or severe personal injury and/or property damage.
WARNING
Failure to comply could result in death or severe personal injury and/or property dam­age.
CAUTION Failure to comply could result in minor personal injury and/or property damage.
IMPORTANT
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev. 10
Used to point out helpful suggestions that will result in improved installation, reliability or operation.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.
© 09/2018 Airxcel Commercial/Industrial Group
2
Your equipment is covered by a LIMITED WARRANTY against defects in material and workmanship.
This is a vertical, wallmount unit designed for many different applications in both residential and commercial settings. It is self-contained and arrives completely assembled, factory­charged and wired. The unit is 100% run-tested at the factory to ensure proper operation. Your unit is supplied with high­quality copper tubing and enhanced aluminum-finned coils for high heat transfer efficiency and long life. The unit cabinet is constructed of G-90 galvanized steel. All exterior surfaces are finished with a baked-on polyester coating. This will provide excellent corrosion protection in most applications. However, if the unit is installed in an area with a corrosive atmosphere, such as near an industrial plant or on the seacoast, additional coating should be considered to extend the life of the coils and cabinet.
This unit was designed for up to 105ºF of ambient temperature for the cooling mode; for heating mode, this unit was designed for up to 78ºF of room temperature and minimum 15ºF ambient temperature.
INSPECTION AND UNPACKING
A thorough inspection of the shipping container should be made immediately upon receiving your unit. Look for any punctures or openings. If it appears as if damage has occurred, it should be noted on the freight bill before signing. The delivering carrier should be contacted immediately to inspect damage, and no installation work should begin until this inspection is completed.
DANGER
BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT, POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK, INJURY, DEATH, OR DAMAGE TO EQUIPMENT.
SAFETY RULES
WARNING
FAILURE TO FOLLOW THESE RULES AND INSTRUCTIONS COULD CAUSE A MALFUNCTION DESTRUCTION OF EQUIPMENT WHICH COULD RESULT IN PROPERTY DAMAGE, SERIOUS BODILY INJURY, OR DEATH.
1. Installation and repair MUST be done by a qualified person. The equipment should be inspected before use and at least once annually by a professional service person.
2. AVOID ELECTRICAL SHOCK! Turn power OFF when servicing. There may be more than one disconnect switch to de-energize unit.
3. Close cover(s) before returning breaker(s) to “ON” position.
4. Please observe good safety practices by wearing personal protective equipment such as gloves and safety glasses to avoid injury.
5. Installation MUST conform to local codes. In the absence of local codes, refer to the National Electrical Code (NEC), ANS/NFPA No. 70-1993 and recommendations made by the National Board of Fire Underwriters.
In all cases, the equipment MUST be installed in accordance with the installation instructions described in this manual.
WARNING
IMPROPER INSTALLATION MAY DAMAGE EQUIPMENT, CAN CREATE HAZARD, AND WILL VOID THE WARRANTY
OPERATING INSTRUCTIONS
If heating and cooling functions are controlled by separate thermostats, turn the furnace thermostat to the “OFF” position during the cooling season to prevent simultaneous operation of the heating and cooling systems. Reverse the procedure during the heating season.
If the same thermostat controls both heating and cooling functions, set the thermostat to either HEAT or COOL as desired.
Set the desired temperature on your thermostat and set the fan switch to “ON” (for continuous air circulation) or to “AUTOMATIC” (for air circulation only when the heat pump system is operating).
IMPORTANT
Wait at least three (3) minutes after turning the air conditioner off before trying to restart. If an attempt is made to start the compressor before the refrigerant pressures are equalized, the compressor motor may trip on its overload. An additional waiting period will be required before restarting.
MAINTENANCE
1. Always install and keep filters clean. Check filters every 2 weeks. Clean or replace if necessary. The factory-installed filter is located behind the center front access panel.
TO CHANGE SYSTEM FILTER:
A. Turn the power to the unit off at the unit disconnect. The
disconnect is located on the front of the unit behind a
small access door. B. Remove the front center access door from the unit. C. Remove and replace the filter with the type and size
indicated in the table below. D. Replace the access door and turn on the power to the unit
NOTE: If your system has a filter grille installed in the return air opening, the unit filter should have been discarded during installation.
The filter installed into the return air grille assembly should be replaced with the same size and type provided with the grille.
If your system is equipped with a fresh air intake, the filter for the fresh air assembly is accessed through the front center panel. The filter is a permanent washable type.
Unit Model QTY Filter Size - In (mm) Type
36 1 16 x 30 x 1 (406 x 762 x 25) (Standard) Disposable 36 1 16 x 30 x 2 (406 x 762 x 51) (Optional) Pleated 42,48,60 1 20 x 30 x 1 (508 x 762 x 25) (Standard) Disposable 42,48,60 1 20 x 30 x 2 (508 x 762 x 51) (Optional) Pleated
WARNING
SERIOUS INJURY MAY RESULT IF WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL CONNECTIONS OR POWER SOURCE.
3
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
TO CLEAN FRESH AIR INTAKE FILTER:
A. Follow steps A and B at left
“TO CHANGE SYSTEM FILTER”.
B. Gently pull out the filter from the
bottom. C. Wash the filter with water. D. Reinstall the filter, by sliding it into the
retaining rail. E. Replace the access door and turn the
power on to the unit.
2. Keep the outdoor coil clean. Wash it down with a garden hose if necessary.
BE SURE THE UNIT DISCONNECT IS IN THE “OFF” POSITION AND THAT ALL ELECTRICAL POWER TO THE UNIT IS TURNED OFF BEFORE CLEANING THE SYSTEM.
3. Since the heat pump is located outdoors, it is exposed to all weather elements. Treat it with a good automobile paste wax twice a year (in the spring and fall).
Check with your contractor if you have any questions regarding the maintenance or operation of your unit.
INSTALLATION (A: CODES)
The installer SHALL comply with all local, state, and federal codes and/or regulations pertaining to this type of equipment and its installation. Such codes and/or regulations should take precedence over any recommendations contained herein.
Installations SHALL be made in accordance with the National Electrical Code, local codes, and recommendations made by the National Board of Fire Underwriters.
INSTALLATION (B: UNIT SITE SELECTION)
1. To eliminate noise from being transmitted into noise sensitive areas, the unit should NOT be installed on walls adjoining bedrooms, sleeping quarters, or adjacent to windows.
2. Locating the unit as close as possible to the main duct system or area to be conditioned, will prevent lengthy duct runs and unnecessary thermal and air-pressure losses.
3. The clearance to combustibles is 0” on all sides, and 1/4” for the first three (3) feet of supply duct.
4. The condenser air inlets (left, right and bottom inlets) SHALL be located at least 8” away from walls or other obstructions for unrestricted airflow.
5. The condenser air outlet should be located at least 6’ away from any obstructions to prevent recirculation of condenser air.
6. Bottom of the unit SHALL be located at least 12” away from the ground or other obstructions for unrestricted airflow.
7. Service clearance is 28” from the electrical box access panel located on the front of the unit and 28” from the center, upper, and lower front access panels.
8. The wall selected for unit installation MUST be able to or be made to safely support the weight of the unit.
9. Do NOT locate where heat, lint or exhaust fumes will be discharged on the unit (as from dryer vents).
INSTALLATION (C: UNIT PREPARATION)
1. TH Series model units have top rain flashing built onto the unit. The bottom-mounting flange for all models is shipped separately and in place. (Refer to “Section J. Unit Installation” for the recommended use of the bottom flange.)
2. Electrical entrances are located on the right side and left side of all TH Series units. Refer to “Section H. Electrical Hook-up” for details.
3. Bend the lids of return and supply opening to form a return and supply air collars and install air gaskets.
4. The supply and return air ducts should be checked to be sure they:
e. Match the openings on the unit to be installed. f. Have the same distance between them vertically as
the openings on the unit to be installed.
5. Return and supply grilles must be used when the return and supply are not ducted. When a supply grille is used in the installation, the louver spacing must be no greater than 5/8 inch.
6. If the factory-installed filter is used on your installation, access to the filter is made through the center panel on the front of the unit.
IF A REMOTE FILTER IS USED, SUCH AS A FILTER GRILLE, THE FACTORY-INSTALLED FILTER MUST BE REMOVED AND DISCARDED.
INSTALLATION (D: DUCTWORK)
1. Properly-sized duct systems are critical for satisfactory operation of any air conditioning system. All ductwork MUST be correctly sized for the design air flow requirement of the equipment.
2. The recommended operation duct static is to deduct 0.07” W.C. for any size of heater 5 kW to 20 kW on factory or field-installed heaters.
3. Ductwork routed through wall cavities, as well as any duct not in conditioned space, MUST be insulated. Supply ducting routed through exterior walls MUST be insulated with 1” insulation to the back of the unit.
4. Supply and return air ducts should be flush with the exterior wall and sized to fit over the unit duct collars in order to compress the collar air gasket.
5. If supply duct is flashed to the exterior of a building constructed with combustible material, the flashing MUST be insulated in order to maintain the required clearances to combustible materials. Required clearance is 1/4” for the first three (3) feet of supply duct.
INSTALLATION (E: FILTERS)
1. One-inch disposable filters are supplied standard in each unit. Two-inch disposable filters can also be used and are available as an option. The filter rack is adjustable to accommodate 2” filters. The filter rack on this series is adapted by removing the 1” filter brackets. Refer to the Maintenance section for the procedures for changing the filters.
2. If a filter grille is used in the installation, the filter should be properly sized to allow a maximum velocity of 400 FPM.
WHEN A FILTER IS USED, THE FACTORY-INSTALLED FILTER MUST BE REMOVED.
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev. 10
4
INSTALLATION (F: ELECTRICAL POWER)
The installer MUST check available power to make certain it matches the unit nameplate rating and that constant voltage can be maintained to the unit. Unsatisfactory and unsafe performance could otherwise result. The local power company should be contacted about questions concerning power supply.
INSTALLATION (G: BREAKER/DISCONNECT)
These units are standard equipped from the factory with a unit disconnect. This is in the form of a circuit breaker (230V models) or disconnect (460V models). If an optional electric heat kit is to be installed, follow the instructions included with the heater assembly. See Figure 1 for reference.
WARNING
ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A QUALIFIED, LICENSED ELECTRICIAN. IMPROPER ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN CREATE A HAZARD AND WILL VOID WARRANTY.
INSTALLATION (H: ELECTRICAL HOOKUP)
The line voltage electrical service can be routed through the right side panel or left side panel. Each area is supplied with two line voltage knock-outs (1/2” – 3/4” and 1” – 1 1/4”). Low voltage wiring can be routed through the right side panel.
NOTE: When routing line voltage through the return air compartment, conduit MUST be used (even though this is a dry area) to comply with the NEC code. Refer to the ELECTRICAL DATA tables for minimum wire size and maximum breaker size. All wire sizes listed under the dual-feed circuit column are based on no more than three (3) conductors in the same conduit. If two circuits or more than three (3) conductors are to be routed in the same conduit, the ampacity of the wire size listed MUST be derated. Refer to Article 310 of the NEC code for adjustment factors. Be sure to install a ground wire of the proper size to the unit’s equipment ground lug.
The blower motor must be powered by 240V or 277V supply. If the unit is supplied by 460V power, and a neutral connection is unavailable, the motor may be powered by a 460V to 277V or 240V transformer.
powered fresh air option, seven (7) conductor thermostat wires should be run to the unit. Thermostat wire should be sized as shown on the table below.
Wire Gauge Maximum Length - Ft (meters)
20 45 (13.7) 18 60 (18.3) 16 100 (30.5) 14 160 (48.8) 12 250 (76.2)
Refer to wiring diagrams for connection details.
STAGING OF ELECTRIC HEAT Units with electric heat assemblies are wired for two stage heat in normal operation. The first stage is refrigerant heat (Y and G terminals are energized and the O terminal is de­energized). The second stage is auxiliary resistance heat (W is energized). TH Series units are equipped with an emergency heat lock-out relay. This will disable the compressor when the E terminal is energized. Do not install a jumper between the W and E terminals; this would keep the compressor contacts from being energized and prevent the compressor from operating.
INSTALLATION (J: UNIT INSTALLATION)
TH UNITS ARE FOR USE IN 1-STORY BUILDINGS ONLY.
1. As previously stated, the wall that the unit is to be installed onto MUST be strong enough to support the unit under the condition for which it will be used. For example, a unit to be installed on a building that is intended to be transported will require more wall strength than a unit installed at a permanent site. Existing walls may need additional reinforcement. NEVER RELY ON EXTERIOR SIDING OR PLYWOOD TO SUPPORT THE UNIT. Figure 2 below represents a typical installation of a single-story stud wall at a permanent site. Since building materials and techniques vary with regions and intended use, a building contractor and/or local building code official MUST be consulted for suitable construction methods.
2. Locate and attach the lower mounting bracket in the desired location on the building.
3. Apply a suitable amount of caulk or silicone across the entire length of the top rain flashing and side mounting flanges.
4. Remove the flanges on both ends of the pallet and slide the unit approximately 2” off the rear of pallet. Lift unit gently into location with fork truck, taking care to align unit with lower mounting bracket.
5. While allowing a small portion of weight on the lower bracket, push the unit against the wall and fasten appropriately.
INSTALLATION (I: LOW VOLTAGE WIRING)
230 volt, 1- and 3-phase units are equipped with dual-primary voltage transformers for 208/240 volt operation. These models are factory wired to the 240 volt tap. For 208 volt operation connect the factory-installed black wires from the 240 volt tap to the 208 volt tap. The acceptable voltage range of the tap is as follows.
Tap Voltage Range
240 Volt 253 - 216 208 Volt 220 - 187
Six (6) conductor thermostat wires should be run from the thermostat location to the unit. If the unit is equipped with a
Unit Model A B
36 39 71
42/48/60 42 86 1/2
MOUNTING FLANGE BOLT
PATTERN DIMENSIONS
5
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
SPECIAL NOTES FOR UNIT INSTALLATION
1. Minimum 12” clearance at the bottom of the unit for unrestricted airflow
2. Ensure the ambient temperature uniformity around unit
3. Intake and discharge of the outdoor air flow must not be restricted or altered
4. All insulation and sealing related to the installation must be completed properly
5. External Static pressure should not exceed the minimum value in the AHRI Standard 390
INSTALLATION (K: CONDENSATE DRAIN)
A 3/4” drain hose is located on the bottom side of the unit. The drain may be extended for condensate removal to comply with local codes (use fitting size or larger). Install a condensate trap on this line.
INSTALLATION (L: OPTIONS)
Eubank wallmount air conditioners and heat pumps have the ability to equip a variety of options:
Electric Heat 5-20kW
Sound Attenuation Module
Powered Ventilation Damper
Low Ambient Packages
Economizer
Lead Lag Controllers
Option kits must be installed according to the respective installation manual to ensure safe and reliable operation. Installation manuals are included with the option kit or can be found on the Eubank website, www.EubankWallMount.com.
INSTALLATION (M: SEQUENCE OF OPERATION)
COOLING MODE
Low-voltage thermostat terminal R is connected to Y, O, and G, at the unit low-voltage terminal board.
The system reversing valve is energized during the cooling mode. Power is supplied to the reversing valve solenoid through the low-voltage O terminal. The low-voltage Y terminal to the control will energize the contactor latch coil (causing the contactor to energize the compressor). The low-voltage Y terminal to the control will also energize the control’s timer. During the cooling mode, the defrost thermostat is open (coil temperature is above 30°F) and will not allow the time to be accumulated to initiate the defrost mode. The outdoor fan is wired through the N/C points of the control’s relay and the N/O points of the contactor. The fan motor will be energized whenever the contactor is energized (except during defrost).
HEATING MODE
Low-voltage terminal R is connected to Y and G, at the unit low-voltage terminal board.
The system reversing valve is not powered during the heating mode. With the thermostat system switch turned to heat. The Y terminal will energize the compressor, outdoor fan, and the indoor blower.
DEFROST MODE
To prevent ice build-up on the coil during the heating mode, as the outdoor coil temperature falls below 30°F ±5°F, an outdoor
defrost thermostat closes. (This thermostat is located on a coil tube.) When the thermostat closes, the timer on the defrost control starts accumulating the compressor run time. After the selected time (30, 60,or 90 minutes) has been accumulated, the controller will start the defrost cycle regardless of the outside temperature. During the defrost cycle, the system is switched back into the cooling mode by the control de­energizing the reversing valve solenoid. The N/C pole of the control fan relay is opened, turning off the outdoor fan to allow the outdoor coil to be warmed (defrosted) faster. The defrost control energizes the indoor auxiliary heat relays through the E terminal to temper the indoor supply air. This terminal should be connected to E (second-stage heat) on the thermostat.
After the defrost thermostat reaches 65°F ±5°F, the defrost cycle will end. The control will not allow the defrost to continue longer than 10 minutes.
DEFROST TIME SELECTION
The defrost control has three selectable time intervals: 30, 60 and 90 minutes. The timing is factory set at 60 minutes. This timing has been determined by testing to provide the best operating efficiency. In areas where the humidity is lower than normal, the timer may be set to a higher time (90 minutes). To change the time, move the timer jumper to the postmarked 30 for 30 minutes, 60 for 60 minutes, or 90 for 90 minutes.
DEFROST TEST POST
The defrost control has test posts to speed up the defrost time setting by a factor of 256.
If you want to initiate a defrost without waiting for the time to accumulate, you can jumper the two test pins (marked test). If the coil temperature is above 30°F you will need to jumper the DFT (defrost thermostat) terminals to simulate a closed thermostat. The defrost cycle should occur in 7 seconds for a 30-minute setting, 14 seconds for a 60-minute setting, and 17 seconds for an 90-minute setting. If the jumper is removed immediately when the defrost cycle starts, the cycle will end if the defrost thermostat is opened (coil above 65°F). If the test pins remain jumped, and the defrost thermostat is closed, the defrost will end in 2.3 seconds, which is the 10-minute default.
DURING THE ABOVE TEST, DO NOT CONTACT OR SHORT ANY OTHER PIN. THIS MAY DAMAGE THE CONTROL.
INSTALLATION (N: HIGH-PRESSURE LOCKOUT)
FIELD CHARGING
Compared to a cooling-only unit, a heat pump is difficult to field charge correctly without the use of charging scales. It is recommended the charge be weighed in with an accurate charging scale. The correct charge weight can be found on the unit name plate.
TH Series units may be equipped with a high-pressure switch. This switch is wired through a lockout relay to lock out the system if the high side pressure exceeds 650 psi. The high side pressure MUST be below 450 psi before the system can be reset.
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev. 10
6
EXPLODED PARTS DRAWING - 36/42/48/60
7
Eubank TH Series Heat Pump I&O Manual
09/2018 Rev. 10
PART NUMBER
DESCRIPTION
1
COMP-BZP31-001
ZP31K5EPFV130
X
1
3020004
ZP31K5ETF5130
X
1
3020005
ZP31K5ETFD130
X
1
COMP-BZP44-001
ZP44K5EPFV130
X
1
COMP-BZP44-003
ZP44K5ETF5130
X
1
COMP-BZP44-004
ZP44K5ETFD130
X
1
COMP-BZP54-001
ZP54K5EPFV130
X
1
COMP-BZP54-003
ZP54K5ETF5130
X
1
COMP-BZP54-004
ZP54K5ETFD130
X
2
COND-H436
OUTDOOR COIL
XXX
2
3070001
OUTDOOR COIL
XXXXX
X
3
550505
DISTRIBUTOR 3 CIRCUIT-OD COIL
XXX
3
550517
DISTRIBUTOR 6 CIRCUIT-OD COIL
XXXXX
X
4
T36-EVAP
EVAP COIL
XXX
4
3070002
EVAP COIL
XXXXX
X
5
550517
DISTRIBUTOR 6 CIRCUIT-EVAP
XXX
5
550521
DISTIBUTOR 9 CIRCUIT-EVAP
XXXXX
X
6
TXV410-E3
TXV VALVE
XXX
6
TXV410-E5-HP
TXV VALVE
XXXXX
X
6A
550792
REVERSING VALVE
7
61508
BI-FLOW FILTER DRIER
XXXXXXXXX
8
T36-0008
FAN SHROUD HV36
XXX
8
T60-0008
FAN SHROUD HV48-60
XXXXX
X
9
421508
MOTOR MOUNT OD FAN
XXX
9
259109
MOTOR MOUNT OD FAN
XXXXX
X
10
025015/3010014
MOTOR OD 230V 825 RPM
X
X
10
025018
MOTOR OD 460V 1/4 HP 825 RPM
X
10
351145
MOTOR OD 230V 1075 RPM 1/2 HP
XXX
X
10
351146
MOTOR OD 460V 1/2 HP
X
X
11
259114
OD FAN BLADE 22" HV36-60
XXXXXXXXX
12
359104
1/3 HP ECM BLOWER MTR 230V/277V
XXX
12A
3010020
1/3 HP ECM MODULE
XXX
12
359105
1/2 HP ECM BLOWER MTR 230V/277V
XXXXX
X
12A
3010021
1/2 HP ECM MODULE
XXXXX
X
12B
T36-0131
ECM MODULE BRACKET
XXXXXXXXX
13
050001
R.BLOWER WHEEL 98-7T CW
XXX
13A
050000
L.BLOWER WHEEL 98-7T CCW
XXX
13
3020002
R.BLOWER WHEEL 100-9T CW
XXXXX
X
13A
3020003
L.BLOWER WHEEL 100-9T CCW
XXXXX
X
14
421506
BLWR MTR BRKT
XXXXXXXXX
14A
454280
BLWR MTR BRKT GROMMET TUBE
XXXXXXXXX
14B
454282
BLWR MTR BRKT WASHER TUBE
XXXXXXXXX
14C
454284
BLWR MTR BRKT MOUNTING SLEEVE
XXXXXXXXX
14D
454236
BLWR MTR BRKT WASHER
XXXXXXXXX
14E
750058
BLWR MTR BRKT BOLT(1/4-20)
XXXXXXXXX
15
T36-0000B
ASSEMBLY LEFT SIDE PANEL HV36
XXX
15A
T36-0135
OD.GRILL INLET LEFT SIDE HV36
XXX
15
T60-0008
ASSEMBLY LEFT SIDE PANEL HV48-60
XXXXX
X
15A
T60-0091
OD.GRILL INLET LEFT SIDE HV48-60
XXXXX
X
15B
T36-0126
ERV INTAKE AIR PANEL
XXXXXXXXX
16
T36-0001B
ASSEMBLY RIGHT SIDE PANEL HV36
XXX
16A
T36-0134
OD.GRILLINLET RIGHT SIDE HV36
XXX
16
T60-0001B
ASSEMBLY RIGHT SIDE PANEL HV48-60
XXXXX
X
16A
T60-0081
OD.GRILL INLET RIGHT SIDE HV48-60
XXXXX
X
17
T36-0007B
TOP HV36
XXX
17
T60-0007B
TOP HV48-60
XXXXX
X
18
T36-0012
ASSEMBLY REAR PANEL HV-36
XXX
18
T60-0012
ASSEMBLY REAR PANEL HV48-60
XXXXX
X
19
T36-0003
ASSEMBLY DIVIDER DECK HV-36
XXX
19
T60-0003
ASSEMBLY DIVIDER DECK HV48-60
XXXXX
X
20
T36-0005
ASSEMBLY BLOWER DECK HV36
XXX
20
T60-0005
ASSEMBLY BLOWER DECK HV48-60
XXXXX
X
21
2022-0006P
ASSEMBLY DRAIN PAN HV36
XXX
21
2023-0006P
ASSEMBLY DRAIN PAN HV48-60
XXXXX
X
22
T36-0098
BASE PAN ASSEMBLY HV36
XXX
22
T60-0098
BASE PAN ASSEMBLY HV48-60
XXXXX
X
23
T36-0018
BLOWER FLANGE HV36
XXX
23
T60-0018
BLOWER FLANGE HV60
XXXXX
X
24
T36-0010B
UPPER FRONT PANEL HV36
XXX
24
T60-0010B
UPPER FRONT PANEL HV48-60
XXXXX
X
24A
2022-5062
DISCONNECT ACCESS DOOR HV36-60
XXXXXXXXX
24B
70518
DISCONNECT ACCESS DOOR LATCH HV36-60
XXXXXXXXX
25
T36-0011B
MIDDLE FRONT PANEL (no fresh air) HV36
XXX
25
T36-0011EB
MIDDLE FRONT PANEL (economizer f/a) HV36
XXX
25
T36-0011FB
MIDDLE FRONT PANEL (barometric f/a) HV36
XXX
36S
36T
36D
42/48S
42/48T
42/48D
60S
60T
60D
Eubank TH Series Heat Pump I&O Manual 09/2018 Rev. 10
8
Loading...
+ 17 hidden pages