Disconnect the power and clean the exterior
only of this switch with a moist (not wet) cloth.
Do not use any chemical or abrasive cleaners.
Incandescent lighting loads - 16A maximum
Fluorescent lighting loads - 6A maximum
Compact lluorescent/low energy lighting loads
Low voltage lighting loads - 3A maximum
Note: a maximum of 6 fl uorescent light
fi ttings is recommended with total power factor
correction capacitance not exceeding 40µf.
Fans and ventilation equipment – 3A maximum
SON light fi ttings must be switched via a
contactor or other external relay. If you are
using this switch to control magnetic switch
start fl uorescent fi ttings and your light fi ttings
strike inconsistently, a power factor correction
capacitor may be required. If your light fi tting
fl ickers or fails to turn off correctly, this is most
likely to be due to incorrect or missing power
Check with the manufacturer of the light fi tting
and/or supplier of power factor correction
capacitors for the exact specifi cation required
for your installation. A minimum of 1µF for each
fi tting may be connected.
If you experience problems:
If your light is defective or develops a fault,
please return it to the place where you bought
it. You can call our Helpline for advice. The
Helpline will gladly give advice on any aspect of
any Eterna Lighting product but may not be able
to give specifi c instructions regarding individual
If in doubt, consult a qualifi ed electrician.
Email: sales@eterna-lighting.co.uk
For all other information visit our website
www.eterna-lighting.co.uk

front of the switch and lift off the lid.
you will need to make hole(s) in the rear
to the colour code on previous page.
to wait 20s after restoring the power before
If you are using this switch to control
with a minimum value of 1µF for each light
The timer can be triggered by applying a live
the parts listed on the front of this booklet. If
This time delay switch must be installed by
from www.communities.gov.uk following the
As the buyer, installer and/or user of this
that it is fi t for the purpose for which you have
This product is designed and constructed
than normal ambient temperatures, may result
total Wattage and start up surge current (if
your switch is part of the provision of a new
the requirements of the Building Regulations
When making connections, ensure that the
terminals are tightened securely and that
the terminals are tightened onto the bared
This switch is double insulated; do not connect
You are advised at every stage of your
tests that should be carried out: these tests are