Eterna Lighting SELMDDEM3 Installation Instructions

REPLACEMENT BATTERY TYPE:
3.6V 800mAh Ni-Cd batteries.
BATTERY REPLACEMENT:
If after routine operation check, the lamp does not remain lit for the three hour period, a new batter y pack may be required.
01. Switch o the electricity at the mains.
02. Remove the diuser.
03. Remove the two screws indicated on the gear tray and open the tting.
04. Disconnect the battery from the circuit board.
05. Cut the cable tie that secures the battery pack in place and lift the battery pack out of the tting.
06. Write current date on the new battery pack.
07. Fit new battery pack securing in place using
cable tie.
08. Connect the battery to the circuit board.
09. Close and secure gear tray.
10. Replace diuser.
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” eective August 2005—UK WEEE Regulations eective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
WHEN YOUR PRODUCT COMES TO THE END OF ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE R ECYCLE IT WHER E FACILITIES EXIST  DO NOT DISPOSE WIT H HOUSEHOLD WASTE.
INDUSTRIAL BATTERIES:
Within cer tain products Eterna Lighting Ltd places lead acid, lithium ion, nickel cadmium & nickel metal hydride batteries on the market. Industrial batteries are subject to waste regulation under the Waste Bat teries and Accumulators Regulations 2009 and should be disposed of responsibly. Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged to take back, free of charge and within a reasonable time, waste industrial batteries of the same chemistr y supplied to a Purchaser, for treatment and recycling and is required to do this in any calendar year new industrial batteries are placed on the market. In certain circumstances, this may include batteries not originally supplied by Eterna. If any Purchaser requires Eterna to take back Industrial batteries, they should write to the Operations Director, Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then advise on the necessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.
INSTALLATION INSTRUCTIONS
A guide for qualied electricians
3 HOURS DURATION IN EMERGENCY MODE
Pack contents:
The light source is designed to last the lifetime of the luminaire.
The light source contained in this luminaire shall only be replaced by the manufacturer, service agent or a similar qualied person.
CAUTION, RISK OF ELECTRIC SHOCK.
Email: sales@eterna-lighting.co.uk / technical@eterna-lighting.co.uk
Visit our website: www.eterna-lighting.co.uk
SPECIFICATIONS:
Self test in accordance with BS EN 62034 : 2012
Rated wattage: 3.5W Viewing distance: 30m
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting produc t, but may not be able to give specic instructions regarding individual installations.
Made in ChinaIssue 1120
Model:
SELMDDEM3
Self Test Recessed LED Emergency Drop Sign
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
AND RETAIN FOR FUTURE REFERENCE
READ THIS FIRST:
DANGER!
Check the pack and make sure you have all of the parts listed on the front of this booklet. If not, contact the outlet where you bought this product.
This light tting must be installed by a competent person in accordance with the Building Regulations making reference to the current edition of the IEE Wiring Regulations (BS7671).
As the buyer, installer and/or user of this product it is your own responsibility to ensure that this tting is t for the purpose for which you have intended it. Eterna Lighting cannot accept any liability for loss, damage or premature failure resulting from inappropriate use.
This product is designed and constructed according to the principles of the appropriate British Standard and is intended for normal service. Use of this tting in any other environment, for example in higher than normal ambient temperatures, may result in a foreshortened working life.
The batteries supplied with this tting are consumable parts and therefore may be outside of any warranty oered.
Switch o the mains before commencing installation and remove the appropriate circuit fuse.
When working at heights, please use a suitable platform.
Suitable for indoor use only.
This product is suitable for installation on sur faces with normal ammability e.g. wood, plasterboard, masonry. It is not suitable for use on highly ammable sur faces (e.g. polystyrene, textiles).
This product is suitable for mounting in plasterboard ceilings, suspended ceilings and similar board surfaces. Check specication of ceiling for suitability.
Before making xing hole(s), check that there are no obstructions hidden beneath the mounting surface such as pipes or cables.
The chosen location of your new tting should allow for the product to be securely mounted and safely connected to the mains supply (lighting circuit).
Do not attach to surfaces which are damp or freshly painted.
This product is designed for permanent connection to xed wiring: this should be either a suitable lighting circuit (protected with a 5 or 6 Amp MCB or fuse) or a fused spur (with a 3 Amp fuse) via a fused connection unit.
Make connections to the electrical supply in accordance with the following code:
Live - Brown or Red, Neutral - Blue or Black Earth - Green and Yellow
When making connections, ensure that the terminals are tightened securely and that no strands of wire protrude. Check that the terminals are tightened onto the bared conductors and not onto any insulation. Wrap loose terminal block s well with insulating tape.
This product must be connected to Earth.
You are advised at every stage of your installation to double-check any electrical connections you have made. After you have completed your installation there are electrical tests that should be carried out: these tests are specied in the Wiring Regulations (BS7671) referred to in the Building Regulations.
IMPORTANT NOTES:
The control gear must be operated only within the enclosure supplied. The gear must not be operated outside of the enclosure.
The battery charging circuit and DC ballast are separated from the mains by at least basic (single layer) insulation.
When energised by a constant mains supply, the battery will be constantly charged whether or not the lamp is illuminated. On failure of the constant mains supply, the tting will switch automatically using transistorised switching from battery charging to battery discharge powering the lamp whether or not the lamp was illuminated before the power failure. Both the mains and battery supplies incorporate fuse protection: see tting for location and rating.
CLEANING:
Clean this t ting only with a soft dry cloth. Do not use any chemical or abrasive cleaners.
NOTE: please keep this instruction booklet and the test record in a safe place. A re ocer or other authorised person may want to see your record of inspection and testing.
INSTALLATION:
NOTE: Wires should be
stripped 13-14.5mm for best t with the push-t terminal block.
01. Undo the screws at each end of the diuser or front plate and lift o.
02. Decide which of the cable entries you need to use and remove one of the knock-outs if necessary.
03. Cut the hole in your mounting surface using the dimensions, see Fig 1.
04. Oer the tting up through the hole in the ceiling and allow to rest with the two large ears on the top side of your ceiling, see Fig 2.
05. Undo the screws at each end of the gear tray and allow to drop open.
06. Thread the mains supply cable in through the hole in the back of the tting.
07. Make the electrical connections according to the colour code opposite. Take care not to leave any strands protruding from the terminals and to tighten all terminals securely. Ensure also that the terminals clamp onto the bare wire and not onto the insulation.
10. Mark the current date on the battery pack.
11. Connect the battery pack to the circuit board.
12. Close the gear tray and secure using the screws removed earlier, see Fig 3.
13. Fit the sign panel into the slotted front plate:
A) Oer the top of the sign panel into the slot in the diuser from beneath and press down on the top of the diuser until it rests on the shoulders at the top of the panel.
B) Fit the small split-pins into the holes at each end of the top edge of the sign panel and bend the ends over to stop them from coming out again, see Fig 3.
14. Replace the diuser or front plate and tighten securely making sure that the tting is properly located around the hole in your ceiling.
NOTE: this unit has a permanent live mains supply, please ensure you isolate before removing cover.
There may also be a seperate switched supply that controls the emergency light tting - this also needs to be isolated.
13-14 .5m m
Wire
Fitting
Cover
Screw
115mm
Fig 2
Fig 1
320mm
375mm
Fig 3
CEILING
15mm
55mm
CEILING
Screw
Legend
Folded Pin Ends
Cover
ø
Loading...