Eterna Lighting EBPM3 Installation Instructions

REPLACEMENT BATTERY TYPE:
3.6V 3.0Ah Ni-CD.
BATTERY REPLACEMENT:
If after routine operation check, the lamp does not remain lit for the three hour period, a new bat tery pack may be required.
01) Switch o the electricity at the mains.
02) Allow batteries to fully discharge then reconnect to supply and allow to charge for 24 hours.
03) Test again for 3 hours, if light does not remain lit change the battery pack as follows:
04) Isolate the mains supply to the unit.
05) Remove the cover of emergency pack.
06) Unplug the battery lead.
07) Remove the battery pack .
08) Write current date on the new emergency pack.
09) Fit new battery pack.
10) Replace cover.
11) Restore power and allow to charge for 24 hours.
12) Perform operation check and update test record.
IMPORTANT NOTES:
The ballast and control gear must be operated only within the enclosure supplied. The gear must not be operated outside of the enclosure.
The battery charging circuit and DC ballast are separated from the mains by at least basic (single layer) insulation.
When energised by a constant mains supply, the battery will be constantly charged whether or not the lamp is illuminated. On failure of the constant mains supply, the tting will switch automatically using transistorised switching from battery charging to battery discharge powering the lamp whether or not the lamp was illuminated before the power failure. Both the mains and battery supplies incorporate fuse protection: see tting for location and rating.
If battery short circuits on battery terminals then fuse needs to be replaced before recharging.
Ballast is proofed against polarity reversal.
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” eective August 2005—UK WEEE Regulations eective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
WHEN YOUR PRODUC T COMES TO THE END O F ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE RECYCLE IT WHER E FACILITIES EXIST  DO NOT DISPOSE WITH HOUSEHOLD WASTE.
INDUSTRIAL BATTERIES:
Within cer tain products Eterna Lighting Ltd places lead acid, lithium ion, nickel cadmium & nickel metal hydride batteries on the market. Industrial batteries are subject to waste regulation under the Waste Batteries and Accumulators Regulations 2009 and should be disposed of responsibly. Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged to take back, free of charge and within a reasonable time, waste industrial batteries of the same chemistry supplied to a Purchaser, for treatment and rec ycling and is required to do this in any calendar year new industrial batteries are placed on the market. In cer tain circumstances, this may include batteries not originally supplied by Eterna. If any Purchaser requires Eterna to take back Industrial bat teries, they should write to the Operations Direc tor, Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then advise on the necessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.
CLEANING:
Clean this t ting only with a soft dry cloth.
Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your produc t is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting product, but may not be able to give specic instructions regarding individual installations.
A guide for qualied electricians
3 HOURS DURATION IN EMERGENCY MODE
DANGER!
NOTE: this unit has a
permanent live mains supply,
please ensure you isolate
before removing cover. There is
Pack contents:
1 x Emergency pack 1 x Maintenance check record
Emergency Pack For Commercial
LED Downlights & LED Panel Lights
Model:
EBPM3
also a seperate switched supply
that controls the emergency
light tting - this also needs to
be isolated.
Email: sales@eterna-lighting.co.uk / technical@eterna-lighting.co.uk
Visit our website: www.eterna-lighting.co.uk
Made in China
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
Made in ChinaIssue 0516
These instructions are provided as a guideline to assist you.
AND RETAIN FOR FUTURE REFERENCE
READ THIS FIRST:
Check the pack and make sure you have all of the parts listed on the front of this booklet. If not, contact the outlet where you bought this product.
This tting must be installed by a competent person in accordance with the current building and IEE wiring regulations.
As the buyer, installer and/or user of this product it is your own responsibility to ensure that this tting is t for the purpose for which you have intended it. Eterna Lighting cannot accept any liability for loss, damage or premature failure resulting from inappropriate use.
Switch o the mains before commencing installation and remove the appropriate circuit fuse or lock of MCB.
Disconnec t from the electrical supply before ash or high voltage testing.
This unit is suitable for indoor use only.
Do not cover the t ting with any insulating materials.
This product is designed for permanent connection to xed wiring: this should be a suitable circuit (protected with the appropriate MCB or fuse)
When making connections, ensure that the terminals are tightened securely and that no strands of wire protrude. Check that the terminals are tightened onto the bared conductors and not onto any insulation.
This product must be connected to Ear th termination.
Make connections to the electrical supply in accordance with the following code:
Live: Brown or Red (L) Neutral: Blue or Black (N) Earth: Green and Yellow (E)
You are advised at every stage of your installation to double-check any electrical connections you have made. After you have completed your installation there are electrical tests that should be carried out: these tests are specied in the Wiring Regulations (BS7671) referred to in the Building Regulations.
The batteries supplied with this tting are a consumable part and therefore may be outside of any warranty oered.
INSTALLATION:
DANGER! Please note that there are two live
supplies, one switched and one permanent; please ensure you isolate both before you undertake any work on the emergency tting.
This emergency pack is designed for use with the Eterna General Purpose Downlight and Panel Light.
01. Switch o the mains before commencing installation and remove the appropriate circuit fuse or MCB.
02. Site the emergency pack within one metre of the luminaire to be converted.
03. Connect a permanent live supply to the emergenc y pack & connect the battery cables.
LED PANEL LIGHT INSTALLATION:
NOTE: Before commencing installation or
maintenance ensure that the mains supply is isolated and locked o.
NOTE: If using with suface mount (SURFMK), remove control gear from box.
1. Remove the cable from the driver supplied.
2. Connect the cable from the panel / downlight to
the supplied connection box.
3. Connect the emergency pack output trailing lead
marked “LED Light” to the connection box making sure the polarity is observed.
4. Connect the emergency pack lead marked “LED
Driver” to the output side of the driver which was supplied with the panel / downlight.
5. Connect 240V mains switch supply to the input
side of the driver.
6. Connect a permanent 240V mains supply to the
emergency pack.
7. Connect the two battery leads from the pack.
8. Insert the green LED indicator into the 5mm hole
and secure in place using a cable tie; the green LED should be visible when the light is on.
9. Mark the installation date on the battery pack.
10. Restore power; a green indicator light will be present to show that the batteries are charging.
NOTE: For non-maintained operation do not connect a switched supply to the tting.
OPERATION CHECKS:
Periodic testing should be carried out to ensure emergency lighting is operating correctly. Interruption of the supply, causing the tting to be energised from the battery, should be carried out by the operation of a local keyswitch or other isolation device. During this period all ttings should be examined visually to ensure that they are functioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure that the normal supply has been restored.
DA ILY:
Visual inspection of the battery charge LED.
EACH MONTH:
Isolate the power supply for a period sucient to ensure that each lamp is illuminated. Endorse the test record form supplied.
ONCE EACH YEAR:
Isolate the power supply and check that the light is still illuminated after 3 hours. Endorse the test record form.
Because of the possibilit y of a failure of the normal lighting supply occurring shortly after a period of testing of the emergency lighting system or during the subsequent recharge period, all full duration tests shall wherever possible be undertaken preceding time of low risk to allow for battery recharge.
NOTE: please keep this instruction booklet and the test record in a safe place. A re ocer or other authorised person may want to see your record of inspection and testing.
Permanent Mains Power Supply (220-240V)
Emergency Box (EBPM3)
L
N
Light cable
Indicator LED Charge
Driver Cable
LED Light Cable
Panel Light
Cable tie
Driver
Connection Box
5mm hole
SW
L1
N
LED Light
Battery
Loading...
+ 2 hidden pages