Eterna Lighting CO12SCEM3 Installation Instructions

INSTALLATION INSTRUCTIONS
A guide for qualied electricians
3 HOURS DURATION IN EMERGENCY MODE
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” eective August 2005—UK WEEE Regulations eective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
WHEN YOUR PRODUC T COMES TO THE END OF ITS LIFE OR YOU CHOOSE TO REPLACE IT, PLEASE RECYCLE IT WHERE FACILITIES EXIST  DO NOT DISPOSE WITH HOUSEHOLD WASTE.
INDUSTRIAL BATTERIES:
Within certain produc ts Eterna Lighting Ltd places lead acid, lithium ion, nickel cadmium & nickel metal hydride batteries on the market. Industrial batteries are subject to waste regulation under the Waste Batteries and Accumulators Regulations 2009 and should be disposed of responsibly. Purchasers may be able to dispose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged to take back , free of charge and within a reasonable time, waste industrial batteries of the same chemistry supplied to a Purchaser, for treatment and recycling and is required to do this in any calendar year new industrial batteries are placed on the market. In certain circumstances, this may include batteries not originally supplied by Eterna. If any Purchaser requires Eterna to take back Industrial batteries, they should write to the Operations Director, Eterna Lighting Ltd, Huxley Close, NN8 6AB, who will then advise on the necessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.
CLEANING:
Clean this tting only with a soft dry cloth.
Do not use any chemical or abrasive cleaners.
IF YOU EXPERIENCE PROBLEMS:
If you believe your product is defective, please return it to the place where you bought it. Our Technical Team will gladly advise on any Eterna Lighting product, but may not be able to give specic instructions regarding individual installations.
Pack contents: 1 x LED ceiling tting 1 x Maintenance Check Record
Model:
CO12SCEM3
Email: sales@eterna-lighting.co.uk / technical@eterna-lighting.co.uk
Visit our website: www.eterna-lighting.co.uk
12W IP65 LED Circular Ceiling/Wall Light With Emergency
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
AND RETAIN FOR FUTURE REFERENCE
Made in ChinaIssue 0121
READ THIS FIRST:
This product must be installed by a competent person in accordance with the current building and IEE wiring regulations.
As the buyer, installer and/or user of this product it is your own responsibility to ensure that this tting is t for the purpose for which you have intended it. Eterna Lighting cannot accept any liability for loss, damage or premature failure resulting from inappropriate use.
Switch o the mains before commencing installation and remove the appropriate circuit fuse or lock o MCB.
WARNING: There are two mains feed. Disconnect both before removing cover.
The batteries supplied with this tting are consumable parts and therefore may be outside of any warranty oered.
This unit is suitable for indoor or outdoor use.
This product is suitable for installation on surfaces with normal ammability e.g. wood, plasterboard and masonry. It is not suitable for use on highly ammable sur faces (e.g. polystyrene, textiles).
Before making xing hole(s), check that there are no obstructions hidden beneath the mounting surface such as pipes or cables.
Ensure that the tting will be accessible after installation for maintenance and self testing.
When making connections ensure that the terminals are tightened securely and that no strands of wire protrude. Check that the terminals are tightened onto the bared conductors and not onto any insulation.
This product is double insulated, do not connect any part to Earth.
You are advised at every stage of your installation to double-check any electrical connections you have made. After you have completed your installation there are electrical tests that should be carried out, these tests are specied in the current IEE wiring and building regulations.
Brown (Power Cable)
White L’ - L (Loop Cable)
Blue (Power Cable)
L L’ N
LIVE (Power Cable)
NEUTRAL (Power Cable)
INSTALLATION:
Choose the location for your new tting according to the conditions listed opposite.
01) Remove diuser.
02) Unscrew the gear tray screw and allow the gear tray to rest on its hinge.
03) Drill holes in the back of your tting for your xing screws, take care and drill gently to ensure a clean hole through. Use a drill bit sized appropriately to your xing screws (not supplied).
04) Using the back of your tting as a template, mark the position of your xing holes on your mounting sur face.
05) Prepare the holes in your mounting sur face as appropriate for your xings.
06) Pierce the rubber grommet in the back of your tting making a hole just large enough to make a tight t around the incoming mains cable.
07) Thread the cable through the grommet and oer the tting to the ceiling / wall.
08) Secure the tting in place. Note, if protection against ingress of moisture is required, the heads of screws must be covered with a silicone or similar sealant.
09) Check that the grommet is still correctly tted in the cable entry hole and around the incoming cable.
10) Make the electrical connections to the terminal block according to the markings:
Brown to live (L) • Blue to neutral (N)
11) Mark the current date on the bat tery pack.
12) Ensure the battery plug is connected to the socket on the driver.
13) Replace diuser and apply decorative trim if using.
14) Restore the power and check tting is working correctly. A green light should always be present indicating the tting is charging.
NOTE: For non-maintained operation, remove link wire from L and L1. For switched operation, remove link wire and make a switched supply into L1.
OPERATION CHECKS:
Periodic testing should be carried out to ensure emergency lighting is operating correctly. Interruption of the supply, causing the tting to be energised from the battery, should be carried out by the operation of a local keyswitch or other isolation device. During this period all ttings should be examined visually to ensure that they are func tioning correctly. At the end of the test period the supply shall be restored and all indicator lamps or devices checked to ensure that the normal supply has been restored.
DA ILY:
Visual inspection of the battery charge LED.
EACH MONTH:
Isolate the power supply for a period sucient to ensure that each lamp is illuminated. Endorse the test record form supplied.
ONCE EACH YEAR:
Isolate the power supply and check that the light is still illuminated after 3 hours. Endorse the test record form.
Because of the possibility of a failure of the normal lighting supply occurring shortly af ter a period of testing of the emergency lighting system or during the subsequent recharge period, all full duration tests shall wherever possible be under taken preceding time of low risk to allow for batter y recharge.
NOTE: please keep this instruction booklet and the test record in a safe place. A re ocer or other authorised person may want to see your record of inspection and testing.
BATTERY REPLACEMENT:
If after routine operation check, the lamp does not remain lit for the three hour period, a new battery pack may be required.
01. Switch o the electricity at the mains (both permanent live and switch live) and allow batteries to fully discharge then reconnect to supply and allow charging for 24 hours.
02. Test again for 3 hours, if light does not remain lit, then change the battery pack as follows:
03. Remove the diuser and remove the gear tray.
04. Remove the battery case from the gear and
remove the battery.
05. Write current date on the new battery pack and t a new battery by reversing the above procedure.
06. Plug battery pack into circuit board.
07. Ret gear tray and diuser.
08. Restore power and allow charging for 24 hours.
09. Perform full operation check and update test record.
REPLACEMENT BATTERY TYPE:
3.2V 1500mAh Lithium
LAMP REPLACEMENT:
The light source is designed to last the lifetime of the luminaire.
The light source contained in this luminaire shall only be replaced by the manufacturer, service agent or a similar qualied person.
CAUTION, RISK OF ELECTRIC SHOCK.
Loading...