Eterna LEDREM3, LEDMDDEM3 Installation Instructions Manual

Model:
LEDREM3 / LEDMDDEM3
LED Maintained Recessed Emergency Fittings
These instructions are provided as a guideline to assist you.
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLATION
AND RETAIN FOR FUTURE REFERENCE
Pack contents:
1 x Down legend (LED MDDEM3 only)
1 x Maintenance chec k record
INSTALLATION INSTRUCTIONS
A guide for qualied electricians
3 HOURS DURATION IN EMERGENCY MODE
REPLACEMENT BATTERY TYPE:
LEDREM3: 3.6V 1500mAh 3 x C Cells . LEDMDDEM3: 4.8V 6 00mAh Ni-Cd batte ries.
BATTERY REPLACEMENT:
If after routi ne operation check, th e lamp does not remain lit for the th ree hour period, a new bat tery pack may be required.
01. Switch o the electricit y at the mains.
02. Allow batterie s to fully discharge then reconn ect to supply and allow to ch arge for 24 hours.
03. Test again for 3 hours, if li ght does not remain lit change the bat tery pack as follows:
04. Remove the di user.
05. Remove the two scr ews indicated on the gear tray and open the t ting.
LEDREM3:
06. Unplug the ba ttery lead from the circ uit board.
07. Remove the two screws in the top of the g ear tray that secure the bat tery pack in place and lif t the battery p ack out of the tting.
08. Write current da te on the new battery pack .
09. Fit new batter y pack securing in place using th e screws removed fr om the old pack.
10. Plug battery pa ck into circuit board.
LEDMDDEM3:
06. Disconne ct the battery from th e circuit board.
07. Cut the cable tie that secures the bat tery pack in place and lift t he battery pack out of th e tting.
08. Write current da te on the new battery pack .
09. Fit new batter y pack securing in place using cable tie.
10. Connect the bat tery to the circuit board.
11. Close and secure gear tray.
12. Replace diuser.
13. Restore power and allow to ch arge for 24 hours.
14. Perform full oper ation check and update test record.
EVENTUALLY, YOU MAY WANT TO REPLACE THIS PRODUCT:
Regulations require the recycling of Waste from Electrical and Electronic Equipment (European “WEEE Directive” eective August 2005—UK WEEE Regulations eective 2nd January 2007). Environment Agency Registered Producer: WEE/GA0248QZ.
WHEN YOUR PR ODUCT COMES TO T HE END OF ITS LIFE OR YOU CH OOSE TO REPLACE IT, PLEA SE RECYCLE IT WHERE FACI LITIES EXIS T  DO NOT DISPOSE WI TH HOUSEHOLD WASTE.
INDUSTRIAL BATTERIES:
Within cert ain products Eterna L ighting Ltd places lead acid, lithium io n, nickel cadmium & nickel m etal hydride batteries on the market. Industrial batteries are subject to waste regulat ion under the Waste Batte ries and Accumulators Regulations 2009 and should be disposed of responsibl y. Purchasers may be able to disp ose of their waste industrial batteries locally via legitimate licensed trade waste contractors. Eterna is obliged to take back, f ree of charge and within a rea sonable time, waste indu strial batteries of t he same chemistry supplied to a Purch aser, for treatment and rec ycling and is required t o do this in any calendar year ne w industrial ba tteries are placed on th e market. In certain circumstances, this may include batteries not originally supplied by Eterna. If any Purchaser requires Eterna to take back Indus trial batteries, th ey should write to the Operatio ns Director, Eterna Lighti ng Ltd, Huxley Close, NN8 6AB, wh o will then advise on the n ecessary arrangements for the receipt, proper treatment and recycling of, the waste industrial batteries.
SPECIFICATIONS:
Volta ge: 240V BLF / EBLF: 0.92 / 0.67
LEDREM3: Nominal lumens: 162.3 lm Rated wattag e: 5.20W
LEDMDDEM3:
Rated wattag e: 3.5W Viewing dist ance: 32m
IF YOU EXPERIENCE PROBLEMS:
If you believe you r product is defec tive, please return it to the place wher e you bought it. Our Technical Team will gladly adv ise on any Eterna Lighting pr oduct, but may not be able to gi ve specic instruct ions regarding individual installations.
LEDMDDEM3
LEDREM3
Email: sales@eterna-lighting.co.uk / technical@eterna-lighting.co.uk
Visit our website: www.eterna-lighting.co.uk
Made in ChinaIssue 0418
The light source cont ained in this luminaire shall only be rep laced by the manufacturer, service age nt or a similar qualied pers on.
CAUTION, RISK OF ELECTRIC SHOCK.
The light source is designed to last the lifetime of the luminaire.
READ THIS FIRST:
Check the pack and m ake sure you have all of the parts liste d on the front of this bookle t. If not, contact the outlet where you bought this product.
This light ttin g must be installed by a compe tent person in accord ance with the Building Regulat ions making refere nce to the current edition of the I EE Wiring Regula tions (BS7671).
As the buyer, install er and/or user of this product it is your own responsi bility to ensure that this tt ing is t for the purpo se for which you have intended it. Eterna Lightin g cannot accept any liability fo r loss, damage or premature failure resulting from inappropriate use.
This product is designed and constructed according to the principles o f the appropriate British Stan dard and is intended fo r normal service. Use of this  tting in any other environm ent, for example in higher than normal ambi ent temperatures, may result in a foreshortened working life.
The batteri es supplied with this ttin g are consumable par ts and therefore may be out side of any warranty oered.
Switch o the mains be fore commencing installati on and remove the appropriate circuit fuse.
When working at h eights, please use a suita ble platform.
Suitable for indoor use only.
This produc t is suitable for installatio n on surfaces with normal ammability e.g. wood, plasterboard, masonry. It is not sui table for use on highly ammable sur faces (e.g. polystyren e, textiles).
This produc t is suitable for mounting in pla sterboard ceilings, suspen ded ceilings* and similar boa rd surfaces. *C heck specication of ceili ng for suitability.
Before makin g xing hole(s), check that there are no obstructi ons hidden beneath the mount ing surface such as pipes or cab les.
The chosen loc ation of your new tting shou ld allow for the produc t to be securely mounted and s afely connected to th e mains supply (lighting circuit).
Do not attach to su rfaces which are damp or fre shly painted.
This produc t is designed for permanent co nnection to xed wiring: this s hould be either a suitable lighting circuit (p rotected with a 5 or 6 Amp MCB or fuse) or a fused spu r (with a 3 Amp fuse) via a fused connection u nit.
Make connecti ons to the electrical supp ly in accordance with the f ollowing code:
Live - Brown or Red, N eutral - Blue or Black Earth - Gree n and Yellow
When making con nections, ensure that the te rminals are tightened se curely and that no strands of wi re protrude. Chec k that the terminals are tightene d onto the bared cond uctors and not onto any insulation. Wrap lo ose terminal blocks wel l with insulating tape.
This produc t must be connected to Ear th.
You are advised at ever y stage of your installatio n to double-check any electrical connections you have made. After you h ave completed your installatio n there are elec trical tests that should b e carried out: these tests are sp ecied in the Wiring Reg ulations (BS7671) refer red to in the Building Regulati ons.
OPERATION CHECKS:
Periodic testin g should be carried out to ensu re emergency lighting is operating correctly. Interruption of t he supply, causing the tting to be energised fro m the battery, should be car ried out by the operation o f a local keyswitch or other iso lation device. During th is period all ttings shou ld be examined visu ally to ensure that they are funct ioning correctly. At the end o f the test period the supply shall be restore d and all indicator lamps or devi ces checked to ensure th at the normal supply has been restored.
DA ILY:
Visual inspec tion of the battery cha rge LED.
EACH MONTH:
Isolate the power su pply for a period sucien t to ensure that each lamp is i lluminated. Endorse the test record form supplied.
ONCE EACH YEAR :
Isolate the power su pply and check that the light is still illuminate d after 3 hours. Endorse t he test record form.
Because of the p ossibility of a failure of the n ormal lighting supply o ccurring shortly af ter a period of testing of the eme rgency lighting system o r during the subsequent re charge period, all full du ration tests shall whe rever possible be undert aken preceding time o f low risk to allow for batter y recharge.
NOTE: please keep th is instruction book let and the test record in a s afe place. A re ocer or other authorised pe rson may want to see your record of inspection and testing.
IMPORTANT NOTES:
The ballast and control gear must be operated only within the enclosure supplied. The gear must not be operated outside of the enclosure.
The battery charging circuit and DC ballast are separated from the mains by at least basic (single layer) insulation.
When energised by a constant mains supply, the battery will be constantly charged whether or not the lamp is illuminated. On failure of the constant mains supply, the tting will switch automatically using transistorised switching from battery charging to battery discharge powering the lamp whether or not the lamp was illuminated before the power failure. Both the mains and battery supplies incorporate fuse protection: see tting for location and rating.
CLEANING:
Clean this tti ng only with a soft dr y cloth. Do not use any chemi cal or abrasive cleaner s.
INSTALLATION:
01. Undo the screws at each end of the diuser or front plate and lift o.
02. Decide which of the cable entries you need to use and remove one of the knock-outs if necessary.
03. Cut the hole in your mounting surface using the dimensions, see Fig 1.
04. Oer the tting up through the hole in the ceiling and allow to rest with the two large ears on the top side of your ceiling, see Fig 2.
05. Undo the screws at each end of the gear tray and allow to drop open.
06. Thread the mains supply cable in through the hole in the back of the tting.
07. Make the electrical connections according to the colour code opposite. Take care not to leave any strands protruding from the terminals and to tighten all terminals securely. Ensure also that the terminals clamp onto the bare wire and not onto the insulation.
LEDREM3 ONLY
08. To operate the tting in non-maintained mode, remove the link from the terminals “L” & “Lsw”.
09. If the lamp is to be switched, remove the link from between the terminals marked “L” & “Lsw” and connect cables to and from your switch.
10. Mark the current date on the battery pack.
11. Connect the battery pack to the circuit board.
12. Close the gear tray and secure using the screws removed earlier, see Fig 3.
13. If you have chosen one of the drop-sign models, you need to t the sign panel into the diuser or slotted front plate:
A) Oer the top of the sign panel into the slot in the diuser from beneath and press down on the top of the diuser until it rests on the shoulders at the top of the panel.
B) Fit the small split-pins into the holes at each end of the top edge of the sign panel and bend the ends over to stop them from coming out again, see Fig 3.
14. Replace the diuser or front plate and tighten securely making sure that the tting is properly located around the hole in your ceiling.
55mm
CEILING
CEILING
115mm
320mm
375mm
ø
15mm
Screw
Legend
Folded Pin Ends
Cover
Screw
Cover
Fitting
Fig 1
Fig 2
Fig 3
NOTE: Wires should b e
stripped 13-14.5mm for best t with th e push-t terminal block.
13-14 .5m m
Wire
DANGER!
NOTE: this unit has a permanent live mains supply, please ensure you isolate before removing cover.
There may also be a seperate switched supply that controls the emergency light tting - this also needs to be isolated.