E-Tech ET8 User Manual

Page 1
USER’S MANUAL
Versions commencing November 2001A$12.00 INC GST
E-TECH ET8 CONTROL PANEL V4 – USER’S MANUAL, REVISION 1
E-TECH ET8 ALARM CONTROL PANEL AND DIALLER
Page 2
“Australia’s largest
designer and
high quality
security products”
E-T ech Security Pr oducts Pty Ltd
Quality Endorsed Fictional Company ISO9001
LIC.No. QEC2074 NSW Head Office only
HEAD OFFICE: E-Tech Security Products Pty Ltd
ABN 000 110 110 12 Security Close Safe Hills NSW 2147 Australia Ph +61 23 9988 7766 Fax +61 23 9988 7765
ET8 V4 INSTALLER MANUAL
Revision 1, November 2001
Document Part Number: 890–265 For product:
100–191 ET8 LED Control Panel (V4) 100–688 ET8 LCD Control Panel (V4)
© 2001 E-Tech Security Products Pty Ltd ACN 000 110 110 ET8 V4 installer
Specifications may change without notice.
E-TECH SECURITY PRODUCTS TELECOMMUNICATIONS COMPLIANCE
Australian Communications Authority
Page 3
CONTENTS
Features ...................................................................... 4
Introduction ................................................................. 5
Keypad ........................................................................ 6
Keypad Indicators ...................................................... 7
OPERATION by KEYPAD ........................................... 8
Arming ...................................................................... 9
Disarming .............................................................. 10
Resetting Alarms ................................................... 10
Monitor Mode ........................................................ 11
Panic ...................................................................... 12
Duress .................................................................... 12
Fire Alarm .............................................................. 13
Medical Alarm ....................................................... 13
Excluding Zones ................................................... 14
Alarm Memory ....................................................... 15
OPERATION by RADIO KEY ..................................... 16
PROGRAMMING ....................................................... 17
Programming Options Table ................................ 17
User Code programming ...................................... 18
Entry/Exit Timer programming ............................. 18
Telephone Number programming ....................... 19
Monitoring, Central Station ...................................... 20
Monitoring, Audible .................................................. 21
Wireless Accessories ............................................... 20
Remote Operation by Telephone ............................ 22
E-TECH ACCESSORIES ......................................... 24
Wireless Accessories ........................................... 25
Troubleshooting ........................................................ 26
Installation Record.................................................... 27
OPERATION SUMMARY .......................................... 28
Page 4
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
4
8 Fully programmable zones
Any combination of hardwire or radio zones
Full radio supervision
Contact ID Dialler Format
Ultra-Modern and Impact resistant Housing
E-Tech Audible Dialler Format
"Follow Me" A udib le Dialler Option
Separate 24 Hour Tamper input
Single or Double Trigger Zones
Remote LED or LCD Ke ypads (Max 3)
Fully programmab le via the system Ke ypad - Eliminates the need for expensiv e programmers or Proms .
Inbuilt Vibration Sensor Analyser
All programming data is permanently stored in a non-volatile EEprom memory
Windows based Up\Down load Software allows remote progr amming and ev ent status
True Dynamic Battery Test e v ery time the Panel is armed / disarmed and ev ery hour
Area Partitionable (2 Areas). An y Zone can be programmed to any area, as well as common areas
Comes complete with an AC plug pack and supports a 12V 7Ah battery to maintain systems security under all power supply conditions
Monitor Mode (Home Mode)
Outputs are separately fused with Automatic Reset Fuses
Day Mode and Door Chime f eature.
30 Event Memory
Supports 8 Radio Devices (Radio PIRs, Radio Reeds etc)
Supports 14 Radio Keys
All inputs and outputs are heavily protected against lightning and high voltage supply transients . An earth terminal is provided for extr a protec­tion
15 User Codes
‘Arm only’ codes can be progr ammed
Programmable Inputs to activ ate selectable Outputs
Designed utilising the latest SMD Technology
Simple to Program and Use.
E-TECH ET8 FEATURES
Page 5
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
5
INTRODUCTION
The E-Tech ET8 micro computer based 8 zone control panel is the heart of your security system to which all your detection devices connect.
Each Zone of the panel can be connected to one or more detection devices to protect separate rooms of your premises.
Detection devices may be connected to the ET8 control system directly by cabling or with optional wireless (Radio) devices.
Detection devices called Passive Infra-Red Detectors (or P.I.R’s for short) can detect the movement of an intruder by sensing their body heat. P.I.R’s are used to cover various critical areas of your premises where an intruder may enter or trespass. Another detection device used is called a Reed Switch. Reed Switches are attached to windows and doors to detect if a window or door has been opened. A Reed Switch consists of a magnet which is normally attached to the moving part of a window or door and the Reed switch which mounts to the door or window frame.
The panel is “Armed” when it is set to detect an intruder. At other times it is “Disarmed”.
Normally a zone is considered Sealed. Activation of a detection device will cause the zone to be Unsealed and may cause an alarm.
Detectors such as fire detectors and panic buttons must be able to generate an alarm at all times regardless of the panel setting. A zone with this assignment is called a 24 hour zone.
Some detection devices may be required to generate an alarm or warning only when the panel is Disarmed. A zone with this assignment is called a Day zone.
Before leaving the premises you must Arm the panel to enable it to detect intruders and generate an alarm. After arming, the panel will ignore detectors during the Exit Delay Time to enable you to depart without triggering an alarm.
Arming the system may be done through the keypad or with the use of optional Radio Keys for Arming by remote control from outside the premises.
When you enter the premises the panel will ignore selected zones for the Entry Delay Time and will not alarm unless you don’t Disarm the panel during this allowed time.
Disarming the system may be done by keypad or with the use of optional Radio Keys.
Monitor mode allows you to Arm selected zones while others are ignored. Typically, perimeter zones (doors and windows) can be monitored while you are at home.
If you wish to split your alarm system into two areas with access limited to each area by code numbers then Area operation is used. Radio Keys can also Arm and Disarm Areas.
The control panel housing and the covers over external sirens are protected by tamper switches to detect someone attempting to disable the security system. Activation of these switches will cause an instant tamper alarm.
If a detector becomes faulty, you can Exclude the associated zone so that it is totally ignored and cannot generate an alarm. Including the zone will enable it to generate an alarm again.
The control panel is fitted with a rechargeable stand-by battery to ensure your security system continues to operate if the mains power is interrupted. This control panel automatically tests the battery every hour and whenever you Arm/Disarm the panel. (Dynamic Battery test).
Whenever an alarm occurs, it may be silenced with a User Code or by optional Radio Keys, otherwise it will reset at the end of Alarm Reset Time.
All alarms are stored in memory and may be viewed at any time by entering Memory Mode.
Page 6
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
6
KEYPAD
The ET8 control panel may be supplied with either the LED keypad (100-192) or the E-Tech LCD Keypad (100-667).
The keypad provides important visual and audible indications and is the main interface for operating and programming the ET8 control panel.
2
5
8
0
1
4
7
P
3
6
9
E
ARM
MONITOR
EXCLUDE
MEMORY
Not Ready
Backlit LCD icon display
PANIC buttons
PANIC buttons
Not Ready light
The “Not Ready” light is on when the panel is not ready to Arm. i.e, a zone is unsealed, there may still be movement in the premises or a door or window left open
ARM button
ARM button
MONITOR button
MONITOR button
EXCLUDE button
EXCLUDE button
PROGRAM button
ENTER button
MEMORY button
MEMORY button
LED KEYPAD LCD KEYPAD
PROGRAM button
Protective flap not shown
Protective flap not shown
ENTER button
PAN IC
ARM
1
4
7
0
2
5
8
ENTER
3
6
9
MONITOR
EXCLUDE
PROGRAM
PAN ICMEMORY
105mm 90mm
150mm
135mm
DISPLAY TEST (LCD Keypad only)
To display all the keypad icons press and hold the button for at least 2 seconds. All the icons will be on whilst the button is held down.
Display Test can be activated at any time either in operating mode or any program mode.
Page 7
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
7
KEYPAD INDICATORS
Zone is sealed
Zone is unsealed, or Power fault or System is Armed, or phone line fault
Disarmed
Disarmed
Disarmed
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Normal
Ready to Arm
Zone is unsealed
Ready to Arm
Armed (AREA 1)
Armed (AREA 2)
Monitor Mode
Memory Mode selected
Receiving radio signal
Dialler is on line
(And in Memory Mode indicates a low battery alarm from a radio device)
Indicates that a Radio Key or other radio device has a low battery
Phone line fault or failure to communicate
User Program Mode
Not ready to Arm
Zone alarm
Monitor Mode (
LED Keypad only)
Mains Power is off The panels backup
battery is low
New alarms in memory
Zones are excluded
Tamper alarm
Installer Program Mode
ZONES 1~8
ARMED
ARM2
MAINS
BATTERY
MEMORY
EXCLUDE
TAMPER
PROGRAM
LINE
READY
RADIO
Not Ready
OFF ON FLASHING
STATUS
LED KEYPAD LCD KEYPAD
1 beep
3 beeps
1 long beep
10 beeps
10
Each key press
Valid command
Error
Mains Power is off or Panel Battery is low
KEYPAD BEEPER SOUNDS
Page 8
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
8
OPERATION
This section describes the operation of a typical control panel installation. Keep in mind that your installation may vary depending on the selected options and equipment. The operating instructions which follow will cover the most common options.
Consult your installation company if you require further information.
All control panel operations are controlled by the ET8 LED or LCD keypad except if an optional key switch or radio control equipment is installed.
OPERATING RULES
Generally, the panel will be Disarmed. Armed or Monitor modes provide different levels of security for your premises when you are home or away. Three other temporary modes; Program, Memory and Exclude, allow you to perform various operations. The panel will automatically exit from these temporary modes if you do not press any buttons on the keypad in a 4 minute period.
If you make a mistake while entering any codes, press the Enter or E button and start again.
When you are required to enter your access code, you are given five opportunities to enter it correctly. After the fifth invalid attempt the alarm is activated (requiring the correct code to silence the alarm). This prevents anyone trying to guess your code by entering random numbers.
AREA OPERATION
Area Partitioning allows the 8 zones to be split into two partitions; Area1 and Area2.
The panel then effectively operates as two separate systems sharing only the siren outputs and dialler.
USER CODE ASSIGNMENT
A User Code assigned to an Area can Arm and Disarm only that Area. User Codes assigned to both Areas will operate both Areas simultaneously.
COMMON AREA ZONES
Zones assigned to both Areas are Armed only when Area1 and Area2 are both Armed. This allows the Common Area zone/s to be shared by both Areas.
For example, Office A and Office B operate as separate areas but the entrance foyer used by both offices is assigned to both areas meaning it will automatically Arm when both Areas have Armed. The Common Area then automatically disarms when either Area1 or Area2 Disarms.
OPERATION
Arming and Disarming is carried out as normal from a single keypad or separate keypads installed in both areas or by Radio Key.
Area operation only applies to zones when they are in the Armed state. This means that Day, 24hr and Monitor zones are independent of the area operations.
Note: Area partitioning is in addition to Monitor Mode. Any zone may be allocated to any area.
Page 9
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
9
OPERATION
The control panel must be Armed prior to vacating the premises in order to detect intruders. Ensure that the panel is not in Program, Memory or Exclude modes.
Note: If the panel is already in alarm, you must first silence the alarm before you can Arm.
If something is wrong when Arming the control panel, the normal 3 beeps will be replaced by other warnings.
10
10 beeps means Mains Power is
turned off or the Backup Battery is low.
One long beep indicates an invalid
entry or an alarm is outstanding and needs to be reset by entering your User Code first.
SIREN WARNING:
At the end of the exit time, all zones should be Sealed. If any are Unsealed, the siren will sound for 2 seconds as a warning to indicate that those zones have been automatically excluded. For maximum security, you should return, Disarm, check the premises and then Arm again. Continual warnings could mean that a detector is faulty and may have to be manually excluded.
If the auto-exclude option is disabled, the siren will sound for the duration of reset time if a zone is Unsealed at the end of exit time.
or...
[User Code]
ARM
ARM
ENTER
ENTER
or...
The light must be offNot ReadyThe light must be onReady
Press...Press...
The Armed light will turn on
Leave the premises within the Exit Delay Time
3 beeps will sound at the end of Exit Delay Time
The icon will turn on
Leave the premises within the Exit Delay Time
3 beeps will sound at the end of Exit Delay Time
[User Code]
LED KEYPAD
ARMING
LCD KEYPAD
Page 10
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
10
When you enter the protected premises through a delay zone, the keypad responds with regular beeps* as a reminder to Disarm. You then have your programmed entry delay time to Disarm the panel by entering one of your user codes. If the panel is not Disarmed by the end of the entry delay time, an alarm will occur.
By using the optional radio keys you may Disarm your system from within your premises
or from outside your entrance door. There is also the option to Chirp the outside siren three times and to flash the strobe light for two seconds as an indication that you have Disarmed your system.
If you make a mistake in entering your code, then you must press enter and start again. Five incorrect entries will cause an alarm.
* If Entry Beeps are programmed on.
OPERATION
Your panel can be reset and the alarm silenced by the same key sequence as Disarming the panel.
If you arrive at your premises and find the strobe light flashing (if installed), reset the panel as above. To check the cause of the alarm, you can view the alarms in memory by entering Memory Mode.
[User Code] [User Code]
ENTER
Enter the premises through a delay zoneEnter the premises through a delay zone
Press...Press...
The Armed light will turn off The icon will turn off
LED KEYPAD
DISARMING
LCD KEYPAD
RESETTING ALARMS
Alarms may be caused by:
A zone has been triggered while Armed
A Tamper has been triggered
A PANIC button has been triggered
All of these may cause your sirens and strobe to operate. Various visual indications relevant to the alarm will be retained in the memory. If this occurs, Disarming your control panel will reset the alarm. The cause of the alarm can be identified by entering the Alarm Memory Mode as described on page 15.
ALARMS, DEFINITION
Page 11
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
11
OPERATION
Monitor mode allows you to Arm selected zones while others are ignored. Typically, perimeter zones (doors and windows) can be monitored while you are at home.
Your installer must program which zones will be active in Monitor mode.
The panel must be fully Disarmed before Arming in Monitor Mode.
If an alarm occurs while in Monitor mode, entering
[User Code]
will silence the alarm.
This will also Disarm the panel, so remember to enter monitor again if needed.
By using the optional Radio Keys you can enter Monitor Mode by pressing the OFF button twice within 4 seconds. (Your installer must enable Radio Key Monitor Arming for this to work).
or...
[User Code]
ENTER
ENTER
or...
Press...Press...
The Monitor light will turn on
Only the zones which have been programmed by your installer as Monitor zones will be Armed
Only the zones which have been programmed by your installer as Monitor zones will be Armed
The MONITOR icon will turn on
[User Code]
MONITOR
MONITOR
LED KEYPAD
MONITOR MODE
LCD KEYPAD
Page 12
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
12
The keypad PANIC function may have been programmed to be either AUDIBLE - activates siren or buzzers, or SILENT - If your system is monitored by a Central Station, sends a PANIC report by dialler. (If PANIC reports have been enabled by your installer).
OPERATION
PANIC cannot be used while the panel is in Program, Memory or Exclude mode.
Note: Your installer may have installed a separate PANIC button. To activate the panic alarm simply press that button.
Press...Press...
or...
or...
Both keys together
(If Keypad Panic Shortcut has been enabled by your installer) (If Keypad Panic Shortcut has been enabled by your installer)
[User Code]
PANIC
PANIC
PANIC
PANIC
ENTER
ENTER
Both keys together
or...
or...
[User Code]
LED KEYPAD
KEYPAD PANIC
LCD KEYPAD
A DURESS alarm can be triggered to alert the Central Station that you are being forced to Disarm the panel against your will.
To Disarm and send a DURESS alarm, prefix your User Code with one of the digits 5, 6, 8 or 9 when Disarming.
DURESS alarms are only used if your system is monitored by a Central Station.
DURESS IS NORMALLY NOT ENABLED. TO ENABLE THE DURESS FUNCTION, CONSULT YOUR INSTALLER
2. If Duress Alarm Report has been enabled by your installer 2. If Duress Alarm Report has been enabled by your installer
1. If your system is monitored by a central monitoring station 1. If your system is monitored by a central monitoring station
1. By default, Duress Alarm does not sound the RESET output 1. By default, Duress Alarm does not sound the RESET output
Disarms and sends a Duress Alarm report by dialler. Disarms and sends a Duress Alarm report by dialler.
Duress Alarm can be programmed to sound the RESET output.
Digits 5, 6 & 8 in front of the user code can also be used trigger the Duress alarm
Digits 5, 6 & 8 in front of the user code can also be used trigger the Duress alarm
Duress Alarm can be programmed to sound the RESET output.
Press... Press...
9
[User Code] [User Code]
LED KEYPAD
KEYPAD DURESS ALARM
LCD KEYPAD
Page 13
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
13
1. If Keypad Fire Alarm has been enabled by your installer 1. If Keypad Fire Alarm has been enabled by your installer
2. If Fire Alarm Report has been enabled by your installer 2. If Fire Alarm Report has been enabled by your installer
1. If your system is monitored by a central monitoring station 1. If your system is monitored by a central monitoring station
Sounds the siren (Fire Alarm siren sound) Sounds the siren (Fire Alarm siren sound)
Sends a Fire Alarm report by dialler. Sends a Fire Alarm report by dialler.
Press... Press...
LED KEYPAD
KEYPAD FIRE ALARM
LCD KEYPAD
2. If Medical Alarm Report has been enabled by your installer 2. If Medical Alarm Report has been enabled by your installer
1. If your system is monitored by a central monitoring station 1. If your system is monitored by a central monitoring station
Sends a Medical Alarm report by dialler. Sends a Medical Alarm report by dialler.
Press... Press...
Medical Alarm does not sound sirens. Medical Alarm does not sound sirens.
LED KEYPAD
KEYPAD MEDICAL ALARM
LCD KEYPAD
OPERATION
Page 14
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
14
OPERATION
If a detector becomes faulty and cannot be Sealed when arming the panel, then its zone may be Excluded so that it does not generate alarms.
When zones have been Excluded, the EXCLUDE light flashes continuously while the panel is Disarmed and also when Armed.
Zones can only be Excluded when the panel is Disarmed.
Zone Exclude IS not permanent. Excluded zones are automatically INCLUDED next time the panel is Disarmed.
Zones can be manually included by the same method as Excluding. Simply use the [ZONE NUMBER] sequence to turn OFF the
zone lights to be Included.
The zone light of each Excluded zone will turn on The zone light of each Excluded zone will turn on
or...
[User Code]
[Zone No.] [Zone No.][Zone No.] [Zone No.]
ENTER
ENTER
ENTER
ENTER
ENTER
or...
Press...Press...
Press... Press...
The
The The
Enter the zone number of the zone/s to be Excluded
to exit Exclude mode to exit Exclude mode
Enter the zone number of the zone/s to be Excluded
Exclude light will turn on
Exclude light will flash continuously
The EXCLUDE icon will turn on
EXCLUDE icon will flash continuously
[User Code]
LED KEYPAD
EXCLUDING ZONES
LCD KEYPAD
NOTES
EXCLUDE E works only when the panel is Disarmed.
EXCLUDE [User Code] E works in any state.
EXCLUDE [User Code] E can only exclude the zones in the Area assigned to that code.
Page 15
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
15
OPERATION
The ET8 Control Panel stores a comprehensive Alarm Memory, including Arming, Disarming, Low Battery, Mains Fail and Alarm events.
The memory is constantly upgraded and the last 30 events are always available for viewing.
This Memory display can only be selected while the panel is in the Disarmed state.
TO CLEAR THE MEMORY LIGHT
The MEMORY light flashes continuously when an alarm has occurred as a reminder to view the alarm memory.
The MEMORY light stops flashing after the memory is viewed as shown above.
The MEMORY light is automatically cleared next time the panel is Armed.
MEMORY MODE - EVENTS INDICATED BY KEYPAD LIGHTS:
LIGHT ALARM EVENT
Zone lights 1~8 Zone alarm ARM Panel Armed (no lights) Panel Disarmed TAMPER Tamper alarm (Siren cover, panel etc) EXCLUDE Panic alarm BATTERY Low Battery MAINS Mains power failure RADIO, BATTERY, ZONE Radio Device battery low RADIO, BATTERY, ARM Radio Key battery low
The most recent event will be displayed The most recent event will be displayed
The next most recent event will be displayed The next most recent event will be displayed
...and so on (up to 30 events) ...and so on (up to 30 events)
or... or...
[User Code] [User Code]
ENTER
ENTER
ENTER
Press... Press...
Press... Press...
Press... Press...
Press... Press...
Press... Press...
The The
to exit Memory mode to exit Memory mode
Memory light will turn on
MEMORY icon will turn on
LED KEYPAD
VIEWING EVENT MEMORY
LCD KEYPAD
Page 16
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
16
RADIO KEY OPERATION
E-TECH RADIO KEY 3 BUTTON
The optional E-Tech Radio Key allows you to Arm, Disarm and activate PANIC. The Radio Key can also Arm Monitor Mode, (if this has been enabled by your installer).
ARMING
Press the ON button.
• The keypad will give 3 beeps.
• The outside siren will give 1 ‘chirp’. (If enabled by your installer)
• The strobe light will flash briefly
DISARMING
Press the OFF button.
• The keypad will give 3 beeps.
• The outside siren will give 3 ‘chirps’. (If enabled by your installer).
• The strobe light will flash briefly.
ARMING MONITOR MODE
Press the OFF button twice within 4 seconds.
• The keypad will give 9 beeps.
• The outside siren will NOT ‘chirp’.
• The strobe light will flash briefly.
PANIC
Press and hold the PANIC button for at least 4 seconds.
• The siren and strobe will activate, (If enabled by your installer)
• The dialler will report a Panic alarm, (If enabled by your installer and if your system is monitored by a central station).
Press the OFF button to reset a Panic alarm
* The E-Tech Radio Key is optional and is not supplied with any E-Tech control panels as standard * E-Tech radio products require a E-Tech Radio Interface (100-200) to be fitted to the control panel.
Page 17
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
17
OPTION OPTION No PROGRAMMEDRANGE
FACTORY
DEFAULT
User Code 1 (Master Code) P11E 123 3 to 6 digits
3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 3 to 6 digits 1 to 99 sec 10 to 990 sec 1 to 99 sec Up to 15 digits
User Code 2 P12E User Code 3 P13E User Code 4 P14E User Code 5 P15E User Code 6 P16E User Code 7 P17E User Code 8 P18E User Code 9 P19E User Code 10 P20E User Code 11 P21E User Code 12 P22E User Code 13 P23E User Code 14 P24E User Code 15 P25E Entry Delay 1 Entry Delay 2 Exit Delay Follow Me Telephone No.
P26E P27E P28E P00E
20 seconds 60 seconds 60 seconds
NOTE: The Entry Delay 2 timer programs in 10 second intervals. Example: if a value of 6 is programmed, the time is 60 seconds.
PROGRAMMING OPTIONS TABLE
PROGRAMMING
Various system options, as listed below, can be programmed by the user. These options can only be accessed from Program Mode.
User Codes may need to be re-programmed if a person has forgotten their code, to give a new user access to the system or to give someone temporary access.
User Codes 2-15 can be set as Arm Only Codes. These codes can Arm but cannot
Disarm the panel. (Useful for assigning to cleaners, tradesmen etc.)
You may need to change the Entry and Exit timers if you find the delays are too long or short.
If Audible Monitoring is programmed by your installer, the Follow Me Telephone Number is the telephone number the dialler will call in the event of an alarm.
If your E-Tech ET8 panel is monitored by a Central Station, the Follow Me number is ignored.
For all other programming changes, talk to your installer.
The panel will automatically exit Program Mode is no buttons are pressed within a 4 minute period.
FACTORY DEFAULT MASTER CODE IS: 123
Page 18
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
18
PROGRAMMING
Enters Program Mode. The PROGRAM light will be on. Enters Program Mode. The PROGRAM light will be on.
The two digit option number for the code to be programmed. The existing code (if any) will be displayed. The existing code (if any) will be displayed.
The two digit option number for the code to be programmed.
To exit Program Mode
The panel must be in Program Mode. (Program light ON)
When an is displayed, the ARM light or icon is displayed, followed by the digits of the codeArm Only code
To exit Program Mode
Enter the new code twice. The new code will be displayed.
Enter the new code twice. The new code will be displayed.
[Master Code] [Master Code]
[Option No.] [Option No.]
[NEW CODE] [NEW CODE] [NEW CODE]
[NEW CODE]
ENTER
ENTER
ENTER
ENTER
ENTER
Press... Press...
Press... Press...
Press...
To program User Code 1 (The Master Code) to be 1234: To program User Code 2 as an ARM ONLY code to be 5678:
Press...
Press... Press...
P12E ARM E E E5678 5678
P11E E E1234 1234
EXAMPLES
LED KEYPAD
PROGRAMMING USER CODES
LCD KEYPAD
Enters Program Mode. The PROGRAM light will be on. Enters Program Mode. The PROGRAM light will be on.
The existing time will be displayed.
The new time will be displayed.
The existing time will be displayed.
The new time will be displayed.
To exit Program Mode
To exit Program Mode
The panel must be in Program Mode. (Program light ON)
[Master Code] [Master Code]
[Option No.*] [Option No.*]
[NEW TIME] [NEW TIME]
ENTER
ENTER
ENTER
ENTER
Press... Press...
Press... Press...
Press...
Press...
To program Entry Delay Time1 to be 15 seconds: To program Exit Delay Time to be 40 seconds:
Press... Press...
P28E E40
P26E E15
EXAMPLES
LED KEYPAD
PROGRAMMING TIMERS
LCD KEYPAD
Page 19
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
19
PROGRAMMING
Enters Program Mode. The PROGRAM light will be on. Enters Program Mode. The PROGRAM light will be on.
The existing telephone number (if any) will be displayed. The existing telephone number (if any) will be displayed.
The new telephone number will be displayed. The new telephone number will be displayed.
To exit Program Mode To exit Program Mode
The panel must be in Program Mode. (Program light ON)
[Master Code]
[Option No.*]
[NEW TELEPHONE NUMBER] [NEW TELEPHONE NUMBER]
ENTER
ENTER
ENTER
ENTER
Press... Press...
Press... Press...
Press... Press...
To program the Follow Me Telephone Number to be 9123 1234: To the Follow Me Telephone Number:DELETE
Press... Press...
[Master Code]
[Option No.*]
P00E E912341234
P00E MEMORY E
EXAMPLES
LED KEYPAD
PROGRAMMING THE FOLLOW-ME TELEPHONE NUMBER
LCD KEYPAD
* For a list of option numbers, see the Programming Options Table on page 17
[Master Code]
[Master Code]
ENTER
To enter PROGRAM MODE
ENTER
To exit PROGRAM MODE
Page 20
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
20
MONITORING
CENTRAL STATION MONITORING
The ET8 control panel has an on-board digital dialler which can send detailed alarm messages to a Central Monitoring Station.
The digital messages can include information about the zone or zones which caused the alarm, tamper alarms, low battery or mains failure reports, and it can also (by user number) identify the users who Arm and Disarm the system.
Central Station Monitoring is highly recommended and is the most effective method of monitoring your ET8 alarm system. For further information about 24 hour monitoring, contact your installer or E-Tech Security Products.
MONITORED PREMISES
CENTRAL STATION MONITORING
TELEPHONE LINE MONITORING STATION
Page 21
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
21
* The Primary and Secondary telephone numbers are normally only
used for central station monitoring. These numbers can only be programmed in Installer Program Mode.
** The Follow Me Telephone Number replaces the Primary AND
Secondary telephone numbers.
MONITORED PREMISES
AUDIBLE MONITORING
TELEPHONE LINE MOBILE TELEPHONE
FIXED TELEPHONE
AUDIBLE MONITORING
The ET8 can also be programmed to send audible messages to any telephone or mobile phone.
When programmed for audible monitoring, the ET8 calls a pre-programmed number (or numbers) and sounds a series of beeps over the phone. These beeps can identify the zone or zones which caused the alarm and well as several other alarm types.
FOLLOW ME TELEPHONE NUMBER
The Follow Me Telephone Number is the telephone number to which the ET8 sends alarm reports when Audible Monitoring is enabled.
The Follow Me Telephone Number can be changed by the user in User program Mode.
If the Follow Me Telephone Number is programmed, the Primary and Secondary telephone numbers are ignored, even if programmed. (When Audible Monitoring is enabled).
See page 19 for information on programming the Follow Me Telephone Number.
AUDIBLE MONITORING SEQUENCE
When triggered by an alarm, the ET8 will dial the programmed telephone number/s and output the audible message for 45 seconds or until it is acknowledged.
ACKNOWLEDGING THE ALARM
The person receiving the call can then acknowledge the alarm by pressing the key on their telephone. Press the key for at least 2 seconds during pauses in the audible message.
If the alarm is not acknowledged, the keypad’s LINE light will flash continuously until the panel is next Armed.
Page 22
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
22
OPERATING THE ET8 BY TELEPHONE
The ET8 will allow a user to call in to the panel, using a standard DTMF telephone, and remotely Arm or Disarm all areas and also turn on or off Aux 1 and Aux 2.
To ensure security of operation a user can only carry out remote operations after entering a valid user code.
WHAT’S NEEDED:
A telephone with DTMF tones.
A Valid User code programmed in the
ET8.
The ET8 to be connected (via Mode 3 socket) to a working telephone line at the installed premises.
You need to know the telephone number of the line that the ET8 is connected to.
REMOTE OPERATION
NOTES
If the ET8 does not receive commands for periods longer than 10 seconds it will assume that the call is finished and it will hang up.
If an alarm occurs which requires the ET8 to dial out while attempting remote control, the ET8 will treat the alarm as a priority, give a constant tone as a warning and then hang up.
When all remote control commands are finished press to force the ET8 to hang up.
SEQUENCE OF OPERATION.
1. Phone the ET8 telephone number and listen for the required number of rings (ring ring...ring ring) and then hang up.
2. Wait 10 seconds and then call the number again within 50 seconds.
3. The ET8 will answer the second call immediately, sound a beep for 2 seconds then, after a pause, it will sound a lower frequency tone. The ET8 is now ready to receive telephone commands.
4. Press the button on the telephone. This tells the ET8 that telephone commands will follow. It will respond with either 3 beeps if all OK (One long beep means try again).
5. Now enter a valid User Code (that is normally used for Arming or Disarming the ET8) followed by the button.
The ET8 will respond with 3 beeps if it recognises the code or 1 long beep to signal the code was invalid and to try again.
6. Enter the required command. See: Summary Of Telephone Commands.
7. Press to finish. This tells the ET8 to hang up. Also, hang up your telephone.
Page 23
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
23
REMOTE OPERATION
EXAMPLE: ARMING THE ET8 BY TELEPHONE
1. Dial the ET8 telephone number. Listen for one double ring then hang up.
2. Wait 10 seconds, then dial the ET8 telephone number again.
The ET8 will answer immediately and gives a 2 second beep followed by low tone.
3. PRESS To prepare the ET8 ( 3 beeps)
4. PRESS [User Code] to authorise the next command ( 3 beeps)
5. PRESS to Arm the panel ( 3 beeps)
6. PRESS to finish and hang up
SUMMARY OF TELEPHONE COMMANDS
Prepare to receive commands Arm Areas Disarm Areas Turn Aux 1 Output ON or OFF Turn Aux 2 Output ON or OFF Finished – hang up
AUDIBLE FEEDBACK
3 BEEPS:
The User Code is valid
Successful Arming or Disarming
An Auxiliary output has been turned ON.
1 LONG BEEP:
ET8 is already Armed
Invalid code. Try again.
1 SHORT BEEP:
An Auxiliary output has been turned OFF.
Page 24
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
24
SWITCHES
A variety of switches are available for protecting doors and windows. The line-up includes surface and flush mount reed switches, emergency buttons, roller door reed switches and the unique E-Techensor vibration sensor for highly effective perimeter protection.
E-TECH ACCESSORIES
MOTION DETECTORS
E-Tech manufactures a range of high quality and efficient motion detectors - including passive infra-red detectors, dual technology / microwave and infra-red devices as well as ceiling mounted 360° detectors.
All E-Tech detectors are designed using the most modern technology and techniques that ensure superior reliability and performance.
100-021
Quantum
100-226
Quantum
Plus
100-210
Quantum
Dual
100-048
Quantum 360
QUANTUM - 15m passive infra-red detector with selectable pulse count; suitable for domestic and commercial installations. PetAware model
available.
QUANTUM PLUS - 15m passive infra-red detector with selectable pulse count, temperature compensation and downward looking ‘creep’ zones.
QUANTUM DUAL - 15m combination microwave and passive infra-red detector. This combination of detection technologies virtually eliminates the possibility of unwanted alarms but faithfully detects humans. PetAware model available.
QUANTUM 360 - Ceiling mounted 360° passive infra-red detector with selectable pulse count and sensitivity. Provides 8 metre coverage mounted at standard 2.4 metre ceiling height.
CCTV
The E-Tech range of Closed Circuit TV equipment includes Dome cameras, B/W or Colour cameras, Miniature hidden cameras, Monitors - even digital video recorders and remote telephone video systems.
SIRENS
The range of warning devices includes horn speakers, polytough siren covers, internal screamers and satellite sirens with their own battery backup.
PET AWARE DETECTORS
The E-Tech Quantum Pet Aware PIR and Pet Aware DUAL are able to discriminate between
household pets and unwanted human intruders, allowing you to secure your home with your pets indoors.
Page 25
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
25
WIRELESS PRODUCTS
RADIO ACCESSORIES
Ask your installer about the range of E-Tech radio devices for the optional extra convenience of wireless remote control and wireless detection.
Operating your E-Tech security system can be as convenient as opening your car door. The E-Tech Radio Key provides the benefits of separate ON, OFF and PANIC buttons in a slim, waterproof remote control.
* E-Tech radio products require a E-Tech Radio Interface (100-200) to be fitted to the control panel.
E-TECH RADIO KEY 3 BUTTON
Fully waterproof, ultra slim 3 button Radio Key for remote control of the control panel.
With separate buttons for ON (Arm), OFF (Disarm) and PANIC functions. Includes long life lithium battery.
E-TECH RADIO PIR
E-Tech Radio PIR (Passive Infrared) motion detector for wireless motion detection.
Can be used in combination with E-Tech hardwired detectors in areas where it is not possible to install wires. Includes long life
lithium battery.
Also available, the 100-663PET radio Pet Aware model, which detects humans but is immune to household pets.
E-TECH RADIO KEY PENDANT
Fully waterproof pendant style
transmitter can be used as a
portable wireless Panic button.
Supplied with a neckchain as well
as wristwatch straps. Ideal for use
as a medical alarm for the elderly or infirm. (Central Station Monitoring is especially recommended when used for medical alarm purposes). Includes long life lithium battery.
E-TECH RADIO SMOKE DETECTOR
Radio Smoke Detector using Ionisation smoke detection technology. With on board sounder.
A single battery powers the smoke detector and the transmitter. Includes 9V lithium battery.
E-TECH RADIO KEYPAD
A unique fully portable radio keypad. The E-Tech Radio Keypad provides totally wireless Arming/Disarming of the E-Tech ET8, ET16 & D24 control panels.
Also operates Monitor mode and Panic when used with the E-Tech ET16, D24 panels.
The E-Tech radio Keypad is suitable for use as a portable keypad or for adding an extra keypad in areas where it is not possible to install wires.
E-TECH RADIO REED SWITCH
E-Tech Radio Reed Switch for
wireless door and window
protection. Includes long life
lithium battery.
Page 26
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
26
SYMPTOM POSSIBLE CAUSE REMEDY
Zone light on or long beeps when Arming
One or more Zone Detection Devices (e.g., PIR, Reed Switch) may be Unsealed
Close door or window, find the cause of movement
10 beeps from keypad MAINS light flashing BATTERY light flashing
The mains power may be off, ...or the panels backup battery may be low, ...or a Radio Device battery may be low.
Make sure the plug pack is plugged in and the power point is turned on.
Call your installer.
1 long beep from keypad Invalid keypad entry Press E button and try again
2 second siren at the end of Exit Delay time
A zone was Unsealed at the end of Exit Delay time
Disarm the panel and check all zones
Strobe light is flashing There has been an alarm Reset the alarm by Disarming the
panel and check the Alarm Memory
Siren sounds while the panel is Disarmed
A 24 hour zone has been triggered. E.g, Siren Tamper, Box Tamper, Panic Button.
Reset the alarm by Disarming the panel and call your installer.
EXCLUDE light is flashing A zone/s has been Excluded
TAMPER light flashing The 24 hour Tamper input has
triggered
Call your installer
ALARM MEMORY light is flashing There are alarms in memory To clear the ALARM MEMORY light,
view the Alarm memory otherwise the light will clear next time you Arm the panel.
Cannot enter Program Mode The panel is Armed.
Only the Master Code can enter Program Mode.
Disarm the panel before attempting to enter Program Mode. Try again using the Master Code.
TROUBLESHOOTING
Page 27
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
27
Date purchased:
INSTALLATION RECORD
Date installed:
Installation Company:
Telephone:
Monitoring Company:
Telephone:
ZONES DEVICE TYPE
PIR, Reed switch, etc
Entrance, bedroom1, etc
DESCRIPTION
P41E
ENTRY DELA
Y 1
ZONE ASSIGNMENT
P43E ENTRY DELA
Y 2
P42E
HANDOVER
P40E
INST
ANT
P45E AREA 1
P46E
AREA 2
P51E
MONITOR
P52E
24 HOUR
P54E RESET OUTPUT
P55E
STROBE OUTPUT
P56E
SONALERT OUTPUT
P57E
SIREN OUTPUT
P74E Report (dialler)
1
2
3
4
5
6
7
8
© 2001 E-Tech Security Products
P26E ENTRY DELAY TIME 1 Seconds
Seconds
Seconds
Minutes
P27E ENTRY DELAY TIME 2
P28E EXIT DELAY TIME
P29E SIREN RESET TIME
E-TECH ET8
ALARM CONTROL PANEL
CODE
OPTION No CODE HOLDER
AREA 1 AREA 2 RADIO KEY
CODE (Y/N)
User Code 1 P11E
Master Code
(Keypad Code only)
User Code 2 P12E User Code 3 P13E User Code 4 P14E User Code 5 P15E User Code 6 P16E User Code 7 P17E User Code 8 P18E User Code 9 P19E User Code 10 P20E User Code 11 P21E User Code 12 P22E User Code 13 P23E User Code 14 P24E User Code 15 P25E
INSTALLATION RECORD
Page 28
E-TECH ET8 V4 CONTROL PANEL - USER MANUAL
28
OPERATION SUMMARY
ARM
DISARM
MONITOR MODE
PANIC
KEYPAD DURESS
EXCLUDING ZONES
ALARM MEMORY
or...
or...
or...
or...
or...
Press repeatedly to display the last
30 events
or...
Both keys together
(Keypad Panic Shortcut must be ON, P62E 4E)
Press and hold for 4 seconds (P68E 3E & 4E must be OFF)
Press twice within 4 seconds P69E 5E must be ON
[User Code]
[User Code]
[User Code]
[User Code]
[User Code]
[Zone No.] [Zone No.]
[User Code][x]
[User Code]
LED KEYPAD
OPERATION
LCD KEYPAD RADIO KEY
PANIC
PANIC
PANIC
PANIC
ARM
ARM
MONITOR
MONITOR
EXCLUDE
EXCLUDE
MEMORY
MEMORY
MEMORY
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
To Disarm and report a Duress Alarm, add any of the digits 5, 6, 8 or 9 before the User Code when Disarming
Enter the zone numbers to be Excluded
To exit Exclude mode
To exit Memory mode
x 2
Hold
Press repeatedly to display
the last 30 events
Both keys together
(Keypad Panic Shortcut must be ON, P62E 4E)
or...
or...
or...
or...
or... or...
[Zone No.] [Zone No.]
[x]
[User Code]
[User Code]
[User Code]
[User Code]
[User Code]
[User Code]
[User Code]
Enter the zone numbers to be Excluded
To exit Exclude mode
To exit Memory mode
Loading...