E-Tech 09, 15, 36, 22, 28 Installation, Operating And Maintenance Instructions

09/09/2004 - 66402800
excellence in hot water
Installation, operating and maintenance instructions
E-Tech 09 - 15 Single phase
E-Tech 22 - 28 - 36 Tri phase
- 1 -
WARNINGS 2
Who should read these instructions 2 Symbols 2 Recommendations 2 Applicable standards 2 Importants notes 2 Manual handling instructions 2 Removing the boiler from the packaging 2
INTRODUCTION 3
Description of the specifications 3 Lining 3 Heating body 3 Heating elements 3 Equipment 3 Connection 3 Dual stage thermostat 3 Certification 3 Legend 3
INSTRUCTIONS 5
User data 5 Setting up 5 Optional internal timeclock 5 Pressure in the heating system 5
TECHNICAL CHARACTERISTICS 6
Electrical data of model 09 7 Electrical data of model 15 8 Power variation (kW) relative to voltage 8 Electrical data of model 22 - 28 - 36 9
MOUNTING 10
Dimensions 10 Wall mounting 10 Installation room 10
INSTALLATION 11
Disassembling 11 Heating connection 12 Heating connection + DHW : “Y” plan 12 Heating connection + DHW : “S” plan 12 Electric connection / Models : 09 - 15 13 Electric connection / Models : 22 - 28 - 36 14 Sizing of supply wires 14 Wiring diagrams / Models : 09 - 15 - 22 15 Wiring diagrams / Model : 28 16 Wiring diagrams / Model: 36 17 Power wiring / Models : 09 - 15 18 Power wiring / Model : 22 19 Power wiring / Model : 28 20 Power wiring / Model : 36 21
HONEYWELL SUNDIAL WIRING DIAGRAMS 22
Honeywell Sundial Wiring Centre ‘S’ plan 22 Honeywell Sundial Wiring Centre ‘Y’ plan 23
COMMISSIONING AND MAINTENANCE 24
Commissioning - Water 24 Commissioning - Electrical 24 Starting the boiler 24 Maintenance 24
REMOVAL THE HEATING ELEMENTS 25
SPARE PARTS 26
INDEX
- 2 -
WHO SHOULD READ THESE INSTRUCTIONS
These instructions should be read by:
- the specifying engineer
- the installer
- the user
- the service engineer
SYMBOLS
RECOMMENDATIONS
• These instructions are an integral part of the equipment to which they refer and the user must be provided with a copy.
• The product must be installed and serviced by qualified engineers, in compliance with current standards.
• The manufacturer cannot accept liability for any damage resulting from incorrect installation or from the use of components or fittings not specified by the manufacturer.
• Any failure to follow instructions relating to tests and test procedures may result in personal injury or risks of pollution.
It is important to switch the boiler off before carrying out any work.
APPLICABLE STANDARDS
The Boilers have been manufactured to comply with the following standards BS EN60335-2-35: 1998, BS EN55014-2:1997 and BS EN50081-1-1: 1992.
IMPORTANTS NOTES
These instructions are an integral part of the equipment to which they relate and must be handed to the user.
The product must be installed and serviced by qualified engineers in accordance with the regulations in force.
The manufacturer declines all liability for any damage caused as a result of incorrect installation or in the event of the use of appliances or accessories that are not specified by the manufacturer.
The manufacturer reserves the right to change the technical characteristics and specification of its products without notice.
the availability of certain versions and their accessories can vary following the market
MANUAL HANDLING INSTRUCTIONS
WARNINGS
Danger of burns
Essential instruction for the safety of persons and the environment.
Danger of electrocution
Essential instruction for the correct operation of the installation.
REMOVING THE BOILER FROM THE PACKAGING
• Before lifting the boiler from the packaging, ensure that the installation area is clear and that there are no obstacles making installation difficult or unsafe.
• Lay the boiler on its back (as shown on the box side), open the box and remove the cardboard packaging.
• Remove the polythene cover and the polystyrene corner protection pieces.
•With help from another person, lift the boiler from the packaging holding the lipped front edges of the side panels.
• Do not lift or carry the boiler using the top automatic air vent and bottom pump.
The weight of this boiler is 36Kg, which could present a risk of injury.
Care should be taken when loading and unload­ing the boiler to and from vehicles.
We recommend that the boiler be handled by two people until it is securely fixed to a wall.
The safest route from the vehicle to the point of installation should be carefully assessed before unloading the boiler.
Mechanical lifting aids should be utilised whenever possible.
RISK OF INJURY LIFT WITH CARE
HEAVY
APPLIANCE
GET HELP
- 3 -
DESCRIPTION OF THE SPECIFICATIONS
This wall hung electric boiler is available in 5 models :
• models 09 and 15 are supplied with 230 Volt single phase
• models 22, 28 and 36 are only supplied with 400 V triphase + N
The maximum power can be adjusted for all models by acting on the terminals bridges.
- Model 09: Adjustable power from 4.2 to 8.4 kW
- Model 15: Adjustable power from 7.2 to 14.4 kW
- Model 22: Adjustable power from 14.4 to 21.6 kW
- Model 28: Adjustable power from 21.6 to 28.8 kW
- Model 36: Adjustable power from 30 to 36 kW
LINING
The boiler is protected by a steel lining that first of all undergoes a degreasing and phosphation process before being lacquered and burnt at 220°C.
HEATING BODY
The boiler heat exchanger is constructed from mild steel with welded joints. It is hydraulic tested under a pressure of 4.5 bar (maximum working pressure = 3 bar).
HEATING ELEMENTS
Immersion heaters, constructed from stainless steel Incoloy 800 and mounted in the top of the boiler, provide the power source for the Boiler.
EQUIPMENT
The boiler is equipped with all the necessary components to allow direct connection to a heating system without the need for a feed and expansion cistern. These components include; primary 10 litre expansion vessel (suitable for a system water content of up to 160 litres), pressure and temperature gauge, safety valve, circulating pump, low water pressure switch, control and high limit thermostats, on/off and power level switches.
CONNECTION
The boiler is suitable for connection to most heating and hot water systems, with a maximum working pressure of 3bar and a maximum temperature of 85°C. It can also be used in multiple boiler installations allowing greater outputs to be achieved.
The boiler, and connection glands for both the main power supply and optional external controls are provided, suitable for single or three phase electrical supply depending upon boiler output required. An internal 3 amp MCB is linked to the incoming electrical supply to provide the internal control circuit, from which optional controls can be connected e.g. internal or external timeclock, room thermostat or Honeywell Sundial controls.
DUAL STAGE THERMOSTAT
The temperature of the boiler is controlled by a dual stage thermostat which is set by the user to give the desired boiler temperature. When the boiler has heated up to within 7°C of the set temperature, the thermostat switches off one power stage and therefore reduces the heat input. Thanks to this simple but effective form of modulation, the boiler has longer working cycles and requires less stops and starts, thus resulting in a more even temperature across the boiler. It also means less wear and tear on components and, importantly it uses less power once it has reached working temperature.
CERTIFICATION
The boilers have been manufactured to comply with the following standards BS EN60335-2-35: 1998, BS EN55014-2:1997 and BS EN50081-1-1: 1992.
LEGEND
1. Base for relay of DWL priority
2. Control circuit
3. Relay
4. Timer
5. Control terminals
6. Power terminals
INTRODUCTION
4321
5 6
3
- 4 -
INTRODUCTION
Top cover
Rear panel
Water pressure switch
Expansion vessel connection
Supplementary heating return
(not used)
Heating return
Automatic air vent
Expansion vessel
Valve of expansion vessel
Heating out
Manual reset high limit pressure gauge
Expansion vessel connection
Circulating pump
Heating elements
Heating body
Pressure safety valve
Cable glands
Hand side panel
Control panel
Brass pocket
- 5 -
USER DATA
All user controls are situated on the front panel of the boiler, there are no user controls inside the boiler casing. The following instructions assume that the boiler has been commissioned, and that the system is filled with water and has been fully vented.
SETTING UP
• Before switching on any electrical supplies to the boiler ensure that the combined temperature and pressure gauge reads at least 1 bar and the control thermostat is set to the desired temperature.
• If an internal time clock is fitted ensure that this is switched on (see “Optional Internal Time Clock”) and if any other auxiliary controls are fitted e.g. programmer, room thermostats, cylinder thermostats etc, consult appropriate manufacturers' instructions to switch these on.
• Switch on any local means of isolation to boiler.
• Switch the boiler on using the ON/OFF switch (the neon light on the switch should now glow).
•Turn on both power level switches - after a short period of time the boiler temperature should start to rise, indicated by the combined temperature and pressure gauge. If the boiler fails to operate, the overheat safety thermostat should be checked. Access to the thermostat reset button is obtained by unscrewing (anti-clockwise) the domed button cover on the front panel (a screwdriver is not required).The reset button can then be seen - press the button, a click should be heard and the button is reset. If no click was heard the device is not at fault and further investigation is required by a suitably qualified engineer.
• The internal clock or external programmer can now be set to allow on/off periods as desired. The ON/OFF switch and 2 power level switches should be left in the ON position during normal use.
the power level switches will automatically switch on and off during normal boiler operation, depending on boiler temperature.
• If the boiler is not in regular daily use during cold periods, it is recommended that it be fitted with a frost sensing thermostat to override the timeclock and prevent the system from freezing.
• As with most boilers and heating appliances the casing and pipework can get hot during normal running so the boiler must not be covered and the surrounding area must be kept clear.
OPTIONAL INTERNAL TIMECLOCK
• This operates on a 24-hour sequence. Around- the outside of the clock there are a number of white tabs - these allow 15 minute switching times.To set a boiler cycle simply push outwards the number of tabs required for your heating period.
Remember : tab OUT = BOILER ON
tab IN = BOILER OFF
The time of day is marked by an arrow on the inner part of the clock
- set the outer time to coincide with this arrow.
On the centre part of the clock there is a switch. This has three positions :
• Switch down - timeclock off
• Switch middle - timeclock timed (normal position)
• Switch up - timeclock on constant.
PRESSURE IN THE HEATING SYSTEM
The CH pressure must be a minimum of 1 bar and must be checked by the end user on a regular basis. If the pressure drops under 0.5 bar, the integrated water pressure switch blocks the appliance until the pressure in the system returns to a level above 0.8 bar. The installer fits the system with a separate fill valve underneath the appliance. Make sure that the appliance is powered off when filling the system. To do this, turn the on/off switch. For more information, please ask your installer when the system is delivered. A safety valve is provided underneath the appliance. If the system pressure exceeds 3 bars, this valve opens and drains the water from the system. In this case, please contact your installer.
INSTRUCTIONS
1 2 3 54 6 7
LEGEND
1. ON/OFF switch
2. Power levels switch
3. Optional internal clock or controler
4. Combined temperature and pressure gauge
5. Boiler shutdown indicator light
6. Manual reset high limit thermostat
7. Control thermostat : 1 = 40°C 2 = 50°C 3 = 60°C 4 = 70°C 5 = 80°C
- 6 -
TECHNICAL CHARACTERISTICS
4545454545Weight empty (kg)
332332332332332Depth (mm)
442442442442442Width (mm)
763763763763763Height (mm)
3/4”3/4”3/4”3/4”3/4”Heating connection
12585452010
Hydraulic presure drop (mbar)
8585858585
Max. working temperature (°C)
0.80.80.80.80.8
Min. working pressure (bars)
33333
Max. working pressure (bars)
1010101010
Expansion vessel capacity (Litres)
1313131313
Water capacity (Litres)
66533Number of elements
3 x 2 kW2 x 2.4 kW2 x 2.4 kW2 x 2.4 kW2 x 1.4 kWHeating element type
26.45 Ohm22 Ohm22 Ohm22 Ohm37.8 Ohm
Ohmic esistance of element
3 x 400 V + N3 x 400 V + N3 x 400 V + N1 x 230 V1 x 230 VNominal supply voltage
30 to
36 kW
21.6 to
28.8 kW
14.4 to
21.6 kW
7.2 to
14.4 kW
4.2 to
8.4 kW
Power
3628221509Model
- 7 -
TECHNICAL CHARACTERISTICS
Electrical data of model 09
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Single phase 8.4 kW (*)
Terminals 1 and 2 shunted Terminal 3 L1 (A)24 1236 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A)24 1236 Relay K3 activated Power (kW) 5.6 2.8 8.4
Single phase 7 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)24630 Terminals 3, 4 and 5 shunted Terminal 1 N (A)24630 Relay K3 activated Power (kW) 5.6 1.4 7
Single phase 5.6 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)12 1224 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A)12 1224 Relay K3 disactivated (**) Power (kW) 2.8 2.8 5.6
Single phase 4.2 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)12631.2 Terminals 3, 4 and 5 shunted Terminal 1 N (A)12631.2 Relay K3 disactivated (**) Power (kW) 2.8 1.4 4.2
1N23L456
1N23L456
1N23L456
1N23L456
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
Electrical data of model 15
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
- 8 -
TECHNICAL CHARACTERISTICS
Single phase 14.4 kW (*) Terminals 1 and 2 shunted Terminal 3 L1 (A) 41.6 20.8 62.4 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A) 41.6 20.8 62.4 Relay K3 activated Power (kW) 9.6 4.8 14.4
Single phase 12 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 41.6 10.4 52 Terminals 3, 4 and 5 shunted Terminal 1 N (A) 41.6 10.4 52 Relay K3 activated Power (kW) 9.6 2.4 12
Single phase 9.6 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 20.8 20.8 41.6 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A) 20.8 20.8 41.6 Relay K3 disactivated (**) Power (kW) 4.8 4.8 9.6
Single phase 7.2 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 20.8 10.4 31.2 Terminals 3, 4 and 5 shunted Terminal 1 N (A) 20.8 10.4 31.2 Relay K3 disactivated (**) Power (kW) 4.8 2.4 7.2
1N23L456
1N23L456
1N23L456
1N23L456
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
220 V 230 V 240 V 3 x 380 V 3 x 400 V 3 x 415 V
E-Tech W 09
7.7 8.4 9.1
E-Tech W 15
13.2 14.4 15.7
E-Tech W 22
19.5 21.6 23.3
E-Tech W 28
26.0 28.8 31.0
E-Tech W 36
32.5 36.0 38.8
Power variation (kW) relative to voltage
Electrical data of model 28
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 28.8 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 20.8 41.6 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 20.8 41.6 Relay K4 activated Ter minal 5 L3 (A) 20.8 20.8 41.6
Terminal 1 N (A) 000 Power (kW) 14.4 14.4 28.8
Tri phase 21.6 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 10.4 31.2 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 10.4 31.2 Relay K4 disactivated (**) Ter minal 5 L3 (A) 20.8 10.4 31.2
Terminal 1 N (A) 000 Power (kW) 14.4 7.2 21.6
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.
- 9 -
TECHNICAL CHARACTERISTICS
Electrical data of model 22
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 21.6 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 10.4 31.2 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 10.4 31.2 Relay K43 activated Terminal 5 L3 (A) 20.8 10.4 31.2
Terminal 1 N (A) 000 Power (kW) 14.4 7.2 21.6
Tri phase 14.4 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A) 10.4 10.4 20.8 Terminals 5 and 6 shunted Terminal 3 L2 (A) 10.4 10.4 20.8 Relay K3 disactivated (**) Ter minal 5 L3 (A) 10.4 10.4 20.8
Terminal 1 N (A) 000 Power (kW) 7.2 7.2 14.4
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
Electrical data of model 36
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 36 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A)26 2652 Terminals 5 and 6 shunted Terminal 3 L2 (A)26 2652 Relay K4 activated Ter minal 5 L3 (A)26 2652
Terminal 1 N (A) 000 Power (kW)18 1836
Tri phase 30 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A)26 1743 Terminals 5 and 6 shunted Terminal 3 L2 (A)26 1743 Relay K4 disactivated (**) Ter minal 5 L3 (A)26 1743
Terminal 1 N (A) 000 Power (kW)18 1230
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.
Loading...
+ 22 hidden pages