E-Tech 09, 15, 36, 22, 28 Installation, Operating And Maintenance Instructions

Page 1
09/09/2004 - 66402800
excellence in hot water
Installation, operating and maintenance instructions
E-Tech 09 - 15 Single phase
E-Tech 22 - 28 - 36 Tri phase
Page 2
- 1 -
WARNINGS 2
Who should read these instructions 2 Symbols 2 Recommendations 2 Applicable standards 2 Importants notes 2 Manual handling instructions 2 Removing the boiler from the packaging 2
INTRODUCTION 3
Description of the specifications 3 Lining 3 Heating body 3 Heating elements 3 Equipment 3 Connection 3 Dual stage thermostat 3 Certification 3 Legend 3
INSTRUCTIONS 5
User data 5 Setting up 5 Optional internal timeclock 5 Pressure in the heating system 5
TECHNICAL CHARACTERISTICS 6
Electrical data of model 09 7 Electrical data of model 15 8 Power variation (kW) relative to voltage 8 Electrical data of model 22 - 28 - 36 9
MOUNTING 10
Dimensions 10 Wall mounting 10 Installation room 10
INSTALLATION 11
Disassembling 11 Heating connection 12 Heating connection + DHW : “Y” plan 12 Heating connection + DHW : “S” plan 12 Electric connection / Models : 09 - 15 13 Electric connection / Models : 22 - 28 - 36 14 Sizing of supply wires 14 Wiring diagrams / Models : 09 - 15 - 22 15 Wiring diagrams / Model : 28 16 Wiring diagrams / Model: 36 17 Power wiring / Models : 09 - 15 18 Power wiring / Model : 22 19 Power wiring / Model : 28 20 Power wiring / Model : 36 21
HONEYWELL SUNDIAL WIRING DIAGRAMS 22
Honeywell Sundial Wiring Centre ‘S’ plan 22 Honeywell Sundial Wiring Centre ‘Y’ plan 23
COMMISSIONING AND MAINTENANCE 24
Commissioning - Water 24 Commissioning - Electrical 24 Starting the boiler 24 Maintenance 24
REMOVAL THE HEATING ELEMENTS 25
SPARE PARTS 26
INDEX
Page 3
- 2 -
WHO SHOULD READ THESE INSTRUCTIONS
These instructions should be read by:
- the specifying engineer
- the installer
- the user
- the service engineer
SYMBOLS
RECOMMENDATIONS
• These instructions are an integral part of the equipment to which they refer and the user must be provided with a copy.
• The product must be installed and serviced by qualified engineers, in compliance with current standards.
• The manufacturer cannot accept liability for any damage resulting from incorrect installation or from the use of components or fittings not specified by the manufacturer.
• Any failure to follow instructions relating to tests and test procedures may result in personal injury or risks of pollution.
It is important to switch the boiler off before carrying out any work.
APPLICABLE STANDARDS
The Boilers have been manufactured to comply with the following standards BS EN60335-2-35: 1998, BS EN55014-2:1997 and BS EN50081-1-1: 1992.
IMPORTANTS NOTES
These instructions are an integral part of the equipment to which they relate and must be handed to the user.
The product must be installed and serviced by qualified engineers in accordance with the regulations in force.
The manufacturer declines all liability for any damage caused as a result of incorrect installation or in the event of the use of appliances or accessories that are not specified by the manufacturer.
The manufacturer reserves the right to change the technical characteristics and specification of its products without notice.
the availability of certain versions and their accessories can vary following the market
MANUAL HANDLING INSTRUCTIONS
WARNINGS
Danger of burns
Essential instruction for the safety of persons and the environment.
Danger of electrocution
Essential instruction for the correct operation of the installation.
REMOVING THE BOILER FROM THE PACKAGING
• Before lifting the boiler from the packaging, ensure that the installation area is clear and that there are no obstacles making installation difficult or unsafe.
• Lay the boiler on its back (as shown on the box side), open the box and remove the cardboard packaging.
• Remove the polythene cover and the polystyrene corner protection pieces.
•With help from another person, lift the boiler from the packaging holding the lipped front edges of the side panels.
• Do not lift or carry the boiler using the top automatic air vent and bottom pump.
The weight of this boiler is 36Kg, which could present a risk of injury.
Care should be taken when loading and unload­ing the boiler to and from vehicles.
We recommend that the boiler be handled by two people until it is securely fixed to a wall.
The safest route from the vehicle to the point of installation should be carefully assessed before unloading the boiler.
Mechanical lifting aids should be utilised whenever possible.
RISK OF INJURY LIFT WITH CARE
HEAVY
APPLIANCE
GET HELP
Page 4
- 3 -
DESCRIPTION OF THE SPECIFICATIONS
This wall hung electric boiler is available in 5 models :
• models 09 and 15 are supplied with 230 Volt single phase
• models 22, 28 and 36 are only supplied with 400 V triphase + N
The maximum power can be adjusted for all models by acting on the terminals bridges.
- Model 09: Adjustable power from 4.2 to 8.4 kW
- Model 15: Adjustable power from 7.2 to 14.4 kW
- Model 22: Adjustable power from 14.4 to 21.6 kW
- Model 28: Adjustable power from 21.6 to 28.8 kW
- Model 36: Adjustable power from 30 to 36 kW
LINING
The boiler is protected by a steel lining that first of all undergoes a degreasing and phosphation process before being lacquered and burnt at 220°C.
HEATING BODY
The boiler heat exchanger is constructed from mild steel with welded joints. It is hydraulic tested under a pressure of 4.5 bar (maximum working pressure = 3 bar).
HEATING ELEMENTS
Immersion heaters, constructed from stainless steel Incoloy 800 and mounted in the top of the boiler, provide the power source for the Boiler.
EQUIPMENT
The boiler is equipped with all the necessary components to allow direct connection to a heating system without the need for a feed and expansion cistern. These components include; primary 10 litre expansion vessel (suitable for a system water content of up to 160 litres), pressure and temperature gauge, safety valve, circulating pump, low water pressure switch, control and high limit thermostats, on/off and power level switches.
CONNECTION
The boiler is suitable for connection to most heating and hot water systems, with a maximum working pressure of 3bar and a maximum temperature of 85°C. It can also be used in multiple boiler installations allowing greater outputs to be achieved.
The boiler, and connection glands for both the main power supply and optional external controls are provided, suitable for single or three phase electrical supply depending upon boiler output required. An internal 3 amp MCB is linked to the incoming electrical supply to provide the internal control circuit, from which optional controls can be connected e.g. internal or external timeclock, room thermostat or Honeywell Sundial controls.
DUAL STAGE THERMOSTAT
The temperature of the boiler is controlled by a dual stage thermostat which is set by the user to give the desired boiler temperature. When the boiler has heated up to within 7°C of the set temperature, the thermostat switches off one power stage and therefore reduces the heat input. Thanks to this simple but effective form of modulation, the boiler has longer working cycles and requires less stops and starts, thus resulting in a more even temperature across the boiler. It also means less wear and tear on components and, importantly it uses less power once it has reached working temperature.
CERTIFICATION
The boilers have been manufactured to comply with the following standards BS EN60335-2-35: 1998, BS EN55014-2:1997 and BS EN50081-1-1: 1992.
LEGEND
1. Base for relay of DWL priority
2. Control circuit
3. Relay
4. Timer
5. Control terminals
6. Power terminals
INTRODUCTION
4321
5 6
3
Page 5
- 4 -
INTRODUCTION
Top cover
Rear panel
Water pressure switch
Expansion vessel connection
Supplementary heating return
(not used)
Heating return
Automatic air vent
Expansion vessel
Valve of expansion vessel
Heating out
Manual reset high limit pressure gauge
Expansion vessel connection
Circulating pump
Heating elements
Heating body
Pressure safety valve
Cable glands
Hand side panel
Control panel
Brass pocket
Page 6
- 5 -
USER DATA
All user controls are situated on the front panel of the boiler, there are no user controls inside the boiler casing. The following instructions assume that the boiler has been commissioned, and that the system is filled with water and has been fully vented.
SETTING UP
• Before switching on any electrical supplies to the boiler ensure that the combined temperature and pressure gauge reads at least 1 bar and the control thermostat is set to the desired temperature.
• If an internal time clock is fitted ensure that this is switched on (see “Optional Internal Time Clock”) and if any other auxiliary controls are fitted e.g. programmer, room thermostats, cylinder thermostats etc, consult appropriate manufacturers' instructions to switch these on.
• Switch on any local means of isolation to boiler.
• Switch the boiler on using the ON/OFF switch (the neon light on the switch should now glow).
•Turn on both power level switches - after a short period of time the boiler temperature should start to rise, indicated by the combined temperature and pressure gauge. If the boiler fails to operate, the overheat safety thermostat should be checked. Access to the thermostat reset button is obtained by unscrewing (anti-clockwise) the domed button cover on the front panel (a screwdriver is not required).The reset button can then be seen - press the button, a click should be heard and the button is reset. If no click was heard the device is not at fault and further investigation is required by a suitably qualified engineer.
• The internal clock or external programmer can now be set to allow on/off periods as desired. The ON/OFF switch and 2 power level switches should be left in the ON position during normal use.
the power level switches will automatically switch on and off during normal boiler operation, depending on boiler temperature.
• If the boiler is not in regular daily use during cold periods, it is recommended that it be fitted with a frost sensing thermostat to override the timeclock and prevent the system from freezing.
• As with most boilers and heating appliances the casing and pipework can get hot during normal running so the boiler must not be covered and the surrounding area must be kept clear.
OPTIONAL INTERNAL TIMECLOCK
• This operates on a 24-hour sequence. Around- the outside of the clock there are a number of white tabs - these allow 15 minute switching times.To set a boiler cycle simply push outwards the number of tabs required for your heating period.
Remember : tab OUT = BOILER ON
tab IN = BOILER OFF
The time of day is marked by an arrow on the inner part of the clock
- set the outer time to coincide with this arrow.
On the centre part of the clock there is a switch. This has three positions :
• Switch down - timeclock off
• Switch middle - timeclock timed (normal position)
• Switch up - timeclock on constant.
PRESSURE IN THE HEATING SYSTEM
The CH pressure must be a minimum of 1 bar and must be checked by the end user on a regular basis. If the pressure drops under 0.5 bar, the integrated water pressure switch blocks the appliance until the pressure in the system returns to a level above 0.8 bar. The installer fits the system with a separate fill valve underneath the appliance. Make sure that the appliance is powered off when filling the system. To do this, turn the on/off switch. For more information, please ask your installer when the system is delivered. A safety valve is provided underneath the appliance. If the system pressure exceeds 3 bars, this valve opens and drains the water from the system. In this case, please contact your installer.
INSTRUCTIONS
1 2 3 54 6 7
LEGEND
1. ON/OFF switch
2. Power levels switch
3. Optional internal clock or controler
4. Combined temperature and pressure gauge
5. Boiler shutdown indicator light
6. Manual reset high limit thermostat
7. Control thermostat : 1 = 40°C 2 = 50°C 3 = 60°C 4 = 70°C 5 = 80°C
Page 7
- 6 -
TECHNICAL CHARACTERISTICS
4545454545Weight empty (kg)
332332332332332Depth (mm)
442442442442442Width (mm)
763763763763763Height (mm)
3/4”3/4”3/4”3/4”3/4”Heating connection
12585452010
Hydraulic presure drop (mbar)
8585858585
Max. working temperature (°C)
0.80.80.80.80.8
Min. working pressure (bars)
33333
Max. working pressure (bars)
1010101010
Expansion vessel capacity (Litres)
1313131313
Water capacity (Litres)
66533Number of elements
3 x 2 kW2 x 2.4 kW2 x 2.4 kW2 x 2.4 kW2 x 1.4 kWHeating element type
26.45 Ohm22 Ohm22 Ohm22 Ohm37.8 Ohm
Ohmic esistance of element
3 x 400 V + N3 x 400 V + N3 x 400 V + N1 x 230 V1 x 230 VNominal supply voltage
30 to
36 kW
21.6 to
28.8 kW
14.4 to
21.6 kW
7.2 to
14.4 kW
4.2 to
8.4 kW
Power
3628221509Model
Page 8
- 7 -
TECHNICAL CHARACTERISTICS
Electrical data of model 09
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Single phase 8.4 kW (*)
Terminals 1 and 2 shunted Terminal 3 L1 (A)24 1236 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A)24 1236 Relay K3 activated Power (kW) 5.6 2.8 8.4
Single phase 7 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)24630 Terminals 3, 4 and 5 shunted Terminal 1 N (A)24630 Relay K3 activated Power (kW) 5.6 1.4 7
Single phase 5.6 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)12 1224 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A)12 1224 Relay K3 disactivated (**) Power (kW) 2.8 2.8 5.6
Single phase 4.2 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A)12631.2 Terminals 3, 4 and 5 shunted Terminal 1 N (A)12631.2 Relay K3 disactivated (**) Power (kW) 2.8 1.4 4.2
1N23L456
1N23L456
1N23L456
1N23L456
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
Page 9
Electrical data of model 15
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
- 8 -
TECHNICAL CHARACTERISTICS
Single phase 14.4 kW (*) Terminals 1 and 2 shunted Terminal 3 L1 (A) 41.6 20.8 62.4 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A) 41.6 20.8 62.4 Relay K3 activated Power (kW) 9.6 4.8 14.4
Single phase 12 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 41.6 10.4 52 Terminals 3, 4 and 5 shunted Terminal 1 N (A) 41.6 10.4 52 Relay K3 activated Power (kW) 9.6 2.4 12
Single phase 9.6 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 20.8 20.8 41.6 Terminals 3, 4, 5 and 6 shunted Ter minal 1 N (A) 20.8 20.8 41.6 Relay K3 disactivated (**) Power (kW) 4.8 4.8 9.6
Single phase 7.2 kW
Terminals 1 and 2 shunted Terminal 3 L1 (A) 20.8 10.4 31.2 Terminals 3, 4 and 5 shunted Terminal 1 N (A) 20.8 10.4 31.2 Relay K3 disactivated (**) Power (kW) 4.8 2.4 7.2
1N23L456
1N23L456
1N23L456
1N23L456
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
220 V 230 V 240 V 3 x 380 V 3 x 400 V 3 x 415 V
E-Tech W 09
7.7 8.4 9.1
E-Tech W 15
13.2 14.4 15.7
E-Tech W 22
19.5 21.6 23.3
E-Tech W 28
26.0 28.8 31.0
E-Tech W 36
32.5 36.0 38.8
Power variation (kW) relative to voltage
Page 10
Electrical data of model 28
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 28.8 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 20.8 41.6 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 20.8 41.6 Relay K4 activated Ter minal 5 L3 (A) 20.8 20.8 41.6
Terminal 1 N (A) 000 Power (kW) 14.4 14.4 28.8
Tri phase 21.6 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 10.4 31.2 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 10.4 31.2 Relay K4 disactivated (**) Ter minal 5 L3 (A) 20.8 10.4 31.2
Terminal 1 N (A) 000 Power (kW) 14.4 7.2 21.6
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.
- 9 -
TECHNICAL CHARACTERISTICS
Electrical data of model 22
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 21.6 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A) 20.8 10.4 31.2 Terminals 5 and 6 shunted Terminal 3 L2 (A) 20.8 10.4 31.2 Relay K43 activated Terminal 5 L3 (A) 20.8 10.4 31.2
Terminal 1 N (A) 000 Power (kW) 14.4 7.2 21.6
Tri phase 14.4 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A) 10.4 10.4 20.8 Terminals 5 and 6 shunted Terminal 3 L2 (A) 10.4 10.4 20.8 Relay K3 disactivated (**) Ter minal 5 L3 (A) 10.4 10.4 20.8
Terminal 1 N (A) 000 Power (kW) 7.2 7.2 14.4
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 17 and 18 in order to desactivate the relay.
Electrical data of model 36
ST AGE 1 ST AGE 2 TOTAL POWER TERMINALS
Tri phase 36 kW (*)
Terminals 3 and 4 shunted Terminal 2 L1 (A)26 2652 Terminals 5 and 6 shunted Terminal 3 L2 (A)26 2652 Relay K4 activated Ter minal 5 L3 (A)26 2652
Terminal 1 N (A) 000 Power (kW)18 1836
Tri phase 30 kW
Terminals 3 and 4 shunted Terminal 2 L1 (A)26 1743 Terminals 5 and 6 shunted Terminal 3 L2 (A)26 1743 Relay K4 disactivated (**) Ter minal 5 L3 (A)26 1743
Terminal 1 N (A) 000 Power (kW)18 1230
1N2L13L24 5L36
1N2L13L24 5L36
This values are based on standard supply voltage in Europe, that is 1 x 230V for single phase and 3 x 400V + N for tri phase. (*) Factory configuration / (**) Remove the shunt 19 and 20 in order to desactivate the relay.
Page 11
- 10 -
MOUNTING
Min.
25 mm
Min. 400 mm
Min. 200 mm
763 mm
763 mm
442 mm
332 mm
178 mm 379 mm
90 mm
101,6 m
m
101,6 mm
48,4 mm
53,2 m
m
53,2 m
m
48,4 m
m
• The boiler must be fixed to a non flammable wall.
• Observing the clearances shown below, drill 2 off 14mm x 100mm holes.
• Fit the 2 bolts supplied and hang the wall bracket.
• Fit washers and nuts
• Hang the boiler
FROST PROTECTION
The boiler is NOT fitted with frost protection. If the boiler is being installed in a position where freezing could take place, then a suitable external frost thermostat should be fitted.
CONNECTING TO THE SYSTEM
The boiler is designed to operate on a sealed system (ie. no open vent or feed and expansion cistern). Hot water expansion within the system is taken up by the internal 10 litre expansion vessel.This is suitable for systems up to 160 litres capacity. If the system capacity is more than this then an additional expansion vessel may be required.This can be fitted external to the boiler at a convenient place on the pipework. Please note that the circulation pump is fitted to the flow connection.
INSTALLATION ROOM
The appliance must be positioned in such a way as to be easily accessible at all times. In addition, the following minimum distances around the appliance must be complied with
WALL MOUNTING
DIMENSIONS
Page 12
- 11 -
INSTALLATION
Panel removal and access to hydraulic connections
1. undo screws
2. tilt panel towards you and lift clear remove the top cover
3. loosen screws of the control panel
4. turn up the control panel
5. block the control panel with the screw
DISASSEMBLING
A
B
C
1
2
2
3
4
5
Page 13
- 12 -
INSTALLATION
39
38
3
7
36
35
34
3
3
32
31
29
28
2
7
26
25
24
2
3
22
21
19
1
8
1
7
16
15
14
1
3
12
11
9
8
7
6
5
4
3
2
1
39
38
3
7
36
35
34
3
3
32
31
29
28
2
7
26
25
24
2
3
22
21
19
1
8
1
7
16
15
14
1
3
12
11
9
8
7
6
5
4
3
2
1
39
38
3
7
36
35
34
3
3
32
31
29
28
2
7
26
25
24
2
3
22
21
19
1
8
1
7
16
15
14
1
3
12
11
9
8
7
6
5
4
3
2
1
39
38
3
7
36
35
34
3
3
32
31
29
28
2
7
26
25
24
2
3
22
21
19
1
8
1
7
16
15
14
1
3
12
11
9
8
7
6
5
4
3
2
1
15
15
13 14
13 14
11 12
11 12
HEATING CONNECTION
HEATING CONNECTION + DHW : “S” PLAN
HEATING CONNECTION + DHW : “Y” PLAN
Limiting the maximum adjustable temperature
Factory setting
30 - 85°C
Floor heating
30 - 50°C
Limiting the minimum
adjustable temperature
60 - 85°C
Limiting the minimum
adjustable temperature
60 - 85°C
NOTE:
• controller not supplied in standard
NOTE:
• controller not supplied in standard
NOTE:
• controller not supplied in standard
M M
Page 14
- 13 -
INSTALLATION
• This appliance must be permanently connected to fixed wiring and must be earthed.
• The wiring must be carried out by a competent person and be in accordance with the current IEE Wiring Regulations.
• Isolation device must be provided with a minimum contact clearance of 3mm.
• The MCB must be readily accessible and adjacent to the appliance.
7 8
7 8
5 6
5 6
3 4
3 4
1 2
1 2
NL1
53 4
L1
1 2
N
6
Power supply 230 V mono +
Safety contactor
53 4
L1
1 2
N
6
NL1
Power supply
230 V mono
ELECTRIC CONNECTION / MODELS : 09 - 15
Page 15
- 14 -
INSTALLATION
• This appliance must be permanently connected to fixed wiring and must be earthed.
• The wiring must be carried out by a competent person and be in accordance with the current IEE Wiring Regulations.
• Isolation device must be provided with a minimum contact clearance of 3mm.
• The MCB must be readily accessible and adjacent to the appliance.
7 8
7 8
5 6
5 6
3 4
3 4
1 2
1 2
L3 L2 NL1
5
L3
3 4
L2
1 2
N L1
6
Power supply
3 x 400 V + Neutral +
Safety contactor
L3 L2 NL1
5
L3
3 4
L2
1 2
N L1
6
Power supply
3 x 400 V + Neutral
ELECTRIC CONNECTION / MODELS : 22 - 28 - 36
SIZING OF SUPPLY WIRES
the supply wires are sized depending of the type and current of the MCB, this last is firstly sized depending of the nominal current of the boiler. The admissible current of the supply wires depends of the ambient temperature, the section and the length of the wires, the wires insulation, the wires canalisation, the mounting type and the environment. The following values are given for information for an ambient temperature of 30°C and a maximal length of 5 meters. In all the cases, the installation must be in accordance with the current IEE Wiring Regulations.
16 25 32 40 63 80
1.5
2.5 4 6
10 16
Nominal current of the MCB
(A)
Nominal section
(mm2)
Page 16
- 15 -
INSTALLATION
WIRING DIAGRAMS / MODELS : 09 - 15 - 22
L1 1 2
br
br br bk
N 3 4
b
b
or
bbb
bk
bb
7
t
p
bb
8
b
9
b
5
6
b
bk or
g
b
r
3 amp
MCB
C
2
1
r
C
1
2
or
10 11 12 13
y
y
t
or
or or r r
gg
gpk pk
b
bw
b
w
g
b
14 15
16
M
2.1. 2.2.
2.1. 2.2.
17 18
t
w
r
ABC
DE
HJ
JL
I
K1
K3
K2
F
G
b Blue
bk Black
br Brown
g Grey
or Orange
pk Pink
r Red
vViolet
w White
yYellow
A ON/OFF switch
B Manual reset high limit thermostat
CWater pressure switch
D Alarm indicator
E Switch indicator
F Optional room thermostat
G Cirluating pump
H Boiler thermostat 60 - 85°C
I Boiler thermostat 53 - 78°C
J Power level switch
K1 Power relay 1 - level 1
K2 Power relay 1 - level 2
K3 Power relay 2 - level 1
LTimer
1-2: Life (230V ~ 50Hz)
3-4: Neutral
5-6: Time clock
(optional)
7-8: Master Relay
(optional)
10-11: Stop Bridge
12-13: Room thermostat
(optional)
14-15: Boiler pump
17-18: Relay K3 disactivated
Page 17
- 16 -
INSTALLATION
WIRING DIAGRAMS / MODEL : 28
L1 1 2
br
br br bk
N 3 4
b
b
or
bbb
bk
bb
7
t
p
bb
8
b
9
b
5
6
b
bk or
g
b
r
3 amp
MCB
C
2
1
r
C
1
2
or
10 11 12 13
y
y
t
or
or or r r
gg
gpk pk pk
b
bw
b
w
g
b
14 15
16
M
2.1. 2.2.
2.1. 2.2.
17 18
t
w
r
ABC
DE
HJ
JL
I
K1
K3
bw
19 20
w
pk
K4
K2
F
G
b Blue
bk Black
br Brown
g Grey
or Orange
pk Pink
r Red
vViolet
w White
yYellow
A ON/OFF switch
B Manual reset high limit thermostat
CWater pressure switch
D Alarm indicator
E Switch indicator
F Optional room thermostat
G Cirluating pump
H Boiler thermostat 60 - 85°C
I Boiler thermostat 53 - 78°C
J Power level switch
K1 Power relay 1 - level 1
K2 Power relay 1 - level 2
K3 Power relay 2 - level 1
K4 Power relay 2 - level 2
LTimer
1-2: Life (230V ~ 50Hz)
3-4: Neutral
5-6: Time clock
(optional)
7-8: Master Relay
(optional)
10-11: Stop Bridge
12-13: Room thermostat
(optional)
14-15: Boiler pump
17-18: Relay K3 disactivated
19-20: Relay K4 disactivated
Page 18
- 17 -
INSTALLATION
WIRING DIAGRAMS / MODEL : 36
L1 1 2
br
br br bk
N 3 4
b
b
or
bbb
bk
bb
7
t
p
bb
8
b
9
b
5
6
b
bk or
g
b
r
3 amp
MCB
C
2
1
r
C
1
2
or
10 11 12 13
y
y
t
or
or or r r
gg
gpk pk pk
b
bw
b
w
g
b
14 15
16
M
2.1. 2.2.
2.1. 2.2.
17 18
t
w
r
ABC
DE
HJ
JL
I
K1
K3
bw
19 20
w
pk
K4
bw
21 22
w
r
K5
bw
23 24
w
pk
K6
K2
F
G
b Blue
bk Black
br Brown
g Grey
or Orange
pk Pink
r Red
vViolet
w White
yYellow
A ON/OFF switch
B Manual reset high limit thermostat
CWater pressure switch
D Alarm indicator
E Switch indicator
F Optional room thermostat
G Cirluating pump
H Boiler thermostat 60 - 85°C
I Boiler thermostat 53 - 78°C
J Power level switch
K1 Power relay 1 - level 1
K2 Power relay 1 - level 2
K3 Power relay 2 - level 1
K4 Power relay 2 - level 2
K5 Power relay 3 - level 1
K6 Power relay 3 - level 2
LTimer
1-2: Life (230V ~ 50Hz)
3-4: Neutral
5-6: Time clock
(optional)
7-8: Master Relay
(optional)
10-11: Stop Bridge
12-13: Room thermostat
(optional)
14-15: Boiler pump
17-18: Relay K3 disactivated
19-20: Relay K4 disactivated
21-22: Relay K5 disactivated
23-24: Relay K6 disactivated
Page 19
- 18 -
INSTALLATION
POWER WIRING / MODELS : 09-15
K1 K2 K3
3 x b
3 x b
2 x or
2 x bk
r
r
r
bk
b
b
b
b
b
b
bk
or
or
r
r
bk
b
b
b
b
b
b
bk
or
or
r
8.4 kW
Type 9
MONO
PHASE
7 kW 5.6 kW 4.2 kW
1
N
23
L
456 1
N
23
L
456 1
N
23
L
4561
N
23
L
456
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
17 18
14.4 kW
Type 15
MONO
PHASE
12 kW 9.6 kW 7.2 kW
1
N
23
L
456 1
N
23
L
456 1
N
23
L
4561
N
23
L
456
Page 20
- 19 -
INSTALLATION
POWER WIRING / MODEL : 22
21.6 kW
Type 22
TRI
PHASE
14.4 kW
1
N
2
L1
3
L2
45
L3
6 1
N
2
L1
3
L2
45
L3
6
17 18
17 18
17 18
17 18
3 x b
3 x or
2 x bk
1 x bk
2 x r
1 x r
K1
or
r
bk
b
or
r
bk
b
K2
Or
r
Bk
b
or
r
bk
b
K3
or
r
bk
b
or
r
bk
b
Page 21
- 20 -
INSTALLATION
POWER WIRING / MODEL : 28
28.8 kW
Type 28
TRI
PHASE
21.6 kW
1
N
2
L1
3
L2
45
L3
6 1
N
2
L1
3
L2
45
L3
6
19 20
19 20
19 20
19 20
4 x b
4 x or
3 x bk
1 x bk
3 x r
1 x r
K1
or
r
bk
b
or
r
bk
b
K2
Or
r
Bk
b
or
r
bk
b
K4
or
r
bk
b
or
r
bk
b
K3
or
r
bk
b
or
r
bk
b
Page 22
- 21 -
INSTALLATION
POWER WIRING / MODEL : 36
6 x b
6 x or
5 x bk
1 x bk
5 x r
1 x r
K1
or
r
bk
b
or
r
bk
b
K2
Or
r
Bk
b
or
r
bk
b
K3
or
r
bk
b
or
r
bk
b
K4
or
r
bk
b
or
r
bk
b
K5
or
r
bk
b
or
r
bk
b
K6
or
r
bk
b
or
r
bk
b
36 kW
Type 36
TRI
PHASE
30 kW
1
N
2
L1
3
L2
45
L3
6 1
N
2
L1
3
L2
45
L3
6
19 20
19 20
19 20
19 20
Page 23
- 22 -
HONEYWELL SUNDIAL WIRING DIAGRAMS
Note: Illustrated model = 36 kW Tri Phase
Note: All bold numbers indicate a DIN rail terminal connection
CYLINDER STAT
HTGHW
NL
143256
T6306B ROOM STAT
2
1
3
V4043H HTG ZONE VALVE
MOTOR
789 10
V4043H DHW ZONE VALVE
MOTOR
Honeywell Sundial Wiring Centre `S ` Plan
Note: Earth wires not shown for clarity
During installation the earth wires from each component connect to terminal 3 in the wiring centre
E
bk- black br- brown r-red w-white y- yellow o - orange b - blue v - violet p - pink gr - grey
CABLE COLOUR CODES
gr
gr
gr
gr
b
b
b
b
b
brbr
br
br
o
o
o
o
C
L1 1 2
br
br br bk
N 3 4
b
b
or
bbb
bk
bb
7
t
p
bb
8b9
b
5
6
b
bk or
g
b
r
3 amp
MCB
C
2
1
r
C
1
2
or
10 11 12 13
y
y
t
or
or or r r
gg
gpk pk pk
b
bw
b
w
g
b
14 15
16
M
2.1. 2.2.
2.1. 2.2.
17 18
t
w
r
ABC
DE
HJ
JL
I
bw
19 20
w
pk
bw
21 22
w
r
bw
23 24
w
pk
F
G
Page 24
- 23 -
HONEYWELL SUNDIAL WIRING DIAGRAMS
Note: Illustrated model = 36 kW Tri Phase
Note: All bold numbers indicate a DIN rail terminal connection
CYLINDER STAT
HTG
HW ON
NL
143256
T6306B ROOM STAT
2
1
3
78910
Honeywell Sundial Wiring Centre `Y ` Plan
Note: Earth wires not shown for clarity
During installation the earth wires from each component connect to terminal 3 in the wiring centre
E
bk- black br- brown r-red w-white y- yellow o - orange b - blue v - violet p - pink gr - grey
CABLE COLOUR CODES
gr
b
b
b
o
1
2
C
HW OFF
V4073A MID POSITION ZONE VALVE
w
w
L1 1 2
br
br br bk
N 3 4
b
b
or
bbb
bk
bb
7
t
p
bb
8b9
b
5
6
b
bk or
g
b
r
3 amp
MCB
C
2
1
r
C
1
2
or
10 11 12 13
y
y
t
or
or or r r
gg
gpk pk pk
b
bw
b
w
g
b
14 15
16
M
2.1. 2.2.
2.1. 2.2.
17 18
t
w
r
ABC
DE
HJ
JL
I
bw
19 20
w
pk
bw
21 22
w
r
bw
23 24
w
pk
F
G
Page 25
- 24 -
COMMISSIONING - WATER
1. The system must be thoroughly cleansed prior to connection of the boiler. The system water should be treated to prevent general corrosion and deposition of scale or sludge in the boiler, please refer to BS7593. If installing the boiler onto an existing system, ACV recommend that an approved system cleaner is used.
2. Fill and pressurise the boiler and system to 1.5 bar, making sure to vent the boiler via the automatic air vent on top of the boiler. Note that the black dust cap on the air vent should be left loose to allow the auto vent to function.
3. Check for leaks. For specialist advice on water treatment products, contact:
Fernox, Britannia Works Clavering, Essex CB11 4QZ Tel 01799 550811
COMMISSIONING - ELECTRICAL
The Electrical installation supplying this boiler must conform to the current IEE Regulations.
1. Remove the front panel and check all electrical connections for tightness.
2. Ensure all internal relays, contactors etc are secure on the DIN rails.
3. Set all panel control switches to off.
4. Check the power stage delay timer settings - Adjuster (A) is factory set to the 1 to 10 minute position which is the optimum setting for the boiler and should be verified during commissioning.
- Adjuster (B) is used to set the DELAY ON time of the following stage contactors, the available settings are in 1 minute increments if A is set to 1 to 10 minutes. This function is particularly useful in areas where gradual switching of electrical load is required and the resulting maximum demand kept to a minimum.The timers add to the flexibility of the installation but must be optimised by a qualified engineer.The normal setting is 1.
5. Set internal MCB to off position.
6. Set the control thermostat to desired temperature.
ST ARTING THE BOILER
1. Switch on the internal or external timeclock (if fitted)
2. Switch on internal MCB
3. Switch on local isolator to boiler
4. Turn the boiler on using the ON/OFF switch
5. Switch on the power levels switch stage 1, the first stage contactors will energise
6. Switch on the power levels switch stage 2, after a short delay the second stage contactors will energise. Note: the power stage delay timer settings should be verified as shown in item 4 under "Commissioning - Electrical"
7. The boiler temperature will now rise as indicated by the combined temperature and pressure gauge
8. The temperature will continue to rise until the control thermostat temperature setting is reached then the boiler will switch off.
Once these procedures have been followed the system can be left to operate normally by the following method.
1. Ensure that boiler thermostat is set to the desired temperature
2. Turn the boiler on using the ON/OFF switch
3. Turn on power level switch 1
4. Turn on power level switch 2
5. Set timeclock (if fitted) and/or external controls to desired boiler operating on/off times.
After one week of operation all electrical connections should be re-checked for tightness and the boiler water system checked for leaks and air and rectified if necessary.
MAINTENANCE
For safety reasons it is recommended that the boiler is serviced annually and that servicing is carried out by a qualified service engineer.
Before carrying out any work on the system ensure that the boiler is cool and all electrical supplies are isolated.
1. After removing front cover undo the four screws retaining the front control panel and gently let the panel suspend on the wiring to the rear of the panel. Undertake a visual inspection of the boiler looking out for signs of water leakage from joints, expansion vessel, and the area around the elements on top of the boiler.
2. Undertake a visual inspection of all cabling in the boiler casing checking for signs of overheating or burning.
3. Check all push-on electrical connectors for tightness and good connection to the relative components.
4. Using a correct fitting screwdriver check all electrical terminals on DIN rails and on all components for tightness.
5. Check the settings on the internal timers in accordance with the "Commissioning - Electrical" section.
6. Replace the control panel and the boiler front cover and refit screws.
7. Reinstate the electrical supply and follow the procedures set out in the commissioning section.
COMMISSIONING AND MAINTENANCE
A
B
Page 26
- 25 -
REMOVAL THE HEATING ELEMENTS
2
1
3
Page 27
N° Casing 09 15 22 28 36
A01 Side panel 21471421 21471421 21471421 21471421 21471421 A02 Front panel 21473421 21473421 21473421 21473421 21473421 A03 Top cover 21475421 21475421 21475421 21475421 21475421 A04 Rear panel 21474421 21474421 21474421 21474421 21474421 A05 Control panel ABS 497B1025 497B1025 497B1025 497B1025 497B1025 A06 Wall mounting 21480069 21480069 21480069 21480069 21480069 A07 Body heating 30537482 30537482 30537482 30537482 30537482 A08 Control panel 21477421 21477421 21477421 21477421 21477421
A09 Electric support 21479421 21479421 21479421 21479421 21479421
- 26 -
SPARE PARTS
A01
A03
A07
A06
A02
A04
A05
A08
A09
A01
Page 28
- 27 -
SPARE PARTS
N° Accessories 09 15 22 28 36
B01 Base for relay 54428195 54428195 54428195 54428195 54428195 B02 Control circuit “Siemens” 54766015 54766015 54766015 54766015 54766015 B03 Relay Siemens 3TG 54452082 54452082 54452082 54452082 54452082 B04 Timer “Crouset” 54428192 54428192 54428192 54428192 54428192 B05 Blocking 54452092 54452092 54452092 54452092 54452092 B06 Terminal WKN 16/U blue 54767014 54767014 54767014 54767014 54767014 B07 Terminal 16 mm2WKN 16/U 54428179 54428179 54428179 54428179 54428179 B08 Terminal end APN 16 mm
2
54428091 54428091 54428091 54428091 54428091 B09 Terminal WKN10 sl/u 54428155 54428155 54428155 54428155 54428155 B10 Shunt IVBWKN 16-2 54428278 54428278 54428278 54428278 54428278 B11 Control ter minal block 54767015 54767015 54767015 54767015 54767015 B12 Green switch 54766016 54766016 54766016 54766016 54766016 B13 Yellow switch 54766017 54766017 54766017 54766017 54766017 B14 Combined T° and pressure gauge Ø 40mm 54763012 54763012 54763012 54763012 54763012 B15 Red alar m indicator Ø 10mm / 240V 54766001 54766001 54766001 54766001 54766001 B16 Control ther mostat 2 Stages 54764017 54764017 54764017 54764017 54764017 B17 Button ther mostat 54764021 54764021 54764021 54764021 54764021 B18 Manual reset high limit ther mostat 103°C 54764009 54764009 54764009 54764009 54764009 B19 Cable gland (PG29) 54428113 54428113 54428113 54428113 54428113 B20 Brass pocket 63438003 63438003 63438003 63438003 63438003 B21 Heating element 2 x 1.4 kW 54428183 ---­B22 Heating element 2 x 2.4 kW - 54428182 54428182 54428182 ­B23 Heating element 3 x 2 kW ----54428204 B24 Water pressure switch 557D3011 557D3011 557D3011 557D3011 557D3011 B25 Circulating pump 557A4009 557A4009 557A4009 557A4009 557A4009 B26 Pressure safety valve 3 bars Ø 1/2” 55426017 55426017 55426017 55426017 55426017 B27 Automatic air vent 55445007 55445007 55445007 55445007 55445007 B28 Flexible tube B29 Expansion vessel 10 Litres 557A7006 557A7006 557A7006 557A7006 557A7006 B30 Complete control panel 24614142 24614142 24614143 24614144 24614145
Page 29
- 28 -
SPARE PARTS
B01 B02 B03 B04 B05
B06 B07 B08 B09 B10
B11 B12 B13 B14
B16 B17 B18 B19
B21 B22 B23 B24
B15
B20
B25
B26 B27 B28 B29
- - -
B30
- - -
Page 30
- 29 -
Page 31
Page 32
INTERNATIONAL
ACV international n.v
KERKPLEIN, 39 B-1601 RUISBROEK - BELGIUM TEL.: +32 2 334 82 20 FAX:+32 2 378 16 49 E-MAIL: international.info@acv-world.com
BELGIUM
ACV BELGIUM nv/sa
KERKPLEIN, 39 B-1601 RUISBROEK-BELGIUM TEL.: +32 2 334 82 40 FAX:+32 2 334 82 59 E-MAIL: belgium.info@acv-world.com
CHILE
ALBIN TROTTER Y ACV LTDA
SAN PABLO 3800 QUINTA NORMAL - SANTIAGO - CHILE TEL.:+56 2 772 01 69 FAX:+56 2 772 92 62/63 E-MAIL: chile.info@acv-world.com
CZECH REPUBLIC
ACV CR SPOL. s.r.o
NA KRECKU 365 CR-109 04 PRAHA 10 - CZECH REPUBLIC TEL.:+420 2 720 83 341 FAX:+420 2 720 83 343 E-MAIL: ceskarepublika.info@acv-world.com
DEUTSCHLAND
ACV WÄRMETECHNIK GMBH & CO KG
GEWERBEGEBIET GARTENSTRASSE D-08132 MÜLSEN OT ST. JACOB - DEUTSCHLAND TEL.:+49 37601 311 30 FAX:+49 37601 311 31 E-MAIL: deutschland.info@acv-world.com
ESPAÑA
ACV ESPAÑA
C/DE LA TEIXIDORA, 76 POL. IND. LES HORTES E-08302 MATARÓ - ESPANA TEL.:+34 93 759 54 51 FAX:+34 93 759 34 98 E-MAIL: spain.info@acv-world.com
FRANCE
ACV FRANCE sa
31, RUE AMPERE - Z.I MI - PLAINE F-69680 CHASSIEU - FRANCE TEL.:+33 4 72 47 07 76 FAX:+33 4 72 47 08 72 E-MAIL: france.info@acv-world.com
ITALIA
ACV ITALIA
VIA PANA 92 I-48018 FAENZA (RA) - ITALIA TEL.:+39 0546 64 61 44 FAX:+39 0546 64 61 50 E-MAIL: italia.info@acv-world.com
NEDERLAND
ACV NEDERLAND bv
POSTBUS 350 NL-2980 AJ RIDDERKERK - NEDERLAND TEL.:+31 180 42 10 55 FAX:+31 180 41 58 02 E-MAIL: nederland.info@acv-world.com
POLAND
ACV POLSKA sp. z.o.o.
UL.WITOSA 3 87 - 800 WLOCLAWEK - POLAND TEL.:+48 54 412 56 00 FAX:+48 54 412 56 01 E-MAIL: polska.info@acv-world.com
PORTUGAL
BOILERNOX LDA
RUA OUTEIRO DO POMAR CASAL DO CEGO, FRACÇÃO C, PAVILHÃO 3 - MARRAZES 2400-402 LEIRIA - PORTUGAL TEL.:+351 244 837 239/40 FAX:+351 244 823 758 E-MAIL: boilernox@mail.telepac.pt
RUSSIA
ACV RUSSIA
1/9, MALYI KISELNYI 103031 MOSCOW - RUSSIA TEL.:+7 095 928 48 02 / +7 095 921 89 79 FAX:+7 095 928 08 77 E-MAIL: russia.info@acv-world.com
SLOVAK REPUBLIC
ACV SLOVAKIA s.r.o.
PLUHOVÁ 49 831 04 BRATISLAVA - SLOVAK REPUBLIC TEL.:+421 2 444 62 276 FAX:+421 2 444 62 275 E-MAIL: slovakia.info@acv-world.com
SLOVENIA
ACV D.O.O. SLOVENIA
OPEKARNA 22b 1420 TRBOVLJE - SLOVENIA TEL.:+386 356 32 830 FAX:+ 386 356 32 831 E-MAIL: slovenia.info@acv-world.com
UK
ACV UK Ltd
ST. DAVID’S BUSINESS PARK DALGETY BAY - FIFE - KY11 9PF TEL.:+44 1383 82 01 00 FAX:+44 1383 82 01 80 E-MAIL: uk.info@acv-world.com
USA
TRIANGLE TUBE PHASE III
FREEWAY CENTER - 1 TRIANGLE LANE BLACKWOOD NJ 08012 - USA TEL.:+1 856 228 8881 FAX:+1 856 228 3584 E-MAIL: sales@triangletube.com
excellence in hot water
www.acv-world.com
ARGENTINA
TECNOPRACTICA
ALFEREZ BOUCHARD 4857 1605 CARAPACHAY - BUENOS AIRES TEL.: +54 11 47 65 33 35 FAX:+54 11 47 65 43 07 E-MAIL: jchas@tecnopractica.com
AUSTRALIA
HUNT HEATING PTY LTD
10 GARDEN BOULEVARD 3172 VICTORIA - AUSTRALIA TEL.: +61 3 9558 7077 FAX:+61 3 9558 7027 E-MAIL: enquiries@huntheat.com.au
BRAZIL
SIMETAL INDUSTRIA E COMERCIO DE FERRAMENTAS LTDA
RUA GERSON ANDREIS 535 95112 - 130 CAXIAS DO SUL - BRAZIL TEL.: +55 54 227 12 44 FAX:+55 54 227 12 26 E-MAIL: export@simetall.com.br
BULGARIA
PROXIMUS ENGINEERING LTD
7 BIAL KREM STR. 9010 VARNA - BULGARIA TEL.:+359 52 500 070 FAX:+359 52 301 131 E-MAIL: info@proximus-bg.com
CHINA
BEIJING HUADIAN HT POWER TECHNOLOGY DEVELOPMENT CO. LTD
ROOM B-912, TOWER B, COFCO PLAZA N°. 8, JIANGUOMENNEI AVENUE BEIJING 100005 - PEOPLE’S REPUBLIC OF CHINA TEL.:+86 10 652 30 363/393 EXT 101 FAX:+86 10 652 27 071 E-MAIL: li.zheng@acv-world.com
SHANGHAI COOLTECH LTD
14/F E. CHINA MERCHANTS PLAZA N°. 333 CHENGDU ROAD (N) 200041 SHANGHAI - CHINA TEL.:+86 21 52 98 11 22 - 820 FAX:+86 21 52 98 13 58 E-MAIL: cooltech@cooltech.sh.cn
DENMARK
VARMEHUSET
FRICHSVEJ 40 A 8600 SILKEBORG - DENMARK TEL.:+45 86 82 63 55 FAX:+45 86 82 65 03 E-MAIL: vh@varmehuset.dk
ESTONIA
TERMOX AS
TAHE 112A 51013 TARTU - ESTONIA TEL.:+372 736 73 39 FAX:+372 736 73 44 E-MAIL: termox@termox.ee
GREECE
ESTIAS
MARASLI STREET 7 54248 THESSALONIKI - GREECE TEL.:+30 23 10 31 98 77 / +30 23 10 32 03 58 FAX:+30 23 10 31 97 22 E-MAIL: info@genikithermanseon.gr
ÎLE MAURICE
SOTRATECH
29, RUE MELDRUM BEAU BASSIN - ÎLE MAURICE TEL.:+230 46 76 970 FAX:+230 46 76 971 E-MAIL: stech@intnet.mu
LITHUANIA
UAB “GILIUS IR KO”
SAVARNORIU PR. 192 3000 KAUNAS - LITHUANIA TEL.:+370 37 308 930 FAX:+370 37 308 932
MAROC
CASATHERM
PLACE EL YASSIR 20300 CASABLANCA - MAROC TEL.:+212 22 40 15 23 FAX:+212 22 24 04 86
NEW ZEALAND
ENERGY PRODUCTS INTERNATIONAL
8/10 BELFAST PLACE PO BOX 15058 HAMILTON - NEW ZEALAND TEL.:+64 7 847 27 05 FAX:+64 7 847 42 22 E-MAIL: pmckenzie@tycoint.com
ÖSTERREICH
PROTHERM HEIZUNGSTECHNIK Gmbh
TRAUNUFERSTRASSE 113 4052 ANSFELDEN - ÖSTERREICH TEL.:+43 7229 804 82 FAX:+43 7229 804 92 E-MAIL: protherm@nextra.at
ROMANIA
SC TRUST EURO THERM SA
D.N PIATRA NEAMT - ROMAN km 2 C.P 5 O.P 3 jud. Neamt 5600 PIATRA NEAMT - ROMANIA TEL.:+40 233 20 62 06 FAX:+40 233 20 62 00 E-MAIL: office@eurotherm.ro
TUNISIE
SO.CO.ME CHAUMAX
BOÎTE POSTALE N°44 1002 TUNIS - TUNISIE TEL.:+216 71 78 15 91 FAX:+216 71 78 87 31
UKRAINE
UKRTEPLOSERVICE LTD
PR. LAGUTENKO 14 83086 DONETSK - UKRAINE TEL.:+38 062 382 60 47/48 FAX:+38 062 335 16 89
Loading...