ETC®, SmartPack™, SmartSwitch™ and SmartLink™ are either registered trademarks or trademarks of
Electronic Theatre Controls, Inc. in the United States and other countries. LonWorks® and LON® are registered trademarks of
the Echelon
®
Corporation. All other trademarks, both marked and not marked, are the property of their respective owners.
Introduction
Congratulations on your purchase of the ETC® SmartPack™ Wall Mount dimming pack.
SmartPack continues ETC's tradition of providing the highest quality products for the
entertainment and architectural lighting market.
Using this Manual
Use this manual during the installation of the SmartPack Wall Mount unit. This manual
includes instructions for installing SmartPack units to operate together on a SmartLink™
control network. For user configuration and system operation instructions please refer to
the Wall Mount SmartPack User Manual.
The following symbols are used in this manual to alert you to danger or important
information.
Note:
CAUTION:
WARNING:
WARNING:
Please email comments about this manual to: TechComm@etcconnect.com
Provides important information about your installation.
A Caution statement indicates situations where there may be undefined or
unwanted consequences of an action, potential for data loss or an equipment
problem.
A Warning statement indicates situations where damage may occur, people
may be harmed, or there are serious or dangerous consequences of an
action.
RISK OF ELECTRIC SHOCK! This warning statement indicates situations
where there is a risk of electric shock.
Introduction1
Product Variants
The instructions in this manual apply to the CE SmartPack Wall Mount dimming packs
Part Number
7021A1103
7021A1103-LPS
7021A110512 channel /
7021A1105-LPS
7021A1106
7021A1106-LPS
7021A11076 channel /
7021A1107-LPS
7021A11103 channel /
7021A1110-LPS
7021A1111
7021A1112
7021A1113
7021A1114
7021A1115
7021A1116
Channel Count/
Breaker Type
12 channel /
10A breakers
10A (ND) 2 pole
breakers
6 channel /
15A breakers
15A (ND) 2 pole
breakers
25A (ND) 2 pole
breakers
12 channel /
10A breakers
12 channel /
10A (ND)
breakers
12 channel /
10A breakers
12 channel /
10A (ND)
breakers
12 channel /
10A breakers
12 channel /
10A (ND)
breakers
Operating
Voltage
230 VAC
47-63Hz
single or
three phase
Installed Weight
(loaded)
22Kg / 48lbs
A SmartPack with a “-LPS”
part number suffix includes a
LinkPower supply which is
factory installed for SmartLink
station power.
21Kg / 46lbs
28Kg / 61lbsThruPower Switch
28Kg / 61lbsThruPower Switch
28Kg / 61lbsThruPower Relay
28Kg / 61lbsThruPower Relay
24Kg / 53lbsRelay (only)
24Kg / 53lbsRelay (only)
Notes
2SmartPack Wall Mount Installation Manual
Option kits available for the SmartPack Wall Mount unit include:
I/O compartment
DMX512 In / DMX512 Thru
Emergency contact input
SmartLink™ enabled
Optional LinkPower supply
for wall station support.
3, 6, or 12 dimmer channels available
Variable speed cooling fan
Capable of dimming multiple load types
CE Compliant
32 built-in presets and a sequencer for
stand-alone operation.
optional - supplies power for up to four
SmartLink wall stations
requires 15 rack units of space (18 rack
units for ThruPower and relay models)
Introduction3
Help from ETC Technical Services
If you are having difficulties, your most convenient resources are the references given in
this manual. To search more widely, try the ETC web site at www.etcconnect.com
of these resources is sufficient, contact ETC Technical Services directly at one of the offices
identified below. Emergency service is available from all ETC offices outside of normal
business hours.
When calling for help, please have the following information handy:
•Model of SmartPack Wall Mount
•Other components in the system (if any) including other Smartlink host products,
LinkPower supply, quantity and type of SmartLink wall stations, etc.
•DMX control source used for system-wide control.
. If none
Americas
ETC International
Technical Services Department
3031 Pleasant View Road
Middleton, WI 53562
800-775-4382 (USA, toll-free)
+1-608 831-4116
service@etcconnect.com
Asia
ETC Asia, Ltd.
Technical Services Department
Room 1801, 18/F,
Tower I, Phase I, Enterprise Square
9 Sheung Yuet Road
Kowloon Bay, Kowloon, Hong Kong
+852 2799 1220
service@etcasia.com
United Kingdom
Electronic Theatre Controls, Ltd.
Technical Services Department
Unit 26-28 Victoria Industrial Estate
Victoria Road,
London W3 6UU, UK
+44 (0)20 8896 1000
service@etceurope.com
Germany
Electronic Theatre Controls, GmbH
Technical Services Department
Ohmstrasse 3
93607, Holzkirchen, Germany
+49 (80 24) 47 00-0
techserv-hoki@etcconnect.com
4SmartPack Wall Mount Installation Manual
Prepare for Installation
Installation Environment
•Dry room (30-95% humidity, non-condensing)
•0-35°C (32-95°F) ambient temperature
•Dust free
•Wall-mounting location must support 23kg (50lbs)
•Minimum 25.4cm (10”) clearance in front of unit for airflow vents
Electrical Requirements
•50-60Hz
•230/400 VAC, 3Ø+N+PE 40A per phase
•230 VAC, 1Ø+N+PE 120A per phase
•For use on TN-C, TN-S, TN-CS and TT supplies
•Not suitable for use on Delta IT supplies
•This equipment must be connected to a suitable safety earth/ground.
Cable Specification
PurposeCable Type/DescriptionNote
AC Input - Three phase
230/400 VAC 3Ø+N+PE,
50-60Hz, 40A per phase
AC Input - Single phase
230 VAC, 1Ø+N+PE,
50-60Hz, 120A per
phase
DMX512
SmartLink™
Emergency
2
25mm
cable
Use only cables of size and rating
complying with local wiring regulations.
Recommended - Belden 9729
Alternatives
Carol - C0910
General -0E8990
Olfex - 9729
Omni - D62402
Quabbin - 8604
Olympic - 2998
Pro-Plex - PC224T
Belden 8471 plus 1 - 2.50mm
drain wire recommended (drain wire not
required if installed in grounded metal
conduit).
2 - 1.5mm
/ 2AWG maximum stranded
2
ESD
2
twisted
Supply gauge must be coordinated
with upstream protective switchgear.
CAT 5 cable is also approved for
DMX distribution if installed in
grounded metal conduit.
• For use of CAT 5 cable, you will
need to purchase a CAT 5
termination kit (ETC part number
4100A1013) from a local ETC
office or service provider.
For use with wall stations and
SmartLink pack to pack
synchronization. SmartLink is FTT10A topology-free and polarity
independent.
Contact input for emergency lighting
loads.
Prepare for Installation5
Compliance
CE Compliance
•EN55015, EN55022B, EN61000-6-2, EN60439-1
•Complies with CE Directives 336/83/EEC and 73/23/EEC
Verify the Contents of the Shipping Carton
•SmartPack unit with cover attached.
•Warning labels. If necessary replace the warning label on your SmartPack unit with the
label displaying the operational language of the installed location.
•SmartPack User Manual and Mounting Template.
•DMX Cable Preparation Kit with 8-pin connector (4100A1012).
Additional Parts and Specialty Tools Required
•4 x 6-8mm (1/4” - 3/8”) bolts or screws, 50-100mm (2 - 4”) long, and suitable wall plugs,
are suggested. Mounting hardware and surface must support 23kg (50 lbs).
•Conduit punch, Conduit or bushes 12.7mm (1/2”) diameter
•Slotted screwdriver for line terminals
•Phillips screwdriver
•4.75mm (3/16”) wide slotted-style screwdriver for load terminals
•Jeweler’s screwdriver for data terminals
•Wire strippers
6SmartPack Wall Mount Installation Manual
Cable Routing and Conduit Access
1 N
1 L1
2 N
2 L1
3 N
3 L1
4 N
4 L1
5 N
5 L2
6 N
6 L2
1 L
7 N
7 L2
8 N
8 L2
9 N
9 L3
10 N
10 L3
11 N
11 L3
12 N
12 L3
2L
3 L
4 L
5 L
6 L
7 L
8 L
9 L
10 L
11 L
12 L
Rear
Rear
Rear
Rear
Removable plates on top and bottom.
Remove appropriate plate to punch
conduit access as needed for AC Input
and load wiring. Remove plate
permanently if SmartPack is mounted
below another SmartPack or SmartSwitch.
Removable plates on either side.
Remove appropriate plate to punch
conduit access as needed for AC Input
and load wiring. Remove plate
permanently if SmartPack is mounted
to the side of another SmartPack.
Top
Bottom
Right Side
Left Side
Load Terminals
Access Holes for
mounting bolts or screws.
Earth/Ground BusAC Input Lugs
Knockouts in the lower side
panels accommodate conduit
or bushes for low voltage
control wiring to the
I/O compartment.
I/O Compartment - all lowvoltage (control terminations
conveniently located in the lower
panel.
CAUTION:
In order to maintain safety, proper air flow and cooling, do not leave any panels
removed unless facing an adjoined pack.
Prepare for Installation7
Installation Procedure
127mm
(5.0”)
305mm
(12.0”)
•SmartPack Wall Mount units may be
mounted up to two high by any width.
Allow clearances as described on
page 5
•Overall dimensions of the enclosure:
435mm x 157mm x 666mm
(17.2” x 6.2” x 26.2”)
or, for ThruPower or Relay racks:
435mm x 157mm x 741mm
(17.2” x 6.2” x 29.2”)
Install Mounting Hardware
Step 1:Affix the mounting template, if included in the shipping carton, to the wall to guide
the placement of the mounting bolts or screws. If the mounting template is not
provided, use the measurements below.
Step 2:Install the hardware required for mounting the SmartPack using the four
measured keyholes on the mounting template as a guide.
•Four 6-8mm (1/4” - 3/8”) bolts or screws, 50-100mm (2 - 4”) long, and
suitable wall plugs are suggested mounting hardware.
•Both the surface and the mounting hardware must support 23kg (50lbs).
•Expose at least 25mm (1”) of threads for mounting the SmartPack.
Note:
Access holes to tighten bolts / screws are shown in the Cable Routing and
Conduit Access graphic on page 7.
Mount the SmartPack
Step 1:Remove the four screws securing the cover to the SmartPack.
Step 2:Remove the cover assembly.
Note:
8SmartPack Wall Mount Installation Manual
Step 3:Mount the SmartPack to the mounting bolts previously installed.
Step 4:Tighten the bolts securely.
The SmartPack Wall Mount unit ships with a debris shield to protect the
electronics during installation. Leave this shield in place during installation and
remove only after installation is complete and before energization.
•Check for a plumb installation and follow all local code restrictions.
Rough-In Conduit and Cable
SmartPack Wall Mount dimmer packs have removable plates located on top, bottom and
both sides to accommodate conduit fittings for supply and load wiring. Additional wiring
space is provided at the top of the unit for contractor wiring convenience.
Two knockouts are provided, one on each lower side, specifically for low voltage (control)
wiring. See “Cable Routing and Conduit Access” on page 7.
Step 1:Install conduit for AC input power and load wiring to the panels in the appropriate
locations.
•The SmartPack dimmer pack is available with either 3, 6, or 12 dimmers.
Make certain conduit is sized appropriately for the required wire.
Step 2:Install conduit as required for low voltage (control) wiring.
Note:
Step 3:Pull AC input wiring and load wiring through the conduit previously installed.
CAUTION:
Step 4:Pull all low voltage control wiring through the conduit previously installed to the
Low voltage wiring must be routed separately from high voltage wiring.
a: All low voltage terminations are conveniently located in the I/O compartment
of the SmartPack. Two 12.7mm (1/2”) knockouts are provided for low voltage
control wiring.
a: Individual loads with earth ground and neutral connections.
b: Power supply wiring for predetermined three-phase or single phase
operation.
The SmartPack Wall Mount unit ships with a debris shield to protect the
electronics during installation. Leave this shield in place during installation and
remove only after installation is complete, before energization. If debris falls into
the fan or electronics remove the debris before applying power to the unit.
I/O compartment knockouts. Installation requirements for low voltage wiring may
include the following:
•DMX IN
•DMX PASS-THRU
devices.
•SmartLink
independent. Wiring may be bus, star, loop, home run (up to two home run
termination points available) or any combination of these.
•Emergency
lighting loads to full and all non-emergency lighting loads OFF. Contact ETC
for guidance on use with emergency lighting systems.
- required when SmartPack is to be controlled by a DMX source.
- allows pass-thru of the DMX signal to other DMX
- station wiring is FTT-10A, topology-free and polarity
- receives a contact input that switches selected emergency
Installation Procedure9
Connect Wiring
LOAD1
N1
N2
NL1L2L3EARTH
To Circuit Breakers
Input Wiring
Supply cable:
Lugs will accommodate
25mm
2
/ 3AWG maximum
stranded cable.
Important Note:
Supply cable gauge must be
coordinated with upstream protective
switchgear.
EarthL3L2L1N
LOAD1
N1
N2
NL1L2L3EARTH
To Circuit Breakers
Input Wiring
Important Note:
Jumper wires must match
specifications for incoming line wire.
Important Note:
For operation on single phase supplies
at full power, upstream switchgear,
such as RCD's or main breakers, must
be located separately outside the
enclosure. Please contact ETC
technical services for assistance.
EarthL1N
L3L2
Power Supply Connections
Three-Phase Supply Connections
Note:
If a DIN rail option kit is fitted with RCD and/or terminals, please follow the wiring
instructions supplied with the kit.
Single-Phase Supply Connections (Europe)
CAUTION:
The SmartPack Wall Mount unit ships with a debris shield to protect the
electronics during installation. Leave this shield in place during installation and
remove only after installation is complete and before energization. If debris falls
into the fan or electronics remove the debris before applying power to the unit.
10SmartPack Wall Mount Installation Manual
Load Connections
1 N
1 L1
2 N
2 L1
3 N
3 L1
4 N
4 L1
5 N
5 L2
6 N
6 L2
7 N
7 N2
8 N
8 L2
9 N
9 L3
10 N
10 L3
11 N
11 L3
12 N
12 L3
N
N
N
N
N
N
N
N
N
N
N
N
Incoming Load Wiring
Earth/Ground Bus
Insert load
conductors here.
These wires installed by
ETC prior to shipping the
unit.
Earth/Ground Connections
Connect the earth/ground conductor for each load to the Earth/Ground Bus.
Neutral Connections
Step 1:Prepare load conductors by stripping 6mm of insulation from the end.
Step 2:Insert the stripped end into the terminal and tighten the screw using a 4.75mm
(3/16”) wide slotted style screwdriver.
•Terminals accept wire between 1.5mm
•Take care not to tighten the load connection onto the wire insulation.
1 N
1 L1
2 N
2 L1
3 N
3 L1
4 N
4 L1
5 N
5 L2
6 N
N
N
2
/ 16AWG and 6mm2 / 8AWG.
6 L2
7 N
7 N2
8 N
8 L2
9 N
9 L3
Installation Procedure11
Connect Control Wiring
I/O panel to
chassis ground
Link Power supply
(optional)
Data to CPU
Emergency /SmartLink
DMX In
DMX Thru
ESD Ground
Presets, Sequence,
Sequence Timing
SmartPack
SmartPack
Unison DRd12
rack
LinkPower
supply
installed
Belden 8471 plus
12.5mm
2
ESD
drain
SmartLink
Stations
SmartPack
SmartLink
ATC
Emergency, SmartLink, DMX In and DMX Pass-Thru are connected in the
I/O compartment of the SmartPack Wall Mount unit. Each connection uses a pluggable
screw terminal which can be removed for easy wiring.
The RJ45 connection labeled J2 on the I/O board connects the I/O control board to the
control CPU board for data communication to the SmartPack. This connection is made at
the factory prior to shipment.
The LinkPower supply provides power for up to four SmartLink wall stations per system.
SmartPack Wall Mount is available with or without the LinkPower supply option. For field
installation of the LinkPower supply reference LinkPower Supply Kit, page 19.
Emergency/SmartLink
SmartLink is a control protocol that provides added functionality to the SmartPack dimming
pack for inter-connectivity and shared communication of specific data to other SmartLink
enabled host products. Reference the SmartPack User Manual for configuration details.
Recall
Up
Preset
Enter
Back
Down
Hold
Preset 1
Preset 2
Preset 3
Preset 1
Preset 6
Preset 4
Preset 2
Preset 7
Preset 5
Preset 3
12SmartPack Wall Mount Installation Manual
Preset 8
Preset 1
Preset 9
Preset 4
Preset 2
Preset 5
Preset 10
Preset 3
Preset 4
Preset 5
The six position pluggable screw terminal labeled J3 Panic/LON is provided as the
termination point for both Emergency and SmartLink control.
COM
Emergency
NET A
NET B
NET B
NET A
123456
Connect Emergency
Step 1:Strip 6.35mm (1/4”) of insulation from the ends of the two 1.5mm
Step 2:Remove the 6 position pluggable connector from J3 on the I/O PCB.
Step 3:Twist the two 1.5mm
Step 4:Insert the 1.5mm
Step 5:Tighten the screw firmly onto each wire.
Connect SmartLink
Termination is available for up to two separate SmartLink data runs and is FTT-10A
topology-free and polarity independent utilizing a LonWorks
SmartLink wall stations, ETC recommends terminating the station data run to the
SmartPack with the LinkPower supply installed and utilizing the second data bus for
SmartLink pack to pack synchronization. A clean, well organized wire installation assists
with troubleshooting efforts when needed.
Note:
J2
Control
LON1
LON2
1 2 3 4
DMX
NC
PAN
COM
NETA
NETB
NETB
NETA
2
wires.
2
wires together as close to the connector as possible.
2
into pins 5 and 6.
®
network. For systems utilizing
One SmartLink host product (SmartPack, SmartSwitch, Unison DRd with
SmartLink or Sensor + with SmartLink) in the system must have a LinkPower
Supply or Station Power Module installed for wall station power. A SmartLink
LinkPower supply (7021K1010) is limited to powering four SmartLink stations.
Alternatively, you may power up to 16 SmartLink stations when using a SmartLink
Station Power Module (S-SPM). You may have up to four SmartLink host products
in a SmartLink system.
Step 1:Cut the Belden 8471 cable so that a 20cm (8”) tail extends from the edge of the
panel.
Step 2:Strip 18cm (7”) of the outer jacket off.
Step 3:If pulling two Belden 8471 cables, label each pair with data type and run
designation. Example: SL1 and SL2.
Step 4:Strip 6.35mm (1/4”) of insulation from the ends of the Belden 8471 wires.
Step 5:Insert the white wire from SL1 data run into pin 1 (NETB) terminal on the
pluggable connector. Tighten the screw firmly onto the wire.
Step 6:Insert the associated SL1 black wire into pin 2 (NETA) terminal on the pluggable
connector. Tighten the screw firmly onto the wire.
Step 7:Repeat steps 5-6 to terminate the second data run (SL2) if required to the
remaining pins 3 and 4 terminals on the connector. Tighten the screw firmly onto
each wire.
Step 8:Reinstall the 6 position pluggable connector to J3 on the I/O PCB.
Installation Procedure13
Connect ESD Ground
As shown with Belden 9729 color code
Pin 1 - Com
Pin 2 - DMX - (Black)
Pin 3 - DMX + (Red)
DMX In and Pass-Thru on the same pluggable
screw connector as shown.
For use with CAT 5 cable, contact ETC for a
CAT 5 termination and IDC connector kit (ETC
part number 4100A1013), sold separately.
For installations with SmartLink data runs (Belden 8471) installed in grounded metal
conduit there is no need to run or terminate an additional ESD drain wire. For installations
not installed in grounded metal conduit follow the instructions below for ESD
termination.
Step 1:Locate the grounding lug on the tray of the I/O panel, just to the right of the I/O
termination board.
Step 2:Loosen, but do not remove, the set screw on the grounding lug.
Step 3:Strip 6.35mm (1/4”) of insulation from the end of the 2.5mm
2
ESD drain wire(s)
and twist together.
Step 4:Insert the bare end into the grounding lug and secure with the set screw.
DMX 512
Two 8 position receptacles are provided on the I/O termination board, one for DMX In and
the other for DMX-Thru. Prior to connecting DMX, follow the instructions for Belden 9729
cable preparation as defined on the single sheet instructions packaged with the 8 position
pluggable screw connector. A cable preparation kit for installation of CAT 5 cable (ETC part
number 4100A1013) is available for purchase, contact ETC for details.
Connect DMX
(J4) DMX IN
n/c
n/c
n/c
DATA-
7021B5602
preliminary
n/c
678
DATA+
12345678
COM
DMX+
DMX-
(J5) DMX
PASS-THRU
n/c
n/c
n/c
DMX+
n/c
678
DATA-
DATA+
12345678
DMX-
ISOCOM
n/c
n/c
Step 1:For DMX In and DMX Pass-Thru using Belden 9729 as recommended, prepare
the Belden cable as described in the DMX Cable Preparation kit instructions.
Step 2:Using the 8 position pluggable screw connector provided in the cable preparation
kit, connect Shield (Com), DMX- and DMX+ as indicated in the graphic above.
Step 3:DMX Pass-Thru using Belden 9729 can utilize the same pluggable screw
connector as DMX In. Connect Shield (Com), DMX - and DMX + as indicated in
the graphic above.
14SmartPack Wall Mount Installation Manual
Data Termination
Switch UP= termination ON
Switch DOWN = termination OFF
The I/O board includes termination switches for both SmartLink data runs and DMX512.
Follow termination guidelines as indicated in the graphic below.
J2
Control
Guidelines for Data Termination:
For SmartLink (silk-screened as LON) data termination:
•For a single pack installation set switch 1 and 2 to the UP position.
•If multiple packs are installed, only one pack should terminate LON, switch 1 and 2 UP.
All other packs should have LON switches 1 and 2 set DOWN.
•If there are no SmartLink data runs set switch 1 and 2 DOWN.
For DMX 512 data termination:
•If the pack is the last or the only DMX device on the data run set switch 3 UP.
•If the pack is not the last DMX device on the data run set switch 3 DOWN.
DMX
LON
LON
1 2 3 4
NC
NETB
NETA
Installation Procedure15
Final Installation and Power Up
Verify Installation
•Is the SmartPack unit securely mounted with all mounting bolts tight?
•Is there sufficient clearance 254mm (10”) in front of the unit?
•Check wiring:
•Are all power supply and load cables landed and properly terminated?
•Are all emergency lighting circuits separated from normal circuits with a voltage
barrier?
•Are all unused cable access openings covered with plugs or removable plates?
•Do all control cables meet specifications?
•Are all low voltage connections terminated properly?
•Are all data terminations terminated?
•Remove all debris and the debris shield from the unit.
•The SmartPack Wall Mount unit ships with a debris shield to protect the electronics
during installation. Leave this shield in place during installation and remove only
after installation is complete and before energization. If debris falls into the fan or
electronics remove the debris before applying power to the unit.
Final Installation
Step 1:Attach the ground wire with the ring terminal from the chassis to the grounding
stud on the I/O panel and secure.
Step 2:Close the I/O panel and secure with two screws.
a: All wires should be dressed neatly.
b: Ensure the wires are not crimped in the I/O Panel while closing.
Step 3:Attach the ground wire with the spade connector to the front cover and secure
the front cover to the unit.
Step 4:Apply power to the unit.
Test Loads via Menu
After power is applied to the unit, select the operating language and test each load using
the TEST MENU.
Select the operating language:
Step 1:Apply power to the unit. Available languages for SmartPack will scroll in the
display at 3-second intervals.
Step 2:Press when the preferred language is displayed:
•Set Language - English
•Choisir la langue - Français
•Sprache auswählen - Deutsch
•Seleccionar idioma - Español
16SmartPack Wall Mount Installation Manual
Set a level for a dimmer:
Test Dimmer: [ All ]
T
Level: 100%
Step 1:Press to enter the Test menu.
Step 2:Use < or to scroll the selection of dimmers, choose one or [ALL] dimmers.
Step 3:Use + or - to set a level, press. The menu will progress to the next dimmer.
Step 4:Press. “Exit Test Mode” displays.
•Exit Test Mode and retain all Test levels, scroll to [Keep Test On] and
press.
•Exit Test menu, clearing all Test levels and return to the previous menu,
scroll to [Test: all off], press .
•Press < to return to the Test menu.
•Press << to exit the Test menu, clearing all Test levels, and return to the main
menu.
Verify DMX512 Operation
Test each load with DMX512 input using a controle console or DMX512 test device.
Troubleshooting SmartLink
After all SmartLink control stations are installed and connected to the SmartLink enabled
product, check for shorts and cross-connections with a digital voltmeter.
•Check the voltage between Net A and ground. This reading should be between 18
- 21 Volts.
•Check the voltage between Net B and ground. This reading also should be
between 18-21 Volts.
•Check the voltage between Net A and Net B. This reading should be between 3642 Volts.
Check that two LED indicators (located at CR1 and CR2) are illuminated on the LinkPower
supply board.
•If both are illuminated the data connections are good.
•If CR1 is illuminated but not CR2, Net A is shorted to ground.
•If CR2 is illuminated but not CR1, Net B is shorted to ground.
•If neither LED is illuminated, Net A and Net B are both shorted.
If you have any difficulties installing your system, please contact ETC Technical Services
at the office nearest you.
Installation Procedure17
18SmartPack Wall Mount Installation Manual
Appendix A
Step 4
Step 5
LinkPower
supply
I/O board
LinkPower Supply Kit
One SmartLink LinkPower Supply (S-LPS) powers up to four wall stations over the
SmartLink™ network.
Note:
You may have only one station power source on the SmartLink network. This
source may be either the LinkPower Supply (S-LPS) or a SmartLink Station Power
Module (S-SPM) which powers up to 16 SmartLink stations. As well, you may
have up to four SmartLink host products in a SmartLink system. One SmartLink
host product (SmartPack, SmartSwitch, Unison DRd with SmartLink or Sensor +
with SmartLink) in the system must have a LinkPower Supply or Station Power
Module installed for wall station power.
Installation Procedure
The LinkPower supply kit includes a LinkPower supply and four screws.
Step 1:Remove power from the control electronics by turning the Standby breaker off.
Step 2:Remove the two screws securing the I/O panel to the chassis.
Step 3:Fold the I/O panel down to reveal the control terminations.
Step 4:Angle the LinkPower supply board approximately 10° and insert the four pins as
found on the LinkPower supply into the receptacle on the I/O board.
Step 5:Align the LinkPower supply with the four screw mounts located on the I/O panel
and secure with the four screws provided. Do not over tighten the screws.
Step 6:Close the I/O panel and secure with the two screws.
Step 7:Re-apply power to the control electronics.
ALinkPower Supply Kit19
Corporate Headquarters
London, UK
Rome, IT
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK Tel +44 (0)20 8896 1000 Fax +44 (0)20 8896 2000