LIGHT CHANNEL OBJECTS
Object 0: "Input: Lock light channel" (length = 1-bit)
The switching/dimming outputs for the light channel are locked with an
ON telegram and unlocked with an OFF telegram.
Parameters can be set to determine the status of the light channel after
locking and unlocking.
Object 1: "Input: Light channel manual ON/OFF" (length = 1-bit)
Note: essential when in half automatic mode!
Manual operation is maintained when persons are present until the switch
off time has elapsed if "while presence" is set in the parameters. Light
measurement is not active if the parameter "With disabled light processing
during off-period" has been selected. After this, the detector switches to
normal operating mode. Manual operation has no impact on motion
detection. The function is transmitted to communication objects 5/6.
Object 2: "Input: Light channel manual dimming" (length = 4 bits)
Function: active when constant light control/regulation has been selected!
Input for dim up/dim down KNX touch sensors. Writing on this object
manually overrides the light channel and the commands are transmitted to
the dimming actuator via object 7.
Manual operation is maintained when persons are present until the switch
off time has elapsed if "while presence" is set in the parameters. Light
measurement is not active if "With disabled light processing during off-period"
has been selected. After this, the detector switches to normal operating mode.
Manual operation has no impact on motion detection.
Object 3: "Input: Light channel manual dim value" (length = 1 byte)
Function: active when constant light control/regulation has been selected!
Input to preset dim values. Writing on this object manually overrides the light
channel and the values are transmitted to the dimming actuator via objects
8 and 9.
Manual operation is maintained when persons are present until the switch
off time has elapsed if "while presence" is set in the parameters. Light
measurement is not active if "With disabled light processing during off-period"
has been selected. After this, the detector switches to normal operating mode.
Manual operation has no impact on motion detection.
Object 4: "Input: Light channel control/regulating without presence" (length = 1 bit)
Operating mode: controlling
This object can be used to enable light control without presence.
Operating mode: regulating
This object can be used to enable light regulation without presence.
Object 5: "Output: Light channel ON/OFF" (length = 1-bit)
If artificial lighting is required (threshold 1/set value via parameter) and
persons are present, the output sends an ON telegram.
If natural light is sufficient and/or no persons are present, an OFF telegram
is sent once the switch off time has elapsed.
Object 6: "Output: Light channel 2 ON/OFF" (length = 1-bit)
Function: switching - only available with switching function!
If artificial lighting is required (difference between threshold 2 and threshold
1 via parameter) and persons are present, the output sends an ON telegram.
If natural light is sufficient and/or no persons are present, an OFF telegram is
sent once the switch off time has elapsed.
Object 7: "Output: Light channel dimming" (length = 4 bits)
Function: constant light control/regulation
Telegrams can be transmitted to the dimming actuator via this object by
manually pressing and holding down a touch sensor (object 2). only active
when "constant light control/regulation" has been enabled!
Object 8: "Output: Light channel dim value 1" (length = 1 byte)
Function: constant light control/regulation
If artificial lighting is required and persons are present, the output sends a
value telegram (1byte). If natural light is sufficient (controller to minimum)
and/or no persons are present, the lighting is set to 0 % or the device
switches to orientation lighting once the switch off time has elapsed. only
active when "constant light control/regulation" has been enabled!
Object 9: "Output: Light channel dim value 2" (length = 1 byte)
Function: constant light control/regulation
If artificial lighting is required and persons are present, the output sends a
value telegram (1byte).
If natural light is sufficient (controller to minimum) and/or no persons are
present, the lighting is set to 0 % or the device switches to orientation lighting
once the switch off time has elapsed.
Option to offset dim value 2 and dim value 1 via parameter. only active
when "constant light control/regulation" has been enabled!
Object 10: "Input: Light channel 1 threshold" (length = 2 byte)
(Operating mode: switching)
This object can be used to specify the threshold (lux) for channel 1 via
telegram. This is only available if "threshold via telegram" has been selected.
Object 10: "Input: Light channel set value control" (length = 2 byte)
(Operating mode: controlling)
This object can be used to specify the set value (lux) for light control via
telegram. This is only available if "threshold via telegram" has been selected.
Object 10: "Input: Light channel regulating lower light value" (length = 2 byte)
(Operating mode: regulating)
This object can be used to specify the lower light value (lux) for light
regulation via telegram. This is only available if "threshold via telegram"
has been selected.
Object 11: "Input: Light channel 2 threshold" (length = 2 byte)
(Operating mode: switching)
This object can be used to specify the threshold (lux) for channel 2 via
telegram. This is only available if "threshold via telegram" has been selected.
Object 11: "Input: Light channel regulating upper light value" (length = 2 byte)
(Operating mode: regulating)
This object can be used to specify the upper light value (lux) for light
regulation via telegram. This is only available if "threshold via telegram"
has been selected.
Object 12/13: "Input: Light channel 1/2 actuator feedback" (length = 1 bit)
Function: constant light control/regulation
This object can be used to evaluate the status object of an actuator. In the event
that the actuator is not only controlled by the detector, the detector will be
switched on with an ON telegram and then switched off once the switch off time
has elapsed (provided no further movement is detected). If an OFF telegram is
sent, the detector will be switched off and will then revert immediately to standy
mode. This is only available if "actuator feedback" has been enabled.
Object 14: "Input: Select orientation light" (length = 1 bit)
Function: constant light control/regulation
An ON telegram changes the setting from orientation light value 1 to orientation
light value 2, while an OFF telegram switches it from value 2 to value 1.
Object 15: “Input: Orientation light ON/OFF” (length = 1 bit)
Function: constant light control/regulation
An OFF telegram is used to switch off the orientation light function, while an
ON telegram switches it on.